Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-1
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Section 3: Molded Case Circuit Breakers
Molded Case Circuit Breakers Features ........................................3-2
Spectra RMS Circuit Breakers with
MicroVersaTrip Plus Trip Units Features .....................................3-3
Molded Case Circuit Breakers Quick Reference Guide .............3-4
Miniature Circuit Breakers and Supplementary Protectors:
Plug-in Circuit Breakers – 240V Class.............................................3-5
Bolt-on Circuit Breakers – 240V Class...........................................3-12
Bolt-on Circuit Breakers – 480/277V Class ...................................3-17
Cable-in Cable-out (lug-lug) – 240V Class ....................................3-18
DIN-Rail Mount – 240V Class ..........................................................3-21
Molded Case Switches ....................................................................3-23
E2000 Miniature Circuit Breakers
EP60 Series.........................................................................................3-24
EP100 Series.......................................................................................3-26
EP100 UC Series ...............................................................................3-28
Series CA Auxiliary Switch and Bell Alarm..................................3-30
Shunt Trip and Undervoltage Release...........................................3-32
Technical Data ...................................................................................3-33
Accessories........................................................................................3-34
Industrial Circuit Breakers—Spectra RMS, Spectra RMS with
MicroVersaTrip Plus Trip Units, Spectra RMS with MicroVersaTrip
PM Trip Units, Thermal Magnetic and J/K with MicroVersaTrip
RMS-9 and Power+ 4 Trip Units:
How to Order .........................................................................................3-37
MicroVersaTrip PM Trip Units – Features.....................................3-40
MicroVersaTrip PM Trip Unit Characteristics ..............................3-41
MicroVersaTrip PM Trip Units – How to Order ............................3-42
R-Frame Molded Case Circuit Breakers – How to Order...........3-43
Electric Trip Spectra RMS Breakers –
Quick Reference Guide ..................................................................3-44
Electric Trip Spectra RMS Breakers – IEC/JIS Ratings .............3-45
Thermal Magnetic Trip – Quick Reference Guide .......................3-46
Molded Case Circuit Breakers – Quick Reference Guide..........3-47
15-150A Circuit Breakers, Electronic Trip, Spectra RMS ...........3-48
15-150A Circuit Breakers, Thermal-Magnetic Trip, E150 Line ...3-50
70-250A Circuit Breakers, Electronic Trip, Spectra RMS ...........3-52
70-250A Circuit Breakers, Thermal-Magnetic Trip, F225 Line ...3-54
125-400A Circuit Breakers, Thermal-Magnetic Trip, Q Line ......3-55
125-600A Circuit Breakers, Electronic Trip, Spectra RMS .........3-56
60-600A Circuit Breakers, Electronic Trip, Spectra RMS ...........3-59
60-600A Circuit Breakers, Electronic Trip, Spectra RMS with
MicroVersaTrip PM Trip Units.......................................................3-59
125-600A Circuit Breakers, Thermal-Magnetic Trip,
J600 Line...........................................................................................3-62
300-1200A Circuit Breakers, Electronic Trip, Spectra RMS .......3-64
300-1200A Circuit Breakers, Electronic Trip, Spectra RMS with
MicroVersaTrip Plus and PM ........................................................3-66
300-1200A Circuit Breakers, Thermal-Magnetic Trip,
K1200 Line.........................................................................................3-69
400-2000A Circuit Breakers, Electronic Trip – R Frame..............3-71
150-1200A Molded Case Switches, Spectra RMS.......................3-72
3-1200A, Motor Circuit Protectors, Spectra RMS .......................3-73
50-1200A, Mine Duty Circuit Breakers, Standard Duty...............3-76
Replacement Breakers, TriBreak, Internally Fused ....................3-77
Replacement Breakers, THLC Current Limiting, Unfused ..........3-79
Replacement Breakers, J and K Frame Circuit Breakers with
MicroVersa Trip Trip Units.............................................................3-80
Replacement Breakers, J and K Frame Circuit Breakers with
Power+ 4 Trip Units.........................................................................3-82
Internal Accessories
Spectra RMS Circuit Breakers .......................................................3-83
Molded Case Circuit Breakers........................................................3-85
Internally Mounted Signaling and Controlling Functions...........3-86
External Accessories
Cable Operators.................................................................................3-92
Handle Operators ..............................................................................3-93
Flange-Mounted Operators .............................................................3-94
Door-Mounted Operators.................................................................3-96
Motor Operators and Plug-in Hardware .......................................3-98
Mechanical Interlocks and Locking Devices...............................3-99
Breaker Mounting Hardware and Kits ........................................3-100
Lugs and Associated Hardware ...................................................3-101
Neutral Grounds and Sensors ......................................................3-103
Plug-in Hardware ............................................................................3-104
R Frame Accessories......................................................................3-105
Power Management System Accessories ....................................3-106
Spectra RMS Accessories – Other .................................................3-109
Prices and data subject to change without notice
3-2 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Features
Spectra RMS Molded Case Circuit Breakers
SE150, SF250, SG600, and SK1200 circuit breaker frames have a
digital, solid-state, rms sensing trip system with field installable,
front-mounted rating plugs to establish or change the breaker
ampere rating. Adjustable instantaneous with tracking short-time
is standard on all frames including SE150. The trip system uses
digital sampling to determine the rms value of sinusoidal and
nonsinusoidal currents.
MicroVersaTrip Plus Trip Units or MicroVersaTrip PM Trip Units
SG600 and SK1200 are optionally available with either
MicroVersaTrip Plus or MicroVersaTrip PM trip units which offer
expanded functionality in the same space-saving size of standard
Spectra RMS breakers. The trip system uses digital sampling to
determine the rms value of sinusoidal and nonsinusoidal currents.
MicroVersaTrip Plus Trip Units
MicroVersaTrip Plus trip units utilize a digital, LCD display with a
four-button keypad to provide local set-up and readout of trip set-
tings. A 3-phase ammeter and trip indicators are standard, as is a
clear plastic cover with provisions for sealing to allow tamper-
resistant installation. The trip unit digitally measures the current
waveform in each phase to determine the true rms value of the
current, regardless of the waveshape.
MicroVersaTrip Plus trip units provide accurate, predictable over-
load and short-circuit protection for distribution systems that include
ac and dc variable speed drives, rectifiers, induction heating, and
other loads that cause high harmonic distortion as well as standard
circuit. They provide maximum breaker-to-breaker selectivity and
custom load protection. Short-time and ground fault functions
include the flexibility of coordination with or without an I2t ramp.
MicroVersaTrip PM Trip Unit
The MicroVersaTrip PM trip unit adds power management system
capability, advanced metering, and protective relays to the basic
functions of the MicroVersaTrip Plus trip unit. The MicroVersaTrip
PM trip unit communicates directly on the GE POWER LEADER
communication bus.
A complete circuit breaker consists of a UL listed circuit breaker
frame and a rating plug (UL listed interchangeable trip unit).
Terminal lugs for cable connection are available if required.
—All frames use the same UL listed, field-installable internal
accessories (auxiliary switch, shunt trip, undervoltage release
and bell alarm).
—All frame sizes have maximum UL listed interrupting ratings of
200 kA @ 240 Vac and 100 kA @ 480 Vac with 600 Vac ratings to 65
kA depending on frame size. UL listed current limiting versions are
provided through the SG600 frame for the 65 kA @ 480 Vac and the
100 kA @ 480 Vac models, with no increase in physical frame size.
—Spectra RMS Mag-Break instantaneous-only motor circuit protec-
tors also use the same digital, solid-state trip unit and rating plugs
as the circuit breakers. The interchangeable rating plug establish-
es the instantaneous pickup range (with tracking short-time) but
does not change the frame ampere rating.
—Spectra RMS molded case switches have a fixed, high-set
instantaneous trip (without tracking short-time function) and have
short-circuit withstand ratings equal to their equivalent breaker
frame size interrupting rating in most cases.
—Spectra RMS breakers are ambient insensitive. Trip times will not
vary over the range 10-50°C breaker ambient. Refer to
GET-7002 for further application information.
—Spectra RMS breakers contain no parts that would support fungus
growth and are, therefore, inherently fungusproof.
Other MCCB Features
—UL489 Listed
—Broad product line to meet virtually any application need.
—Reduced downtime. A tripped breaker is easily spotted and can
be immediately reset after the fault has been corrected.
—Eliminates single phasing. A common trip bar disconnects all
poles simultaneously on both overloads and short circuits.
—Offers application flexibility through the use of a wide variety of
accessory devices and special attachments.
—Repetitive operation—no fuses to replace.
—Breakers can be repetitively tested. Fuses must be destroyed to
confirm calibration accuracy.
For more information on these products, order publications listed in
Sections 21 and 22.
Reference Publications
Spectra RMS Molded Case Circuit Breakers
GEH-5591 SE150 & SF250
GEH-5663 SG600
SG600 with MicroVersaTrip Plus and
MicroVersaTrip PM Trip Units
GEH-5592 SK1200
SK1200 with MicroVersaTrip Plus and
MicroVersaTrip PM Trip Units
GEH-5934 MicroVersaTrip Plus and
MicroVersaTrip PM Trip Units
in Spectra RMS Molded Case Circuit Breakers
GEH-5887 Micro-VersaTrip Plus and
MicroVersaTrip PM Rating Plugs
GEH-5549 Standard Rating Plugs
GEH-5551 Shunt Trip/UV Release
GEH-5593 Auxiliary Switch/Bell Alarm
GEH-5885 R-Frame Molded Case Circuit Breakers
DEJ-001 TVPBP Portable Battery Pack
GEH-6250 Voltage Module
GEH-6251 Power Supply Plate
GEH-6252 Voltage Conditioner Plate
GEH-6253 Power Supply Assembly
GEH-6254 Voltage Conditioner Assembly
GEH-6255 Distribution Cable Harness
GEH-6256 Distribution Cable Extension
GEH-6257 Distribution Cable Terminal Block
GEH-6258 Distribution Cable Junction Box
NOTE: NEMA ABI (1975) has been superceded by UL489
Molded Case Circuit Breakers
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-3
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Features
MicroVersaTrip Plus Trip Units
Standard
—3-phase Ammeter with ±4% accuracy.
—Adjustable Long Time (L) pickup, 0.5-1.0X, and delay (3-4 bands).
—Adjustable Instantaneous (I) pickup, 1.5-10X.
—Local Overload and Short Circuit Trip Indicators (T) with overload
pickup warning.
—Interchangeable trip ratings plugs with test set jack for
TVRMS test set.
—Digital LCD display with four-button keypad for function selection
and set point adjustment and sealable, clear Lexan cover for
tamper-resistant settings.
—True rms sensing for accurate response to high harmonic content
waveforms.
—EMI immunity per ANSI C37.90.
Optional
—Adjustable Short-Time (S) pickup, 1.0-9.0C, and delay (4 bands)
with I2t IN/OUT selection.
—Adjustable Ground fault (G) pickup, 0.2-1.0S, and delay (4 bands)
with I2t IN/OUT selection and trip indicator. The 4 short-time and
ground fault delay bands provide broader system selectivity.
World Standards—Frames rated to UL, CSA, IEC 947-2, and JIS.
Universal Internal Accessories—Uses the same front-mounted,
field installable shunt trips, undervoltage releases, bell alarms,
and auxiliary switches as standard Spectra RMS breakers.
Accessory Lead Routing Left or Right—Side channels mean no extra
space required for accessory leads.
Current Limiting—SE150, SF250 and SG600 frames rated 65kA and
100kA @ 480 Vac are UL listed as current limiting.
Reverse Feed—Front-mounted interchangeable rating plugs mean
all frames are UL listed for reverse feed.
SG Frame with MicroVersaTrip
Plus Trip Unit
Long-Time2
Delay (Seconds)
Pick-Up (Multiple of
Current Setting) (C) Delay (Seconds)
Pick-Up (Multiple of
Sensor Ampere Rating) (X) Delay (Seconds)
I
2
t in;
4
.44
I
2
t in;
5
.41
I
2
t out;
6
.10, .20, .30, .40
I
2
t out;
6
.10, .20, .30, .40
5
Time delay at 200% of pick-up setting at lower limit of band.
6
Time delay shown at lower limit of each band. Pick-up tolerances
±
10%. Ground fault pick-up not to exceed 1200 amperes.
1
Contact local GE Sales Office for use on 400 Hz applications. Not UL listed for 400 Hz.
2
Pick-up fixed at 1.1C.
3
20 second delay (band) not available on SG frames.
4
Time delay at 600% of current setting at lower limit of each band.
0.5 to 1.0 in
increments of 0.05
X = Rating Plug Amperes
S = Sensor Ampere Rating
C = Long-Time Current Settings (Pick-Up)
.20 to 1.00 in
increments of .05
1.5 to 10.0 in
increments of 0.5
1.5 to 9.0 in
increments of 0.5
2.4, 4.9, 9.8, 20
3,4
Current Setting (C)
(Pick-Up) (Multiple of
Rating Plug Amperes) (X)
Short-Time Adjustable
Instantaneous Pick-Up
(Multiple of Rating
Plug Amperes) (X)
Ground Fault
MicroVersaTrip Plus Trip Unit Characteristics1
Spectra RMS Circuit Breakers with
MicroVersaTrip Plus Trip Units
Wide Current Setting Range—Interchangeable rating plugs
combined with 5 current sensors and 0.5-1.0X long time pickup
yield ampere ratings from 30 to 1200A.
100% Continuous Current Rated—Optionally available for 100%
UL continuous current rating applications.
Control Power 24 Vdc—Optionally available, provides connection
capability for +24 Vdc into the breaker via the distribution cable
system.
Prices and data subject to change without notice
3-4 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
ac dc 120 120/240 240 277 480 600 125 250 H W D A B C E
1 1/2 100
2150
1150
2225
3 240 315
15-70 1 150
15-125 2 225
15-100 3 240 315
15-70 1 150
2225
3 240 315
15-70 1 150
15-125 2 225
15-100 3 240 315
1150
2225
3 240 315
TQDL 125-200 2 120/240 —— 10 —————
6 1/16 2 2 3/8 —— 12
THQDL 125-200 2 120/240 —— 22 —————
6 1/16 2 2 3/8 —— 12
100-225 2 240 10 10 2 3/4 1
100-225 3 240 10 4 1/8 11/16 1
100-225 2 240 22 22 2 3/4 1
100-225 3 240 22 4 1/8 11/16 1
2 240 22 22 10 1
3 240 22 1
1 120 10 1 10
2 120/240 1 10
THHQL
...GF
THHQB
...GF, GFEP,
AF
15-30 1 120 22 3 9/32 1 2 3/8 —— 10
———
1
UL listed as HACR (heating, air conditioning and refrigeration).
2
Not UL listed.
3
480Y/277 Vac
———3 9/32 2 3/8
TJD 250-400 3 13/168 1/410 1/8
2 7/16 2 7/16 27/32
1 3/161 3/83 13/163 15/16
——6 9/16 2 5/8——
2 7/16 27/32
THQB
THQC
THQL
...GF, GFEP,
AF
15-30
THQD
1
1
3
—6 9/16 2 5/8 2 7/16
——15-30
TQD
1
——
3 9/32 2 3/8 —————
TXQL
1
TXQB
1
TXQC
1
120/240
65
65
3 9/32 2 3/8
THHQL
1
120/240 22
22
22
22 3 9/32 2 3/8
———
——
THHQB
1
THHQC
1
15-100
120/240
—————
——
THQL
1
THQB
1
THQC
1
——
120/240 10
10
5
2
5
2
———
3 9/32 2 3/8
2 3/8 ———3 9/32
TQL/TQB/
TQC 10 120/240 ——
2 3/8
——
———3 9/32
Std.
Pack
THQP
1
15-50 120/240 10
UL Listed Interrupting Ratings—
rms Symmetrical kA
Vac Vdc Dimensions (in.)
Circuit
Breaker
Type
Ampere
Rating
No.
Poles
Maximum
Voltage Rating
15-50 1 120/240 10 3/4
10
15-60 2 120/240 10 1 1/2 5
2 3/8
TQ —— 3
1 277 14 10
10 10
2480/277
65
14
14 14
65125
250
3
1
2
3
——TEY 15-100 3 1/165 1/4
——
2
CB3 Ground Fault, Equipment Ground Fault and Arc Fault (UL File E-51075; Fixed Thermal Magnetic Trip Unit)
Molded Case Circuit Breakers
Quick Reference Guide
Ratings do not apply to molded case switches.
The interruption ratings and voltages shown in the table are
maximum ratings. A circuit breaker of the type given in the left-hand
column may be applied at the given circuit voltage in any electrical
distribution system where the available fault current at the load
terminals of the breaker does not exceed the value in the table.
That circuit breaker type may also be applied at intermediate values
of circuit voltage provided the available fault current at the load
terminals of the breaker does not exceed the value in the table for
the higher value of voltage.
Q Line (UL file E-11592; Fixed Thermal Magnetic Trip Unit)
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-5
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
TQL and THQL 120/240 Vac GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
1105kA TQL1110 $20.00
115
210kA (1) 14-8 Cu/12-8 Al THQL1115 $20.25
120
210kA (1) 14-8 Cu/12-8 Al THQL1120 $20.25
12510kA (1) 14-8 Cu/12-8 Al THQL1125 $20.25
13010kA (1) 14-8 Cu/12-8 Al THQL1130 $20.25
13510kA (1) 8-3 Cu/8-3 Al THQL1135 $21.25
14010kA (1) 8-3 Cu/8-3 Al THQL1140 $21.25
14510kA (1) 8-3 Cu/8-3 Al THQL1145 $21.25
15010kA (1) 8-3 Cu/8-3 Al THQL1150 $21.25
16010kA (1) 8-3 Cu/8-3 Al THQL1160 $21.25
17010kA (1) 6-1/0 Cu/4-1/0 Al THQL1170 $42.50
TQL and THQL 120/240 Vac, Internal Common Trip GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
210
25kA TQL2110 $46.00
21510kA (1) 14-8 Cu/12-8 Al THQL2115 $46.00
22010kA (1) 14-8 Cu/12-8 Al THQL2120 $46.00
22510kA (1) 14-8 Cu/12-8 Al THQL2125 $46.00
23010kA (1) 14-8 Cu/12-8 Al THQL2130 $46.00
23510kA (1) 8-3 Cu/8-3 Al THQL2135 $47.75
24010kA (1) 8-3 Cu/8-3 Al THQL2140 $47.75
24510kA (1) 8-3 Cu/8-3 Al THQL2145 $47.75
25010kA (1) 8-3 Cu/8-3 Al THQL2150 $47.75
26010kA (1) 8-3 Cu/8-3 Al THQL2160 $47.75
27010kA (1) 6-1/0 Cu/4-1/0 Al THQL2170 $95.00
28010kA (1) 6-1/0 Cu/4-1/0 Al THQL2180 $131.00
29010kA (1) 6-1/0 Cu/4-1/0 Al THQL2190 $131.00
2100 10kA (1) 6-1/0 Cu/4-1/0 Al THQL21100 $131.00
2110 10kA (1) 2-2/0 Cu/2-2/0 Al THQL21110 $284.00
2125 10kA (1) 2-2/0 Cu/2-2/0 Al THQL211253$284.00
THQP 120/240 Vac GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-8 Cu/12-8 Al THQP115 $20.25
12010kA 14-8 Cu/12-8 Al THQP120 $20.25
12510kA 14-8 Cu/12-8 Al THQP125 $20.25
13010kA 8-4 Cu/8-4 Al THQP130 $20.25
13510kA 8-4 Cu/8-4 Al THQP135 $21.25
14010kA 8-4 Cu/8-4 Al THQP140 $21.25
14510kA 8-4 Cu/8-4 Al THQP145 $21.25
15010kA 8-4 Cu/8-4 Al THQP150 $21.25
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (Switching Duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
3Recommended for use as main or submain breaker only.
UL listed as HACR (heating, air conditioning and refrigeration).
Miniature Circuit Breakers and Supplementary Protectors
Plug-in Circuit Breakers
240V Class
THQL1120
Prices and data subject to change without notice
3-6 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
THQP 120/240 Vac, Internal Common Trip GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21510kA 14-8 Cu/12-8 Al THQP215 $46.00
22010kA 14-8 Cu/12-8 Al THQP220 $46.00
22510kA 14-8 Cu/12-8 Al THQP225 $46.00
23010kA 8-4 Cu/8-4 Al THQP230 $46.00
23510kA 8-4 Cu/8-4 Al THQP235 $47.75
24010kA 8-4 Cu/8-4 Al THQP240 $47.75
24510kA 8-4 Cu/8-4 Al THQP245 $47.75
25010kA 8-4 Cu/8-4 Al THQP250 $47.75
15-100 ampere UL Listed as HACR (heating, air conditioning and refrigeration).
TQL and THQL 120/240 Vac, Internal Common Trip GO-138
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
2105kA TQL22010 $133.00
21510kA 14-8 Cu/12-8 Al THQL22015 $133.00
22010kA 14-8 Cu/12-8 Al THQL22020 $133.00
22510kA 14-8 Cu/12-8 Al THQL22025 $133.00
23010kA 14-8 Cu/12-8 Al THQL22030 $133.00
23510kA 8-3 Cu/8-3 Al THQL22035 $133.00
24010kA 8-3 Cu/8-3 Al THQL22040 $133.00
24510kA 8-3 Cu/8-3 Al THQL22045 $133.00
25010kA 8-3 Cu/8-3 Al THQL22050 $133.00
26010kA 8-3 Cu/8-3 Al THQL22060 $133.00
27010kA 6-1/0 Cu/4-1/0 Al THQL22070 $156.00
28010kA 6-1/0 Cu/4-1/0 Al THQL22080 $221.00
29010kA 6-1/0 Cu/4-1/0 Al THQL22090 $221.00
2100 10kA 6-1/0 Cu/4-1/0 Al THQL22100 $221.00
TQL and THQL 240 Vac, Internal Common Trip GO-138
# of Ampere 240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
3105kA TQL32010 $165.00
31510kA 14-8 Cu/12-8 Al THQL32015 $165.00
32010kA 14-8 Cu/12-8 Al THQL32020 $165.00
32510kA 14-8 Cu/12-8 Al THQL32025 $165.00
33010kA 14-8 Cu/12-8 Al THQL32030 $165.00
33510kA 8-3 Cu/8-3 Al THQL32035 $165.00
34010kA 8-3 Cu/8-3 Al THQL32040 $165.00
34510kA 8-3 Cu/8-3 Al THQL32045 $165.00
35010kA 8-3 Cu/8-3 Al THQL32050 $165.00
36010kA 8-3 Cu/8-3 Al THQL32060 $165.00
37010kA 6-1/0 Cu/4-1/0 Al THQL32070 $216.00
38010kA 6-1/0 Cu/4-1/0 Al THQL32080 $245.00
39010kA 6-1/0 Cu/4-1/0 Al THQL32090 $245.00
3100 10kA 6-1/0 Cu/4-1/0 Al THQL32100 $245.00
THQL and THHQL 120/240 Vac Arc Fault GO-146A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-10 Cu/14-10 Al THQL1115AF $170.00
12010kA 14-10 Cu/14-10 Al THQL1120AF $170.00
11522kA 14-10 Cu/14-10 Al THHQL1115AF $326.00
12022kA 14-10 Cu/14-10 Al THHQL1120AF $326.00
THQL and THHQL 120/240 Vac Arc Fault GO-146A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21510kA 14-10 Cu/14-10 Al THQL2115AF $385.00
22010kA 14-10 Cu/14-10 Al THQL2120AF $385.00
21522kA 14-10 Cu/14-10 Al THHQL2115AF $701.00
22022kA 14-10 Cu/14-10 Al THHQL2120AF $701.00
1Solid or stranded for 14-10 AWG.
Miniature Circuit Breakers and Supplementary Protectors
Plug-in Circuit Breakers
240V Class
THQL32015
THQL1115AF
THQL2115AF
THQP230
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-7
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
THQL and THHQL 120 Vac, Ground Fault Circuit Interrupters GO-146
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-8 Cu/12-8 Al THQL1115GF $159.00
12010kA 14-8 Cu/12-8 Al THQL1120GF $159.00
13010kA 14-8 Cu/12-8 Al THQL1130GF $159.00
11522kA 14-8 Cu/12-8 Al THHQL1115GF $311.00
12022kA 14-8 Cu/12-8 Al THHQL1120GF $311.00
13022kA 14-8 Cu/12-8 Al THHQL1130GF $311.00
THQL and THHQL 120/240 Vac or 208Y/120 Vac,
Ground Fault Circuit Interrupters Internal Common Trip GO-146
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21510kA 14-8 Cu/12-8 Al THQL2115GF1 $282.00
22010kA 14-8 Cu/12-8 Al THQL2120GF1 $282.00
23010kA 14-8 Cu/12-8 Al THQL2130GF1 $282.00
24010kA 8-3 Cu/8-3 Al THQL2140GF1 $282.00
25010kA 8-3 Cu/8-3 Al THQL2150GF1 $702.00
THQL and THHQL 120 Vac, Equipment Protection Ground Fault Circuit
Breakers Internal Common Trip GO-146
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-8 Cu/12-8 Al THQL1115GFEP $271.00
12010kA 14-8 Cu/12-8 Al THQL1120GFEP $271.00
13010kA 14-8 Cu/12-8 Al THQL1130GFEP $271.00
THQL and THHQL 120/240 Vac or 208Y/120 Vac, Equipment Protection
Ground Fault Circuit Breakers GO-146
# of Ampere 120/240 Vac or 208Y/120
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21510kA 14-8 Cu/12-8 Al THQL2115GFEP $481.00
22010kA 14-8 Cu/12-8 Al THQL2120GFEP $481.00
23010kA 14-8 Cu/12-8 Al THQL2130GFEP $481.00
THQL Interlocking—for use in PowerMark Gold Generator Panels GO-138A
# of Ampere 120/240 Vac or 208Y/120
Poles Rating Interrupting Rating Wire Range1Product Number List Price
23010kA 14-8 Cu/12-8 Al THQL2130GEN $238.75
26010kA 8-3 Cu/8-3 Al THQL2160GEN $238.75
Two breakers required for interlocking.
TQ Circuit Breakers 120/240 Vac GO-138Q
3/4” UL Classified Circuit Breakers for use in Square D QO Load Centers.
10 kAIC RMS symmetrical.
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-8 Cu/12-8 Al TQ1115 $20.25
12010kA 14-8 Cu/12-8 Al TQ1120 $20.25
13010kA 14-8 Cu/12-8 Al TQ1130 $20.25
14010kA 8-2 Cu/8-2 Al TQ1140 $20.25
15010kA 8-2 Cu/8-2 Al TQ1150 $20.25
21510kA 14-8 Cu/12-8 Al TQ2115 $46.00
22010kA 14-8 Cu/12-8 Al TQ2120 $46.00
23010kA 14-8 Cu/12-8 Al TQ2130 $46.00
24010kA 8-2 Cu/8-2 Al TQ2140 $46.00
25010kA 8-2 Cu/8-2 Al TQ2150 $46.00
26010kA 8-2 Cu/8-2 Al TQ2160 $46.00
1Solid or stranded for 14-10 AWG.
Miniature Circuit Breakers and Supplementary Protectors
Plug-in Circuit Breakers
240V Class
THQL1120GF
Prices and data subject to change without notice
3-8 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
THQL and THHQL 120/240 Vac, High Intensity Discharge Lighting Loads GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-8 Cu/12-8 Al THQL1115HID2$26.00
12010kA 14-8 Cu/12-8 Al THQL1120HID2$26.00
12510kA 14-8 Cu/12-8 Al THQL1125HID $26.00
13010kA 14-8 Cu/12-8 Al THQL1130HID $26.00
11522kA 14-8 Cu/12-8 Al THHQL1115HID2$49.50
12022kA 14-8 Cu/12-8 Al THHQL1120HID2$49.50
12522kA 14-8 Cu/12-8 Al THHQL1125HID $49.50
13022kA 14-8 Cu/12-8 Al THHQL1130HID $49.50
UL listed as HID.
THQL and THHQL 120/240 Vac, Internal Common Trip For High Intensity
Discharge Lighting Loads GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21510kA 14-8 Cu/12-8 Al THQL2115HID $57.00
22010kA 14-8 Cu/12-8 Al THQL2120HID $57.00
22510kA 14-8 Cu/12-8 Al THQL2125HID $57.00
23010kA 14-8 Cu/12-8 Al THQL2130HID $57.00
21522kA 14-8 Cu/12-8 Al THHQL2115HID $119.00
22022kA 14-8 Cu/12-8 Al THHQL2120HID $119.00
22522kA 14-8 Cu/12-8 Al THHQL2125HID $119.00
23022kA 14-8 Cu/12-8 Al THHQL2130HID $119.00
UL listed as HID.
THQL 120/240 Vac, High In-Rush Loads GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-8 Cu/12-8 Al THQL1115HM $26.00
12010kA 14-8 Cu/12-8 Al THQL1120HM $26.00
12510kA 14-8 Cu/12-8 Al THQL1125HM $26.00
13010kA 14-8 Cu/12-8 Al THQL1130HM $26.00
14010kA 8-3 Cu/8-3 Al THQL1140HM $26.75
15010kA 8-3 Cu/8-3 Al THQL1150HM $26.75
THQL 120 Vac, For Factory Installed Shunt Trip3,4 Internal Common Trip GO-138
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
32010kA 14-8 Cu/12-8 Al THQL32020ST1 $273.00
THQL 120/240 Vac, Thermal Magnetic Pole plus Nonautomatic Pole
For Switching Neutral GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21510kA 14-8 Cu/12-8 Al THQL21WY15 $74.25
22010kA 14-8 Cu/12-8 Al THQL21WY20 $74.25
22510kA 14-8 Cu/12-8 Al THQL21WY25 $74.25
23010kA 14-8 Cu/12-8 Al THQL21WY30 $74.25
31510kA 14-8 Cu/12-8 Al THQL31WY15 $111.00
32010kA 14-8 Cu/12-8 Al THQL31WY20 $111.00
32510kA 14-8 Cu/12-8 Al THQL31WY25 $111.00
33010kA 14-8 Cu/12-8 Al THQL31WY30 $111.00
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty). Suitable for 120 Vac fluorescent lighting loads.
3For additional shunt trip offerings see page 3-88.
420-60 ampere are UL listed as HACR (heating, air conditioning and refrigeration).
Miniature Circuit Breakers and Supplementary Protectors
Plug-in Circuit Breakers
240V Class
THQL2120HID
THQL1120HM
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-9
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
THQMV Top-Feed Main Circuit Breaker Kits for use with 150A-225A
PowerMark Gold Load Centers GO-138M
# of Ampere Interrupting Rating
Poles Rating @ System Voltage Wire Range1Product Number List Price
2100 22kA 6-350 Cu/Al THQMV100 $259.00
2125 22kA 6-350 Cu/Al THQMV125 $259.00
2150 22kA 6-350 Cu/Al THQMV150 $259.00
2175 22kA 6-350 Cu/Al THQMV175 $259.00
2200 22kA 6-350 Cu/Al THQMV200 $259.00
2225 22kA 6-350 Cu/Al THQMV225 $259.00
THQMV Bottom-Feed Main Circuit Breaker Kits for use with 150A-225A
PowerMark Gold Load Centers Internal Common Trip GO-138M
# of Ampere Interrupting Rating
Poles Rating @ System Voltage Wire Range1Product Number List Price
2100 22kA 6-350 Cu/Al THQMV100B $259.00
2125 22kA 6-350 Cu/Al THQMV125B $259.00
2150 22kA 6-350 Cu/Al THQMV150B $259.00
2175 22kA 6-350 Cu/Al THQMV175B $259.00
2200 22kA 6-350 Cu/Al THQMV200B $259.00
2225 22kA 6-350 Cu/Al THQMV225B $259.00
THLK Sub-free and Feed-through Lugs Internal Common Trip GO-137A
# of Ampere
Poles Rating Wire Range1Product Number List Price
2125 2-3/0 Cu/Al THLK2125 $77.00
3125 2-3/0 Cu/Al THLK3125 $107.00
2150 2-3/0 Cu/Al THLK21502$137.00
2200 6-250 Cu/Al THLK22002$158.00
3225 6-300 Cu/Al THLK32253$250.00
TQDL 120/240 Vac, Internal Common Trip GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
2125 10kA 1/0-250 Cu/Al TQDL21125 $296.00
2150 10kA 1/0-250 Cu/Al TQDL21150 $296.00
2175 10kA 1/0-250 Cu/Al TQDL21175 $296.00
2200 10kA 1/0-250 Cu/Al TQDL21200 $296.00
1Solid or stranded for 14-10 AWG.
