https://www.phoenixcontact.com/us/products/2810612
05/03/2021Page2/7
Current transducers-MACX MCR-SL-CAC- 5-I-2810612
Technical data
Dimensions
Height 104 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C (-4°F...149°F)
Ambient temperature (storage/transport) -40 °C ... 85 °C (-40°F...185°F)
Maximum altitude 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Degree of protection IP20
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Input data
Configurable/programmable Via DIP switches
Input current range 0 A ... 5 A
Setting range for min. input current 0 A AC ... 1 A (configurable)
Setting range for max. input current 0 A AC ... 5 A (configurable)
Overload capacity 2 x IN (continuous)
Surge strength 20 x IN (1 s)
Nominal frequency fN50 Hz
Frequency measuring range 45 Hz ... 65 Hz
Connection method Screw terminal block
Output data
Output name Current output
Configurable/programmable Via DIP switches
Current output signal 0 mA ... 20 mA (configurable)
4 mA ... 20 mA (configurable)
Max. output current 25 mA
Load/output load current output < 500 Ω (20mA)
Ripple < 10 mVPP (for 500 Ω at 20 mA)
Status display LED red (error), LED green (ready)
Switching output
Output name No switching output
Power supply
Nominal supply voltage 24 VDC (-20%...+25%)
Supply voltage range 19.2 VDC ... 30 VDC
Max. current consumption < 32 mA (at UB=24 V DC, IOUT=20 mA)