2For use with PowerMark Gold load centers only.
3For use with three-phase load centers only. Includes mounting base.
UL listed as HACR (heating, air conditioning and refrigeration).
Requires four one-inch spaces.
Miniature Circuit Breakers and Supplementary Protectors
Plug-in Circuit Breakers
240V Class
THQMV200
THQMV200B
THLK2125
TQDL21200
THKL2150
THQP130
Prices and data subject to change without notice
3-10 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
THHQL 120 Vac GO-138A
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11522kA 14-8 Cu/12-8 Al THHQL11152$40.25
12022kA 14-8 Cu/12-8 Al THHQL11202$40.25
12522kA 14-8 Cu/12-8 Al THHQL1125 $40.25
13022kA 8-3 Cu/8-3 Al THHQL1130 $40.25
13522kA 8-3 Cu/8-3 Al THHQL1135 $41.25
14022kA 8-3 Cu/8-3 Al THHQL1140 $41.25
14522kA 8-3 Cu/8-3 Al THHQL1145 $41.25
15022kA 8-3 Cu/8-3 Al THHQL1150 $41.25
16022kA 8-3 Cu/8-3 Al THHQL1160 $41.25
17022kA 6-1/0 Cu/4-1/0 Al THHQL1170 $58.50
THHQL 120/240 Vac, Internal Common Trip GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21522kA 14-8 Cu/12-8 Al THHQL2115 $93.00
22022kA 14-8 Cu/12-8 Al THHQL2120 $93.00
22522kA 14-8 Cu/12-8 Al THHQL2125 $93.00
23022kA 8-3 Cu/8-3 Al THHQL2130 $93.00
23522kA 8-3 Cu/8-3 Al THHQL2135 $97.00
24022kA 8-3 Cu/8-3 Al THHQL2140 $97.00
24522kA 8-3 Cu/8-3 Al THHQL2145 $97.00
25022kA 8-3 Cu/8-3 Al THHQL2150 $97.00
26022kA 8-3 Cu/8-3 Al THHQL2160 $97.00
27022kA 6-1/0 Cu/4-1/0 Al THHQL2170 $148.00
28022kA 6-1/0 Cu/4-1/0 Al THHQL2180 $210.00
29022kA 6-1/0 Cu/4-1/0 Al THHQL2190 $210.00
2100 22kA 6-1/0 Cu/4-1/0 Al THHQL21100 $210.00
2110 22kA 2-2/0 Cu/2-2/0 Al THHQL21110 $686.00
2125 22kA 2-2/0 Cu/2-2/0 Al THHQL21125 $686.00
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
UL listed HACR (heating, air conditioning and refrigeration).
Miniature Circuit Breakers and Supplementary Protectors
Plug-in Circuit Breakers
240V Class
THHQL1120
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-11
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
THHQL 240 Vac, Internal Common Trip GO-138
# of Ampere 240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21522kA 14-8 Cu/12-8 Al THHQL22015 $193.00
22022kA 14-8 Cu/12-8 Al THHQL22020 $193.00
22522kA 14-8 Cu/12-8 Al THHQL22025 $193.00
23022kA 8-3 Cu/8-3 Al THHQL22030 $193.00
23522kA 8-3 Cu/8-3 Al THHQL22035 $193.00
24022kA 8-3 Cu/8-3 Al THHQL22040 $193.00
24522kA 8-3 Cu/8-3 Al THHQL22045 $193.00
25022kA 8-3 Cu/8-3 Al THHQL22050 $193.00
26022kA 8-3 Cu/8-3 Al THHQL22060 $193.00
27022kA 6-1/0 Cu/4-1/0 Al THHQL22070 $251.00
28022kA 6-1/0 Cu/4-1/0 Al THHQL22080 $277.00
29022kA 6-1/0 Cu/4-1/0 Al THHQL22090 $277.00
2100 22kA 6-1/0 Cu/4-1/0 Al THHQL22100 $277.00
31522kA 14-8 Cu/12-8 Al THHQL32015 $251.00
32022kA 14-8 Cu/12-8 Al THHQL32020 $251.00
32522kA 14-8 Cu/12-8 Al THHQL32025 $251.00
33022kA 8-3 Cu/8-3 Al THHQL32030 $251.00
33522kA 8-3 Cu/8-3 Al THHQL32035 $251.00
34022kA 8-3 Cu/8-3 Al THHQL32040 $251.00
34522kA 8-3 Cu/8-3 Al THHQL32045 $251.00
35022kA 8-3 Cu/8-3 Al THHQL32050 $251.00
36022kA 8-3 Cu/8-3 Al THHQL32060 $251.00
37022kA 6-1/0 Cu/4-1/0 Al THHQL32070 $329.00
38022kA 6-1/0 Cu/4-1/0 Al THHQL32080 $359.00
39022kA 6-1/0 Cu/4-1/0 Al THHQL32090 $359.00
3100 22kA 6-1/0 Cu/4-1/0 Al THHQL32100 $359.00
UL listed HACR (heating, air conditioning and refrigeration).
THQDL 120/240 Vac, Internal Common Trip GO-138
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
2125 22kA 1/0-250 Cu/1/0-250 Al THQDL21125 $713.00
2150 22kA 1/0-250 Cu/1/0-250 Al THQDL21150 $713.00
2175 22kA 1/0-250 Cu/1/0-250 Al THQDL21175 $713.00
2200 22kA 1/0-250 Cu/1/0-250 Al THQDL21200 $713.00
TXQL 120/240 Vac GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11565kA 14-8 Cu/12-8 Al TXQL11152$74.75
12065kA 14-8 Cu/12-8 Al TXQL11202$74.75
12565kA 14-8 Cu/12-8 Al TXQL1125 $74.75
13065kA 14-8 Cu/12-8 Al TXQL1130 $74.75
TXQL 120/240 Vac, Internal Common Trip GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21565kA 14-8 Cu/12-8 Al TXQL2115 $186.00
22065kA 14-8 Cu/12-8 Al TXQL2120 $186.00
22565kA 14-8 Cu/12-8 Al TXQL2125 $186.00
23065kA 14-8 Cu/12-8 Al TXQL2130 $186.00
31565kA 14-8 Cu/12-8 Al TXQL32015 $348.00
32065kA 14-8 Cu/12-8 Al TXQL32020 $348.00
32565kA 14-8 Cu/12-8 Al TXQL32025 $348.00
33065kA 14-8 Cu/12-8 Al TXQL32030 $348.00
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
UL listed HACR (heating, air conditioning and refrigeration).
Miniature Circuit Breakers and Supplementary Protectors
Plug-in Circuit Breakers
240V Class
THHQL32015
Prices and data subject to change without notice
3-12 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
TQB, THQB 120/240 Vac GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
1105kA 14-8 Cu/12-8 Al TQB1110 $19.75
11510kA 14-8 Cu/12-8 Al THQB11152$19.75
12010kA 14-8 Cu/12-8 Al THQB11202$19.75
12510kA 14-8 Cu/12-8 Al THQB1125 $19.75
13010kA 14-8 Cu/12-8 Al THQB1130 $19.75
13510kA 8-3 Cu/8-3 Al THQB1135 $19.75
14010kA 8-3 Cu/8-3 Al THQB1140 $19.75
14510kA 8-3 Cu/8-3 Al THQB1145 $19.75
15010kA 8-3 Cu/8-3 Al THQB1150 $19.75
16010kA 8-3 Cu/8-3 Al THQB1160 $19.75
17010kA 6-1/0 Cu/4-1/0 Al THQB1170 $38.00
TQB, THQB 120/240 Vac, Internal Common Trip GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
2105kA 14-8 Cu/12-8 Al TQB2110 $43.50
21510kA 14-8 Cu/12-8 Al THQB2115 $43.50
22010kA 14-8 Cu/12-8 Al THQB2120 $43.50
22510kA 14-8 Cu/12-8 Al THQB2125 $43.50
23010kA 14-8 Cu/12-8 Al THQB2130 $43.50
23510kA 8-3 Cu/8-3 Al THQB2135 $43.50
24010kA 8-3 Cu/8-3 Al THQB2140 $43.50
24510kA 8-3 Cu/8-3 Al THQB2145 $43.50
25010kA 8-3 Cu/8-3 Al THQB2150 $43.50
26010kA 8-3 Cu/8-3 Al THQB2160 $43.50
27010kA 8-3 Cu/8-3 Al THQB2170 $82.50
28010kA 6-1/0 Cu/4-1/0 Al THQB2180 $113.00
29010kA 6-1/0 Cu/4-1/0 Al THQB2190 $113.00
2100 10kA 6-1/0 Cu/4-1/0 Al THQB21100 $113.00
TQB, THQB 240 Vac, Internal Common Trip GO-135B
# of Ampere 240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
2105kA 14-8 Cu/12-8 Al TQB22010 $113.00
21510kA 14-8 Cu/12-8 Al THQB22015 $113.00
22010kA 14-8 Cu/12-8 Al THQB22020 $113.00
22510kA 14-8 Cu/12-8 Al THQB22025 $113.00
23010kA 14-8 Cu/12-8 Al THQB22030 $113.00
23510kA 8-3 Cu/8-3 Al THQB22035 $113.00
24010kA 8-3 Cu/8-3 Al THQB22040 $113.00
24510kA 8-3 Cu/8-3 Al THQB22045 $113.00
25010kA 8-3 Cu/8-3 Al THQB22050 $113.00
26010kA 8-3 Cu/8-3 Al THQB22060 $113.00
27010kA 6-1/0 Cu/4-1/0 Al THQB22070 $148.00
28010kA 6-1/0 Cu/4-1/0 Al THQB22080 $170.00
29010kA 6-1/0 Cu/4-1/0 Al THQB22090 $170.00
2100 10kA 6-1/0 Cu/4-1/0 Al THQB22100 $170.00
3105kA 14-8 Cu/12-8 Al TQB320103$139.00
31510kA 14-8 Cu/12-8 Al THQB32015 $139.00
32010kA 14-8 Cu/12-8 Al THQB32020 $139.00
32510kA 14-8 Cu/12-8 Al THQB32025 $139.00
33010kA 14-8 Cu/12-8 Al THQB32030 $139.00
33510kA 8-3 Cu/8-3 Al THQB32035 $139.00
34010kA 8-3 Cu/8-3 Al THQB32040 $139.00
34510kA 8-3 Cu/8-3 Al THQB32045 $139.00
35010kA 8-3 Cu/8-3 Al THQB32050 $139.00
36010kA 8-3 Cu/8-3 Al THQB32060 $139.00
37010kA 6-1/0 Cu/4-1/0 Al THQB32070 $175.00
38010kA 6-1/0 Cu/4-1/0 Al THQB32080 $199.00
39010kA 6-1/0 Cu/4-1/0 Al THQB32090 $199.00
3100 10kA 6-1/0 Cu/4-1/0 Al THQB32100 $199.00
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (Switching Duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
3Not UL listed.
UL listed HACR (heating, air conditioning and refrigeration).
Miniature Circuit Breakers and Supplementary Protectors
Bolt-on Circuit Breakers
240V Class
THQB2115
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-13
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
THQB, THHQB 120 Vac, Ground Fault Breakers GO-133
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-8 Cu/12-8 Al THQB1115GF $120.00
12010kA 14-8 Cu/12-8 Al THQB1120GF $120.00
13010kA 14-8 Cu/12-8 Al THQB1130GF $120.00
11522kA 14-8 Cu/12-8 Al THHQB1115GF $235.00
12022kA 14-8 Cu/12-8 Al THHQB1120GF $235.00
13022kA 14-8 Cu/12-8 Al THHQB1130GF $235.00
THQB 120/240 or 208Y/120 Vac, Ground Fault Breakers, Internal Common Trip GO-133
# of Ampere 120/240 or 208Y/120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21510kA 14-8 Cu/12-8 Al THQB2115GF $212.00
22010kA 14-8 Cu/12-8 Al THQB2120GF $212.00
23010kA 14-8 Cu/12-8 Al THQB2130GF $212.00
THQB 120 Vac, Equipment Protection Ground Fault Circuit Breakers (30 ma) GO-133
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-8 Cu/12-8 Al THQB1115GFEP $205.00
12010kA 14-8 Cu/12-8 Al THQB1120GFEP $205.00
13010kA 14-8 Cu/12-8 Al THQB1130GFEP $205.00
THQB 120/240 or 208Y/120 Vac, Ground Fault Breakers Equipment Protection
Ground Fault Circuit Breakers, Internal Common Trip GO-133
# of Ampere 120/240 or 208Y/120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21510kA 14-8 Cu/12-8 Al THQB2115GFEP $273.00
22010kA 14-8 Cu/12-8 Al THQB2120GFEP $273.00
23010kA 14-8 Cu/12-8 Al THQB2130GFEP $273.00
THQB 120/240 Vac, High Intensity Discharge Lighting Loads GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-8 Cu/12-8 Al THQB1115HID2$23.75
12010kA 14-8 Cu/12-8 Al THQB1120HID2$23.75
12510kA 14-8 Cu/12-8 Al THQB1125HID $23.75
13010kA 14-8 Cu/12-8 Al THQB1130HID $23.75
UL listed as HID (high intensity discharge).
THHQB 120/240 Vac, High Intensity Discharge Lighting Loads GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11522kA 14-8 Cu/12-8 Al THHQB1115HID2$41.50
12022kA 14-8 Cu/12-8 Al THHQB1120HID2$41.50
12522kA 14-8 Cu/12-8 Al THHQB1125HID $47.00
13022kA 14-8 Cu/12-8 Al THHQB1130HID $47.00
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty). Suitable for switching 120 Vac fluorescent lighting loads.
UL listed as HID (high intensity discharge).
Miniature Circuit Breakers and Supplementary Protectors
Bolt-on Circuit Breakers
240V Class
THQB1115GF
Prices and data subject to change without notice
3-14 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
THQB 120/240 Vac, Internal Common Trip, High Intensity Discharge
Lighting Loads GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21510kA 14-8 Cu/12-8 Al THQB2115HID $52.50
22010kA 14-8 Cu/12-8 Al THQB2120HID $52.50
22510kA 14-8 Cu/12-8 Al THQB2125HID $52.50
23010kA 14-8 Cu/12-8 Al THQB2130HID $52.50
UL listed as HID
THHQB 120/240 Vac, Internal Common Trip, High Intensity Discharge
Lighting Loads GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21522kA 14-8 Cu/12-8 Al THHQB2115HID $98.50
22022kA 14-8 Cu/12-8 Al THHQB2120HID $98.50
22522kA 14-8 Cu/12-8 Al THHQB2125HID $98.50
23022kA 14-8 Cu/12-8 Al THHQB2130HID $98.50
UL listed as HID
THQB 120 Vac with Factory Installed 120 Vac Shunt Trip2,3 GO-135B
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
12010kA 14-8 Cu/12-8 Al THQB1120ST1 $113.00
THQB 120 Vac, Internal Common Trip with Factory Installed 120 Vac Shunt Trip 2,3 GO-135B
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
22010kA 14-8 Cu/12-8 Al THQB2120ST1 $137.00
23010kA 14-8 Cu/12-8 Al THQB2130ST1 $137.00
2100 10kA 6-1/0 Cu/4-1/0 Al THQB21100ST1 $205.00
32010kA 14-8 Cu/12-8 Al THQB32020ST1 $234.00
33010kA 14-8 Cu/12-8 Al THQB32030ST1 $234.00
34010kA 8-3 Cu/8-3 Al THQB32040ST1 $234.00
35010kA 8-3 Cu/8-3 Al THQB32050ST1 $234.00
36010kA 8-3 Cu/8-3 Al THQB32060ST1 $234.00
37010kA 6-1/0 Cu/4-1/0 Al THQB32070ST1 $270.00
38010kA 6-1/0 Cu/4-1/0 Al THQB32080ST1 $295.00
39010kA 6-1/0 Cu/4-1/0 Al THQB32090ST1 $295.00
3100 10kA 6-1/0 Cu/4-1/0 Al THQB32100ST1 $295.00
THQB 120 Vac with Switching Neutral Single Thermal Magnetic Pole;
Single Nonautomatic Pole GO-138A
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21510kA 14-8 Cu/12-8 Al THQB21WY15 $58.50
22010kA 14-8 Cu/12-8 Al THQB21WY20 $58.50
22510kA 14-8 Cu/12-8 Al THQB21WY25 $58.50
23010kA 14-8 Cu/12-8 Al THQB21WY30 $58.50
THQB 120 Vac with Switching Neutral Two Thermal Magnetic Pole;
Single Nonautomatic Pole GO-135B
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
31510kA 14-8 Cu/12-8 Al THQB31WY15 $88.00
32010kA 14-8 Cu/12-8 Al THQB31WY20 $88.00
32510kA 14-8 Cu/12-8 Al THQB31WY25 $88.00
33010kA 14-8 Cu/12-8 Al THQB31WY30 $88.00
1Solid or stranded for 14-10 AWG.
2For additional shunt trip offerings see page 3-88.
320-60 ampere are UL listed as HACR (heating, air conditioning and refrigeration).
Miniature Circuit Breakers and Supplementary Protectors
Bolt-on Circuit Breakers
240V Class
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-15
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Miniature Circuit Breakers and Supplementary Protectors
Bolt-on Circuit Breakers
240V Class
THHQB 120/240 Vac GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11522kA 14-8 Cu/12-8 Al THHQB11152$35.00
12022kA 14-8 Cu/12-8 Al THHQB11202$35.00
12522kA 14-8 Cu/12-8 Al THHQB1125 $39.00
13022kA 14-8 Cu/12-8 Al THHQB1130 $39.00
13522kA 8-3 Cu/8-3 Al THHQB1135 $39.00
14022kA 8-3 Cu/8-3 Al THHQB1140 $39.00
14522kA 8-3 Cu/8-3 Al THHQB1145 $39.00
15022kA 8-3 Cu/8-3 Al THHQB1150 $39.00
16022kA 8-3 Cu/8-3 Al THHQB1160 $39.00
17022kA 6-1/0 Cu/4-1/0 Al THHQB1170 $51.00
THHQB 120/240 Vac, Internal Common Trip GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21522kA 14-8 Cu/12-8 Al THHQB2115 $82.50
22022kA 14-8 Cu/12-8 Al THHQB2120 $82.50
22522kA 14-8 Cu/12-8 Al THHQB2125 $82.50
23022kA 14-8 Cu/12-8 Al THHQB2130 $82.50
23522kA 8-3 Cu/8-3 Al THHQB2135 $82.50
24022kA 8-3 Cu/8-3 Al THHQB2140 $82.50
24522kA 8-3 Cu/8-3 Al THHQB2145 $82.50
25022kA 8-3 Cu/8-3 Al THHQB2150 $82.50
26022kA 8-3 Cu/8-3 Al THHQB2160 $82.50
27022kA 6-1/0 Cu/4-1/0 Al THHQB2170 $126.00
28022kA 6-1/0 Cu/4-1/0 Al THHQB2180 $183.00
29022kA 6-1/0 Cu/4-1/0 Al THHQB2190 $183.00
2100 22kA 6-1/0 Cu/4-1/0 Al THHQB21100 $183.00
THHQB 240 Vac, Internal Common Trip GO-135B
# of Ampere 240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21522kA 14-8 Cu/12-8 Al THHQB22015 $156.00
22022kA 14-8 Cu/12-8 Al THHQB22020 $156.00
22522kA 14-8 Cu/12-8 Al THHQB22025 $156.00
23022kA 14-8 Cu/12-8 Al THHQB22030 $156.00
23522kA 8-3 Cu/8-3 Al THHQB22035 $156.00
24022kA 8-3 Cu/8-3 Al THHQB22040 $156.00
24522kA 8-3 Cu/8-3 Al THHQB22045 $156.00
25022kA 8-3 Cu/8-3 Al THHQB22050 $156.00
26022kA 8-3 Cu/8-3 Al THHQB22060 $156.00
27022kA 6-1/0 Cu/4-1/0 Al THHQB22070 $196.00
28022kA 6-1/0 Cu/4-1/0 Al THHQB22080 $235.00
29022kA 6-1/0 Cu/4-1/0 Al THHQB22090 $235.00
2100 22kA 6-1/0 Cu/4-1/0 Al THHQB22100 $235.00
31522kA 14-8 Cu/12-8 Al THHQB32015 $212.00
32022kA 14-8 Cu/12-8 Al THHQB32020 $212.00
32522kA 14-8 Cu/12-8 Al THHQB32025 $212.00
33022kA 14-8 Cu/12-8 Al THHQB32030 $212.00
33522kA 8-3 Cu/8-3 Al THHQB32035 $212.00
34022kA 8-3 Cu/8-3 Al THHQB32040 $212.00
34522kA 8-3 Cu/8-3 Al THHQB32045 $212.00
35022kA 8-3 Cu/8-3 Al THHQB32050 $212.00
36022kA 8-3 Cu/8-3 Al THHQB32060 $212.00
37022kA 6-1/0 Cu/4-1/0 Al THHQB32070 $263.00
38022kA 6-1/0 Cu/4-1/0 Al THHQB32080 $307.00
39022kA 6-1/0 Cu/4-1/0 Al THHQB32090 $307.00
3100 22kA 6-1/0 Cu/4-1/0 Al THHQB32100 $307.00
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty). Suitable for switching 120 Vac fluorescent lighting loads.
UL listed HACR (heating, air conditioning and refrigeration).
THHQB2115
Prices and data subject to change without notice
3-16 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
TXQB 120/240 Vac GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11565kA 14-8 Cu/12-8 Al TXQB11152$63.50
12065kA 14-8 Cu/12-8 Al TXQB11202$63.50
12565kA 14-8 Cu/12-8 Al TXQB1125 $63.50
13065kA 14-8 Cu/12-8 Al TXQB1130 $63.50
TXQB 120/240 Vac, Internal Common Trip GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21565kA 14-8 Cu/12-8 Al TXQB2115 $154.00
22065kA 14-8 Cu/12-8 Al TXQB2120 $154.00
22565kA 14-8 Cu/12-8 Al TXQB2125 $154.00
23065kA 14-8 Cu/12-8 Al TXQB2130 $154.00
TXQB 240 Vac, Internal Common Trip GO-135B
# of Ampere 240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
31565kA 14-8 Cu/12-8 Al TXQB32015 $263.00
32065kA 14-8 Cu/12-8 Al TXQB32020 $263.00
32565kA 14-8 Cu/12-8 Al TXQB32025 $263.00
33065kA 14-8 Cu/12-8 Al TXQB32030 $263.00
1Solid or stranded for 14-10 AWG.
2UL listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
UL listed HACR (heating, air conditioning and refrigeration).
Miniature Circuit Breakers and Supplementary Protectors
Bolt-on Circuit Breakers
240V Class
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-17
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
TEY 1 pole
65kA @120 Vac; 14kA @120/240, 240, 277 Vac GO-135B
# of Ampere
Poles Rating Wire Range1Product Number List Price
11514-12 Cu/12-10 Al TEY1152,3 $72.00
12014-12 Cu/12-10 Al TEY1202,3 $72.00
12514-12 Cu/12-10 Al TEY1253$72.00
13014-10 Cu/14-10 Al TEY1303$72.00
13514-10 Cu/14-10 Al TEY1353$72.00
14014-10 Cu/14-10 Al TEY1403$72.00
14514-10 Cu/14-10 Al TEY1453$72.00
15014-10 Cu/14-10 Al TEY1503$72.00
16014-10 Cu/14-10 Al TEY160 $72.00
1704-1 Cu/2-1/0 Al TEY170 $142.00
1804-1 Cu/2-1/0 Al TEY180 $142.00
1904-1 Cu/2-1/0 Al TEY190 $142.00
1100 4-1 Cu/2-1/0 Al TEY1100 $142.00
TEY 2 pole
65kA @120, 120/240, 240 Vac; 14kA @277 Vac GO-135B
# of Ampere
Poles Rating Wire Range1Product Number List Price
21514-12 Cu/12-10 Al TEY2153$216.00
22014-12 Cu/12-10 Al TEY2203$216.00
22514-12 Cu/12-10 Al TEY2253$216.00
23014-10 Cu/14-10 Al TEY2303$216.00
23514-12 Cu/12-10 Al TEY2353$216.00
24014-10 Cu/14-10 Al TEY2403$216.00
24514-12 Cu/12-10 Al TEY2453$216.00
25014-10 Cu/14-10 Al TEY2503$216.00
26014-10 Cu/14-10 Al TEY260 $216.00
2704-1 Cu/2-1/0 Al TEY270 $352.00
2804-1 Cu/2-1/0 Al TEY280 $352.00
2904-1 Cu/2-1/0 Al TEY290 $352.00
2100 4-1 Cu/2-1/0 Al TEY2100 $352.00
TEY 3 pole
65kA @120, 120/240, 240 Vac; 14kA @277 Vac GO-135B
# of Ampere
Poles Rating Wire Range1Product Number List Price
31514-12 Cu/12-10 Al TEY3153$316.00
32014-12 Cu/12-10 Al TEY3203$316.00
32514-12 Cu/12-10 Al TEY3253$316.00
33014-10 Cu/14-10 Al TEY3303$316.00
33514-12 Cu/12-10 Al TEY3353$316.00
34014-10 Cu/14-10 Al TEY3403$316.00
34514-12 Cu/12-10 Al TEY3453$316.00
35014-10 Cu/14-10 Al TEY3503$316.00
36014-10 Cu/14-10 Al TEY360 $316.00
3704-1 Cu/2-1/0 Al TEY370 $424.00
3804-1 Cu/2-1/0 Al TEY380 $424.00
3904-1 Cu/2-1/0 Al TEY390 $424.00
3100 4-1 Cu/2-1/0 Al TEY3100 $424.00
1Solid or stranded for 14-10 AWG.
2Single-pole, 15 and 20 ampere breakers are also UL listed as switching duty breakers, suitable for switching
120, 240, or 277 Vac.
3UL listed HID (high intensity discharge).
Miniature Circuit Breakers and Supplementary Protectors
Bolt-on Circuit Breakers
480Y/277V Class
The TEY is a one-inch wide per pole, compact, "bolt-on" circuit breaker for use on
grounded 480Y/277 Vac systems. The bolt-on mounting base, shown in the accessory
table on page 3-34, makes the TEY suitable for various applications as a lug-lug breaker.
1- 2- and 3-pole TEY breakers
Prices and data subject to change without notice
3-18 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
TQC, THQC 120/240 Vac GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number2List Price
1105kA 14-4 Cu/12-2 Al TQC1110WL $20.25
11510kA 14-8 Cu/12-8 Al THQC1115WL3,4 $20.25
12010kA 14-8 Cu/12-8 Al THQC1120WL3,4 $20.25
12510kA 14-8 Cu/12-8 Al THQC1125WL3$20.25
13010kA 14-8 Cu/12-8 Al THQC1130WL3$20.25
13510kA 8-3 Cu/8-3 Al THQC1135WL3$20.25
14010kA 8-3 Cu/8-3 Al THQC1140WL3$20.25
14510kA 8-3 Cu/8-3 Al THQC1145WL3$20.25
15010kA 8-3 Cu/8-3 Al THQC1150WL3$20.25
16010kA 8-3 Cu/8-3 Al THQC1160WL3$20.25
17010kA 6-1/0 Cu/4-1/0 Al THQC1170WL $39.00
TQC, THQC 120/240 Vac, Internal Common Trip GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number2List Price
2105kA 14-4 Cu/12-2 Al TQC2110WL $46.50
21510kA 14-8 Cu/12-8 Al THQC2115WL3$43.50
22010kA 14-8 Cu/12-8 Al THQC2120WL3$43.50
22510kA 14-8 Cu/12-8 Al THQC2125WL3$43.50
23010kA 14-8 Cu/12-8 Al THQC2130WL3$43.50
23510kA 8-3 Cu/8-3 Al THQC2135WL3$43.50
24010kA 8-3 Cu/8-3 Al THQC2140WL3$43.50
24510kA 8-3 Cu/8-3 Al THQC2145WL3$43.50
25010kA 8-3 Cu/8-3 Al THQC2150WL3$43.50
26010kA 8-3 Cu/8-3 Al THQC2160WL3$43.50
27010kA 6-1/0 Cu/4-1/0 Al THQC2170WL $83.50
28010kA 6-1/0 Cu/4-1/0 Al THQC2180WL $116.00
29010kA 6-1/0 Cu/4-1/0 Al THQC2190WL $116.00
2100 10kA 6-1/0 Cu/4-1/0 Al THQC21100WL $116.00
TQC, THQC 240 Vac, Internal Common Trip GO-135B
# of Ampere 240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number2List Price
2105kA 14-4 Cu/12-2 Al TQC22010WL $116.00
21510kA 14-8 Cu/12-8 Al THQC22015WL $116.00
22010kA 14-8 Cu/12-8 Al THQC22020WL $116.00
22510kA 14-8 Cu/12-8 Al THQC22025WL $116.00
23010kA 14-8 Cu/12-8 Al THQC22030WL $116.00
23510kA 8-3 Cu/8-3 Al THQC22035WL $116.00
24010kA 8-3 Cu/8-3 Al THQC22040WL $116.00
24510kA 8-3 Cu/8-3 Al THQC22045WL $116.00
25010kA 8-3 Cu/8-3 Al THQC22050WL $116.00
26010kA 8-3 Cu/8-3 Al THQC22060WL $116.00
27010kA 6-1/0 Cu/4-1/0 Al THQC22070WL $152.00
28010kA 6-1/0 Cu/4-1/0 Al THQC22080WL $173.00
29010kA 6-1/0 Cu/4-1/0 Al THQC22090WL $173.00
2100 10kA 6-1/0 Cu/4-1/0 Al THQC22100WL $173.00
3105kA 14-4 Cu/12-2 Al TQC32010WL $141.00
31510kA 14-8 Cu/12-8 Al THQC32015WL $141.00
32010kA 14-8 Cu/12-8 Al THQC32020WL $141.00
32510kA 14-8 Cu/12-8 Al THQC32025WL $141.00
33010kA 14-8 Cu/12-8 Al THQC32030WL $141.00
33510kA 8-3 Cu/8-3 Al THQC32035WL $141.00
34010kA 8-3 Cu/8-3 Al THQC32040WL $141.00
34510kA 8-3 Cu/8-3 Al THQC32045WL $141.00
35010kA 8-3 Cu/8-3 Al THQC32050WL $141.00
36010kA 8-3 Cu/8-3 Al THQC32060WL $141.00
37010kA 6-1/0 Cu/4-1/0 Al THQC32070WL $178.00
38010kA 6-1/0 Cu/4-1/0 Al THQC32080WL $202.00
39010kA 6-1/0 Cu/4-1/0 Al THQC32090WL $202.00
3100 10kA 6-1/0 Cu/4-1/0 Al THQC32100WL $202.00
1Solid or stranded for 14-10 AWG.
2Use additional suffix “BP” (THQC32020WLBP) for bulk pack of 48 poles. Carton weight 20 lbs. 15-60 ampere breakers only.
3Suitable for mounting on standard 35mm DIN Rail. Refer to table on page 3-21 for termination options.
4UL listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
UL listed HACR (heating, air conditioning and refrigeration). Refer to Q Line accessories listed on pages 3-34 to 3-36.
Miniature Circuit Breakers and Supplementary Protectors
Cable-in Cable-out (lug-lug)
240V Class
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-19
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
THQC 120 Vac, Ground Fault Circuit Interrupter GO-133
# of Ampere 120 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11510kA 14-8 Cu/12-8 Al THQC1115GF2$128.00
12010kA 14-8 Cu/12-8 Al THQC1120GF2$128.00
13010kA 14-8 Cu/12-8 Al THQC1130GF2$128.00
THHQC 120/240 Vac GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number3List Price
11522kA 14-8 Cu/12-8 Al THHQC1115WL4$35.50
12022kA 14-8 Cu/12-8 Al THHQC1120WL4$35.50
12522kA 14-8 Cu/12-8 Al THHQC1125WL4$40.50
13022kA 14-8 Cu/12-8 Al THHQC1130WL4$40.50
13522kA 8-3 Cu/8-3 Al THHQC1135WL4$40.50
14022kA 8-3 Cu/8-3 Al THHQC1140WL4$40.50
14522kA 8-3 Cu/8-3 Al THHQC1145WL4$40.50
15022kA 8-3 Cu/8-3 Al THHQC1150WL4$40.50
16022kA 8-3 Cu/8-3 Al THHQC1160WL4$40.50
17022kA 6-1/0 Cu/4-1/0 Al THHQC1170WL $52.00
THHQC 120/240 Vac, Internal Common Trip GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number3List Price
21522kA 14-8 Cu/12-8 Al THHQC2115WL4$83.50
22022kA 14-8 Cu/12-8 Al THHQC2120WL4$83.50
23022kA 14-8 Cu/12-8 Al THHQC2130WL4$83.50
23522kA 8-3 Cu/8-3 Al THHQC2135WL4$83.50
24022kA 8-3 Cu/8-3 Al THHQC2140WL4$83.50
24522kA 8-3 Cu/8-3 Al THHQC2145WL4$83.50
25022kA 8-3 Cu/8-3 Al THHQC2150WL4$83.50
26022kA 8-3 Cu/8-3 Al THHQC2160WL4$83.50
27022kA 6-1/0 Cu/4-1/0 Al THHQC2170WL $129.00
28022kA 6-1/0 Cu/4-1/0 Al THHQC2180WL $188.00
29022kA 6-1/0 Cu/4-1/0 Al THHQC2190WL $188.00
2100 22kA 6-1/0 Cu/4-1/0 Al THHQC21100WL $188.00
1Solid or stranded for 14-10 AWG.
2Requires mounting plate. See page 3-34. Not suitable for use in GE column panels.
3Use additional suffix “BP” (THQC32020WLBP) for bulk pack of 48 poles. Carton weight 20 lbs. 15 - 60 amperes
breakers only.
4Suitable for mounting on standard 35mm DIN Rail.
UL listed HACR (heating, air conditioning and refrigeration).
Use Q Line mounting accessories listed on pages 3-34 to 3-36.
Miniature Circuit Breakers and Supplementary Protectors
Cable-in Cable-out (lug-lug)
240V Class
THQC1120GF
Prices and data subject to change without notice
3-20 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
THHQC 240 Vac, Internal Common Trip GO-135B
# of Ampere 240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21522kA 14-8 Cu/12-8 Al THHQC22015WL $159.00
22022kA 14-8 Cu/12-8 Al THHQC22020WL $159.00
22522kA 14-8 Cu/12-8 Al THHQC22025WL $159.00
23022kA 14-8 Cu/12-8 Al THHQC22030WL $159.00
23522kA 8-3 Cu/8-3 Al THHQC22035WL $159.00
24022kA 8-3 Cu/8-3 Al THHQC22040WL $159.00
24522kA 8-3 Cu/8-3 Al THHQC22045WL $159.00
25022kA 8-3 Cu/8-3 Al THHQC22050WL $159.00
26022kA 8-3 Cu/8-3 Al THHQC22060WL $159.00
27022kA 6-1/0 Cu/4-1/0 Al THHQC22070WL $200.00
28022kA 6-1/0 Cu/4-1/0 Al THHQC22080WL $240.00
29022kA 6-1/0 Cu/4-1/0 Al THHQC22090WL $240.00
2100 22kA 6-1/0 Cu/4-1/0 Al THHQC22100WL $240.00
31522kA 14-8 Cu/12-8 Al THHQC32015WL $216.00
32022kA 14-8 Cu/12-8 Al THHQC32020WL $216.00
32522kA 14-8 Cu/12-8 Al THHQC32025WL $216.00
33022kA 14-8 Cu/12-8 Al THHQC32030WL $216.00
33522kA 8-3 Cu/8-3 Al THHQC32035WL $216.00
34022kA 8-3 Cu/8-3 Al THHQC32040WL $216.00
34522kA 8-3 Cu/8-3 Al THHQC32045WL $216.00
35022kA 8-3 Cu/8-3 Al THHQC32050WL $216.00
36022kA 8-3 Cu/8-3 Al THHQC32060WL $216.00
37022kA 6-1/0 Cu/4-1/0 Al THHQC32070WL $267.00
38022kA 6-1/0 Cu/4-1/0 Al THHQC32080WL $314.00
39022kA 6-1/0 Cu/4-1/0 Al THHQC32090WL $314.00
3100 22kA 6-1/0 Cu/4-1/0 Al THHQC32100WL $314.00
TXQC 120/240 Vac GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
11565kA 14-8 Cu/12-8 Al TXQC1115WL $63.50
12065kA 14-8 Cu/12-8 Al TXQC1120WL $63.50
12565kA 14-8 Cu/12-8 Al TXQC1125WL $63.50
13065kA 14-8 Cu/12-8 Al TXQC1130WL $63.50
TXQC 120/240 Vac, Internal Common Trip GO-135B
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
21565kA 14-8 Cu/12-8 Al TXQC2115WL $157.00
22065kA 14-8 Cu/12-8 Al TXQC2120WL $157.00
22565kA 14-8 Cu/12-8 Al TXQC2125WL $157.00
23065kA 14-8 Cu/12-8 Al TXQC2130WL $157.00
TXQC 240 Vac, Internal Common Trip GO-138A
# of Ampere 120/240 Vac
Poles Rating Interrupting Rating Wire Range1Product Number List Price
31565kA 14-8 Cu/12-8 Al TXQC32015WL $267.00
32065kA 14-8 Cu/12-8 Al TXQC32020WL $267.00
32565kA 14-8 Cu/12-8 Al TXQC32025WL $267.00
33065kA 14-8 Cu/12-8 Al TXQC32030WL $267.00
1Solid or stranded for 14-10 AWG.
UL listed HACR (heating, air conditioning and refrigeration).
Use Q Line mounting accessories listed on pages 3-34 to 3-36.
Miniature Circuit Breakers and Supplementary Protectors
Cable-in Cable-out (lug-lug)
240V Class
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-21
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Product Features
Multi-terminal Configuration Breakers
—35 mm DIN rail mounting
—Optional front/rear panel mounting kits–THQCFMK, page 3-34.
—Optional load end terminal for up to (4) 0.25-inch quick connnects.
Contact local GE sales office for ring terminal configurations–not DIN rail compatible.
Miniature Circuit Breakers and Supplementary Protectors
DIN-Rail Mount
240V Class
THQC, THHQC 120/240 Vac GO-135B
# of Ampere 120/240 Vac CC Suffix X2 Suffix
Poles Rating Interrupting Rating Product Number List Price List Price Adder List Price Adder
11510kA THQC1115LL1$17.25
12010kA THQC1120LL1$17.25
12510kA THQC1125LL $17.25
13010kA THQC1130LL $17.25
13510kA THQC1135LL $17.25
14010kA THQC1140LL $17.25
14510kA THQC1145LL $17.25
15010kA THQC1150LL $17.25
16010kA THQC1160LL $17.25 $4.00 $1.50
115 22kA THHQC1115LL $32.50
120 22kA THHQC1120LL $32.50
125 22kA THHQC1125LL $37.50
130 22kA THHQC1130LL $37.50
135 22kA THHQC1135LL $37.50
140 22kA THHQC1140LL $37.50
145 22kA THHQC1145LL $37.50
150 22kA THHQC1150LL $37.50
160 22kA THHQC1160LL $37.50
15-60A UL Listed HACR (heating, air conditioning and refrigeration)
THQC, THHQC 120/240 Vac, Internal Common Trip GO-135B
# of Ampere 120/240 Vac CC Suffix X2 Suffix
Poles Rating Interrupting Rating Product Number List Price List Price Adder List Price Adder
21510kA THQC2115LL1$37.50
22010kA THQC2120LL1$37.50
22510kA THQC2125LL $37.50
23010kA THQC2130LL $37.50
23510kA THQC2135LL $37.50
24010kA THQC2140LL $37.50
24510kA THQC2145LL $37.50
25010kA THQC2150LL $37.50
26010kA THQC2160LL $37.50 $8.00 $3.00
215 22kA THHQC2115LL $77.50
220 22kA THHQC2120LL $77.50
225 22kA THHQC2125LL $77.50
230 22kA THHQC2130LL $77.50
235 22kA THHQC2135LL $77.50
240 22kA THHQC2140LL $77.50
245 22kA THHQC2145LL $77.50
250 22kA THHQC2150LL $77.50
260 22kA THHQC2160LL $77.50
15-60A UL Listed HACR (heating, air conditioning and refrigeration)
Terminal Configuration
Suffix2Line Terminal Load Terminal
WL TQAL3A THQEL3
X2 TQAL3A N/A
LL N/A N/A
CC TQAL3A THQECC
None N/A THQEL3
115 and 20 ampere breakers UL listed as SWD (Switching Duty) rated. Suitable for
switching 120 Vac fluorescent lighting loads.
2Use additional suffix “BP” (THQC1120CCBP) for bulk pack of 48 poles. Must be ordered
in multiples of 48 poles.
Additional Q Line mounting accessories listed on pages 3-34 to 3-36.
Terminal Selection GO-135B
Type Wire Range Product Number List Price
Lug–Line only 14-6 Cu/12-2 Al TQAL3A $1.50
Lug–Load only 14-2 Cu/12-2 Al THQEL3 $1.50
Quick Connector–Load only (4) 14 Cu or (4) 12 Al THQECC $2.50
Prices and data subject to change without notice
3-22 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
TQD 240 Vac, Internal Common Trip GO-135F
# of Ampere 240 Vac
Poles Rating Interrupting Rating Product Number1,2 List Price
2100 10kA TQD22100WL $249.00
2125 10kA TQD22125WL $249.00
2150 10kA TQD22150WL $249.00
2175 10kA TQD22175WL $249.00
2200 10kA TQD22200WL $249.00
2225 10kA TQD22225WL $249.00
3100 10kA TQD32100WL $641.00
3125 10kA TQD32125WL $641.00
3150 10kA TQD32150WL $641.00
3175 10kA TQD32175WL $641.00
3200 10kA TQD32200WL $641.00
3225 10kA TQD32225WL $641.00
TQD 240 Vac, Internal Common Trip with Factory Installed 120 Vac Shunt Trip3GO-135F
# of Ampere 240 Vac
Poles Rating Interrupting Rating Product Number1,2 List Price
3125 10kA TQD32125ST1 $793.00
3150 10kA TQD32150ST1 $793.00
3175 10kA TQD32175ST1 $793.00
3200 10kA TQD32200ST1 $793.00
3225 10kA TQD32225ST1 $793.00
THQD 240 Vac, Internal Common Trip GO-135F
# of Ampere 240 Vac
Poles Rating Interrupting Rating Product Number1,2 List Price
2100 22kA THQD22100WL $568.00
2125 22kA THQD22125WL $568.00
2150 22kA THQD22150WL $568.00
2175 22kA THQD22175WL $568.00
2200 22kA THQD22200WL $568.00
2225 22kA THQD22225WL $568.00
3100 22kA THQD32100WL $907.00
3125 22kA THQD32125WL $907.00
3150 22kA THQD32150WL $907.00
3175 22kA THQD32175WL $907.00
3200 22kA THQD32200WL $907.00
3225 22kA THQD32225WL $907.00
TJD 240 Vac, Internal Common Trip GO-135F
# of Ampere 240 Vac
Poles Rating Interrupting Rating Product Number1,2 List Price
2250 22kA TJD422250WL $1494.00
2300 22kA TJD422300WL $1494.00
2350 22kA TJD422350WL $1494.00
2400 22kA TJD422400WL $1494.00
3250 22kA TJD432250WL4$1802.00
3300 22kA TJD432300WL4$1802.00
3350 22kA TJD432350WL4$1802.00
3400 22kA TJD432400WL4$1802.00
1Refer to table on page 3-101 for lug and wire range data.
2Includes line and load lugs. For optional configurations see page 3-38.
3For additional shunt trip options see page 3-88 .
4TJD uses same accessories as J600 line. TJD not listed HACR.
UL listed HACR (heating, air conditioning and refrigeration).
Miniature Circuit Breakers and Supplementary Protectors
Cable-in Cable-out (lug-lug)
240V Class
TJD432300WL
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-23
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Note: Molded case switches may be used as main devices in panelboards and switchboards
but cannot be used as subfeeds or branch breakers because they do not provide wire
protection. Q Line and TEB molded case switches have a 10,000 ampere symmetrical short
circuit withstand rating when protected by a fuse or circuit breaker rated 10,000 amperes IC
or greater and whose ampere rating does not exceed the ampere rating of the switch.
Plug-in TQL 120/240, Vac Internal Common Trip GO-138
# of Ampere 120/240 Vac
Poles Rating Short Circuit Withstand Rating Wire Range1Product Number List Price
26010kA 8-3 Cu/8-3 Al TQL21Y60 $51.00
2100 10kA 6-1/0 Cu/4-1/0 Al TQL21Y100 $147.00
Plug-in TQL 240, Vac Internal Common Trip GO-138
# of Ampere 240 Vac
Poles Rating Short Circuit Withstand Rating Wire Range1Product Number List Price
26010kA 8-3 Cu/8-3 Al TQL22Y60 $139.00
2100 10kA 6-1/0 Cu/4-1/0 Al TQL22Y100 $235.00
36010kA 8-3 Cu/8-3 Al TQL32Y60 $177.00
3100 10kA 6-1/0 Cu/4-1/0 Al TQL32Y100 $266.00
Bolt-on TQB 120/240, Vac Internal Common Trip GO-138
# of Ampere 120/240 Vac
Poles Rating Short Circuit Withstand Rating Wire Range1Product Number List Price
26010kA 8-3 Cu/8-3 Al TQB21Y60 $43.50
2100 10kA 6-1/0 Cu/4-1/0 Al TQB21Y100 $113.00
Bolt-on TQB 240 Vac, Internal Common Trip GO-138
# of Ampere 240 Vac
Poles Rating Short Circuit Withstand Rating Wire Range1Product Number List Price
26010kA 8-3 Cu/8-3 Al TQB22Y60 $113.00
2100 10kA 6-1/0 Cu/4-1/0 Al TQB22Y100 $170.00
36010kA 8-3 Cu/8-3 Al TQB32Y60 $139.00
3100 10kA 6-1/0 Cu/4-1/0 Al TQB32Y100 $199.00
Cable In-Cable Out (Lug-Lug) TQC 120/240 Vac, Internal Common Trip GO-135B
# of Ampere 120/240 Vac
Poles Rating Short Circuit Withstand Rating Wire Range1Product Number List Price
26010kA 8-3 Cu/8-3 Al TQC21Y602$43.50
2100 10kA 6-1/0 Cu/4-1/0 Al TQC21Y100 $116.00
Cable In-Cable Out (Lug-Lug) TQC 240 Vac, Internal Common Trip GO-135B
# of Ampere 240 Vac
Poles Rating Short Circuit Withstand Rating Wire Range1Product Number List Price
26010kA 8-3 Cu/8-3 Al TQC22Y603$116.00
2100 10kA 6-1/0 Cu/4-1/0 Al TQC22Y100 $173.00
36010kA 8-3 Cu/8-3 Al TQB32Y60 $139.00
3100 10kA 6-1/0 Cu/4-1/0 Al TQB32Y100 $199.00
Cable In-Cable Out (Lug-Lug) TQD, TJD 240 Vac, Internal Common Trip GO-135F
# of Ampere 240 Vac
Poles Rating Short Circuit Withstand Rating Product Number 6List Price
2225 14kA TQD22Y225 $198.00
3225 14kA TQD32Y2254$559.00
2400 22kA TJD422Y400 $1169.00
3400 22kA TJD432Y4005$1509.00
1Solid or stranded for 14-10 AWG.
2Suitable for mounting on 35 mm DIN rail.
3For additional shunt trip offerings, see page 3-88.
4TQD32YT225 with dummy trip used for accessorized applications.
5TJD uses same accessories as J600 line.
6Refer to table on page 3-101 for lug and wire range data. Line and load lugs included in basic switch product number.
Miniature Circuit Breakers and Supplementary Protectors
Molded Case Switches
Prices and data subject to change without notice
3-24 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
E2000 Miniature Circuit Breakers
EP60 Series
Performance
Thermal setting In (A) 0.5-63
Rated Vac Un (V) 240/415
Minimum operating voltage UBmin (V) 12
Tripping characteristics B-C-D
Selectivity class 3
Mechanical/electrical endurance 20000/10000
Tr opicalisation acc. to IEC 60068-2 95% RH at 55°C
Te r minal capacity flexible/rigid cable mm225-35
Poles 1, 2, 3, 4
Weight (g/pole) 120
Auxiliaries
Add-on Devices
Short-circuit Capacity
Per UL 1077 & CSA 22.2 No. 235-1989 (File E151139)
Max. Voltage Short Circuit Rating
Rating kAIC RMS Symmetrical kAIC DC
Poles AC DC 120 120/240 277 480Y/277 50 110
1277 50 10 6 6 10
2480Y/277 110 10 10 6 6 10
3, 4 480Y/277 110 10 10 6 6
AC acc. to IEC 60898
Poles V Icn/Ics (kA)
1-4 230/400 6
AC acc. to IEC 60947-2
Poles V Icu (kA)1
1240 10
2,3,4 240 20
2,3,4 415 10
1Ics = 75% Icu
DC acc. to IEC 60947-2
Poles V Icu/Ics (kA)
16020
212525
Applications
—Residential
—Commercial
—Industrial
Approval/Marking
—CE
—cURus
—CEBEC
—KEMA EUR
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-25
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
E2000 Miniature Circuit Breakers
EP60 Series
1 Pole
EP60 Series, 6 kAIC @277 or 480Y/277 Vac, Tripping Characteristics B-C-D GO-135VB
Tripping Characteristic
B (3-5X) C (5-10X) D (10-20X) List
Poles Std. Pack 6 kAIC In (A) Product No. Product No. Product No. Price
0.5 EP61ULC0.5 EP61ULD0.5 $78.00
1–EP61ULC01 EP61ULD01 $65.00
2–EP61ULC02 EP61ULD02 $65.00
3–EP61ULC03 EP61ULD03 $65.00
4–EP61ULC04 EP61ULD04 $65.00
5EP61ULB05 EP61ULC05 EP61ULD05 $65.00
6EP61ULB06 EP61ULC06 EP61ULD06 $65.00
10 EP61ULB10 EP61ULC10 EP61ULD10 $65.00
112
13 EP61ULB13 EP61ULC13 EP61ULD13 $65.00
15 EP61ULB15 EP61ULC15 EP61ULD15 $65.00
16 EP61ULB16 EP61ULC16 EP61ULD16 $65.00
20 EP61ULB20 EP61ULC20 EP61ULD20 $65.00
25 EP61ULB25 EP61ULC25 EP61ULD25 $65.00
30 EP61ULB30 EP61ULC30 EP61ULD30 $65.00
32 EP61ULB32 EP61ULC32 EP61ULD32 $65.00
40 EP61ULB40 EP61ULC40 EP61ULD40 $72.00
50 EP61ULB50 EP61ULC50 EP61ULD50 $76.00
60 EP61ULB60 EP61ULC60 EP61ULD60 $80.00
63 EP61ULB63 EP61ULC63 EP61ULD63 $80.00
0.5 EP62ULC0.5 EP62ULD0.5 $156.00
1–EP62ULC01 EP62ULD01 $141.00
2–EP62ULC02 EP62ULD02 $141.00
3–EP62ULC03 EP62ULD03 $141.00
4–EP62ULC04 EP62ULD04 $141.00
5EP62ULB05 EP62ULC05 EP62ULD05 $141.00
6EP62ULB06 EP62ULC06 EP62ULD06 $141.00
10 EP62ULB10 EP62ULC10 EP62ULD10 $141.00
26
13 EP62ULB13 EP62ULC13 EP62ULD13 $141.00
15 EP62ULB15 EP62ULC15 EP62ULD15 $141.00
16 EP62ULB16 EP62ULC16 EP62ULD16 $141.00
20 EP62ULB20 EP62ULC20 EP62ULD20 $141.00
25 EP62ULB25 EP62ULC25 EP62ULD25 $141.00
30 EP62ULB30 EP62ULC30 EP62ULD30 $141.00
32 EP62ULB32 EP62ULC32 EP62ULD32 $141.00
40 EP62ULB40 EP62ULC40 EP62ULD40 $145.00
50 EP62ULB50 EP62ULC50 EP62ULD50 $156.00
60 EP62ULB60 EP62ULC60 EP62ULD60 $164.00
63 EP62ULB63 EP62ULC63 EP62ULD63 $164.00
0.5 EP63ULC0.5 EP63ULD0.5 $230.00
1–EP63ULC01 EP63ULD01 $204.00
2–EP63ULC02 EP63ULD02 $204.00
3–EP63ULC03 EP63ULD03 $204.00
4–EP63ULC04 EP63ULD04 $204.00
5EP63ULB05 EP63ULC05 EP63ULD05 $204.00
6EP63ULB06 EP63ULC06 EP63ULD06 $204.00
10 EP63ULB10 EP63ULC10 EP63ULD10 $204.00
34
13 EP63ULB13 EP63ULC13 EP63ULD13 $204.00
15 EP63ULB15 EP63ULC15 EP63ULD15 $204.00
16 EP63ULB16 EP63ULC16 EP63ULD16 $204.00
20 EP63ULB20 EP63ULC20 EP63ULD20 $204.00
25 EP63ULB25 EP63ULC25 EP63ULD25 $204.00
30 EP63ULB30 EP63ULC30 EP63ULD30 $204.00
32 EP63ULB32 EP63ULC32 EP63ULD32 $204.00
40 EP63ULB40 EP63ULC40 EP63ULD40 $210.00
50 EP63ULB50 EP63ULC50 EP63ULD50 $219.00
60 EP63ULB60 EP63ULC60 EP63ULD60 $229.00
63 EP63ULB63 EP63ULC63 EP63ULD63 $229.00
0.5 EP64ULC0.5 EP64ULD0.5 $300.00
1–EP64ULC01 EP64ULD01 $269.00
2–EP64ULC02 EP64ULD02 $269.00
3–EP64ULC03 EP64ULD03 $269.00
4–EP64ULC04 EP64ULD04 $269.00
5EP64ULB05 EP64ULC05 EP64ULD05 $269.00
6EP64ULB06 EP64ULC06 EP64ULD06 $269.00
10 EP64ULB10 EP64ULC10 EP64ULD10 $269.00
43
13 EP64ULB13 EP64ULC13 EP64ULD13 $269.00
15 EP64ULB15 EP64ULC15 EP64ULD15 $269.00
16 EP64ULB16 EP64ULC16 EP64ULD16 $269.00
20 EP64ULB20 EP64ULC20 EP64ULD20 $269.00
25 EP64ULB25 EP64ULC25 EP64ULD25 $269.00
30 EP64ULB30 EP64ULC30 EP64ULD30 $269.00
32 EP64ULB32 EP64ULC32 EP64ULD32 $269.00
40 EP64ULB40 EP64ULC40 EP64ULD40 $272.00
50 EP64ULB50 EP64ULC50 EP64ULD50 $285.00
60 EP64ULB60 EP64ULC60 EP64ULD60 $293.00
63 EP64ULB63 EP64ULC63 EP64ULD63 $293.00
2 Pole
3 Pole
4 Pole
Prices and data subject to change without notice
3-26 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
E2000 Miniature Circuit Breakers
EP100 Series
Performance
Thermal setting In (A) 0.5-63
Rated Vac Un (V) 240/415
Minimum operating voltage UBmin (V) 12
Tripping characteristics B-C-D
Selectivity class 3
Mechanical/electrical endurance 20000/10000
Tr opicalisation acc. to IEC 60068-2 95% RH at 55°C
Te r minal capacity flexible/rigid cable mm225-35
Poles 1, 2, 3, 4
Weight (g/pole) 120
Auxiliaries
Add-on Devices
Short-circuit Capacity
Per UL 1077 & CSA 22.2 No. 235-1989 (File E151139)
Max. Voltage Short Circuit Rating
Rating kAIC RMS Symmetrical kAIC DC
Poles AC DC 120 120/240 277 480Y/277 50 110
1277 50 10 10–10–
2480Y/277 110 10 10 10 10
3, 4 480Y/277 110 10 10 10 10
AC acc. to IEC 60898
Poles V Icn (kA)1
1-4 230/400 10
1Ics = 75% Icu
AC acc. to IEC 60947-2
Poles V Icu (kA)2
1240 15
2,3,4 240 30
2,3,4 415 15
2Ics = 50% Icu
DC acc. to IEC 60947-2
Poles V Icu/Ics (kA)
16025
212530
Applications
—Residential
—Commercial
—Industrial
Approval/Marking
—CE
—cURus
—CEBEC
—KEMA EUR
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-27
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
E2000 Miniature Circuit Breakers
EP100 Series
1 Pole
EP100 Series, 10 kAIC @120 or 120/240 Vac, Tripping Characteristics B-C-D GO-135VB
Tripping Characteristic
B (3-5X) C (5-10X) D (10-20X) List
Poles Std. Pack 6 kAIC In (A) Product No. Product No. Product No. Price
0.5 EP101ULC0.5 EP101ULD0.5 $116.00
1–EP101ULC01 EP101ULD01 $97.00
2–EP101ULC02 EP101ULD02 $97.00
3–EP101ULC03 EP101ULD03 $97.00
4–EP101ULC04 EP101ULD04 $97.00
5EP101ULB05 EP101ULC05 EP101ULD05 $97.00
6EP101ULB06 EP101ULC06 EP101ULD06 $97.00
10 EP101ULB10 EP101ULC10 EP101ULD10 $97.00
112
13 EP101ULB13 EP101ULC13 EP101ULD13 $97.00
15 EP101ULB15 EP101ULC15 EP101ULD15 $97.00
16 EP101ULB16 EP101ULC16 EP101ULD16 $97.00
20 EP101ULB20 EP101ULC20 EP101ULD20 $97.00
25 EP101ULB25 EP101ULC25 EP101ULD25 $97.00
30 EP101ULB30 EP101ULC30 EP101ULD30 $97.00
32 EP101ULB32 EP101ULC32 EP101ULD32 $97.00
40 EP101ULB40 EP101ULC40 EP101ULD40 $107.00
50 EP101ULB50 EP101ULC50 EP101ULD50 $113.00
60 EP101ULB60 EP101ULC60 EP101ULD60 $119.00
63 EP101ULB63 EP101ULC63 EP101ULD63 $119.00
0.5 EP102ULC0.5 EP102ULD0.5 $233.00
1–EP102ULC01 EP102ULD01 $210.00
2–EP102ULC02 EP102ULD02 $210.00
3–EP102ULC03 EP102ULD03 $210.00
4–EP102ULC04 EP102ULD04 $210.00
5EP102ULB05 EP102ULC05 EP102ULD05 $210.00
6EP102ULB06 EP102ULC06 EP102ULD06 $210.00
10 EP102ULB10 EP102ULC10 EP102ULD10 $210.00
26
13 EP102ULB13 EP102ULC13 EP102ULD13 $210.00
15 EP102ULB15 EP102ULC15 EP102ULD15 $210.00
16 EP102ULB16 EP102ULC16 EP102ULD16 $210.00
20 EP102ULB20 EP102ULC20 EP102ULD20 $210.00
25 EP102ULB25 EP102ULC25 EP102ULD25 $210.00
30 EP102ULB30 EP102ULC30 EP102ULD30 $210.00
32 EP102ULB32 EP102ULC32 EP102ULD32 $210.00
40 EP102ULB40 EP102ULC40 EP102ULD40 $216.00
50 EP102ULB50 EP102ULC50 EP102ULD50 $233.00
60 EP102ULB60 EP102ULC60 EP102ULD60 $245.00
63 EP102ULB63 EP102ULC63 EP102ULD63 $245.00
0.5 EP103ULC0.5 EP103ULD0.5 $343.00
1–EP103ULC01 EP103ULD01 $304.00
2–EP103ULC02 EP103ULD02 $304.00
3–EP103ULC03 EP103ULD03 $304.00
4–EP103ULC04 EP103ULD04 $304.00
5EP103ULB05 EP103ULC05 EP103ULD05 $304.00
6EP103ULB06 EP103ULC06 EP103ULD06 $304.00
10 EP103ULB10 EP103ULC10 EP103ULD10 $304.00
34
13 EP103ULB13 EP103ULC13 EP103ULD13 $304.00
15 EP103ULB15 EP103ULC15 EP103ULD15 $304.00
16 EP103ULB16 EP103ULC16 EP103ULD16 $304.00
20 EP103ULB20 EP103ULC20 EP103ULD20 $304.00
25 EP103ULB25 EP103ULC25 EP103ULD25 $304.00
30 EP103ULB30 EP103ULC30 EP103ULD30 $304.00
32 EP103ULB32 EP103ULC32 EP103ULD32 $304.00
40 EP103ULB40 EP103ULC40 EP103ULD40 $314.00
50 EP103ULB50 EP103ULC50 EP103ULD50 $327.00
60 EP103ULB60 EP103ULC60 EP103ULD60 $342.00
63 EP103ULB63 EP103ULC63 EP103ULD63 $342.00
0.5 EP104ULC0.5 EP104ULD0.5 $448.00
1–EP104ULC01 EP104ULD01 $401.00
2–EP104ULC02 EP104ULD02 $401.00
3–EP104ULC03 EP104ULD03 $401.00
4–EP104ULC04 EP104ULD04 $401.00
5EP104ULB05 EP104ULC05 EP104ULD05 $401.00
6EP104ULB06 EP104ULC06 EP104ULD06 $401.00
10 EP104ULB10 EP104ULC10 EP104ULD10 $401.00
43
13 EP104ULB13 EP104ULC13 EP104ULD13 $401.00
15 EP104ULB15 EP104ULC15 EP104ULD15 $401.00
16 EP104ULB16 EP104ULC16 EP104ULD16 $401.00
20 EP104ULB20 EP104ULC20 EP104ULD20 $401.00
25 EP104ULB25 EP104ULC25 EP104ULD25 $401.00
30 EP104ULB30 EP104ULC30 EP104ULD30 $401.00
32 EP104ULB32 EP104ULC32 EP104ULD32 $401.00
40 EP104ULB40 EP104ULC40 EP104ULD40 $407.00
50 EP104ULB50 EP104ULC50 EP104ULD50 $425.00
60 EP104ULB60 EP104ULC60 EP104ULD60 $437.00
63 EP104ULB63 EP104ULC63 EP104ULD63 $437.00
2 Pole
3 Pole
4 Pole
Prices and data subject to change without notice
3-28 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
E2000 Miniature Circuit Breakers
EP100 UC Series1
Performance
Thermal setting In (A) 0.5-63
Rated Vac Un (V) 240/400; 230/440
Minimum operating voltage UBmin (V) 12
Tripping characteristics B-C
Selectivity class 3
Mechanical/electrical endurance 20000/10000
Tr opicalisation acc. to IEC 60068-2 95% RH at 55°C
Te r minal capacity flexible/rigid cable mm225-35
Poles 1, 2
Weight (g/pole) 120
Auxiliaries
Add-on Devices
Short-circuit Capacity
AC acc. to IEC 60898
Poles V Icn/Ics (kA)
125 DC 10
1220 DC 6
230/400 AC 6
250 DC 10
2440 DC 6
400 AC 6
AC acc. to IEC 60947-2
Poles V Icu/Ics (kA)
1, 2 240 AC 10
Applications
—Industrial
Approval/Marking
—IEC 60898-2, DIN VDE 0641
—CE
1Not UL approved
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-29
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
E2000 Miniature Circuit Breakers
EP100 UC Series1
1 Pole
EP100 UC Series, 6 kAIC @400 or 230/400 Vac, Tripping Characteristics B-C GO-135VB
Tripping Characteristic
B (3-5X) C (5-10X) List
Poles Std. Pack 6 kAIC In (A) Product No. Product No. Price
0.5 EP101UCC0.5 $145.00
1– EP101UCC01 $121.00
2– EP101UCC02 $121.00
4– EP101UCC04 $121.00
6EP101UCB06 EP101UCC06 $121.00
10 EP101UCB10 EP101UCC10 $121.00
11216EP101UCB16 EP101UCC16 $121.00
20 EP101UCB20 EP101UCC20 $121.00
25 EP101UCB25 EP101UCC25 $121.00
32 EP101UCB32 EP101UCC32 $121.00
40 EP101UCB40 EP101UCC40 $121.00
50 EP101UCB50 EP101UCC50 $145.00
63 EP10s1UCB63 EP101UCC63 $163.00
0.5 EP102UCC0.5 $320.00
1– EP102UCC01 $267.00
2– EP102UCC02 $267.00
4– EP102UCC04 $267.00
6EP102UCB06 EP102UCC06 $267.00
10 EP102UCB10 EP102UCC10 $267.00
2616 EP102UCB16 EP102UCC16 $267.00
20 EP102UCB20 EP102UCC20 $267.00
25 EP102UCB25 EP102UCC25 $267.00
32 EP102UCB32 EP102UCC32 $267.00
40 EP102UCB40 EP102UCC40 $267.00
50 EP102UCB50 EP102UCC50 $319.00
63 EP102UCB63 EP102UCC63 $360.00
1Not UL approved
2 Pole
Prices and data subject to change without notice
3-30 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
E2000 Miniature Circuit Breakers
Series CA Auxiliary Switch and Bell Alarm
Applications
—Commercial
—Industrial
Features
—Common for all MCBs
—Can be coupled on both sides of MCBs
—Gold contact version available for low current and low voltage
applications
—Stack up to four CA on left and right sides
—Permits the pass-through of busbars, pin and fork, top and bottom,
by changing the position of the base of the auxiliaries
Performance
Change-over contacts 1 Form C
Rate current In (A) 5
Rated voltage AC Un (V) 240
Electrical endurance 10000
Te r minal capacity flexible/rigid cable (mm2)2.5
Weight (g) 70
Functions
Auxiliary contacts are units to be added on to protection devices.
They allow information about the status of the protection device to
be monitored from a distance.
Auxiliary contact CA H (function H) reports the OPEN/CLOSED status.
CA S/H or CA S/H G act as either an auxiliary contact (function H) or
a signal contact (function S). The user can set the function at the
time of installation. When used as a signal contact, it reports infor-
mation about the automatic tripping of the protection devices. A test
button on the front simulates functions H or S. There are also a reset
button for the contacts (function S) and a tripping signal (function S).
Approval/Marking
—CE
—cURus
—CEBEC
—KEMA EUR
Series CA GO-135VB
Function Std. Pack Product No. List Price
H1CA H $47.00
S/H 1 CA S/H $59.00
S/H (gold contacts) 1 CA S/H G $59.00
HS
1/2 mod.
Coupling
Stack-on
Busbar pass-through
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-31
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
E2000 Miniature Circuit Breakers
Series CB Auxiliary Switch and Bell Alarm
Applications
—Commercial
—Industrial
Features
—Common for all MCBs
—Can be coupled on both sides of MCBs
—There are two change-over contacts – the upper one features
changeable function S/H
—CB SH/HH-R couples to the right side of the protection devices;
CB SH/HH-L couple to the left
—No stack-on possibilities (only one auxiliary)
—No busbar pass-through facilities
Performance
Change-over contacts 2 Form C
Rate current In (A) 5
Rated voltage AC Un (V) 240
Electrical endurance 10000
Te r minal capacity flexible/rigid cable (mm2)2.5
Weight (g) 80
Functions
The bottom auxiliary contact (function H) reports the OPEN/CLOSED
status.
The top auxiliary contact can act as either an auxiliary contact
(function H) or a signal contact (function S). The user can set the
function at the time of installation. When used as a signal contact,
it reports information about the automatic tripping of the protection
devices.
A test button on the front simulates functions H or S. There are also
a reset button for the contacts (function S) and a tripping signal
(function S).
Approval/Marking
—cURus
Series CB GO-135VB
Function Coupling Std. Pack Product No. List Price
SH/HH Right 1 CB SH/HH-R $87.00
SH/HH Left 1 CB SH/HH-R $87.00 1/2 mod.
Coupling left
Coupling right
HS
Prices and data subject to change without notice
3-32 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
E2000 Miniature Circuit Breakers
Shunt Trip and Undervoltage Release
Applications
—Commercial
—Industrial
Features
—Common devices for all miniature circuit breakers
—Can be coupled on both sides of MCBs
—Permits pass-through of busbars, pin and fork, at top or
bottom terminals
—Stack up to four modules on left and right sides
Approval/Marking
—CURUS
—IEC 947-2
Shunt Trip Tele L
The Tele L allows remote switching of any miniature circuit breaker
by means of push buttons or any other automatic management
processor. A built-in contact, in series with the coil, prevents burnout
damage if the voltage remains.
Shunt Trip Tele L Performance
Rated voltage (V) 110/415, 110/125 DC
(V) 24/60, 24/48 DC
Tripping time (ms) <10
Electrical endurance 10000
Te r minal capacity flexible/rigid cable (mm2)2.5
Weight (g) 125
Shunt Trip Tele L GO-135VB
Voltage
Poles Std. Pack AC DC Product No. List Price
11
24-60 V 24-48 V TELE L-1 $90.00
110-415 V 110-125 V TELE L-2 $90.00
Undervoltage Release Tele U
The Tele U releases the main miniature circuit breaker in case the
power supply drops below 0.5xUn. Time delay is adjustable up to 300 ms.
Undervoltage Release Tele U Performance
Rated voltage AC UN (V) 240
Rated voltage DC/AC UN (V) 12, 24, 48 DC/AC
Tripping voltage (V) 0.5xUN ±10%
Resetting voltage (V) >0.5xUN ±10%
Tripping time (ms) Adjustable 1-300
Electrical endurance 2000
Te r minal capacity flexible/rigid cable (mm2)2.5
Weight (g) 125
Undervoltage Release Tele U GO-135VB
Poles Std. Pack Voltage Product No. List Price
AC 230V TELE U-230 $128.00
11 AC/DC 12V TELE U-12 $128.00
AC/DC 24V TELE U-24 $128.00
AC/DC 48V TELE U-48 $128.00
Coupling
Stack-on
Busbar pass-through
Shunt Trip Tele L Undervoltage Release Tele L
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-33
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
E2000 Miniature Circuit Breakers
Technical Data
Series
EP60 EP100 EP100 UC
Standards UL1077, EN60947-2 UL1077, EN60947-2 IEC EN70898-2
Tripping characteristics B, C, D B, C, D B, C
Nominal current AB: 6-63, C/D: 0.5-63 B: 6-63, C/D: 0.5-63 B: 6-63, C: 0.5-63
Calibration temperature °C 30 30 30
Number of poles (# mod) 1/1+N/2/3/4 1/1+N/2/3/4 1/2
Neutral pole protected yes yes
Nominal voltage Un AC 1P V 240/415 240/415 240/415
2P V 415 415 415
3P/3P+N/4P V 415 415 415
DC 1P (1) Vdc 48 48 220
2P (in series) (1) Vdc 110 110 440
Frequency Hz 50/60 50/60 50/60
Hz DC:magn.trip + 40% DC:magn.trip + 40% DC:magn.trip + 40%
Hz DC:magn.trip + 50% 400:magn.trip + 50% 400:magn.trip + 50%
Maximum service voltage Ubmax between two wires V 250/440; 53/120 250/440; 53/120 250/440; 250/440
Minimum service voltage Ubmin V 12; 12 12; 12 12; 12
Selectivity class (IEC 60898) 333
Isolator application IEC 60947-2 yes yes yes
Rated insulation voltage – Pollution Degree 2 V 500 500 500
Rated insulation voltage – Pollution Degree 3 V 440 440 440
Impulse withstand test voltage Kv 666
Insulation resistance Mohm 10000 10000 10000
Dielectric rigidity Kv 2.5 2.5 2.5
Vibrations resistance (in x,y,z direction) (IEC 77/16,3) 3g 3g 3g
Endurance – electrical at Un, In 10000 10000 1000
Endurance – mechanical 20000 20000 20000
Utilization category (IEC 60947 - 2) AAA
Mounting position any any any
Incoming top or bottom yes yes yes
Protection degree (outside/inside enclosure with door) IP20/IP40 IP20/IP40 IP20/IP40
Self extinguish degree (according to UL94) V2 V2 V2
Tr opicalisation (according to IEC 60068-2/DIN 40046) °C/RH +55%°C/95% RH +55%°C/95% RH +55%°C/95% RH
Operating temperature °C -25/+55 -25/+55 -25/+55
Storage temperature °C -55/+55 -55/+55 -55/+55
Te r minal capacity – Rigid cable min/max (top) mm21/35 1/35 1/35
Te r minal capacity – Flexible cable min*/max (top) mm20.75/25 0.75/25 0.75/25
(*Flexible cable 0.75/1/1.5 mm2with cable lug)
Te r minal capacity – Rigid cable min/max (bottom) mm21/35 1/35 1/35
Te r minal Capacity – Flexible cable min*/max (bottom) mm20.75/25 0.75/25 0.75/25
(*Flexible cable 0.75/1/1.5 mm2with cable lug)
To r que Nm 4.5 4.5 4.5
Add-on services – Auxiliary contacts yes yes yes
Add-on services – Tele U yes yes yes
Add-on services – Tele L yes yes yes
Busbar systems – pin (top/bottom) (non-UL) yes/yes yes/yes yes/yes
Busbar systems – fork (top/bottom) (non-UL) -/yes -/yes -/yes
Accessories yes yes yes
Dimensions, weights, packaging (HxDxW) 86x68xW mm/mod 18 18 18
Weight/mod g 120 120 125
Package mod. 12 12 12
Approvals KEMA KEMA -
CE-marking yes yes yes
Prices and data subject to change without notice
3-34 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Terminals (Lugs) for Q Line Circuit Breakers GO-135B
Ampere Rating Termination Type Wire Range (Cu/Al) Product Number List Price
15-60 Lug (line only) 14-6/12-2 TQAL3A $1.50
15-60 Lug (load only) 14-2/12-2 THQEL3 $1.50
15-60 Quick connector (load only) (4) 14/(4) 12 THQECC $2.50
Internal Accessories for TEY (2- and 3-pole breaker only)
Factory Installed Only GO-135B
Auxiliary Switch,
Single-Pole Add suffix to Breaker
(6A at 240 Vac,1/2A at 125 Vdc, 1/4A at 250 Vdc) Product Number List Price Adder
"A" switch (normally open) AS1A $148.00
"B" switch (normally closed) AS1B $148.00
"AB" switch (both) ASAB $288.00
Shunt Trip 120-277 Vac control voltage ST12 $358.00
Mounting Accessories for THQB, THQC, TEY GO-135B
Product Ampere # of Used With List
Type Rating Poles Frame Product Number Price
Bolt-on Mounting Base 3 TEY TEY3B $31.50
THQB
Back Mounting Plates 1 THQC TQCBMPA1 $8.30
Screw Type
Back Mounting Plates 2 THQC TQCBMPA2 $9.80
Screw Type
Back Mounting Plates 3 THQC TQCBMPA3 $12.00
Screw Type
Back Mounting Plates 10 THQC TQCBMPA10 $32.00
Screw Type
Front-mounting Plates 1 THQC TQCFMP11$8.30
Front-mounting Plates 2 THQC TQCFMP21$9.80
Front-mounting Plates 3 THQC TQCFMP31$12.00
Front-mounting Plates 4 THQC TQCFMP41$14.00
Front/Rear Mounting 15-60A 1 & 2 THQC THQCFMK2$48.00
Clips
DIN rail clips 15-60A 1 & 2 THQC THQCDIN2$24.00
1Not UL listed.
2Price is per pack.
Mounting Accessories for THQC, THQC-GF, GFEP, AF GO-133
Product Type # of Poles Used With Frame Product Number List Price
Snap In Back 1 THQC, THQC-GF TQCGFBMPA1 $6.10
Mounting Plates
Snap In Back 2 THQC, THQC-GF TQCGFBMPA2 $7.60
Mounting Plates
Snap In Back 3 THQC, THQC-GF TQCGFBMPA3 $9.10
Mounting Plates
Snap In Back 10 THQC, THQC-GF TQCGFBMPA10 $25.00
Mounting Plates
Mounting Accessories for TQL G0-134A
Product Ampere # of Used With List
Type Rating Poles Frame Product Number Price
Plug-in Mounting Base 70 amp 2 TQL 571B595DDG1 $23.75
Plug-in Mounting Base 70 amp 3 TQL 571B595DDG2 $32.00
Plug-in Mounting Base 100 amp 3 TQL 565B837G1 $38.00
Plug-in Mounting Base 100 amp 2 TQL 565B837G2 $23.75
Miniature Circuit Breakers and Supplementary Protectors
Accessories
Quick Connector THQECC
Load Lug THQEL3
Mounting Kit THQCFMK
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-35
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Handle Locking Devices GO-135B
Product Type Used With Frame Product Number List Price
Handle Locks - TQC THL103 $6.501
Non Padlocking TQB
TQL
Handle Locks - THQP TQPL $5.501
Non Padlocking
Handle Locks - TEY TEYLD1 $5.00
Non Padlocking
Handle Locks - E150 Line TLD3 $5.00
Non Padlocking
Handle Locks - THLC2, 4 TFKLD1 $6.00
Non Padlocking F225 Line
Handle Locks - SF250 SBD1 $4.702
Non Padlocking SE150
Handle Locking Devices GO-137A
Product Type Used With Frame Product Number List Price
Handle Locks - Padlocking TQD TQDPLD13$20.75
Handle Locks - Padlocking TQDL TQDLPDL13$17.75
Handle Locks - Padlocking TQB THP100 $6.501
TQL
Handle Locks - Padlocking THQP TQPPL $5.75
Handle Locking Devices GO-135B
Product Type Used With Frame Product Number List Price
Handle Locks - Padlocking TQC TQPLD13$4.70
Handle Locks - Padlocking TEY TEYPLD1 $9.00
Handle Locks - Padlocking E150 TEFPLD1 $8.00
TB1
Handle Locks - Padlocking THLC1 TLC1PLD1 $17.00
Handle Locks - Padlocking F225 TFKPLD1 $4.00
Handle Locks - Padlocking THLC2 TLC4PLD1 $22.00
THLC4
TLB4
Handle Locks - Padlocking J600 Line TJKPLD1 $8.00
Handle Locks - Padlocking K1200 Line TKMPLD1 $28.50
Handle Locking Devices GO-135S
Product Type Used With Frame Product Number List Price
Handle Locks - Padlocking SF250 SEPLD3$8.70
SE150
Handle Locks - Padlocking SG600 SGPLD3$15.00
Handle Locks - Padlocking SK1200 SKPLD3$28.50
1GO-137A.
2GO-135S.
3Suitable for circuit breakers used in group mounted panelboard construction only except for J600, K1200, SE150/SE250,
SG600 and SK1200 which screw down to face of breaker.
Miniature Circuit Breakers and Supplementary Protectors
Accessories
THL103
THP100
Prices and data subject to change without notice
3-36 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Handle Locking and Handle Extension Devices EUSERC Approved —
Factory Installed Only GO-135B
Product Type Used With Frame Product Number List Price
Handle Locks - Padlocking TQDPLD2 $32.00
Handle Locks - Padlocking TEDPLD2 $32.00
Handle Locks - Padlocking TJKPLD2 $48.00
Handle Locks - Padlocking THLC1PLD2 $48.00
Handle Locks - Padlocking THLC4PLD2 $48.00
Handle Locks - Padlocking SEFPLD2 $32.001,2
Handle Locks - Padlocking SGPLD2 $48.001
Handle Locks - Padlocking SKPLD2 $60.001
Handle Locking and Handle Extension Devices GO-137A
Product Type Used With Frame Product Number List Price
Snap-on Handle Tie - open THQP THT23$2.30
Snap-on Handle Tie - solid TQL THT104 $2.30
Snap-on Handle Tie - solid, THQP THT1 $2.30
indicating
Snap-on Handle Tie - trip TQC TQHT1 $2.30
indicating
Handle Extension - replacement SK1200 SKHDLEXT $96.501
Breaker Mounting Screw Kits GO-135B
Product Type Used With Frame Product Number List Price
Breaker Mounting Screw Kits THQB TQBS14$6.00
1GO-135S.
2Field Installable
3For 2 THQPs separated by 2 side-by-side THQPs.
4Price is per screw. Packaged in quantities of 24. Must be ordered in multiples of 24.
Miniature Circuit Breakers and Supplementary Protectors
Accessories
THT1
THT104
TQHT1
THT2
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-37
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
How to Order
Spectra RMS
—Circuit Breakers
Determine the required breaker frame, IC rating, and load
requirements. Select frame, trip unit (rating plug), and lug, if
required, product numbers from the tables on pages 3-48 to
3-58. For Spectra breakers with MicroVersaTrip Plus Trip Units
or MicroVersaTrip PM Trip Units refer to pages 3-59 through
3-61. Select field-mounted internal accessory product
numbers, if required, on pages 3-83 and 3-84. Select field-
mounted external accessory product numbers, if required, on
pages 3-92 through 3-104. Order as separate items.
—Mag-Break Motor Circuit Protectors
Determine the required frame and ampere requirements.
Select frame, trip unit (rating plug), and lug, if required,
product numbers from the table on pages 3-73 through 3-75.
Select accessories as noted above for circuit breakers. The
same accessories are used with both circuit breakers and
motor circuit protectors. Order as separate items.
—Molded Case Switches
Determine the required frame and ampere requirements.
Select frame and lug, if required, product numbers from
the table on page 3-72. Rating plugs are not used. Select
accessories as noted above for circuit breakers. Internal
accessories do not require dummy trips. The same accessories
are used with both circuit breakers and molded case switches.
Order as separate items.
Unless otherwise noted, all circuit breakers are UL listed in File
E–11592. Molded case switches are UL listed in File E–57546.
Field-Installable Internal Accessories are UL listed in File E–57253.
Distribution Cable Accessories for MicroVersaTrip Plus Trip Units
and MicroVersaTrip PM Trip Units are UL listed in File E–57253.
E 150 Line
—Thermal Magnetic Circuit Breakers
—Magnetic Circuit Breakers
—Molded Case Switches
The product numbers as shown in the following pages include the
complete breaker or switch. All devices listed come with Cu/Al line
and load lugs. If line lugs are not required on a breaker, eliminate
“WL” from product number; for molded case switches see page
3-38. Unless otherwise noted, all circuit breakers are UL listed in
File E–11592. Molded case switches are UL listed in File E–57546.
F 225 Line
—Thermal Magnetic Circuit Breakers
—Magnetic Circuit Breakers
—Molded Case Switches
These breakers are available with either noninterchangeable trips
(designated Type TFJ) or interchangeable trips (designated Types
TFK/THFK). When ordering Type TFJ, product number includes
complete breaker, trip unit, CU/Al line and load lugs factory
Industrial Circuit Breakers
Spectra RMS, Spectra RMS with MicroVersaTrip Plus Trip Units, Spectra RMS
with MicroVersaTrip PM Trip Units, Thermal Magnetic and J/K with MicroVersaTrip RMS-9
and Power+ 4 Trip Units
assembled. If line lugs are not required on a breaker, eliminate “WL”
from product number, and subtract price of line lugs from price of
complete breaker. If interchangeable trip (Types TFK/THFK) is
required order one of two ways. “Complete circuit breaker” price
includes frame, trip, Cu/Al line and load lugs. Units will be shipped
unassembled unless specified on order “must be factory assembled.”
If line lugs are not required on a breaker, eliminate “WL” from
product number, and subtract price of line lugs from price of com-
plete breaker. To order the frame, trip, and lugs separately, select the
required components from table. Magnetic breakers must be ordered
as components. A complete breaker consists of frame, trip unit, one
line lug per pole and one load lug per pole. Price of “Complete Circuit
Breaker” vs. ordering frame, trip, and line and load lugs separately
is the same.
Molded case switches can also be ordered as complete units
(designated TFK---Y) or as separate components. They are UL listed
only as complete units. To indicate required lugs, see page 3-38.
Unless otherwise noted, all circuit breakers are UL listed in File
E–11592. Molded case switches are UL listed in File E–57546.
J 600 Line
—Thermal Magnetic Circuit Breakers
—Magnetic Circuit Breakers
—Molded Case Switches
These breakers are available with either noninterchangeable trip
(designated Type TJJ) or interchangeable trip (designated Type TJK
and THJK). Type TJJ product numbers include frame, trip, Cu/Al line,
and load lugs factory assembled. If line lugs are not required on the
breaker, eliminate “WL” from product number, and subtract price of
line lugs from price of complete breaker.
TJK breakers are available in two frames, 400 ampere frame (125 to
400 amperes) and 600 ampere frame (250 to 600 amperes). Trip units
are not interchangeable between frames.
“Complete Circuit Breaker” price includes frame, trip unit, Cu/Al
line, and load lugs. Unit will be shipped unassembled unless order
specifies “must be factory assembled.” If line lugs are not required,
eliminate “WL” from product number and subtract price of line lugs
from price of complete breaker.
To order the frame, trip, and lugs separately, select the required
components from table. Magnetic breakers must be ordered as
components. A complete breaker consists of frame, trip, and one
line and one load lug per pole.
Price of ordering “Complete Circuit Breaker” vs. frame, trip, and
line and load lugs separately is the same.
Molded case switches can also be ordered as complete units
(designated Type TJK---Y) or as separate components. They are UL
listed only as complete units. To indicate required lugs, see
page 3-38.
Unless otherwise noted, all circuit breakers are UL listed in File
E–11592. Molded case switches are UL listed in File E–57546.
Prices and data subject to change without notice
3-38 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
K 1200 Line
—Thermal Magnetic Circuit Breakers
—Magnetic Breakers
—Molded Case Switches
These breakers are available only with interchangeable trip units.
Two frame sizes are available, the 800 ampere frame (300 to 800
amperes) and the 1200 ampere frame (600 to 1200 amperes). Trip
units are not interchangeable between frames.
“Complete Circuit Breaker” price includes frame, trip, Cu/Al line, and
load lugs. Units will be shipped unassembled unless specified “must
be factory assembled.” If line lugs are not required on the breaker,
eliminate “WL” from product number and subtract price of line lugs.
To order the frame, trip, and lugs separately, select the required
components from table. Magnetic circuit breakers must be ordered
as components. A complete breaker consists of frame, trip and one
line and one load lug per pole. Price of ordering “Complete Circuit
Breaker” vs. frame, trip, and line and load lugs separately is the
same.
Molded case switches can also be ordered as complete units
(designated Type TKMA---Y) or as separate components. They are
UL listed only as complete units. To indicate required lugs, see the
table below.
Unless otherwise noted, all circuit breakers are UL listed in File
E–11592. Molded case switches are UL listed in File E–57546.
R Frame—1000/1600/2000 Ampere Molded Case Circuit Breakers
—Solid-state MicroVersaTrip Plus or
MicroVersaTrip PM Trip Unit
—Interchangeable trip unit via rating plugs
—65 and 100 kA ratings available
—Standard and 100% rated versions
—Uses standard Power Break accessories
—Stationary/manual only
Circuit Breakers with MicroVersaTrip Trip Units
—Solid-state construction with MicroVersaTrip Plus
digital rms sensing microprocessor trip units.
—Available in J and K frame construction with
ampere ratings from 60-1200A.
For ordering information see pages 3-80 through 3-82. UL listed,
File E–11592. All breakers are UL listed in File E–11592.
Tri-Break Line
—Integrally Fused Thermal Magnetic Circuit Breakers
—Integrally Fused Magnetic Circuit Breakers
—Integrally Fused Molded Case Switches
These breakers are available in four types. Type TB1 (15-100
amperes) product numbers include frame, trip, line and load lugs,
and current limiters all factory assembled. Types TB4 (125 to 400
amperes), TB6 (300 to 600 amperes) and TB8 (600 to 800 amperes)
include frame, trip and limiters, factory assembled, but do not
include line or load lugs. If line and load lugs are required, order
separately. Unless otherwise noted, TB1, TB4, TB6, and TB8 breaker
components are UL listed in File E–42263. Fused molded case
switches are UL listed in File E–57546.
Blank WL XL X2 LL
TQD/TJD Load Lugs
Only
Line and
Load Lugs Line Lugs
Only No Lugs
Molded Case
Breakers, Thermal
Magnetic
Load Lugs
Only
Line and
Load Lugs Load Lugs
Only No Lugs
Molded Case
Switch
Line and
Load Lugs —No Lugs Line Lugs
Only
Load Lugs
Only
Spectra RMS™
Breakers No Lugs
J.K.
MicroVersaTrip
®
Breakers
No Lugs
Mine Duty™
Breakers No Lugs
Mag-Break
®
Breakers
Line and
Load Lugs ———
Order Lugs Separately
For E 150 circuit breakers suffix XL is used to specify "no lugs".
Breaker/Switch
Type
Suffix
Order Lugs Separately
Order Lugs Separately
Industrial Case Circuit Breakers
Mag-Break Line
—Magnetic only circuit breakers (motor circuit protectors)
These breakers are available only with noninterchangeable
adjustable magnetic trip, in frame Types E, F, J, K, and Tri-Break.
All breakers are shipped factory assembled, complete with Cu/Al line
and load lugs.
All magnetic only circuit breakers and limiters are UL Component
Recognized in Files E–11592 and E–66390, respectively, unless
otherwise noted.
Accessories
Order accessories from the appropriate table:
—Thermal Magnetic Circuit Breakers, Magnetic Circuit Breakers,
and Molded Case Switches1—pages 3-85 to 3-104.
—MicroVersaTrip Plus or Power+ 4-function J and K frame Solid
State Circuit Breakers—pages 3-85 to 3-104.
—Spectra RMS Breakers—pages 3-83 to 3-84 and 3-92 to 3-104.
—Spectra RMS Breakers with MicroVersaTrip Plus Trip Units or
MicroVersaTrip PM Trip Units—pages 3-83 to 3-84, 3-92 to 3-104
and 3-106 to 3-109.
1Installation of accessories in molded case switches requires dummy trip; see page 3-91
for information. Dummy trip not required for Tri-Break or Q Line molded case switches.
Molded Case Circuit Breaker and Switch Terminal
Configuration Code
Order standard Cu/Al lugs by using suffix codes presented. Order
lugs separately if special lugs are required. For optional lugs, see
pages 3-101 and 3-102.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-39
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
How to Order
—Determine the required breaker frame (i.e., 150, 400, 600, 800, or
1200 amperes), IC rating, and load requirements (UL Standard or
100%). Determine overcurrent protective functions (LI, LSI, LIG,
LSIG). Select frame product number and list price from table on
pages 3-59 to 3-61 and 3-66 to 3-68.
—Select and price the required rating plug from table below. The
sensor rating of frame must match the sensor rating of the rating
plug in table.
—Select and price lugs and lug covers as required from page 3-102
and 3-103.
—Select and price appropriate combination of Power Management
System accessories from pages 3-106 to 3-109.
—Select and price any other accessories from pages 3-83 to 3-84
and 3-92 to 3-100.
—When ordering, specify separate product numbers as follows:
—Frame
—Rating Plug
—Lugs
—Power Management Accessories
—Other Accessories
Trip Function Definitions
Long-Time (L) Adjustable current setting
Adjustable long-time delay
Short-Time (S) Adjustable short-time pick-up
Adjustable short-time delay with I2t
Adjustable short-time delay without I2t
Instantaneous (I) Adjustable pick-up
Ground Fault (G) Adjustable ground fault pick-up
adjustable ground fault delay with I2t
Adjustable ground fault delay without I2t
Control Power (CP) +24 Vdc control power connection
Pricing Example
SG600 frame, 400 ampere sensor, 400 ampere rating plug, 100kAIC,
100% rated. Trip functions to include long-time (L), short-time (S),
instantaneous (I) and ground fault. 3-phase/4 wire system with 400
ampere neutral sensor. Load lugs only. 120 Vac shunt trip and two
stage auxiliary switch (2AB) with signal level contacts.
Description Product Number List Price GO-135S
Frame SGPP36BD0400 $8987.00
Rating Plug SRPG400B400 $106.00
Load Lugs (3 pole kit) TCLK365 $42.00
Terminal Block SDCTBA11 $110.001
400A neutral sensor TSRG204 $532.00
120 Vac Shunt Trip SAST1 $363.00
2AB Aux. Switch SAUXGAB2 $295.00
1GO-135PM.
Industrial Circuit Breakers
How To Order
Spectra RMS Circuit Breakers with MicroVersa Trip Plus Trip Units
MicroVersaTrip Plus and PM Rating Plug Selection —
All Plugs List Price, $106.00 GO-135S
Circuit Breaker Sensor Rating Plug Rating Plug
Frame Rating Rating (Amperes) Product No.
60 SRPG150B60
80 SRPG150B80
150100 SRPG150B100
125 SRPG150B125
150 SRPG150B150
150 SRPG400B150
200 SRPG400B200
SGHB, SGHH, SGLB, 225 SRPG400B225
SGLL, SGPB, SGPP 400 250 SRPG400B250
300 SRPG400B300
350 SRPG400B350
400 SRPG400B400
300 SRPG600B300
400 SRPG600B400
600 450 SRPG600B450
500 SRPG600B500
600 SRPG600B600
300 SRPK800B300
400 SRPK800B400
800 500 SRPK800B500
600 SRPK800B600
SKHB, SKHH, SKLB, 700 SRPK800B700
SKLL, SKPB, SKPP 800 SRPK800B800
600 SRPK1200B600
700 SRPK1200B700
1200 800 SRPK1200B800
1000 SRPK1200B1000
1200 SRPK1200B12002
2Not suitable for use with 100% rated, 1000A breaker frame.
Note: All Spectra RMS breakers with ground fault option will have a
breaker cable. If the breaker is connected to a 3Ø4w or 1Ø3w
service, a terminal block or junction box is required for connection
to the neutral current sensor.
Prices and data subject to change without notice
3-40 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
MicroVersaTrip PM Trip Unit
The MicroVersaTrip PM trip unit adds power management system
capability, advanced metering, and protective relays to the basic
functions of MicroVersaTrip Plus. MicroVersaTrip PM trip units
communicate directly on the GE POWER LEADER communications
bus. Suitable for use in applications from 45 Hz to 66 Hz. Not suitable
for 400 Hz.
Standard Features
—Adjustable Long-Time (L) pickup, 0.5-1.0X, and delay (3-4 bands).
—Adjustable Instantaneous (I) pickup, 1.5-10X.
—Local Overload and Short-Circuit Trip Indicators (T) with overload
pickup warning.
—Interchangeable trip rating plugs with test set jack for TVRMS test set.
—Digital LCD display with four-button keypad for function selection
and set point adjustment and sealable, clear Lexan cover for
tamper-resistant settings.
—True rms sensing for accurate response to high harmonic content
waveforms.
—EMI immunity per ANSI C37.90.
—POWER LEADER Communications System Link with user-
selectable address assignment for COMNET communication.
—Metering
—3-Phase Ammeter with ±4% accuracy.
—3-Phase Voltmeter, ±2% @ 1X, configurable for Wye and Delta
systems.
—Frequency Meter, ±1 Hz
—kW Meter, ±7% (real power)
—kVA Meter, ±6% (apparent power)
—kWh Meter, ±6% (energy)
Control Power 24 Vdc provides connection capability for +24 Vdc
control power into the breaker via the distribution cable system.
Optional Features
—Adjustable Short-Time (S) pickup, 1.0-9.0C, and delay (4 bands)
with I2t IN/OUT selection.
—Adjustable Ground fault (G) pickup, 0.2-1.0S, and delay (4 bands)
with I2t IN/OUT selection and trip indicator. The 4 short-time and
ground fault delay bands provide broader system selectivity.
—Protective Relays—User selectable in any combination from
1 to 5 relays
—Current Unbalance Relay
—Undervoltage Relay
—Overvoltage Relay
—Voltage Unbalance Relay
—Power Reversal Relay
Note: MicroVersaTrip PM functions require 24 Vdc control power
and voltage sensing signals.
Universal Internal Accessories—Uses the same front-mounted,
field-installable shunt trips, undervoltage releases, bell alarms, and
auxiliary switches as standard Spectra RMS breakers.
Accessory Lead Routing Left or Right—Side channels mean no extra
space required for accessory leads.
Current Limiting—SG600 frames rated 65kA and 100kA @ 480 Vac
are UL listed as current limiting.
Reverse Feed—Front-mounted interchangeable rating plugs mean
all frames are UL listed for reverse feed.
Wide Current Setting Range—Interchangeable rating plugs
combined with 5 current sensors and 0.5-1.0X long time pickup
yield ampere ratings from 30 to 1200A.
100% Continuous Current Rated—Optionally available for 100% UL
continuous current rating applications.
Industrial Circuit Breakers
Spectra RMS Circuit Breakers with
MicroVersaTrip PM Trip Units
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-41
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Metering (M) Metering and Relaying (PM)
Amperes (A) Current ±4% Selectable Phase
Voltage (V) Volts ±2% Selectable Phase in L-L or L-N
Energy (kWh/MWh) Watt hours ±7% Total energy flow through breaker
Real Power (kW/MW) Watts ±6% L-L or L-N Power
Apparent Power (kVA/MVA) Volt amps ±6% L-L or L-N Power
Frequency (45-66 Hz) Hertz ±6%
Voltage Unbalance Relay Adjustable pickup, 10 to 50%
Adjustable delay, 1 to 15 seconds or OFF
Current Unbalance Relay Adjustable pickup, 10 to 50%
Adjustable delay, 1 to 15 seconds or OFF
Undervoltage Relay Adjustable pickup, 50 to 90%
Adjustable delay, 1 to 15 seconds or OFF
Overvoltage Relay Adjustable pickup, 110 to 150%
Adjustable delay, 1 to 15 seconds or OFF
Power Reversal Relay Adjustable pickup, 0.01 MW to .90 MW
Adjustable delay, 1 to 15 seconds or OFF
Communications POWER LEADER™ Communications System Link (comment)
PM Trip Unit
Functions Accuracy and Description
Industrial Circuit Breakers
Spectra RMS Circuit Breakers with
MicroVersaTrip PM Trip Units
Long-Time1
Delay (Seconds)
Pick-Up (Multiple of
Current Settings) (C) Delay (Seconds)
Pick-Up (Multiple of
Sensor Ampere Rating) (S) Delay (Seconds)
0.50 to 1.0 in
increments of 0.05
(11 Settings)
2.4,4.9,9,8,20
2,3
(3-4 Bands)
1.5 to 9.0 in
increments of 0.5
(16 Settings)
I
2
t IN
3
0.44 I
2
T OUT
4
0.1, 0.2, 0.3, 0.4
(8 Bands)
1.5 to 10.0 in
increments of 0.5
(18 Settings)
0.2 to 1.0 in
increments of 0.05
(17 Settings)
I
2
t IN
5
0.41 I
2
t OUT
4
0.1, 0.2, 0.3, 0.4
(8 Bands)
5
Time delay shown at lower limit of each band. Pickup tolerances
±
10%. Ground Fault Pick-up not to exceed 1200 amperes.
1
Pick-up fixed at 1.1C.
2
20-second delay (band) not available on SG frames.
3
Time delay at 600% of current setting at lower limit of each band.
4
Time delay at 200% of pickup setting at the lower limit of each band.
X = Rating Plug Amperes
S = Sensor Ampere Rating
C = Long-Time Current Settings (Pickup)
C = X Times Long-Time Pickup Setting
Short-Time Ground Fault
Current Setting (C)
Pickup (Multiple of
Rating Plus Amperes) (X)
Adjustable
Instantaneous Pickup
(Multiple of Rating
Plug Amperes) (X)
MicroVersaTrip PM Trip Unit Characteristics
Prices and data subject to change without notice
3-42 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
How to Order
—Determine the required breaker frame (i.e., 150, 400, 600, 800, or
1200 amperes), IC rating, and load requirements (UL Standard or
100%). Determine overcurrent protective functions (LI, LSI, LIG,
LSIG) and whether protective relaying is required. Select frame
product number and list price from table on pages 3-59 to 3-61
and 3-66 and 3-68.
—Select and price the required rating plug from table below. The
sensor rating of frame must match the sensor rating of the rating
plug in table.
—Select and price lugs and lug covers as required from page 3-102
and 3-103.
—Select and price appropriate combination of Power Management
System accessories from pages 3-106 to 3-109.
—Select and price an auxiliary switch as required from page 3-109.
—Select and price any other accessories from pages 3-83 to 3-84
and 3-92 to 3-100.
—When ordering, specify separate product numbers as follows:
—Frame
—Rating Plug
—Lugs
—Auxiliary Switch
—Power Management System Accessories
—Other Accessories
Industrial Circuit Breakers
Spectra RMS Circuit Breakers with
MicroVersaTrip PM Trip Units
Trip Unit Function Definitions
Long-Time (L) Adjustable current setting
Adjustable long-time delay
Short-Time (S) Adjustable short-time pick-up
Adjustable short-time delay with l2t
Adjustable short-time delay without l2t
Instantaneous (I) Adjustable pick-up
Ground Fault (G) Adjustable ground fault pick-up
Adjustable ground fault delay with l2t
Adjustable ground fault delay without l2t
Trip Indication Targets Standard
Full Metering (Standard) Amperes (A/kA) – Phase Selectable
Voltage (V) – L-L or L-N and Phase Selectable
Energy (kWh/MWh)
Real Power (kW) – L-L or L-N
Total Power (kVA) – L-L or L-N
Frequency (45-66 Hz)
Protective Relay Functions Adjustable Undervoltage pick-up
Adjustable Undervoltage delay or OFF
Adjustable Overvoltage pick-up
Adjustable Overvoltage delay or OFF
Adjustable Voltage Unbalance pick-up
Adjustable Voltage Unbalance delay or OFF
Adjustable Current Unbalance pick-up
Adjustable Current Unbalance delay or OFF
Adjustable Power Reversal pick-up
Adjustable Power Reversal delay or OFF
Pricing Example
SG600 ampere frame breaker, 100% UL rated with 400 ampere sensors
and 400 ampere rating plug with line and load lugs. Trip functions to
include adjustable long-time (L), short-time (S), instantaneous (I) and
equipment ground fault (G) and internal protective relay functions of
current unbalance (CU), voltage unbalance (VU), undervoltage (UV),
Description Product Number List Price GO Schedule
Frame SGPP36DD0400 $11387.00 135PM
Rating Plug SRPG400B400 $106.00 135S
Line and Load Lugs
(2-3 Pole Kits) TCLK635 $42.00 135S
Auxiliary Switch SAUXPAB1 $149.00 135S
Power Supply Plate SPSA480 $1215.00 135PM
Voltage Conditioner Plate SVCA480Y $1000.00 135PM
Junction Box SDCJBA $155.00 135PM
Harness (2) SPCHA11 $140.00 135PM
400A Neutral Current Sensor TSRG204 $532.00 135S
MicroVersaTrip Plus and PM Rating Plug Selection—
All Plugs List Price, $106.00 GO-135S
Circuit Breaker Sensor Rating Plug Rating Plug
Frame Rating Rating (Amperes) Product No.
60 SRPG150B60
80 SRPG150B80
150100 SRPG150B100
125 SRPG150B125
150 SRPG150B150
150 SRPG400B150
200 SRPG400B200
SGHB, SGHH, SGLB, 225 SRPG400B225
SGLL, SGPB, SGPP 400 250 SRPG400B250
300 SRPG400B300
350 SRPG400B350
400 SRPG400B400
300 SRPG600B300
400 SRPG600B400
600 450 SRPG600B450
500 SRPG600B500
600 SRPG600B600
300 SRPK800B300
400 SRPK800B400
800 500 SRPK800B500
600 SRPK800B600
SKHB, SKHH, SKLB, 700 SRPK800B700
SKLL, SKPB, SKPP 800 SRPK800B800
600 SRPK1200B600
700 SRPK1200B700
1200 800 SRPK1200B800
1000 SRPK1200B1000
1200 SRPK1200B12001
1Not suitable for use with 100% rated, 1000A breaker frame.
overvoltage (OV) and power reversal (PR). Local metering values
available at the breaker shall include Current (Amperes), Voltage
(Volts), Energy (kWh), Real Power (kW), Apparent Power (kVA) and
Frequency (Hz). The available system is 277/480 Vac, 3-phase/4-wire
with 100 kAIC fault current available. The Distribution Cable
Accessories are to be mounted on plates with all the necessary fuse
protection, potential transformers, control power transformers, etc.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-43
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
How To Order:
1. Select frame product number.
2. Select rating plug for current rating from page 3-71.
3. Select appropriate accessories and lugs from page 3-105.
Include suffix “s” for factory installation.
Example
Description Product Number
Frame TRPP36BD10
Rating Plug TR10B600
Neutral CT TSVG810A
Shunt Trip TPST12
Auxiliary Switch TPAS2AB4
Padlocking Provision Standard
Line Side Terminations (Optional) (3)TP16FCA
Load Side Terminations Adapter Kit (1)TPLUGA16
Lugs (2 per pole) (6)TPLUG108
Industrial Circuit Breakers
R-Frame Molded Case Circuit Breakers
Solid-State Interchangeable Trip
400-2000A, 600 Vac, 65,100 kAIC @480V
Standard and 100% Rated
MicroVersaTripPlus
Suitable for Reverse Feed
80% 100%
240 Vac 100,000 Amperes
480 Vac 65,000 Amperes
600 Vac 50,000 Amperes
240 Vac 125,000 Amperes
480 Vac 100,000 Amperes
600 Vac 65,000 Amperes
Hi-Break
®
PA PP
Frame Type Interrupting Rating (rms sym.)
Continuous Current Rating
Standard Break LA LL
R-Frame UL Listed Interrupting Ratings - rms
Symmetrical Amperes
OL, SC
OL,
SC, GF
A
——
B
••
——
C
••
——
D
••
——
E
••
••
F
••
••
G
••
Zone interlocking requires purchase of interlock module TIM1 (120 Vac control voltage).
1
Instantaneous
(I)
Short
Time (S)
Long-Time (L)
Short-Time (S)
Instantaneous (I)
Ground Fault (G)
Adjustable current setting
Adjustable long-time delay
Adjustable short-time pick-up
Adjustable short-time delay with I
2
t
Adjustable short-time delay without I
2
t
Zone
Interlock
GF, ST
(Z2)
Ground
Fault (G)1
Adjustable ground fault pick-up
Adjustable ground fault delay with I
2
t
Adjustable ground fault delay without I
2
t
Targets (T) Zone
Interlock
GF (Z1)2
Zone Selective Interlock (Z1, Z2)
Trip Unit Functions Available
Adjustable pick-up
2
For single-phase, 3-wire or 3-phase, 4-wire GF applications select neutral-current sensor on page 3-105.
Overload/short circuit targets (T1)
Overload/short circuit/ground fault targets (T2)
Ground fault (Z1)
Ground fault/short-time (Z2)
Trip Indication Target (T1, T2)
R-Frame
Breaker
Function Code
Long
Time (L)
MicroVersaTrip Plus Trip Unit Selection Trip Unit Function Definitions
Prices and data subject to change without notice
3-44 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
240 Vac 480 Vac 600 Vac H W D A B C E
2 480
3 600 14
2 480
3 600 18
2 480
3 600 25
2 480
3 600 25
2 480
3 600 22
2 480
3 600 25
2 480
3 600 25
SGH1
2,4
60-150 3 600 65 35 25
2
3
2 600
3 600
2 600
3 600
SGL1
4
3 600 100 65 65
SGP1
4
3 600 200 100 65
2 600
55
3 600
2 600
3 600
2 600
3 600
2 600
3 600
2
3
2
3
2
3
2
3
66
2
3
2
3
47.6 lb/
1
8.56
(217)
5.69
(145)
1.38
(35)
.62
(16)
15.50
(394)
8.25
(210)
5.50
(140)
Circuit
Breaker
Type
Ampere
Rating
No.
Poles
Maximum
Vac
3.38
(86)
200
SF-250 Current Limiting (UL File No. E-11592; CSA LR 40350) 1
Solid-State with Interchangeable Trip Unit (Rating Plug)
UL Listed Interrupting Rating—kA Dimensions Inches (mm) Approx. Ship
Wt./Std.
Pack
.72
(18)
5.65 lb/
1
SE150 Current Limiting (UL File No. E-11592; CSA LR 40350) 1
SED
2
SEH
2
15-150
18
65
18
25
2.41
(61)
2.47
(63)
.69
(18)
65
100
6.31
(160)
4.12
(105)
SEL
SEP
15-150
100
100
10.12
(257)
SFL
SFP
70-250
100
SFH
2
70-250 65 35
.69
(18)
1.19
(30)
9.15 lb/
1
SG600 Current Limiting (UL File No. E-11592; CSA LR 40350) 3
4.12
(105)
3.81
(97)
3.87
(98)
3.87
(98)
65
200
SGD
2
SGH4
2
240 65
65
125-400
——
2535
25
60-150
SGL4 65
SGH6
2
250-600 65 35
SGP4
100
200
65
100 65
125-400
SGL6
SGP6
100 65
250-600
65
200 100 65
10.09
(256)
5.50
(140)
3.81
(97)
4.45
(113)
3.30
(84)
.91
(23)
1.18
(30)
15.85 lb/
1
SK1200 (UL File No. E-11592; CSA LR 40350) 3
SKH8
SKL8
SKP8
600
600
600
65
50 25
SKH12
SKL12
SKP12
300-800
600-1200
600
65
100
200
65
100
200
50
100
600
600
65
42
65
25
42
6
Add 4.00 inches (101 mm) to upper end for SKP (100 kAIC-480V) lug cover.
2
Not current-limiting circuit breaker.
4
MicroVersaTrip Plus™ Trip Units and MicroVersaTrip PM™ Trip Units only.
3
Includes MicroVersaTrip Plus Trip Units and MicroVersaTrip PM Trip Units.
5
Add 1.76 inches (45 mm) to each end with lugs and lug cover installed.
100
1
UL listed as HACR (heating, air conditioning and refrigeration) type.
65
Spectra RMS Circuit Breakers UL/CSA Ratings
Industrial Circuit Breakers
15-1200A Circuit Breakers
Electric Trip Spectra RMS Breakers
Quick Reference Guide
Ratings do not apply to molded case switches. The interruption ratings and voltages shown in the
table are maximum ratings. A circuit breaker of the type given in the left-hand column may be applied
at the given circuit voltage in any electrical distribution system where the available fault current at
the load terminals of the breaker does not exceed the value in the table. That circuit breaker type may
also be applied at intermediate values of circuit voltage provided the available fault current at the
load terminals of the breaker does not exceed the value in the table for the higher value of voltage.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-45
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
15-1200A Circuit Breakers
Electric Trip Spectra RMS Breakers
Quick Reference Guide
Ratings do not apply to molded case switches
IEC/JIS Ratings
I
cu
I
cs
I
cu
I
cs
I
cu
I
cs
I
cu
I
cs
220-240 380-415 500 690
2——
3444
2——
3666
2———
38833 83
2———
310 10 5 5 10 5
2——
3147 14
2——
32512 18
2———
3402055525
2———
3550 25 10 65 10
2——
32512 18
2———
3740 20 14 25 14
2———
3965 33 18 65 18
——
3918 18
2——
3918 18
2——
3918 18
———
3735 18 14
735 18 14
35 22
———
35025189 6535
2———
33518147 3522
2———
35025189
50 25 18 9
65 35
2———
3 35 22
2———
3 65 35
2
3
2
3
2
3
2
3
2
3
2
3
Vac
SE150 Current Limiting, 15-32A
Solid-State with Interchangeable Trip Unit (Rating Plug)
Circuit
Breaker
Type
Ampere
Rating
No.
Poles
IEC 947-2 Interruption Capacity —
220-240 Vac 380-415 Vac 500 Vac 690 Vac
Japanese Industry Standard
Interruption Capacity kA
SED
SEH
5
10
——
——
9
15-32
15-32
10
65 33 15
18
100
20
SEL
SEP 100
40-160
SED
SEH
SEL
SEP
40-160
20
20
100 50
17353365
18
18
65
100
200
10
15
20
20
14
SE150 Current Limiting, 40-160A
9147
50 15
200
——
18
65
——
25
100
200
65
100
SF250 Current Limiting
100200
65 33
50100
SFH
SFL
SFP
70-250
70-250
65 33 35 17
100 50 65 33
200 100 100 50
—— 65 25
100 65
200 100
SG600 Current Limiting
SGH1
1
SGH4
60-150
125-400
65
65
33
33
25
25
13
13
25
25
——
——
SGH6 250-600 65 33 25 13
65
65
65 25
SGL1
1
50 65100
——
SGP1
1
60-150
100
200 200100
65
100
33
50 100
SGL4
SGP4
125-400
100 50 65 33
50100100200
100 65
200 100
SGL6
SGP6
250-600
100
200 50
100
200
50
100
65
100
65
100
SK1200
SKH8 65 50 25 65 25
33
SKL8
SKP8
SKH12
300-800 100
140
16
25
35
65
85
13
16
25
42
50
13
21
25
14
18
14
18
100
140
50
65
85
42
50
14
18
SKL12
SKP12
600-1250
65
100
140
16
25
35
50
65
70
13
21
25
25
42
50
13
16
25
14
18
14
18
65
100
140
14
18
1
MicroVersaTrip Plus™ trip system only.
50
65
85
25
42
50
kA
SE
SF
SG
SK
Prices and data subject to change without notice
3-46 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
10-1200A Circuit Breakers
Thermal Magnetic Trip
Ratings do not apply to molded case switches. The interruption rat-
ings and voltages shown in the table are maximum ratings. A circuit
breaker of the type given in the left-hand column may be applied at
the given circuit voltage in any electrical distribution system where
the available fault current at the load terminals of the breaker does
not exceed the value in the table. That circuit breaker type may also
be applied at intermediate values of circuit voltage provided the
available fault current at the load terminals of the breaker does not
exceed the value in the table for the higher value of voltage.
TJJ, TJK, THJK TFJ, TFK, THFK
Quick Reference Guide
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-47
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Molded Case Circuit Breakers
Quick Reference Guide
Ratings do not apply to molded case switches. The interruption rat-
ings and voltages shown in the table are maximum ratings. A circuit
breaker of the type given in the left-hand column may be applied at
the given circuit voltage in any electrical distribution system where
the available fault current at the load terminals of the breaker does
not exceed the value in the table. That circuit breaker type may also
be applied at intermediate values of circuit voltage provided the
available fault current at the load terminals of the breaker does not
exceed the value in the table for the higher value of voltage.
ac dc 120 120/240 240 277 480 600 125 250 H W D A B C E
TRL…10, 16 400-1600 3 600 —— 100 65 50 ——
17 1/2 13 1/2 8 5/16 ——
90/1
TRP…10, 16 400-1600 3 600 —— 125 100 65 ——
17 1/2 13 1/2 8 5/16 ——
90/1
TRL…20 800-2000 3 600 —— 100 65 50 —— 20 13 1/2 8 5/16 ——
96/1
TRP…20 800-2000 3 600 —— 125 100 65 —— 20 13 1/2 8 5/16 ——
96/1
TB1
2,3
15-100 3 600 —— 200 200 200 ——
10 5/16 4 1/8 3 5/8 2 21/32 6 9/32 11/16 23/32 8 lb/1
31 lb/1
33 lb/1
53 lb/1
55 lb/1
53 lb/1
55 lb/1
2 480 250 10
3 600 ——
TEML
6
3-150 3 600 250 ——100 65 25 ——
6 5/16 4 1/8 3 7/8 2 41/64 2 15/64 11/16 23/32 3 1/2 lb/1
TEC &
TECL
7
3-150 3 600 100 100 100 8 3/16 4 1/8 3 3/8 2 41/64 2 15/64 11/16 23/32 1.2 lb/1
TECL Only
10 lb/1
12 lb/1
31 lb/1
33 lb/1
16 lb/1
17 1/2/1
53 lb/1
55 lb/1
38 lb/1
41 1/2/1
53 lb/1
55 lb/1
TJ4V
8,9
42 42 30 22
THJ4V
8,9
65 65 35 25
TJL4V
8
100 100 65 30
TK4V
8
800-1200 3 600 —— 42 42 30 22 ——
15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8
TKL4V
8
800-1200 3 600 —— 100 100 65 42 ——
15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8
TJH1S-6S 60-600 3 600 —— 65 65 35 25 ——
16 1/8 8 1/4 3 13/16 3 15/16 9 13/16 1 3/8 1 3/16
TJL1S-6S 60-600 3 600 —— 100 100 65 30 ——
16 1/8 8 1/4 3 13/16 3 15/16 9 13/16 1 3/8 1 3/16
TKH8S, 12S 300-1200 3 600 —— 65 65 50 25 ——
21 7/8 8 1/4 5 1/2 8 9/16 12 11/16 1 3/8 5/8
TKL8S, 12S 300-1200 3 600 —— 100 100 65 42 ——
21 7/8 8 1/4 5 1/2 8 9/16 12 11/16 1 3/8 5/8
3
CSA LR 57114.
9
Suitable for single-phase, use outer two poles.
6003 ——
4
CSA LR 40350.
1 3/8 1 3/168 1/4 3 13/16 3 15/16 3 13/16
5/8
MicroVersaTrip (UL File E-11592; Solid-State Trip Units)
150-600 10 1/8
5 7/8 8 9/16 12 1/16 1 3/8——21 7/8 8 1/4100 100 100
15 1/2800-1200TKC
TBC8 800 3 600
8 1/4 5 1/2 8 9/16 5/81 3/85 11/16—— 3042 223 600
3 600600TBC6 ———— 100 100100 5/821 7/8 8 1/4 5 7/8 8 9/16 12 1/16 1 3/8
1 3/163042600 3 13/16 3 13/16 3 13/16 1 3/8——10 1/8 8 1/4
TBC4
223400-600TJC
600225-400 3 100 100100——
TFC
1 3/161 3/89 13/163 15/164 1/28 1/416 1/8——
3 600225 ———— 221825 3 7/83 13/164 1/810 1/8 1 3/1611/163 7/8
2 15/64 11/16 23/32 21 lb/66 5/16 4 1/8 3 3/8 2 41/6410 10 10TEC 3-150
12 1/16 1 3/8 5/8
Mag-Break (UL Files E-11592, E-66390; Magnetic Trip Unit) 5
21 7/8 8 1/4 5 7/8 8 9/16200 100
TB8
2,4
600-800 3 600 200
200 200 —— 200
TB6
2,4
300-600 3 600
—— 200
TB4
2,4
125-400 3 600
8 9/165 7/88 1/421 7/8
1 3/16
5/81 3/812 1/16
4 1/2 3 15/16 9 13/16 1 3/8 16 1/8
No.
Poles
Ampere
Rating
200 200
Tri-Break (UL File E-42263; Integrally Fused, Thermal Magnetic Trip Unit)
Circuit
Breaker
Type
8 1/4
R Frame1 (UL File E-11592; Interchangeable Solid-State MicroVersaTrip Plus Trip Unit; CSA LR 10263)
UL Listed Interrupting Ratings—
rms Symmetrical Amps (In Thousands)
Dimensions (In.)
Approx.
Ship
Wt./Std.
Pack
Vac Vdc
Maximum
Voltage
Rating
1
Rotary handle (not toggle handle).
5
Per UL 489, interrupting capacities are not shown on product label
.
2
UL listed with internally mounted accessories at 100,000 amps IC.
Contact GE Sales Office for availability of 200 kAIC ratings with
internal accessories.
6
Discontinued.
7
Ratings shown for TEC in combination with TECL.
8
With Power+ 4 trip unit.
TJC TJL6S
Prices and data subject to change without notice
3-48 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
15-150A Circuit Breakers
Electronic Trip
Spectra RMS
SE150 Line Circuit Breakers
SE150 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, UL listed HACR GO-135S
SEL, SEP UL Current Limiting
2-Pole, UL/CSA: 150A, 480 Vac Max., IEC 947-2: 160A, 415 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adj. Inst.
Trip Range Amps UL 489 IC @480 Vac UL 489 IC @480 Vac
18kA 25kA
Ampere Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Number Price Number Price Number Price Range
15 43 182 SRPE30A15 $106.00
20 58 254 SRPE30A20 $106.00 30 SEDA24AT0030 $214.00 SEHA24AT0030 $530.00
25 73 332 SRPE30A25 $106.00
30 87 415 SRPE30A30 $106.00
40 118 501 SRPE60A40 $106.00
50 148 637 SRPE60A50 $106.00 60 SEDA24AT0060 $214.00 SEHA24AT0060 $530.00 12-3/0 Cu
60 178 777 SRPE60A60 $106.00 TCAL18 $3.00 12-3/0 Al
70 206 863 SRPE100A70 $106.00
80 236 999 SRPE100A80 $106.00 10 0 SEDA24AT0100 $312.00 SEHA24AT0100 $634.00
90 267 1138 SRPE100A90 $106.00
100 297 1280 SRPE100A100 $106.00
110 328 1426 SRPE150A110 $106.00
125374 1640 SRPE150A125 $106.00 150 SEDA24AT0150 $837.00 SEHA24AT0150 $1427.00
150 450 1991 SRPE150A150 $106.00
SE150 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, UL listed HACR GO-135S
2-Pole, UL/CSA: 150A, 480 Vac Max., IEC 947-2: 160A, 415 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adj. Inst.
Trip Range Amps UL 489 IC @480 Vac UL 489 IC @480 Vac
65kA 100kA
Ampere Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Number Price Number Price Number Price Range
15 43 182 SRPE30A15 $106.00
20 58 254 SRPE30A20 $106.00 30 SELA24AT0030 $549.00 SEPA24AT0030 $895.00
25 73 332 SRPE30A25 $106.00
30 87 415 SRPE30A30 $106.00
40 118 501 SRPE60A40 $106.00
50 148 637 SRPE60A50 $106.00 60 SELA24AT0060 $549.00 SEPA24AT0060 $895.00 12-3/0 Cu
60 178 777 SRPE60A60 $106.00 TCAL18 $3.00
70 206 863 SRPE100A70 $106.00 12-3/0 Al
80 236 999 SRPE100A80 $106.00 10 0 SELA24AT0100 $744.00 SEPA24AT0100 $1179.00
90 267 1138 SRPE100A90 $106.00
100 297 1280 SRPE100A100 $106.00
110 328 1426 SRPE150A110 $106.00
125374 1640 SRPE150A125 $106.00 150 SELA24AT0150 $1808.00 SEPA24AT0150 $2777.00
150 450 1991 SRPE150A150 $106.00
Features
—Interchangeable trip using rating plugs
—True digital rms sensing
—Universal internal accessories UL listed for field installation
—Adjustable instantaneous with short-time tracking function
—CE marked
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-49
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
15-150A Circuit Breakers
Electronic Trip
Spectra RMS
SE150 Line Circuit Breakers
SE150 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, UL listed HACR GO-135S
3-Pole, UL/CSA: 150A, 600 Vac Max., IEC 947-2: 160A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adj. Inst.
Trip Range Amps UL 489 IC @480 Vac UL 489 IC @480 Vac
18kA 25kA
Ampere Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Number Price Number Price Number Price Range
15 43 182 SRPE30A15 $106.00
20 58 254 SRPE30A20 $106.00 30 SEDA36AT0030 $382.00 SEHA36AT0030 $632.00
25 73 332 SRPE30A25 $106.00
30 87 415 SRPE30A30 $106.00
40 118 501 SRPE60A40 $106.00
50 148 637 SRPE60A50 $106.00 60 SEDA36AT0060 $382.00 SEHA36AT0060 $632.00 12-3/0 Cu
60 178 777 SRPE60A60 $106.00 TCAL18 $3.00
70 206 863 SRPE100A70 $106.00 12-3/0 Al
80 236 999 SRPE100A80 $106.00 10 0 SEDA36AT0100 $492.00 SEHA36AT0100 $734.00
90 267 1138 SRPE100A90 $106.00
100 297 1280 SRPE100A100 $106.00
110 328 1426 SRPE150A110 $106.00
125374 1640 SRPE150A125 $106.00 150 SEDA36AT0150 $1253.00 SEHA36AT0150 $1815.00
150 450 1991 SRPE150A150 $106.00
SE150 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, UL listed HACR GO-135S
3-Pole, UL/CSA: 150A, 600 Vac Max., IEC 947-2: 160A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adj. Inst.
Trip Range Amps UL 489 IC @480 Vac UL 489 IC @480 Vac
65kA 100kA
Ampere Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Number Price Number Price Number Price Range
15 43 182 SRPE30A15 $106.00
20 58 254 SRPE30A20 $106.00 30 SELA36AT0030 $753.00 SEPA36AT0030 $1189.00
25 73 332 SRPE30A25 $106.00
30 87 415 SRPE30A30 $106.00
40 118 501 SRPE60A40 $106.00
50 148 637 SRPE60A50 $106.00 60 SELA36AT0060 $753.00 SEPA36AT0060 $1189.00 12-3/0 Cu
60 178 777 SRPE60A60 $106.00 TCAL18 $3.00
70 206 863 SRPE100A70 $106.00 12-3/0 Al
80 236 999 SRPE100A80 $106.00 10 0 SELA36AT0100 $895.00 SEPA36AT0100 $1482.00
90 267 1138 SRPE100A90 $106.00
100 297 1280 SRPE100A100 $106.00
110 328 1426 SRPE150A110 $106.00
125374 1640 SRPE150A125 $106.00 150 SELA36AT0150 $2165.00 SEPA36AT0150 $3477.00
150 450 1991 SRPE150A150 $106.00
Prices and data subject to change without notice
3-50 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
15-150A Circuit Breakers
Thermal-Magnetic Trip
E150 Line Circuit Breakers
Types TEB, TED, THED
Noninterchangeable Trip
Note: All UL listed as HACR type except 10 ampere
60°C/75°F Conductor 10-150 Amperes
Rating Through 100 Amperes 120-600 Vac
75°C above 100 Amperes 125, 250 Vdc
Single Pole — Includes Cu/Al load lugs only. If line lugs are required, add suffix “WL” to Product Number. GO-135B
Type TEB Type TED Type THED
Ampere 120 Vac 125 Vdc 277 Vac 125 Vdc 347 Vac1277 Vac 347 Vac1
Rating Product Number List Price Product Number List Price Product Number List Price Product Number List Price Product Number List Price
10 TEB1110102$78.50 TED1130102$82.50
15 TEB1110153$78.50 TED1130153$82.50 TED1140153$152.00 THED113015 $229.00 THED1140153$416.00
20 TEB1110203$78.50 TED1130203$82.50 TED1140203$152.00 THED113020 $229.00 THED1140203$416.00
25 TEB111025 $78.50 TED113025 $82.50 TED114025 $152.00 THED113025 $229.00 THED114025 $416.00
30 TEB111030 $78.50 TED113030 $82.50 TED114030 $152.00 THED113030 $229.00 THED114030 $416.00
35 TEB111035 $78.50 TED113035 $82.50 —— ——
40 TEB111040 $78.50 TED113040 $82.50 —— ——
45 TEB111045 $78.50 TED113045 $82.50 —— ——
50 TEB111050 $78.50 TED113050 $82.50 —— ——
60 TEB111060 $78.50 TED113060 $82.50 —— ——
70 TEB111070 $134.00 TED113070 $159.00 ——
80 TEB111080 $134.00 TED113080 $159.00 ——
90 TEB111090 $134.00 TED113090 $159.00 ——
100 TEB111100 $134.00 TED113100 $159.00 ——
Two Pole — Includes Cu/Al load lugs. For optional lugs, see page 3-101 and 3-102. GO-135B
Type TEB Type TED Type THED, Hi-Break4
Ampere 240 Vac, 250 Vdc 480 Vac, 250 Vdc 480 Vac, 250 Vdc
Rating Product Number List Price Product Number List Price Product Number List Price
10 TEB122010WL2$159.00 TED124010WL2$290.00 ——
15 TEB122015WL $159.00 TED124015WL $290.00 THED124015WL $560.00
20 TEB122020WL $159.00 TED124020WL $290.00 THED124020WL $560.00
25 TEB122025WL $159.00 TED124025WL $290.00 THED124025WL $560.00
30 TEB122030WL $159.00 TED124030WL $290.00 THED124030WL $560.00
35 TEB122035WL $159.00 TED124035WL $290.00 THED124035WL $560.00
40 TEB122040WL $159.00 TED124040WL $290.00 THED124040WL $560.00
45 TEB122045WL $159.00 TED124045WL $290.00 THED124045WL $560.00
50 TEB122050WL $159.00 TED124050WL $290.00 THED124050WL $560.00
60 TEB122060WL $159.00 TED124060WL $290.00 THED124060WL $560.00
70 TEB122070WL $261.00 TED124070WL $377.00 THED124070WL $653.00
80 TEB122080WL $261.00 TED124080WL $377.00 THED124080WL $653.00
90 TEB122090WL $261.00 TED124090WL $377.00 THED124090WL $653.00
100 TEB122100WL $261.00 TED124100WL $377.00 THED124100WL $653.00
110— TED124110WL $1000.00 ——
125— TED124125WL $1000.00 ——
150— TED124150WL $1000.00 ——
1Suitable for 10 kAIC at 480 Vac, but not labeled or UL listed.
2Not UL listed
3Single-pole, 15-and 20-ampere breakers are also UL listed as switching duty breakers, suitable for switching 120 Vac (TEB), 277, 347 Vac (TED, THED) fluorescent lighting loads.
4Two-pole breaker is furnished in three-pole case.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-51
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
15-150A Circuit Breakers
Thermal-Magnetic Trip
E150 Line Circuit Breakers
Types TEB, TED, THED
Note: All UL listed as HACR type except 10 ampere
60°C/75°F Conductor 10-150 Amperes
Rating Through 100 Amperes 120-600 Vac
75°C above 100 Amperes 125, 250 Vdc
Three Pole — Includes Cu/Al load lugs. For optional lugs, see page 3-101 and 3-102. GO-135B
Type TEB Type TED Type THED, Hi-Break
Ampere 240 Vac 480 Vac 600 Vac 480 Vac 600 Vac
Rating Product Number List Price Product Number List Price Product Number List Price Product Number Product Number List Price
10 TEB132010WL1$240.00 TED134010WL1$377.00 TED136010WL1$439.00 ———
15 TEB132015WL $240.00 TED134015WL $377.00 TED136015WL $439.00 THED134015WL THED136015WL $655.00
20 TEB132020WL $240.00 TED134020WL $377.00 TED136020WL $439.00 THED136020WL $655.00
25 TEB132025WL $240.00 TED134025WL $377.00 TED136025WL $439.00 THED136025WL $655.00
30 TEB132030WL $240.00 TED134030WL $377.00 TED136030WL $439.00 THED134030WL THED136030WL $655.00
35 TEB132035WL $240.00 TED134035WL $377.00 TED136035WL $439.00 THED136035WL $655.00
40 TEB132040WL $240.00 TED134040WL $377.00 TED136040WL $439.00 THED136040WL $655.00
45 TEB132045WL $240.00 TED134045WL $377.00 TED136045WL $439.00 THED134045WL THED136045WL $655.00
50 TEB132050WL $240.00 TED134050WL $377.00 TED136050WL $439.00 THED136050WL $655.00
60 TEB132060WL $240.00 TED134060WL $377.00 TED136060WL $439.00 ——
70 TEB132070WL $339.00 TED134070WL $445.00 TED136070WL $534.00 THED134070WL THED136070WL $742.00
80 TEB132080WL $339.00 TED134080WL $445.00 TED136080WL $534.00 ———
90 TEB132090WL $339.00 TED134090WL $445.00 TED136090WL $534.00 THED134090WL THED136090WL $742.00
100 TEB132100WL $339.00 TED134100WL $445.00 TED136100WL $534.00 THED134100WL THED136100WL $742.00
110— TED134110WL $1198.00 TED136110WL $1198.00 THED134110WL THED136110WL $1683.00
125— TED134125WL $1198.00 TED136125WL $1198.00 THED134125WL THED136125WL $1683.00
150— TED134150WL $1198.00 TED136150WL $1198.00 THED134150WL THED136150WL $1683.00
100NA TED134Y1002$377.00 TED136Y1002$445.00 ———
150NA — TED134Y1502$967.00 TED136Y1502$967.00 ———
1Not UL listed.
2Includes factory-installed dummy trip.
Accessories: See pages 3-85 to 3-104.
Prices and data subject to change without notice
3-52 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
SF250 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, UL listed HACR GO-135S
SFH UL Current Limiting
2-Pole, UL/CSA: 250A, 480 Vac Max., IEC 947-2: 250A, 415 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous
UL 489 IC @480 Vac
Trip Ampere Range 35kA
Ampere Product List Current Product List Product List Wire
Rating Low High Number Price Sensor Number Price Number Price Range
70 205 700 SRPF250A70 $106.00
90 265 900 SRPF250A90 $106.00
100 295 1000 SRPF250A100 $106.00
110 325 1100 SRPF250A110 $106.00 8-350 Cu
125 370 1250 SRPF250A125 $106.00 250 SFHA24AT0250 $1134.00 TCAL29 $8.00
150 440 1500 SRPF250A150 $106.00 8-350 Al
175515 1750 SRPF250A175 $106.00
200 590 2000 SRPF250A200 $106.00
225 665 2250 SRPF250A225 $106.00
250 736 2500 SRPF250A250 $106.00
SF250 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, UL listed HACR GO-135S
SFL, SFP UL Current Limiting
2-Pole, UL/CSA: 250A, 480 Vac Max., IEC 947-2: 250A, 415 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous
UL 489 IC @480 Vac UL 489 IC @480 Vac
Trip Ampere Range 65kA 100kA
Ampere Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Number Price Number Price Number Price Range
70 205 700 SRPF250A70 $106.00
90 265 900 SRPF250A90 $106.00
100 295 1000 SRPF250A100 $106.00
110 325 1100 SRPF250A110 $106.00 8-350 Cu
125 370 1250 SRPF250A125 $106.00 250 SFLA24AT0250 $2175.00 SFPA24AT0250 $2790.00 TCAL29 $8.00
150 440 1500 SRPF250A150 $106.00 8-350 Al
175515 1750 SRPF250A175 $106.00
200 590 2000 SRPF250A200 $106.00
225 665 2250 SRPF250A225 $106.00
250 736 2500 SRPF250A250 $106.00
SF250 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, UL listed HACR GO-135S
SFH UL Current Limiting
3-Pole, UL/CSA: 250A, 600 Vac Max., IEC 947-2: 250A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous
UL 489 IC @480 Vac
Trip Ampere Range 35kA
Ampere Product List Current Product List Product List Wire
Rating Low High Number Price Sensor Number Price Number Price Range
70 205 700 SRPF250A70 $106.00
90 265 900 SRPF250A90 $106.00
100 295 1000 SRPF250A100 $106.00
110 325 1100 SRPF250A110 $106.00 8-350 Cu
125 370 1250 SRPF250A125 $106.00 250 SFHA36AT0250 $1441.00 TCAL29 $8.00
150 440 1500 SRPF250A150 $106.00 8-350 Al
175515 1750 SRPF250A175 $106.00
200 590 2000 SRPF250A200 $106.00
225 665 2250 SRPF250A225 $106.00
250 736 2500 SRPF250A250 $106.00
Industrial Circuit Breakers
70-250A Circuit Breakers
Electronic Trip
Spectra RMS
SF250 Line Circuit Breakers
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-53
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
70-250A Circuit Breakers
Electronic Trip
Spectra RMS
SF250 Line Circuit Breakers
SF250 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, UL listed HACR GO-135S
SFL, SFP UL Current Limiting
3-Pole, UL/CSA: 250A, 600 Vac Max., IEC 947-2: 250A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous
UL 489 IC @480 Vac UL 489 IC @480 Vac
Trip Ampere Range 65kA 100kA
Ampere Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Number Price Number Price Number Price Range
70 205 700 SRPF250A70 $106.00
90 265 900 SRPF250A90 $106.00
100 295 1000 SRPF250A100 $106.00
110 325 1100 SRPF250A110 $106.00 8-350 Cu
125 370 1250 SRPF250A125 $106.00 250 SFLA36AT0250 $2631.00 SFPA36AT0250 $3490.00 TCAL29 $8.00
150 440 1500 SRPF250A150 $106.00 8-350 Al
175515 1750 SRPF250A175 $106.00
200 590 2000 SRPF250A200 $106.00
225 665 2250 SRPF250A225 $106.00
250 736 2500 SRPF250A250 $106.00
Prices and data subject to change without notice
3-54 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
70-250A Circuit Breakers
Thermal-Magnetic Trip
F225 Line Circuit Breakers
Types TFJ, TFK, THFK
F225 Line Circuit Breakers
—70-250 Amperes–TFJ Noninterchangeable Trip, suitable for reverse feed
—70-225A TFK, THFK Interchangeable Trip, not suitable for reverse feed
—480 or 600 Vac
—250 Vdc
Note: All TFJ, TFK and THFK breakers are UL listed as HACR
Type TFJ — Noninterchangeable Trip GO-135B
Adjustable Instantaneous Complete Breaker Complete Breaker
Trip Ampere Range 480 Vac Max 600 Vac Max
Ampere Rating Low High Product Number List Price Product Number List Price Copper/Aluminum Lugs Wire Size
Tw o-Pole Three-Pole
70 600 900 TFJ224070WL $1122.00 TFJ236070WL $1407.00
80 700 1000 TFJ224080WL $1122.00 TFJ236080WL $1407.00
90 600 900 TFJ224090WL $1122.00 TFJ236090WL $1407.00
100600 1250 TFJ224100WL $1122.00 TFJ236100WL $1407.00
110 660 1250 TFJ224110WL $1122.00 TFJ236110WL $1407.00
125600 1250 TFJ224125WL $1122.00 TFJ236125WL $1407.00 TCAL24 4-300 Cu/Al
150700 1500 TFJ224150WL $1122.00 TFJ236150WL $1407.00
175800 1750 TFJ224175WL $1122.00 TFJ236175WL $1407.00
200 900 2000 TFJ224200WL $1122.00 TFJ236200WL $1407.00
225 1000 2250 TFJ224225WL $1122.00 TFJ236225WL $1407.00
250 1000 2250 TFJ236250WL $2075.00 11
Types TFK, THFK — Interchangeable Trip GO-135B
Terminal Lugs for
Adjustable
Complete Circuit Breaker Includes Line and Load Lugs Trip Unit Only Frame Only Front Connection (Copper/Aluminum)2
Instantaneous Standard High-Break Product Number
Ampere Trip Ampere Range Product List Product List Use with Standard List Product List (Order 1 line and List Wire
Rating Low High Number Price Number Price and Hi-Break Frames Price Number Price 1 load per pole) Price Size
Tw o-Pole, 480 Vac Max., 250 Vdc Max.
70 600 900 TFK224070WL $1122.00 THFK224070WL $2315.00 TFK226T070 $337.00
80 700 1000 TFK224080WL $1122.00 THFK224080WL $2315.00 TFK226T080 $337.00 TFK224F000 $753.00
90 600 900 TFK224090WL $1122.00 THFK224090WL $2315.00 TFK226T090 $337.00 Standard
100600 1250 TFK224100WL $1122.00 THFK224100WL $2315.00 TFK226T100 $337.00 Frame
110 660 1250 TFK224110WL $1122.00 THFK224110WL $2315.00 TFK226T110 $337.00
125600 1250 TFK224125WL $1122.00 THFK224125WL $2315.00 TFK226T125 $337.00 TCAL24 $8.00 4-300 Cu/Al
150700 1500 TFK224150WL $1122.00 THFK224150WL $2315.00 TFK226T150 $337.00
175800 1750 TFK224175WL $1122.00 THFK224175WL $2315.00 TFK226T175 $337.00 THFK224F000 $1946.00
200 900 2000 TFK224200WL $1122.00 THFK224200WL $2315.00 TFK226T200 $337.00 Hi-Break
225 1000 2250 TFK224225WL $1122.00 THFK224225WL $2315.00 TFK226T225 $337.00 Frame
Three-Pole, 600 Vac Max., 250 Vdc Max.
70 600 900 TFK236070WL $1407.00 THFK236070WL $2787.00 TFK236T070 $445.00
80 700 1000 TFK236080WL $1407.00 THFK236080WL $2787.00 TFK236T080 $445.00 TFK236F000 $914.00
90 600 900 TFK236090WL $1407.00 THFK236090WL $2787.00 TFK236T090 $445.00 Standard
100600 1250 TFK236100WL $1407.00 THFK236100WL $2787.00 TFK236T100 $445.00 Frame
110 660 1250 TFK236110WL $1407.00 THFK236110WL $2787.00 TFK236T110 $445.00
125600 1250 TFK236125WL $1407.00 THFK236125WL $2787.00 TFK236T125 $445.00 TCAL24 $8.00 4-300 Cu/Al
150700 1500 TFK236150WL $1407.00 THFK236150WL $2787.00 TFK236T150 $445.00
175800 1750 TFK236175WL $1407.00 THFK236175WL $2787.00 TFK236T175 $445.00 THFK236F000 $2294.00
200 900 2000 TFK236200WL $1407.00 THFK236200WL $2787.00 TFK236T200 $445.00 Hi-Break
225 1000 2250 TFK236225WL $1407.00 THFK236225WL $2787.00 TFK236T225 $445.00 Frame
225 600 1400 TFK236TM12253$555.00
Mag 1000 2250 TFK236TM22253$555.00
Only
1TC024 load end. Wire range #4-300 copper only.
2For optional lug see page 3-101.
Accessories: See pages 3-85 to 3-104.
Type TFK
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-55
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Three-Pole TJD GO-135F
TJD Lug-lug 240 Vac122 kAIC
Ampere Rating Product Number List Price
250 TJD432250WL2$1802.00
300 TJD432300WL2$1802.00
350 TJD432350WL2$1802.00
400 TJD432400WL2$1802.00
400 Molded Case Switch TJD432Y4002$1509.00
1Includes line and load lugs. For optional configurations, see page 3-21.
2TJD uses same accessories as J600 line. TJD not listed HACR.
See page 3-4 for size and ratings.
Industrial Circuit Breakers
125-400A Circuit Breakers
Thermal-Magnetic Trip
Q Line Circuit Breakers
Types TJD
TJD432300WL
Prices and data subject to change without notice
3-56 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
SGL, SGP UL Current Limiting
UL/CSA: 400A, 600 Vac Max., IEC 947-2: 400A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 65kA (240 Vac) 35kA
Ampere Trip Ampere Range Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Number Price Range
125 380 1275 SRPG400A125 $106.00 2-pole lug kit
150 455 1530 SRPG400A150 $106.00 (2) 2/0-500 Cu
175 530 1785 SRPG400A175 $106.00 2SGDA22AT04001$1540.00 SGHA26AT0400 $1959.00 TCLK2652$28.00 or
200 605 2040 SRPG400A200 $106.00 (1) 8-600 Cu
225 680 2295 SRPG400A225 $106.00 400
250 755 2550 SRPG400A250 $106.00 3-pole lug kit
300 905 3060 SRPG400A300 $106.00 3SGDA32AT04001$1860.00 SGHA36AT0400 $2383.00 (2) 2/0-500 Al
350 1060 3570 SRPG400A350 $106.00 TCLK3652$42.00 or
400 1210 4080 SRPG400A400 $106.00 (1) 6-600 Al
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
SGL, SGP UL Current Limiting
UL/CSA: 400A, 600 Vac Max., IEC 947-2: 400A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 65kA 100kA
Ampere Trip Ampere Range Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Number Price Range
125 380 1275 SRPG400A125 $106.00 2-pole lug kit
150 455 1530 SRPG400A150 $106.00 (2) 2/0-500 Cu
175 530 1785 SRPG400A175 $106.00 2SGLA26AT0400 $2926.00 SGPA26AT0400 $3856.00 TCLK2652$28.00 or
200 605 2040 SRPG400A200 $106.00 (1) 8-600 Cu
225 680 2295 SRPG400A225 $106.00 400
250 755 2550 SRPG400A250 $106.00 3-pole lug kit
300 905 3060 SRPG400A300 $106.00 3SGLA36AT0400 $3487.00 SGPA36AT0400 $4653.00 (2) 2/0-500 Al
350 1060 3570 SRPG400A350 $106.00 TCLK3652$42.00 or
400 1210 4080 SRPG400A400 $106.00 (1) 6-600 Al
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
SGL, SGP UL Current Limiting
UL/CSA: 600A, 600 Vac Max., IEC 947-2: 630A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 35kA 65kA
Ampere Trip Ampere Range Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Number Price Range
250 765 2530 SRPG600A250 $106.00 2-pole lug kit
300 915 3035 SRPG600A300 $106.00 2SGHA26AT0600 $2663.00 SGLA26AT0600 $3545.00 (2) 2/0-500 Cu
350 1070 3545 SRPG600A350 $106.00 TCLK2652$28.00 or
400 1220 4050 SRPG600A400 $106.00 600 (1) 8-600 Cu
450 1375 4555 SRPG600A450 $106.00 3-pole lug kit
500 1525 5060 SRPG600A500 $106.00 3SGHA36AT0600 $3354.00 SGLA36AT0600 $4270.00 (2) 2/0-500 Al
600 1830 6075 SRPG600A600 $106.00 TCLK3652$42.00 or (1) 6-600 Al
1Rated 240 Vac max.
2Order one kit for either line or load end; two kits required for both.
Industrial Circuit Breakers
125-600A Circuit Breakers
Electronic Trip
Spectra RMS
SG600
Digital, Solid-State Spectra RMS Breakers
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-57
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
125-600A Circuit Breakers
Electronic Trip
Spectra RMS
SG600
Digital, Solid-State Spectra RMS Breakers
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
SGL, SGP UL Current Limiting
UL/CSA: 600A, 600 Vac Max., IEC 947-2: 630A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac
Instantaneous 100kA
Ampere Trip Ampere Range Product List Current Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Range
250 765 2530 SRPG600A250 $106.00 2-pole lug kit
300 915 3035 SRPG600A300 $106.00 2SGPA26AT0600 $4607.00 (2) 2/0-500 Cu
350 1070 3545 SRPG600A350 $106.00 TCLK2651$28.00 or
400 1220 4050 SRPG600A400 $106.00 600 (1) 8-600 Cu
450 1375 4555 SRPG600A450 $106.00 3-pole lug kit
500 1525 5060 SRPG600A500 $106.00 3SGPA36AT0600 $5548.00 (2) 2/0-500 Al
600 1830 6075 SRPG600A600 $106.00 TCLK3651$42.00 or (1) 6-600 Al
1Order one kit for either line or load end; two kits required for both.
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
SGL, SGP UL Current Limiting
100% UL Rated, 3-Pole: 400A, 600 Vac Max.; IEC 947-2: 400A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 35kAIC 65kAIC
Ampere Trip Ampere Range Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Number Price Range
125 380 1275 SRPG400A125 $106.00
150 455 1530 SRPG400A150 $106.00 (2) 2/0-500 Cu
175 530 1785 SRPG400A175 $106.00 or
200 605 2040 SRPG400A200 $106.00 (1) 8-600 Cu
225 680 2295 SRPG400A225 $106.00 400 3 SGHH36AT0400 $4381.00 SGLL36AT0400 $5501.00 TCLK365 $42.00
250 755 2550 SRPG400A250 $106.00
300 905 3060 SRPG400A300 $106.00 (2) 2/0-500 Al
350 1060 3570 SRPG400A350 $106.00 or
400 1210 4080 SRPG400A400 $106.00 (1) 6-600 Al
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
SGL, SGP UL Current Limiting
100% UL Rated, 3-Pole: 400A, 600 Vac Max.; IEC 947-2: 400A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac
Instantaneous 100kAIC
Ampere Trip Ampere Range Product List Current Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Range
125 380 1275 SRPG400A125 $106.00
150 455 1530 SRPG400A150 $106.00 (2) 2/0-500 Cu
175 530 1785 SRPG400A175 $106.00 or
200 605 2040 SRPG400A200 $106.00 (1) 8-600 Cu
225 680 2295 SRPG400A225 $106.00 400 3 SGPP36AT0400 $6049.00 TCLK365 $42.00
250 755 2550 SRPG400A250 $106.00
300 905 3060 SRPG400A300 $106.00 (2) 2/0-500 Al
350 1060 3570 SRPG400A350 $106.00 or
400 1210 4080 SRPG400A400 $106.00 (1) 6-600 Al
Prices and data subject to change without notice
3-58 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
125-600A Circuit Breakers
Electronic Trip
Spectra RMS
SG600
Digital, Solid-State Spectra RMS Breakers
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
SGL, SGP UL Current Limiting
100% UL Rated, 3-Pole: 600A, 600 Vac Max.; IEC 947-2: 630A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 35kAIC 65kAIC
Ampere Trip Ampere Range Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Number Price Range
250 765 2530 SRPG600A250 $106.00
300 915 3035 SRPG600A300 $106.00 (2) 2/0-500 Cu
350 1070 3545 SRPG600A350 $106.00 or (1) 8-600 Cu
400 1220 4050 SRPG600A400 $106.00 600 3 SGHH36AT0600 $5451.00 SGLL36AT0600 $6783.00 TCLK365 $42.00
450 1375 4555 SRPG600A450 $106.00 (2) 2/0-500 Al
500 1525 5060 SRPG600A500 $106.00 (1) 6-600 Al
600 1830 6075 SRPG600A600 $106.00
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
SGL, SGP UL Current Limiting
100% UL Rated, 3-Pole: 600A, 600 Vac Max.; IEC 947-2: 630A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac
Instantaneous 100kAIC
Ampere Trip Ampere Range Product List Current Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Range
250 765 2530 SRPG600A250 $106.00
300 915 3035 SRPG600A300 $106.00 (2) 2/0-500 Cu
350 1070 3545 SRPG600A350 $106.00 or (1) 8-600 Cu
400 1220 4050 SRPG600A400 $106.00 600 3 SGPP36AT0600 $7212.00 TCLK365 $42.00
450 1375 4555 SRPG600A450 $106.00 (2) 2/0-500 Al
500 1525 5060 SRPG600A500 $106.00 or (1) 6-600 Al
600 1830 6075 SRPG600A600 $106.00
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-59
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
60-600A Circuit Breakers
Electronic Trip
Spectra RMS
SG600 with MicroVersaTrip Plus and PM
MicroVersaTrip Plus, Standard UL Rated GO-135S
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SGL, SGP UL Current Limiting; 3-Pole, UL/CSA: 600 Vac Max., IEC 947-2: 630A, 690 Vac Max.
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 35kA 65kA 100kA
Sensor Function Product Number List Price Product Number List Price Product Number List Price Product Number List Price Wire Range
LIT SGHB36BA0150 $2597.00 SGLB36BA0150 $3752.00 SGPB36BA0150 $4932.00
LSIT SGHB36BB0150 $3962.00 SGLB36BB0150 $5117.00 SGPB36BB0150 $6297.00
150 LIGT1SGHB36BC0150 $3807.00 SGLB36BC0150 $4962.00 SGPB36BC0150 $6142.00
LSIGT1SGHB36BD0150 $5172.00 SGLB36BD0150 $6327.00 SGPB36BD0150 $7507.00
LIT-CP2SGHB36BE0150 $2897.00 SGLB36BE0150 $4052.00 SGPB36BE0150 $5232.00 (2) 2/0-500 Cu
LSIT-CP2SGHB36BF0150 $4262.00 SGLB36BF0150 $5417.00 SGPB36BF0150 $6597.00 or
LIT SGHB36BA0400 $2597.00 SGLB36BA0400 $3752.00 SGPB36BA0400 $4932.00 3-Pole $42.00 (1) 8-600 Cu
LSIT SGHB36BB0400 $3962.00 SGLB36BB0400 $5117.00 SGPB36BB0400 $6297.00 lug kit
400 LIGT1SGHB36BC0400 $3807.00 SGLB36BC0400 $4962.00 SGPB36BC0400 $6142.00 TCLK3653
LSIGT1SGHB36BD0400 $5172.00 SGLB36BD0400 $6327.00 SGPB36BD0400 $7507.00 (2) 2/0-500 Al
LIT-CP2SGHB36BE0400 $2897.00 SGLB36BE0400 $4052.00 SGPB36BE0400 $5232.00 or
LSIT-CP2SGHB36BF0400 $4262.00 SGLB36BF0400 $5417.00 SGPB36BF0400 $6597.00 (1) 6-600 Al
LIT SGHB36BA0600 $3551.00 SGLB36BA0600 $4505.00 SGPB36BA0600 $5880.00
LSIT SGHB36BB0600 $4916.00 SGLB36BB0600 $5870.00 SGPB36BB0600 $7245.00
600 LIGT1SGHB36BC0600 $4761.00 SGLB36BC0600 $5715.00 SGPB36BC0600 $7090.00
LSIGT1SGHB36BD0600 $6126.00 SGLB36BD0600 $7080.00 SGPB36BD0600 $8455.00
LIT-CP2SGHB36BE0600 $3851.00 SGLB36BE0600 $4805.00 SGPB36BE0600 $6180.00
LSIT-CP2SGHB36BF0600 $5216.00 SGLB36BF0600 $6170.00 SGPB36BF0600 $7545.00
MicroVersaTrip Plus, 100% UL Rate4GO-135S
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SGL, SGP UL Current Limiting; 3-Pole, UL/CSA: 600 Vac Max., IEC 947-2: 630A, 690 Vac Max.
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 35kA 65kA 100kA
Sensor Function Product Number List Price Product Number List Price Product Number List Price Product Number List Price Wire Range
LIT SGHH36BA0150 $4774.00 SGLL36BA0150 $5919.00 SGPP36BA0150 $6412.00
LSIT SGHH36BB0150 $6139.00 SGLL36BB0150 $7284.00 SGPP36BB0150 $7777.00
150 LIGT1SGHH36BC0150 $5984.00 SGLL36BC0150 $7129.00 SGPP36BC0150 $7622.00
LSIGT1SGHH36BD0150 $7349.00 SGLL36BD0150 $8494.00 SGPP36BD0150 $8987.00
LIT-CP2SGHH36BE0150 $5074.00 SGLL36BE0150 $6219.00 SGPP36BE0150 $6712.00 (2) 2/0-500 Al
LSIT-CP2SGHH36BF0150 $6439.00 SGLL36BF0150 $7584.00 SGPP36BF0150 $8077.00 or
LIT SGHH36BA0400 $4774.00 SGLL36BA0400 $5919.00 SGPP36BA0400 $6412.00 3-Pole $42.00 (1) 6-600 Al
LSIT SGHH36BB0400 $6139.00 SGLL36BB0400 $7284.00 SGPP36BB0400 $7777.00 lug kit
400 LIGT1SGHH36BC0400 $5984.00 SGLL36BC0400 $7129.00 SGPP36BC0400 $7622.00 TCLK3653
LSIGT1SGHH36BD0400 $7349.00 SGLL36BD0400 $8494.00 SGPP36BD0400 $8987.00 (2) 2/0-500 Cu
LIT-CP2SGHH36BE0400 $5074.00 SGLL36BE0400 $6219.00 SGPP36BE0400 $6712.00 or
LSIT-CP2SGHH36BF0400 $6439.00 SGLL36BF0400 $7584.00 SGPP36BF0400 $8077.00 (1) 8-600 Cu
LIT SGHH36BA0600 $5771.00 SGLL36BA0600 $7155.00 SGPP36BA0600 $7644.00
LSIT SGHH36BB0600 $7136.00 SGLL36BB0600 $8520.00 SGPP36BB0600 $9009.00
600 LIGT3SGHH36BC0600 $6981.00 SGLL36BC0600 $8365.00 SGPP36BC0600 $8854.00
LSIGT3SGHH36BD0600 $8346.00 SGLL36BD0600 $9730.00 SGPP36BD0600 $10219.00
LIT-CP4SGHH36BE0600 $6071.00 SGLL36BE0600 $7455.00 SGPP36BE0600 $7944.00
LSIT-CP4SGHH36BF0600 $7436.00 SGLL36BF0600 $8820.00 SGPP36BF0600 $9309.00
1For grounded neutral systems (1**/3w or 3**4w) a neutral current sensor is required. Refer to page 3-109.
2For +24 Vdc Control Power Accessories refer to pages 3-106 to 3-109.
3Order one kit for either line or load end; two kits required for both.
4100% UL rated supplied with back-connected assembly which increases breaker depth. Refer to outline drawing for details.
Prices and data subject to change without notice
3-60 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
60-600A Circuit Breakers
Electronic Trip
Spectra RMS
with MicroVersaTrip PM Trip Units1
MicroVersaTrip PM, Standard UL Rated (No Protective Relays) GO-135S
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SGL, SGP UL Current Limiting; 3-Pole, UL/CSA: 600 Vac Max., IEC 947-2: 630A, 690 Vac Max.
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 35kA 65kA 100kA
Sensor Function Product Number List Price Product Number List Price Product Number List Price Product Number List Price Wire Range
LIT SGHB36CA0150 $3797.00 SGLB36CA0150 $4952.00 SGPB36CA0150 $6132.00
150 LSIT SGHB36CB0150 $5162.00 SGLB36CB0150 $6317.00 SGPB36CB0150 $7497.00 (2) 2/0-500 Cu
LIGT2SGHB36CC0150 $5007.00 SGLB36CC0150 $6162.00 SGPB36CC0150 $7342.00 or
LSIGT2SGHB36CD0150 $6372.00 SGLB36CD0150 $7527.00 SGPB36CD0150 $8707.00 (1) 8-600 Cu
LIT SGHB36CA0400 $3797.00 SGLB36CA0400 $4952.00 SGPB36CA0400 $6132.00 3-Pole $42.00
400 LSIT SGHB36CB0400 $5162.00 SGLB36CB0400 $6317.00 SGPB36CB0400 $7497.00 lug kit
LIGT2SGHB36CC0400 $5007.00 SGLB36CC0400 $6162.00 SGPB36CC0400 $7342.00 TCLK3653(2) 2/0-500 Al
LSIGT2SGHB36CD0400 $6372.00 SGLB36CD0400 $7527.00 SGPB36CD0400 $8707.00 or
LIT SGHB36CA0600 $4751.00 SGLB36CA0600 $5705.00 SGPB36CA0600 $7080.00 (1) 6-600 Al
600 LSIT SGHB36CB0600 $6116.00 SGLB36CB0600 $7070.00 SGPB36CB0600 $8445.00
LIGT2SGHB36CC0600 $5961.00 SGLB36CC0600 $6915.00 SGPB36CC0600 $8290.00
LSIGT2SGHB36CD0600 $7326.00 SGLB36CD0600 $8280.00 SGPB36CD0600 $9655.00
MicroVersaTrip PM, 100% UL Rated4(No Protective Relays) GO-135S
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SGL, SGP UL Current Limiting; 3-Pole, UL/CSA: 600 Vac Max., IEC 947-2: 630A, 690 Vac Max.
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 35kA 65kA 100kA
Sensor Function Product Number List Price Product Number List Price Product Number List Price Product Number List Price Wire Range
LIT SGHH36CA0150 $5974.00 SGLL36CA0150 $7119.00 SGPP36CA0150 $7612.00
150 LSIT SGHH36CB0150 $7339.00 SGLL36CB0150 $8484.00 SGPP36CB0150 $8977.00 (2) 2/0-500 Cu
LIGT2SGHH36CC0150 $7184.00 SGLL36CC0150 $8329.00 SGPP36CC0150 $8822.00 or
LSIGT2SGHH36CD0150 $8549.00 SGLL36CD0150 $9694.00 SGPP36CD0150 $10187.00 (1) 8-600 Cu
LIT SGHH36CA0400 $5974.00 SGLL36CA0400 $7119.00 SGPP36CA0400 $7612.00 3-Pole $42.00
400 LSIT SGHH36CB0400 $7339.00 SGLL36CB0400 $8484.00 SGPP36CB0400 $8977.00 lug kit
LIGT2SGHH36CC0400 $7184.00 SGLL36CC0400 $8329.00 SGPP36CC0400 $8822.00 TCLK3653(2) 2/0-500 Al
LSIGT2SGHH36CD0400 $8549.00 SGLL36CD0400 $9694.00 SGPP36CD0400 $10187.00 or
LIT SGHH36CA0600 $6971.00 SGLL36CA0600 $8355.00 SGPP36CA0600 $8844.00 (1) 6-600 Al
600 LSIT SGHH36CB0600 $8336.00 SGLL36CB0600 $9720.00 SGPP36CB0600 $10209.00
LIGT2SGHH36CC0600 $8181.00 SGLL36CC0600 $9565.00 SGPP36CC0600 $10054.00
LSIGT2SGHH36CD0600 $9546.00 SGLL36CD0600 $10930.00 SGPP36CD0600 $11419.00
MicroVersaTrip Plus and PM Rating Plug Selection —
All Plugs List Price, $106.00 GO-135S
Circuit Breaker Sensor Rating Plug Rating Plug
Frame Rating Rating (Amperes) Product No.
15060SRPG150B60
80 SRPG150B80
100 SRPG150B100
125 SRPG150B125
150 SRPG150B150
400 150 SRPG400B150
200 SRPG400B200
SGHB, SGHH, SGLB, 225 SRPG400B225
SGLL, SGPB, SGPP 250 SRPG400B250
300 SRPG400B300
350 SRPG400B350
400 SRPG400B400
600 300 SRPG600B300
400 SRPG600B400
450 SRPG600B450
500 SRPG600B500
600 SRPG600B600
1MicroVersaTrip PM Trip Units require 24 Vdc control power and voltage sensing signals. Refer to pages 3-106 to 3-109.
2For grounded neutral systems (1**/3w or 3**4w) a neutral current sensor is required. Refer to page 3-109.
3Order one kit for either line or load end; two kits required for both.
4100% UL rated supplied with back-connected assembly which increases breaker depth. Refer to outline drawing for details.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-61
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
60-600A Circuit Breakers
Electronic Trip
Spectra RMS
with MicroVersaTrip PM Trip Units1
MicroVersaTrip PM, Standard UL Rated (With Protective Relaying) GO-135S
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SGL, SGP UL Current Limiting; 3-Pole, UL/CSA: 600 Vac Max., IEC 947-2: 630A, 690 Vac Max.
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 35kA 65kA 100kA
Sensor Function Product Number List Price Product Number List Price Product Number List Price Product Number List Price Wire Range
LIT SGHB36DA0150 $4997.00 SGLB36DA0150 $6152.00 SGPB36DA0150 $7332.00
150 LSIT SGHB36DB0150 $6362.00 SGLB36DB0150 $7517.00 SGPB36DB0150 $8697.00 (2) 2/0-500 Cu
LIGT2SGHB36DC0150 $6207.00 SGLB36DC0150 $7362.00 SGPB36DC0150 $8542.00 or
LSIGT2SGHB36DD0150 $7572.00 SGLB36DD0150 $8727.00 SGPB36DD0150 $9907.00 (1) 8-600 Cu
LIT SGHB36DA0400 $4997.00 SGLB36DA0400 $6152.00 SGPB36DA0400 $7332.00 3-Pole $42.00
400 LSIT SGHB36DB0400 $6362.00 SGLB36DB0400 $7517.00 SGPB36DB0400 $8697.00 lug kit
LIGT2SGHB36DC0400 $6207.00 SGLB36DC0400 $7362.00 SGPB36DC0400 $8542.00 TCLK3653(2) 2/0-500 Al
LSIGT2SGHB36DD0400 $7572.00 SGLB36DD0400 $8727.00 SGPB36DD0400 $9907.00 or
LIT SGHB36DA0600 $5951.00 SGLB36DA0600 $6905.00 SGPB36DA0600 $8280.00 (1)6-600 Al
600 LSIT SGHB36DB0600 $7316.00 SGLB36DB0600 $8270.00 SGPB36DB0600 $9645.00
LIGT2SGHB36DC0600 $7161.00 SGLB36DC0600 $8115.00 SGPB36DC0600 $9490.00
LSIGT2SGHB36DD0600 $8526.00 SGLB36DD0600 $9480.00 SGPB36DD0600 $10855.00
MicroVersaTrip PM, 100% UL Rated4(With Protective Relays) GO-135S
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SGL, SGP UL Current Limiting; 3-Pole, UL/CSA: 600 Vac Max., IEC 947-2: 630A, 690 Vac Max.
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 35kA 65kA 100kA
Sensor Function Product Number List Price Product Number List Price Product Number List Price Product Number List Price Wire Range
LIT SGHH36DA0150 $7174.00 SGLL36DA0150 $8319.00 SGPP36DA0150 $8812.00
150 LSIT SGHH36DB0150 $8539.00 SGLL36DB0150 $9684.00 SGPP36DB0150 $10177.00 (2) 2/0-500 Cu
LIGT2SGHH36DC0150 $8384.00 SGLL36DC0150 $9529.00 SGPP36DC0150 $10022.00 or
LSIGT2SGHH36DD0150 $9749.00 SGLL36DD0150 $10894.00 SGPP36DD0150 $11387.00 (1) 6-600 Cu
LIT SGHH36DA0400 $7174.00 SGLL36DA0400 $8319.00 SGPP36DA0400 $8812.00 3-Pole $42.00
400 LSIT SGHH36DB0400 $8539.00 SGLL36DB0400 $9684.00 SGPP36DB0400 $10177.00 lug kit
LIGT2SGHH36DC0400 $8384.00 SGLL36DC0400 $9529.00 SGPP36DC0400 $10022.00 TCLK3653(2) 2/0-500 Al
LSIGT2SGHH36DD0400 $9749.00 SGLL36DD0400 $10894.00 SGPP36DD0400 $11387.00 or
LIT SGHH36DA0600 $8171.00 SGLL36DA0600 $9555.00 SGPP36DA0600 $10044.00 (1) 8-600 Al
600 LSIT SGHH36DB0600 $9536.00 SGLL36DB0600 $10920.00 SGPP36DB0600 $11409.00
LIGT2SGHH36DC0600 $9381.00 SGLL36DC0600 $10765.00 SGPP36DC0600 $11254.00
LSIGT2SGHH36DD0600 $10746.00 SGLL36DD0600 $12130.00 SGPP36DD0600 $12619.00
MicroVersaTrip Plus and PM Rating Plug Selection —
All Plugs List Price, $106.00 GO-135S
Circuit Breaker Sensor Rating Plug Rating Plug
Frame Rating Rating (Amperes) Product No.
15060SRPG150B60
80 SRPG150B80
100 SRPG150B100
125 SRPG150B125
150 SRPG150B150
400 150 SRPG400B150
200 SRPG400B200
SGHB, SGHH, SGLB, 225 SRPG400B225
SGLL, SGPB, SGPP 250 SRPG400B250
300 SRPG400B300
350 SRPG400B350
400 SRPG400B400
600 300 SRPG600B300
400 SRPG600B400
450 SRPG600B450
500 SRPG600B500
600 SRPG600B600
1MicroVersaTrip PM Trip Units require 24 Vdc control power and voltage sensing signals. Refer to pages 3-106 to 3-109.
2For grounded neutral systems (1**/3w or 3**4w) a neutral current sensor is required. Refer to page 3-109.
3Order one kit for either line or load end; two kits required for both.
4100% UL rated supplied with back-connected assembly which increases breaker depth. Refer to outline drawing for details.
Prices and data subject to change without notice
3-62 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Type TJJ Noninterchangeable Trip (includes Line and Load Lugs), suitable for reverse feed GO-135B
Frame
2-Pole, 400 Ampere Frame 3-Pole, 400 Ampere Frame Terminal Lugs for Front
Adjustable Instantaneous 600 Vac, 250 Vdc 600 Vac Connection (Cu/Al)
Ampere Trip Ampere Range Product List Product List Copper/ Wire
Rating Low High Number Price Number Price Aluminum Lugs Size
125 375 1250 TJJ426125WL $2118.00 TJJ436125WL $2573.00
150 450 1500 TJJ426150WL $2118.00 TJJ436150WL $2573.00
175 525 1750 TJJ426175WL $2118.00 TJJ436175WL $2573.00
200 600 2000 TJJ426200WL $2118.00 TJJ436200WL $2573.00 TCAL432
225 675 2250 TJJ426225WL $2118.00 TJJ436225WL $2573.00 Included in (1) 6-600 or
250 750 2500 TJJ426250WL $2118.00 TJJ436250WL $2573.00 price of (2) 2/0-250 Cu/Al
300 900 3000 TJJ426300WL $2118.00 TJJ436300WL $2573.00 breaker
350 1050 3500 TJJ426350WL $2118.00 TJJ436350WL $2573.00
400 1200 4000 TJJ426400WL $2118.00 TJJ436400WL $2573.00
Types TJK, THJK — Interchangeable Trip, not suitable for reverse feed GO-135B
Complete Circuit Breaker Terminal Lugs for Front
Includes Line and Load Lugs Connection (Cu/Al)1
Adjustable Instantaneous Trip Unit Only. Use Product Number
Ampere Trip Ampere Range Standard List Hi-Break List Frame Only List with Standard and List (Order 2 List
Rating Low High Product Number Price Product Number Price Product Number Price Hi-Break Frames Price per pole) Price Wire Size
400A FrameTw o-Pole
125 375 1250 TJK426125WL $2118.00 THJK426125WL $3085.00 TJK426T125 $464.00
150 450 1500 TJK426150WL $2118.00 THJK426150WL $3085.00 TJK426F000 $1598.00 TJK426T150 $464.00
175 525 1750 TJK426175WL $2118.00 THJK426175WL $3085.00 Standard TJK426T175 $464.00
200 600 2000 TJK426200WL $2118.00 THJK426200WL $3085.00 Frame TJK426T200 $464.00
225 675 2250 TJK426225WL $2118.00 THJK426225WL $3085.00 TJK426T225 $464.00
250 750 2500 TJK426250WL $2118.00 THJK426250WL $3085.00 TJK426T250 $464.00 TCAL432$14.00 (1) 6-600
300 900 3000 TJK426300WL $2118.00 THJK426300WL $3085.00 TJK426T300 $464.00 or
350 1050 3500 TJK426350WL $2118.00 THJK426350WL $3085.00 THJK426F000 $2565.00 TJK426T350 $464.00 (2) 2/0-250 Cu/Al
400 1200 4000 TJK426400WL $2118.00 THJK426400WL $3085.00 Hi-Break TJK426T400 $464.00
400A Frame—Three-Pole
125 375 1250 TJK436125WL $2573.00 THJK436125WL $3675.00 TJK436T125 $464.00
150 450 1500 TJK436150WL $2573.00 THJK436150WL $3675.00 TJK436F000 $2025.00 TJK436T150 $464.00
175 525 1750 TJK436175WL $2573.00 THJK436175WL $3675.00 Standard TJK436T175 $464.00
200 600 2000 TJK436200WL $2573.00 THJK436200WL $3675.00 Frame TJK436T200 $464.00
225 675 2250 TJK436225WL $2573.00 THJK436225WL $3675.00 TJK436T225 $464.00 TCAL432$14.00 (1) 6-600
250 750 2500 TJK436250WL $2573.00 THJK436250WL $3675.00 TJK436T250 $464.00 or
300 900 3000 TJK436300WL $2573.00 THJK436300WL $3675.00 TJK436T300 $464.00 (2) 2/0-250 Cu/Al
350 1050 3500 TJK436350WL $2573.00 THJK436350WL $3675.00 THJK436F000 $3127.00 TJK436T350 $464.00
400 1200 4000 TJK436400WL $2573.00 THJK436400WL $3675.00 Hi-Break TJK436T400 $464.00
400 600 2000 TJK436TM14003$558.00
Mag 1200 4000 TJK436TM24003$558.00
Only 350 1000 TJK436TM34003$558.00
1For optional lugs, see page 3-101.
2Not UL listed.
3Alternate lug for 750 kcmil Cu/Al cable, Product Number TCAL47 List Price $26.00, GO-135B.
Accessories: See pages 3-85 to 3-104.
Industrial Circuit Breakers
125-600A Circuit Breakers
Thermal-Magnetic Trip
J600 Line Circuit Breakers
Types TJJ, TJK, THJK
TYPE TJK
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-63
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
125-600A Circuit Breakers
Thermal-Magnetic Trip
J600 Line Circuit Breakers
Types TJJ, TJK, THJK
Types TJK, THJK — Interchangeable Trip GO-135S
Complete Circuit Breaker Terminal Lugs for Front
Includes Line and Load Lugs Connection (Cu/Al)1
Adjustable Instantaneous Trip Unit Only. Use Product Number
Ampere Trip Ampere Range Standard List Hi-Break List Frame Only List with Standard and List (Order 2 List
Rating Low High Product Number Price Product Number Price Product Number Price Hi-Break Frames Price per pole) Price Wire Size
600A FrameTw o-Pole
250 750 2500 TJK626250WL $2812.00 THJK626250WL $3704.00 TJK626T250 $1221.00 TCAL432$14.00 (1) 6-600
300 900 3000 TJK626300WL $2812.00 THJK626300WL $3704.00 TJK626F000 $1535.00 TJK626T300 $1221.00 or
350 1050 3500 TJK626350WL $2812.00 THJK626350WL $3704.00 Standard TJK626T350 $1221.00 (2) 2/0-250 Cu/Al
400 1200 4000 TJK626400WL $2812.00 THJK626400WL $3704.00 Frame TJK626T400 $1221.00
450 1350 4500 TJK626450WL $2848.00 THJK626450WL $3740.00 THJK626F000 TJK626T450 $1221.00 (2) 4/0-350 Cu
500 1500 5000 TJK626500WL $2848.00 THJK626500WL $3740.00 Hi-Break $2427.00 TJK626T500 $1221.00 TCAL63 $23.00 or
600 1800 6000 TJK626600WL $2848.00 THJK626600WL $3740.00 Frame TJK626T600 $1221.00 (2) 300-500 Al
600A FrameThree-Pole
250 750 2500 TJK636250WL $3539.00 THJK636250WL $4457.00 TJK636T250 $1221.00 TCAL432$14.00 (1) 6-600
300 900 3000 TJK636300WL $3539.00 THJK636300WL $4457.00 TJK636F000 $2234.00 TJK636T300 $1221.00 or
350 1050 3500 TJK636350WL $3539.00 THJK636350WL $4457.00 Standard TJK636T350 $1221.00 (2) 2/0-250 Cu/Al
400 1200 4000 TJK636400WL $3539.00 THJK636400WL $4457.00 Frame TJK636T400 $1221.00
450 1350 4500 TJK636450WL $3593.00 THJK636450WL $4511.00 THJK636F000 TJK636T450 $1221.00 (2) 4/0-350 Cu
500 1500 5000 TJK636500WL $3593.00 THJK636500WL $4511.00 Hi-Break $3152.00 TJK636T500 $1221.00 TCAL63 $23.00 or
600 1800 600 TJK636600WL $3593.00 THJK636600WL $4511.00 Frame TJK636T600 $1221.00 (2) 300-500 Al
600 6000 2000 TJK636TM16003$1465.00
Mag
Only 1800 6000 TJK636TM26003$1465.00
1For optional lugs, see page 3-101.
2Alternate lug for 750 kcmil Cu/Al cable, Product Number TCAL47 List Price $26.00, GO-135B.
3Not UL listed.
Accessories: See pages 3-85 to 3-104.
Prices and data subject to change without notice
3-64 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
UL/CSA: 800A, 600 Vac Max., IEC 947-2:800A 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 50kA 65kA
Ampere Trip Ampere Range Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Number Price Range
300 940 3015 SRPK800A300 $106.00
400 1255 4015 SRPK800A400 $106.00 2SKHA26AT0800 $3377.00 SKLA26AT0800 $4301.00 (3) 3/0-500 Cu
500 1570 5020 SRPK800A500 $106.00 800 TCAL81 $47.00
600 1875 6195 SRPK800A600 $106.00
700 2155 7420 SRPK800A700 $106.00 3SKHA36AT0800 $4323.00 SKLA36AT0800 $5234.00 (3) 3/0-500 Al
800 2440 8705 SRPK800A800 $106.00
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
UL/CSA: 800A, 600 Vac Max., IEC 947-2:800A 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac
Instantaneous 100kA
Ampere Trip Ampere Range Product List Current Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Range
300 940 3015 SRPK800A300 $106.00
400 1255 4015 SRPK800A400 $106.00 2SKPA26AT0800 $6746.00 (3) 3/0-500 Cu
500 1570 5020 SRPK800A500 $106.00 800 TCAL81 $47.00
600 1875 6195 SRPK800A600 $106.00
700 2155 7420 SRPK800A700 $106.00 3SKPA36AT0800 $8240.00 (3) 3/0-500 Al
800 2440 8705 SRPK800A800 $106.00
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
UL/CSA: 1200A, 600 Vac Max., IEC 947-2: 1250A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 35kA 65kA
Ampere Trip Ampere Range Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Number Price Range
600 1825 6110 SRPK1200A600 $106.00
700 2125 7125 SRPK1200A700 $106.00 2SKHA26AT1200 $7057.00 SKLA26AT1200 $7958.00 (4) 250-500 Cu1
800 2430 8145 SRPK1200A800 $106.00 1200 TCAL125 $76.00
1000 3040 10180 SRPK1200A1000 $106.00 3SKHA36AT1200 $7679.00 SKLA36AT1200 $8586.00 (4) 250-350 Al
1200 3650 12215 SRPK1200A1200 $106.00
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
UL/CSA: 1200A, 600 Vac Max., IEC 947-2: 1250A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac
Instantaneous 100kA
Ampere Trip Ampere Range Product List Current Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Range
600 1825 6110 SRPK1200A600 $106.00
700 2125 7125 SRPK1200A700 $106.00 2SKPA26AT1200 $10136.00 (4) 250-500 Cu1
800 2430 8145 SRPK1200A800 $106.00 1200 TCAL125 $76.00
1000 3040 10180 SRPK1200A1000 $106.00 3SKPA36AT1200 $11183.00 (4) 250-350 Al
1200 3650 12215 SRPK1200A1200 $106.00
1Suitable for 500 kcmil copper for voltage drop consideration, 1200 ampere max. rating.
Industrial Circuit Breakers
300-1200A Circuit Breakers
Electronic Trip
Spectra RMS
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-65
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
300-1200A Circuit Breakers
Electronic Trip
Spectra RMS
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
100% UL Rated, 3-Pole: 800A, 600 Vac Max.; IEC 947-2: 800A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 50kA 65kA
Ampere Trip Ampere Range Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Number Price Range
300 940 3015 SRPK800A300 $106.00
400 1255 4015 SRPK800A400 $106.00 (3) 3/0-500 Cu
500 1570 5020 SRPK800A500 $106.00 800 3 SKHH36AT0800 $7514.00 SKLL36AT0800 $9325.00 TCAL81 $47.00
600 1875 6195 SRPK800A600 $106.00
700 2155 7420 SRPK800A700 $106.00 (3) 3/0-500 Al
800 2440 8705 SRPK800A800 $106.00
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
100% UL Rated, 3-Pole: 800A, 600 Vac Max.; IEC 947-2: 800A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac
Instantaneous 100kA
Ampere Trip Ampere Range Product List Current Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Range
300 940 3015 SRPK800A300 $106.00
400 1255 4015 SRPK800A400 $106.00 (3) 3/0-500 Cu
500 1570 5020 SRPK800A500 $106.00 800 3 SKPP36AT0800 $10712.00 TCAL81 $47.00
600 1875 6195 SRPK800A600 $106.00
700 2155 7420 SRPK800A700 $106.00 (3) 3/0-500 Al
800 2440 8705 SRPK800A800 $106.00
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
100% UL Rated, 3-Pole: 1000A, 600 Vac Max.; IEC 947-2: 1000A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 50kA 65kA
Ampere Trip Ampere Range Product List Current Product List Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Number Price Range
600 1825 6110 SRPK1200A600 $106.00
700 2125 7125 SRPK1200A700 $106.00 (4) 250-500 Cu2
800 2430 8145 SRPK1200A800 $106.00 1200 3 SKHH36AT1000 $11051.00 SKLL36AT1000 $13678.00 TCAL125 $76.00
1000 3040 10180 SRPK1200A1000 $106.00 (4) 250-350 Al
1200 3650 12215 SRPL12000A1200 $106.00 3SKHH36AT12001$11450.00 SKLL36AT12001$14250.00
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350 GO-135S
100% UL Rated, 3-Pole: 1000A, 600 Vac Max.; IEC 947-2: 1000A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac
Instantaneous 100kA
Ampere Trip Ampere Range Product List Current Product List Product List Wire
Rating Low High Number Price Sensor Poles Number Price Number Price Range
600 1825 6110 SRPK1200A600 $106.00
700 2125 7125 SRPK1200A700 $106.00 (4) 250-500 Cu2
800 2430 8145 SRPK1200A800 $106.00 1200 3 SKPP36AT1000 $14538.00 TCAL125 $76.00
1000 3040 10180 SRPK1200A1000 $106.00 (4) 250-350 Al
1200 3650 12215 SRKP1200A1200 $106.00 3SKPP36AT12001$15235.00
1100% UL rated SK1200 supplied with back-connected assembly which increases breaker depth. Refer to outline drawings for details.
2Suitable for 500 kcmil copper for voltage drop consideration, 1200A max. rating.
Prices and data subject to change without notice
3-66 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
300-1200A Circuit Breakers
Electronic Trip
Spectra RMS
SK1200 with MicroVersaTrip Plus and PM
MicroVersaTrip Plus, Standard UL Rated GO-135S
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
3-Pole, UL/CSA: 1200A, 600 Vac Max., IEC 947-2: 1250A, 690 Vac Max. (SKL, SKP only)
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 50kA 65kA 100kA
Sensor Function Product Number List Price Product Number List Price Product Number List Price Product Number List Price Wire Range
LIT SKHB36BA0800 $4588.00 SKLB36BA0800 $5552.00 SKPB36BA0800 $8734.00
LSIT SKHB36BB0800 $5953.00 SKLB36BB0800 $6917.00 SKPB36BB0800 $10099.00
800 LIGT1SKHB36BC0800 $5798.00 SKLB36BC0800 $6762.00 SKPB36BC0800 $9944.00 TCAL81 $47.00 (3) 3/0-500 Cu
LSIGT1SKHB36BD0800 $7163.00 SKLB36BD0800 $8127.00 SKPB36BD0800 $11309.00 (3) 3/0-500 Al
LIT-CP2SKHB36BE0800 $4888.00 SKLB36BE0800 $5852.00 SKPB36BE0800 $9034.00
LSIT-CP2SKHB36BF0800 $6253.00 SKLB36BF0800 $7217.00 SKPB36BF0800 $10399.00
LIT SKHB36BA1200 $8077.00 SKLB36BA1200 $9048.00 SKPB36BA1200 $11854.00
LSIT SKHB36BB1200 $9442.00 SKLB36BB1200 $10413.00 SKPB36BB1200 $13219.00
1200 LIGT1SKHB36BC1200 $9287.00 SKLB36BC1200 $10258.00 SKPB36BC1200 $13064.00 TCAL125 $76.00 (4) 250-350 Cu3
LSIGT1SKHB36BD1200 $10652.00 SKLB36BD1200 $11623.00 SKPB36BD1200 $14429.00 (4) 250-500 Al
LIT-CP2SKHB36BE1200 $8377.00 SKLB36BE1200 $9348.00 SKPB36BE1200 $12154.00
LSIT-CP2SKHB36BF1200 $9742.00 SKLB36BF1200 $10713.00 SKPB36BF1200 $13519.00
MicroVersaTrip Plus, 100% UL Rated4GO-135S
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
3-Pole, UL/CSA: 1200A, 600 Vac Max., IEC 947-2: 1250A, 690 Vac Max. (SKL, SKP only)
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 50kA 65kA 100kA
Sensor Function Product Number List Price Product Number List Price Product Number List Price Product Number List Price Wire Range
LIT SKHH36BA0800 $7975.00 SKLL36BA0800 $9892.00 SKPP36BA0800 $11354.00
LSIT SKHH36BB0800 $9340.00 SKLL36BB0800 $11257.00 SKPP36BB0800 $12719.00
800 LIGT1SKHH36BC0800 $9185.00 SKLL36BC0800 $11102.00 SKPP36BC0800 $12564.00 TCAL81 $47.00 (3) 3/0-500 Cu
LSIGT1SKHH36BD0800 $10550.00 SKLL36BD0800 $12467.00 SKPP36BD0800 $13929.00 (3) 3/0-500 Al
LIT-CP2SKHH36BE0800 $8275.00 SKLL36BE0800 $10192.00 SKPP36BE0800 $11654.00
LSIT-CP2SKHH36BF0800 $9640.00 SKLL36BF0800 $11557.00 SKPP36BF0800 $13019.00
LIT SKHH36BA1000 $11624.00 SKLL36BA1000 $14414.00 SKPP36BA1000 $15410.00
LSIT SKHH36BB1000 $12989.00 SKLL36BB1000 $15779.00 SKPP36BB1000 $16775.00
1200 LIGT1SKHH36BC1000 $12834.00 SKLL36BC1000 $15624.00 SKPP36BC1000 $16620.00
LSIGT1SKHH36BD1000 $14199.00 SKLL36BD1000 $16989.00 SKPP36BD1000 $17985.00
LIT-CP2SKHH36BE1000 $11924.00 SKLL36BE1000 $14714.00 SKPP36BE1000 $15710.00
LSIT-CP2SKHH36BF1000 $13289.00 SKLL36BF1000 $16079.00 SKPP36BF1000 $17075.00 TCAL125 $76.00 (4) 250-350 Cu3
LIT SKHH36BA1200 $11624.00 SKLL36BA1200 $14414.00 SKPP36BA1200 $15410.00 (4) 250-500 Al
LSIT SKHH36BB1200 $12989.00 SKLL36BB1200 $15779.00 SKPP36BB1200 $16775.00
12004LIGT1SKHH36BC1200 $12834.00 SKLL36BC1200 $15624.00 SKPP36BC1200 $16620.00
LSIGT1SKHH36BD1200 $14199.00 SKLL36BD1200 $16989.00 SKPP36BD1200 $17985.00
LIT-CP2SKHH36BE1200 $11924.00 SKLL36BE1200 $14714.00 SKPP36BE1200 $15710.00
LSIT-CP2SKHH36BF1200 $13289.00 SKLL36BF1200 $16079.00 SKPP36BF1200 $17075.00
MicroVersaTrip Plus and PM Rating Plug Selection —
All Plugs List Price, $106.00 GO-135S
300 SRPK800B300
400 SRPK800B400
800 500 SRPK800B500
600 SRPK800B600
SKHB, SKHH, SKLB, 700 SRPK800B700
SKLL, SKPB, SKPP 800 SRPK800B800
600 SRPK1200B600
700 SRPK1200B700
1200 800 SRPK1200B800
1000 SRPK1200B1000
1200 SRPK1200B12006
1For grounded neutral systems (1**/3w or 3**4w) a neutral current sensor is required. Refer to page 3-109.
2For +24 Vdc Control Power Accessories refer to pages 3-106 to 3-109.
3Suitable for 500 kcmil copper, 1200A max. rating.
4100% UL rated SK1200 supplied with back-connected assembly which increases breaker depth. Refer to outline drawing 168D1678 Sh2 for details.
5For ground fault neutral current sensor, use 1200A rating.
6Not suitable for use with 100% rated, 1000A breaker frame.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-67
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
300-1200A Circuit Breakers
Electronic Trip
Spectra RMS
SK1200 with MicroVersaTrip PM1
MicroVersaTrip PM, Standard UL Rated (No Protective Relays)
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
3-Pole, UL/CSA: 1200A, 600 Vac Max., IEC 947-2: 1250A, 690 Vac Max. (SKL, SKP only)
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 50kA 65kA 100kA
Sensor Function Product Number List Price Product Number List Price Product Number List Price Product Number List Price Wire Range
LIT SKHB36CA0800 $5788.00 SKLB36CA0800 $6752.00 SKPB36CA0800 $9934.00
800 LSIT SKHB36CB0800 $7153.00 SKLB36CB0800 $8117.00 SKPB36CB0800 $11299.00 (3) 3/0-500 Cu
LIGT2SKHB36CC0800 $6998.00 SKLB36CC0800 $7962.00 SKPB36CC0800 $11144.00 TCAL81 $47.00 (3) 3/0-500 Al
LSIGT2SKHB36CD0800 $8363.00 SKLB36CD0800 $9327.00 SKPB36CD0800 $12509.00
LIT SKHB36CA1200 $9277.00 SKLB36CA1200 $10248.00 SKPB36CA1200 $13054.00
1200 LSIT SKHB36CB1200 $10642.00 SKLB36CB1200 $11613.00 SKPB36CB1200 $14419.00 (4) 250-350 Cu3
LIGT2SKHB36CC1200 $10487.00 SKLB36CC1200 $11458.00 SKPB36CC1200 $14264.00 TCAL125 $76.00 (4) 250-500 Al
LSIGT2SKHB36CD1200 $11852.00 SKLB36CD1200 $12823.00 SKPB36CD1200 $15629.00
MicroVersaTrip PM, 100% UL Rated (No Protective Relays)
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
3-Pole, UL/CSA: 1200A, 600 Vac Max., IEC 947-2: 1250A, 690 Vac Max. (SKL, SKP only)
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 50kA 5kA 00kA
Sensor Function Product Number List Price Product Number List Price Product Number List Price Product Number List Price Wire Range
LIT SKHH36CA0800 $9175.00 SKLL36CA0800 $11092.00 SKPP36CA0800 $12554.00
800 LSIT SKHH36CB0800 $10540.00 SKLL36CB0800 $12457.00 SKPP36CB0800 $13919.00 (3) 3/0-500 Cu
LIGT2SKHH36CC0800 $10385.00 SKLL36CC0800 $12302.00 SKPP36CC0800 $13764.00 TCAL81 $47.00 (3) 3/0-500 Al
LSIGT2SKHH36CD0800 $11750.00 SKLL36CD0800 $13667.00 SKPP36CD0800 $15129.00
LIT SKHH36CA1000 $12824.00 SKLL36CA1000 $15614.00 SKPP36CA1000 $16610.00
12004LSIT SKHH36CB1000 $14189.00 SKLL36CB1000 $16979.00 SKPP36CB1000 $17975.00
LIGT2SKHH36CC1000 $14034.00 SKLL36CC1000 $16824.00 SKPP36CC1000 $17820.00
LSIGT2SKHH36CD1000 $15399.00 SKLL36CD1000 $18189.00 SKPP36CD1000 $19185.00 TCAL125 $76.00 (4) 250-350Cu4
LIT SKHH36CA1200 $12824.00 SKLL36CA1200 $15614.00 SKPP36CA1200 $16610.00 (4) 250-500 Al
12005LSIT SKHH36CB1200 $14189.00 SKLL36CB1200 $16979.00 SKPP36CB1200 $17975.00
LIGT2SKHH36CC1200 $14034.00 SKLL36CC1200 $16824.00 SKPP36CC1200 $17820.00
LSIGT2SKHH36CD1200 $15399.00 SKLL36CD1200 $18189.00 SKPP36CD1200 $19185.00
1MicroVersaTrip PM Trip Units require 24 Vdc control power and voltage sensing signals. Refer to pages 3-106 to 3-109.
2For grounded neutral systems (1**/3w or 3**4w) a neutral current sensor is required. Refer to page 3-109.
3Suitable for 500 kcmil copper, 1200A max. rating.
4For ground fault neutral current sensor, use 1200A rating.
5100% UL rated SK1200 supplied with back-connected assembly which increases breaker depth. Refer to outline drawing 168D1678 Sh2 for details.
6Not suitable for use with 100% rated, 1000A breaker frame.
MicroVersaTrip Plus and PM Rating Plug Selection —
All Plugs List Price, $106.00 GO-135S
300 SRPK800B300
400 SRPK800B400
800 500 SRPK800B500
600 SRPK800B600
SKHB, SKHH, SKLB, 700 SRPK800B700
SKLL, SKPB, SKPP 800 SRPK800B800
600 SRPK1200B600
700 SRPK1200B700
1200 800 SRPK1200B800
1000 SRPK1200B1000
1200 SRPK1200B12006
Prices and data subject to change without notice
3-68 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
300-1200A Circuit Breakers
Electronic Trip
Spectra RMS
SK1200 with MicroVersaTrip Plus and PM1
MicroVersaTrip PM, Standard UL Rated (With Protective Relaying)
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
3-Pole, UL/CSA: 1200A, 600 Vac Max., IEC 947-2: 1250A, 690 Vac Max. (SKL, SKP only)
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 50kA List Price, 65kA List Price, 100kA List Price, List Price,
Sensor Function Product Number GO-135PM Product Number GO-135PM Product Number GO-135PM Product Number GO-135S Wire Range
LIT SKHB36DA0800 $6988.00 SKLB36DA0800 $7952.00 SKPB36DA0800 $11134.00
800 LSIT SKHB36DB0800 $8353.00 SKLB36DB0800 $9317.00 SKPB36DB0800 $12499.00 (3) 3/0-500 Cu
LIGT2SKHB36DC0800 $8198.00 SKLB36DC0800 $9162.00 SKPB36DC0800 $12344.00 TCAL81 $47.00 (3) 3/0-500 Al
LSIGT2SKHB36DD0800 $9563.00 SKLB36DD0800 $10527.00 SKPB36DD0800 $13709.00
LIT SKHB36DA1200 $10477.00 SKLB36DA1200 $11448.00 SKPB36DA1200 $14254.00
1200 LSIT SKHB36DB1200 $11842.00 SKLB36DB1200 $12813.00 SKPB36DB1200 $15619.00 (4) 250-350 Cu3
LIGT2SKHB36DC1200 $11687.00 SKLB36DC1200 $12658.00 SKPB36DC1200 $15464.00 TCAL125 $76.00 (4) 250-500 Al
LSIGT2SKHB36DD1200 $13052.00 SKLB36DD1200 $14023.00 SKPB36DD1200 $16829.00
MicroVersaTrip PM, 100% UL Rated (With Protective Relays)
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
3-Pole, UL/CSA: 1200A, 600 Vac Max., IEC 947-2: 1250A, 690 Vac Max. (SKL, SKP only)
Frame Terminal Lugs for Front connection (Cu/Al)
IC @480 Vac, UL 489 IC @480 Vac, UL 489 IC @480 Vac, UL 489
Current Trip 50kA List Price, 65kA List Price, 100kA List Price, List Price,
Sensor Function Product Number GO-135PM Product Number GO-135PM Product Number GO-135PM Product Number GO-135S Wire Range
LIT SKHH36DA0800 $10375.00 SKLL36DA0800 $12292.00 SKPP36DA0800 $13754.00
800 LSIT SKHH36DB0800 $11740.00 SKLL36DB0800 $13657.00 SKPP36DB0800 $15119.00 (3) 3/0-500 Cu
LIGT2SKHH36DC0800 $11585.00 SKLL36DC0800 $13502.00 SKPP36DC0800 $14964.00 TCAL81 $47.00 (3) 3/0-500 Al
LSIGT2SKHH36DD0800 $12950.00 SKLL36DD0800 $14867.00 SKPP36DD0800 $16329.00
LIT SKHH36DA1000 $14024.00 SKLL36DA1000 $16814.00 SKPP36DA1000 $17810.00
12004LSIT SKHH36DB1000 $15389.00 SKLL36DB1000 $18179.00 SKPP36DB1000 $19175.00
LIGT2SKHH36DC1000 $15234.00 SKLL36DC1000 $18024.00 SKPP36DC1000 $19020.00
LSIGT2SKHH36DD1000 $16599.00 SKLL36DD1000 $19389.00 SKPP36DD1000 $20385.00 TCAL125 $76.00 (4) 250-350 Cu3
LIT SKHH36DA1200 $14024.00 SKLL36DA1200 $16814.00 SKPP36DA1200 $17810.00 (4) 250-500 Al
12005LSIT SKHH36DB1200 $15389.00 SKLL36DB1200 $18179.00 SKPP36DB1200 $19175.00
LIGT2SKHH36DC1200 $15234.00 SKLL36DC1200 $18024.00 SKPP36DC1200 $19020.00
LSIGT2SKHH36DD1200 $16599.00 SKLL36DD1200 $19389.00 SKPP36DD1200 $20385.00
MicroVersaTrip Plus and PM Rating Plug Selection —
All Plugs List Price, $106.00 GO-135S
300 SRPK800B300
400 SRPK800B400
800 500 SRPK800B500
600 SRPK800B600
SKHB, SKHH, SKLB, 700 SRPK800B700
SKLL, SKPB, SKPP 800 SRPK800B800
600 SRPK1200B600
700 SRPK1200B700
1200 800 SRPK1200B800
1000 SRPK1200B1000
1200 SRPK1200B12006
1MicroVersaTrip PM Trip Units require 24 Vdc control power and voltage sensing signals. Refer to pages 3-106 to 3-109.
2For grounded neutral systems (1**/3w or 3**4w) a neutral current sensor is required. Refer to page 3-109.
3Suitable for 500 kcmil copper, 1200A max. rating.
4For ground fault neutral current sensor, use 1200A rating.
5100% UL rated SK1200 supplied with back-connected assembly which increases breaker depth. Refer to outline drawing 168D1678 Sh2 for details.
6Not suitable for use with 100% rated, 1000A breaker frame.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-69
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
300-1200A Circuit Breakers
Thermal-Magnetic Trip
K1200 Line Circuit Breakers
Types TKM, THMK
Types TKM, THKM — Interchangeable Trip, not suitable for reverse feed GO-135B
Complete Circuit Breaker Terminal Lugs for Front
Includes Line and Load Lugs Connection (Cu/Al)1
Adjustable Instantaneous Trip Unit Only. Use Product Number
AmpereTrip Ampere Range Standard List Hi-Break1List Frame Only List with Standard and List (Order 2 List
Rating Low High Product Number Price Product Number Price Product Number Price Hi-Break Frames Price per pole) Price Wire Size
800A FrameTw o-Pole
300 900 3000 TKMA826300WL $3672.00 THKMA826300WL $4579.00 TKMA836T300 $2268.00
350 1050 3500 TKMA826350WL $3672.00 THKMA826350WL $4579.00 TKM826F000 $1244.00 TKMA836T350 $2268.00
400 1200 4000 TKMA826400WL $3672.00 THKMA826400WL $4579.00 Standard TKMA836T400 $2268.00 TCAL61 $40.00 (2) 2/0-500
450 1350 4500 TKMA826450WL $3672.00 THKMA826450WL $4579.00 Frame TKMA836T450 $2268.00 Cu/Al
500 1500 5000 TKMA826500WL $3672.00 THKMA826500WL $4579.00 TKMA836T500 $2268.00
600 1800 6000 TKMA826600WL $3672.00 THKMA826600WL $4579.00 TKMA836T600 $2268.00
700 2100 6400 TKMA826700WL $3700.00 THKMA826700WL $4611.00 THKM826F000 TKMA836T700 $2268.00 TCAL81 $47.002(3) 3/0-500
800 2400 6400 TKMA826800WL $3700.00 THKMA826800WL $4611.00 Hi-Break Frame $2167.00 TKMA836T800 $2268.00 Cu/Al
800A FrameThree-Pole
300 900 3000 TKMA836300WL $4713.00 THKMA836300WL $5624.00 TKMA836T300 $2268.00
350 1050 3500 TKMA836350WL $4713.00 THKMA836350WL $5624.00 TKM836F000 $2205.00 TKMA836T350 $2268.00
400 1200 4000 TKMA836400WL $4713.00 THKMA836400WL $5624.00 Standard TKMA836T400 $2268.00 TCAL61 $40.00 (2) 2/0-500
450 1350 4500 TKMA836450WL $4713.00 THKMA836450WL $5624.00 Frame TKMA836T450 $2268.00 Cu/Al
500 1500 5000 TKMA836500WL $4713.00 THKMA836500WL $5624.00 TKMA836T500 $2268.00
600 1800 6000 TKMA836600WL $4713.00 THKMA836600WL $5624.00 TKMA836T600 $2268.00
700 2100 6400 TKMA836700WL $4755.00 THKMA836700WL $5666.00 TKMA836T700 $2268.00
800 2400 6400 TKMA836800WL $4755.00 THKMA836800WL $5666.00 TKMA836T800 $2268.00 TCAL81 $47.004(3) 3/0-500
800 1200 4000 THKM836F000 Cu/Al
Mag 2400 8000 Hi-Break Frame $3116.00 TKMA836TM483$2268.00
Only TKMA836TM683$2268.00
1For optional lugs, see page 3-101.
2Not UL listed.
3Internal accessory installation requires dummy trip unit. See page 3-91 for additional details. Nonautomatic trip unit and dummy trip unit not UL listed for field installation.
4GO-135S.
Prices and data subject to change without notice
3-70 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Industrial Circuit Breakers
300-1200A Circuit Breakers
Thermal-Magnetic Trip
K1200 Line Circuit Breakers
Types TKM, THMK
Types TKM, THKM — Interchangeable Trip, not suitable for reverse feed GO-135B
Complete Circuit Breaker Terminal Lugs for Front
Includes Line and Load Lugs Connection (Cu/Al)1
Adjustable Instantaneous Trip Unit Only. Use Product Number
AmpereTrip Ampere Range Standard List Hi-Break1List Frame Only List with Standard and List (Order 2 List
Rating Low High Product Number Price Product Number Price Product Number Price Hi-Break Frames Price per pole) Price Wire Size
1200 Frame—Two-Pole
600 1800 6000 TKMA20600WL $5172.00 THKMA20600WL $6069.00 TKM2F TKMA3T0600 $2294.00 TCAL81 $47.002(3) 3/0-500
700 2100 6400 TKMA20700WL $5172.00 THKMA20700WL $6069.00 Standard $2690.00 TKMA3T0700 $2294.00 Cu/Al
800 2400 6400 TKMA20800WL $5172.00 THKMA20800WL $6069.00 Frame TKMA3T0800 $2294.00
1000 3000 10000 TKMA21000WL3$5472.00 THKMA21000WL3$6353.00 TKMA3T10004$2478.00 (4) 250-3505
1200 3600 10000 TKMA21200WL3$7471.00 THKMA21200WL3$8368.00 TKMA3T12004$4477.00 TCAL121 $76.002Cu or
THKM2F $3587.00 (4) 300-500
Hi-Break Frame Al
1200 Frame—Three-Pole
600 1800 6000 TKMA30600WL $5885.00 THKMA30600WL $6795.00 TKMA3T0600 $2294.00 TCAL81 $47.002(3) 3/0-500
700 2100 6400 TKMA30700WL $5885.00 THKMA30700WL $6795.00 TKMA3T0700 $2294.00 Cu/Al
800 2400 6400 TKMA30800WL $5885.00 THKMA30800WL $6795.00 TKM3F $3309.00 TKMA3T0800 $2294.00
1000 3000 10000 TKMA31000WL4$6243.00 THKMA31000WL4$7153.00 Standard TKMA3T10004$2478.00
1200 3600 10000 TKMA31200WL4$8242.00 THKMA31200WL4$9152.00 Frame TKMA3T12004$4477.00
1200 (4) 250-3505
Mag 1800 6000 THKM2F $4219.00 TKMA3TM5123$4477.00 TCAL121 $76.002Cu or
Only 2400 8000 Hi-Break Frame TKMA3TM6123$4477.00 (4) 300-500
Al
1For optional lugs, see page 3-101.
2GO-135S.
3Not UL listed.
4Not Suitable for use on dc systems.
5Suitable for 500 kcmil Cu for voltage drop considerations.
Accessories: See pages 3-85 to 3-104.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-71
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Circuit Breaker Frame Selection
MicroVersaTrip Plus Trip Units GO-135S
Standard Rating 100% Rating
Current Trip 65kAIC 65kAIC
Sensor Function Product Number List Price Product Number List Price
LIT TRLA36BA10 $10610.00 TRLL36BA10 $13871.00
LSIT TRLA36BB10 $11975.00 TRLL36BB10 $15236.00
LIGT TRLA36BC10 $11820.00 TRLL36BC10 $15081.00
1000 A LSIGT TRLA36BD10 $13185.00 TRLL36BD10 $16446.00
LIGTZ1 TRLA36BE10 $12405.00 TRLL36BE10 $15666.00
LSIGTZ1 TRLA36BF10 $13770.00 TRLL36BF10 $17031.00
LSIGTZ2 TRLA36BG10 $14355.00 TRLL36BG10 $17616.00
LIT TRLA36BA16 $10610.00 TRLL36BA16 $13871.00
LSIT TRLA36BB16 $11975.00 TRLL36BB16 $15236.00
LIGT TRLA36BC16 $11820.00 TRLL36BC16 $15081.00
1600 A LSIGT TRLA36BD16 $13185.00 TRLL36BD16 $16446.00
LIGTZ1 TRLA36BE16 $12405.00 TRLL36BE16 $15666.00
LSIGTZ1 TRLA36BF16 $13770.00 TRLL36BF16 $17031.00
LSIGTZ2 TRLA36BG16 $14355.00 TRLL36BG16 $17616.00
LIT TRLA36BA20 $11488.00 TRLL36BA20 $14986.00
LSIT TRLA36BB20 $12853.00 TRLL36BB20 $16351.00
LIGT TRLA36BC20 $12698.00 TRLL36BC20 $16196.00
2000 A LSIGT TRLA36BD20 $14063.00 TRLL36BD20 $17561.00
LIGTZ1 TRLA36BE20 $13283.00 TRLL36BE20 $16781.00
LSIGTZ1 TRLA36BF20 $14648.00 TRLL36BF20 $18146.00
LSIGTZ2 TRLA36BG20 $15233.00 TRLL36BG20 $18731.00
Standard Rating 100% Rating
Current Trip 100kAIC 100kAIC
Sensor Function Product Number List Price Product Number List Price
LIT TRPA36BA10 $12465.00 TRPP36BA10 $16258.00
LSIT TRPA36BB10 $13830.00 TRPP36BB10 $17623.00
LIGT TRPA36BC10 $13675.00 TRPP36BC10 $17468.00
1000 A LSIGT TRPA36BD10 $15040.00 TRPP36BD10 $18833.00
LIGTZ1 TRPA36BE10 $14260.00 TRPP36BE10 $18053.00
LSIGTZ1 TRPA36BF10 $15625.00 TRPP36BF10 $19418.00
LSIGTZ2 TRPA36BG10 $16210.00 TRPP36BG10 $20003.00
LIT TRPA36BA16 $12465.00 TRPP36BA16 $16258.00
LSIT TRPA36BB16 $13830.00 TRPP36BB16 $17623.00
LIGT TRPA36BC16 $13675.00 TRPP36BC16 $17468.00
1600 A LSIGT TRPA36BD16 $15040.00 TRPP36BD16 $18833.00
LIGTZ1 TRPA36BE16 $14260.00 TRPP36BE16 $18053.00
LSIGTZ1 TRPA36BF16 $15625.00 TRPP36BF16 $19418.00
LSIGTZ2 TRPA36BG16 $16210.00 TRPP36BG16 $20003.00
LIT TRPA36BA20 $13472.00 TRPP36BA20 $17566.00
LSIT TRPA36BB20 $14837.00 TRPP36BB20 $18931.00
LIGT TRPA36BC20 $14682.00 TRPP36BC20 $18776.00
2000 A LSIGT TRPA36BD20 $16047.00 TRPP36BD20 $20141.00
LIGTZ1 TRPA36BE20 $15267.00 TRPP36BE20 $19361.00
LSIGTZ1 TRPA36BF20 $16632.00 TRPP36BF20 $20726.00
LSIGTZ2 TRPA36BG20 $17217.00 TRPP36BG20 $21311.00
R-Frame Current Sensors and Rating Plugs GO-245A
Rating Plug
Sensor Current Rating Product Number List Price
400 A TR10B400 $89.00
1000 A 600 A TR10B600 $89.00
800 A TR10B800 $89.00
1000A TR10B1000 $89.00
600 A TR16B600 $89.00
800 A TR16B800 $89.00
1600 A 1000 A TR16B1000 $89.00
110 0 A TR16B1100 $89.00
1200 A TR16B1200 $89.00
1600 A TR16B1600 $89.00
750 A TR20B750 $89.00
800 A TR20B800 $89.00
1000 A TR20B1000 $89.00
2000 A 1200 A TR20B1200 $89.00
1500 A TR20B1500 $89.00
1600 A TR20B1600 $89.00
2000 A TR20B2000 $89.00
Rating Plug TRTOOL $12.001
Removal Tool
1GO-135S.
Industrial Circuit Breakers
400-2000A Circuit Breakers
Electronic Trip
R Frame Circuit Breaker Frames
—R-Frame Molded Case Circuit Breaker Frames
—600 Vac, 50/60 Hz, 3-Poles only. Suitable for Reverse Feed
—Complete breaker requires frame and rating plug.
—For 4-wire GF application, select neutral CT from page 3-105,
order separately.
—IC Ratings shown are at 480 Vac.
Prices and data subject to change without notice
3-72 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Molded Case Switches
150-1200A
Spectra RMS
Molded Case Switches GO-135S
UL File E-57546, CSA LR 91464
Includes fixed, high-set Instantaneous trip suitable for reverse feed.
Terminal Lugs for Maximum Sort Circuit Withstand Rating2
Switch1Front Connection (Cu/Al) (kA rms symmetrical)
Frame Ampere
Type Rating Product Number List Price Product Number List Price Wire Range 240 Vac 480 Vac 600 Vac
SE150 100 SEDA36AN0100 $650.00 TCAL18 $3.00 Aluminum: #12-3/0 200 100 25
150 SEDA36AN0150 $948.00 Copper: #14-3/0
SF250 250 SFDA36AN0250 $1126.00 TCAL29 $8.00 Aluminum: #8-350 kcmil 200 100 25
Copper: #8-350 kcmil
400 SGDA36AN0400 $1813.00 3-pole lug kit Aluminum:
(2) 2/0-500 kcmil 200 100 42
SG600 600 SGDA36AN0600 $2489.00 TCLK3653$42.00 or (1) #6-600 kcmil
Copper:
(2) 2/0-500 kcmil
or (1) #8-600 kcmil
800 SKDA36AN0800 $2483.00 TCAL81 $47.00 Aluminum:
(3) 3/0-500 kcmil
Copper:
SK1200 (3) 3/0-500 kcmil 100 65 42
1000 SKDA36AN1000 $3600.00 Aluminum:
TCAL125 $76.00 (4) 250-500 kcmil
1200 SKDA36AN1200 $3600.00 Copper:
(4) 250-350 kcmil4
1No rating plug required.
2The maximum withstand rating is limited by the application to the value set forth in this table or the short circuit rating of the upstream fuse or circuit breaker, whichever is less. The
upstream protective device must have an instantaneous trip function or element and its rated ampacity may not exceed the ampere rating of the switch.
3Order one kit for either line or load end; two kits required for both.
4Suitable for 500 kcmil copper, 1200A max. rating.
Noninterchangeable Trip, Includes Cu/Al load lugs. For optional lugs, see page 3-101 and 3-102. GO-135B
Type Ampere Rating Number of Poles Voltage Rating Product Number List Price
TEB 100 1 120 Vac, 125 Vdc TEB111Y1005$65.50
TEB 100 2 240 Vac, 250 Vdc TEB122Y1005$159.00
TEB 100 3 240 Vac TEB132Y1005$240.00
TED 100 1 277 Vac, 125 Vdc TED113Y1005$82.50
TED 100 2 480 Vac, 250 Vdc TED124Y1005$263.00
TED 150 2 480 Vac, 250 Vdc TED124Y1505,6 $708.00
TFJ 225 2 480 Vac TFJ226Y2255,7 $803.00
TFJ 225 3 600 Vac TFJ236Y225 $1174.00
TJ J400 2600 Vac, 250 Vdc TJJ426Y4008$1577.00
TJ J400 2600 VacTJJ436Y4008$1904.00
Interchangeable Trip, Includes Cu/Al load lugs. For optional lugs, see page 3-101 and 3-102. GO-135B
Type Ampere Rating Number of Poles Voltage Rating Product Number List Price
TFK 225 2 480 Vac, 250 Vdc TFK226Y2257,8,9 $937.00
TFK 225 3 600 Vac, 250 Vdc TFK236Y2258,9 $1174.00
TJ K400 2600 Vac, 250 Vdc TJK426Y4008$1874.00
TJ K400 3600 Vac, 250 Vdc TJK436Y4008$2330.00
TJ K600 2600 Vac, 250 Vdc TJK626Y6008$1844.00
TJ K600 3600 Vac, 250 Vdc TJK636Y6008$2595.00
TMK 800 2 600 Vac, 250 Vdc TMKA836Y8008$1692.00
TMK 800 3 600 Vac, 250 Vdc TMKA826Y8008$2769.00
TMK 1000 2 600 Vac, 250 Vdc TMKA2Y10008$3311.00
TMK 1000 3 600 Vac, 250 Vdc TMKA3Y10008$4030.00
TMK 1200 2 600 Vac, 250 Vdc TMKA2Y12008$3420.00
TMK 1200 3 600 Vac, 250 Vdc TMKA3Y12008$4191.00
5Internal accessory requires factory installed dummy trip. Specify on order. Accessories not available for one-pole TEB, TED.
6Not UL listed.
7600 Volts max.
8Internal accessory requires factory installed dummy trip unit. See page 3-91 for additional details. Nonautomatic trip unit and dummy trip not UL listed for field installation.
9UL listed only when ordered as a complete switch.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-73
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Motor Circuit Protectors
3-1200A
Spectra RMS
Spectra RMS Mag-Break Motor Circuit Protectors
Current Limiting, UL Component Recognized1
Features
—Suitable for Reverse Feed
—UL Recognized File E-11592
—CSA Certified LR 40350
—IEC 947-2 690 Vac Max.
—SE 150 160 Ampere Max.
—SF250 250 Ampere Max.
—SG600 630 Ampere Max.
—SK1200 1250 Ampere Max.
—UL Current Limiting
High Interrupting Capacity Spectra RMS Motor Circuit Protectors
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous 65kAIC @480 Vac 100kAIC @480 Vac
Ampere Trip Ampere Range Product List Price, Current Product List Price, Product List Price, Product List Price, Wire
Rating Low High Number GO-135S Sensor Number GO-141S Number GO-141S Number GO-135S Range
SE150 Line 3-Pole
31139 SRPE7A3 $106.00
72290 SRPE7A7 $106.00 7SELA36AI0007 $530.00 SEPA36AI0007 $663.00 TCAL18 $3.00
15 43 182 SRPE30A15 $106.00
20 58 254 SRPE30A20 $106.00 30 SELA36AI0030 $530.00 SEPA36AI0030 $663.00 TCAL18 $3.00
25 73 332 SRPE30A25 $106.00
30 87 415 SRPE30A30 $106.00 14-3/0 Cu
40 118 501 SRPE60A40 $106.00
50 148 637 SRPE60A50 $106.00 60 SELA36AI0060 $686.00 SEPA36AI0060 $858.00 TCAL18 $3.00
60 178 777 SRPE60A60 $106.00 12-3/0 Al
70 206 863 SRPE100A70 $106.00
80 236 999 SRPE100A80 $106.00 100 SELA36AI0100 $754.00 SEPA36AI0100 $943.00 TCAL18 $3.00
90 267 1138 SRPE100A90 $106.00
100 297 1280 SRPE100A100 $106.00
110 328 1426 SRPE150A110 $106.00
125374 1640 SRPE150A125 $106.00 150 SELA36AI0150 $848.00 SEPA36AI0150 $1060.00 TCAL18 $3.00
150 450 1991 SRPE150A150 $106.00
Standard Capacity Mag-Break Motor Circuit Protectors—Adjustable Magnetic Trip, Noninterchangeable Types TEC, TECL GO-141
Complete Breaker (includes line and load lugs)
Adjustable Trip Add-on Limiter Three-Pole,
Ampere Ampere Range2Two-Pole, 480 Vac3Three-Pole, 600 Vac 100 kAIC
Rating Low High Product Number List Price Product Number List Price Product Number List Price
3838 TEC24003 $318.00 TEC36003 $388.00 TECL36003 $231.00
71890TEC24007 $318.00 TEC36007 $388.00 TECL36007 $231.00
15 42 198 TEC24015 $318.00 TEC36015 $388.00 TECL36015 $231.00
30 90 390 TEC24030 $318.00 TEC36030 $388.00 TECL36030 $231.00
50 180 660 TEC24050 $377.00 TEC36050 $464.00 TECL36050 $231.00
100300 1300 TEC24100 $413.00 TEC36100 $498.00 TECL36100 $524.00
150600 2700 TEC24150 $477.00 TEC36150 $545.00 TECL36150 $1079.00
1Per UL 489, interrupting capacities are not shown on product label.
2AC only
3Two-pole furnished in three-pole case.
Prices and data subject to change without notice
3-74 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Motor Circuit Protectors
150-1200A
Spectra RMS
Spectra RMS Mag-Break Motor Circuit Protectors
Current Limiting, UL Component Recognized 1
SF250 Line 3-Pole
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous 65kAIC @480 Vac 100kAIC @480 Vac
Ampere Trip Ampere Range Product List Price, Current Product List Price, Product List Price, Product List Price, Wire
Rating Low High Number GO-135S Sensor Number GO-141S Number GO-141S Number GO-135S Range
SE150 Line 3-Pole
70 205 700 SRPF250A70 $106.00
90 265 900 SRPF250A90 $106.00
100 295 1000 SRPF250A100 $106.00
110 325 1100 SRPF250A110 $106.00
125 370 1250 SRPF250A125 $106.00 250 SFLA36AI0250 $1297.00 SFPA36AI0250 $1622.00 TCAL29 $8.00 8-350 Cu
150 440 1500 SRPF250A150 $106.00 8-350 Al
175515 1750 SRPF250A175 $106.00
200 590 2000 SRPF250A200 $106.00
225 665 2250 SRPF250A225 $106.00
250 736 2500 SRPF250A250 $106.00
Types TFC, TJC, TKC 3-Pole GO-135B
Adjustable Instantaneous
Trip Ampere Range Complete Breaker (includes line and load lugs)
Ampere Rating Low High Product Number List Price
225 600 1400 TFC36225 $1448.00
100 2250 TFC36225A $1448.00
400 330 1100 TJC36400E $2589.00
550 1670 TJC36400F $2589.00
1000 3300 TJC36400G $2589.00
1200 4000 TJC36400B $2589.00
600 1000 3300 TJC36600G $3676.00
1800 6000 TJC36600H $3676.00
800 3000 6000 TKC36800L2$4880.00
5000 10000 TKC36800M2$4880.00
1200 3000 6000 TKC361200L2$8412.00
1200 5000 10000 TKC361200M2$8412.00
Type TBC with Current Limiters GO-135B
Complete Breaker (includes line and load lugs)
Adjustable Instantaneous Standard Replacement
Trip Ampere Range Three-Pole Current Limiters
Ampere Rating Low High Product Number List Price Product Number List Price
225 550 1670 TBC43225F14F $3810.00 TB10F14 $377.00
400 1000 3300 TBC43400F14G $5149.00 TB10F14 $377.00
600 3000 6000 TBC63600J14L $7443.00 TB10BJ14 $543.00
800 2400 6000 TBC83800K222$8622.00 TB15K22 $543.00
1Per UL 489, interrupting capacities are not shown on product label.
2Balanced three-phase inrush current will trip the circuit breaker at lower than indicated currents.
For motors over 350 hp, use Spectra RMS SK frame or circuit breakers with MicroVersaTrip Plus Trip Units
Accessories: See pages 3-83 to 3-104.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-75
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Motor Circuit Protectors
150-1200A
Spectra RMS
Spectra RMS Mag-Break Motor Circuit Protectors
Current Limiting, UL Component Recognized 1
SG 600 Line 3-Pole
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous 65kAIC @480 Vac
Ampere Trip Ampere Range Product List Price, Current Product List Price, Product List Price, Product List Price, Wire
Rating Low High Number GO-135S Sensor Number GO-141S Number GO-141S Number GO-135S Range
400 Ampere Max.
125 380 1275 SRPG400A125 $106.00
150 455 1530 SRPG400A150 $106.00 3-Pole (2) 2/0-500 Cu
175 530 1785 SRPG400A175 $106.00 lug kit or
200 605 2040 SRPG400A200 $106.00 (1) 8-600 Cu
225 680 2295 SRPG400A225 $106.00 400 SGLA36AI0400 $2396.00 SGPA36AI0400 $2995.00 TCLK3652$42.00
250 755 2550 SRPG400A250 $106.00
300 905 3060 SRPG400A300 $106.00 (2) 2/0-500 Al
350 1060 3570 SRPG400A350 $106.00 or
400 1210 4080 SRPG400A400 $106.00 (1) 6-600 Al
600 Ampere Max.
250 765 2530 SRPG600A250 $106.00
300 915 3035 SRPG600A300 $106.00 3-Pole (2) 2/0-500 Cu
350 1070 3545 SRPG600A350 $106.00 lug kit or (1) 8-600 Cu
400 1220 4050 SRPG600A400 $106.00
450 1375 4555 SRPG600A450 $106.00 600 SGLA36AI0600 $3481.00 SGPA36AI0600 $4350.00 TCLK3652$42.00 (2) 2/0-500 Al
500 1525 5060 SRPG600A500 $106.00 or (1) 6-600 Al
600 1830 6075 SRPG600A600 $106.00
SK1200 Line (Not Current Limiting) 3-Pole
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous 65kAIC @480 Vac
Ampere Trip Ampere Range Product List Price, Current Product List Price, Product List Price, Wire
Rating Low High Number GO-135S Sensor Number GO-141S Number GO-135S Range
800 Ampere Max.
300 940 3015 SRPK800A300 $106.00
400 1250 4015 SRPK800A400 $106.00 (3) 3/0-500 Cu
500 1570 5020 SRPK800A500 $106.00 800 SKLA36AI0800 $4490.00 TCAL81 $47.00
600 1875 6195 SRPK800A600 $106.00
700 2155 7420 SRPK800A700 $106.00 (3) 3/0-500 Al
800 2440 8705 SRPK800A800 $106.00
1200 Ampere Max.
600 1825 6110 SRPK1200A600 $106.00
700 2125 7125 SRPK1200A700 $106.00 (4) 250-500 Cu3
800 2430 8145 SRPK1200A800 $106.00 1200 SKLA36AI1200 $7859.00 TCAL125 $76.00
100 3040 10180 SRPK1200A1000 $106.00 (4) 250-350 Al
1200 3650 12215 SRPK1200A1200 $106.00
1Per UL 489, interrupting capacities are not shown on product label.
2Order one kit for either the line or load end; two kits required for both.
3Suitable for 500 kcmil copper, 1200A max. rating.
Prices and data subject to change without notice
3-76 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Special Purpose
Mine Duty Breakers
Mine Duty Circuit Breakers
Standard Duty
50-1200 amperes
600 Vac
300 Vdc
Three-Pole 1000 Wye 577 Vac (Not UL Listed) — Without Line or Load Lugs1GO-135A
Complete Breaker Frame Only Trip Unit Only
Thermal Magnetic Magnetic Only Thermal Magnetic Magnetic Only
Ampere Magnetic Instantaneous Trip Product Product Product Product Product
Rating Low High Number List Price Number List Price Number List Price Number List Price Number List Price
E Frame — 100 Amperes Maximum, Noninterchangeable Trip
50 5021802TE131050MD $1104.00 TE131M050MD $1104.00 ——
100 10 025002TE131100MD $1104.00 TE131M100MD $1104.00 ——
J Frame — 225 Amperes Maximum, Interchangeable Trip3
225 300 1000 TJ132225MD1 TJ132M2MD1 TJ132FMD $3231.00 TJ32225TMD1 $920.00 TJ32M2TMD1 $920.00
225 500 1500 TJ132225MD2 TJ132M2MD2 TJ32225TMD2 $920.00 TJ32M2TMD2 $920.00
J Frame — 400 Amperes Maximum, Interchangeable Trip3
400 500 1500 TJ134400MD2 TJ134M4MD2 TJ134FMD $4499.00 TJ34400TMD2 $1007.00 TJ34M4TMD2 $1007.00
400 900 3000 TJ134400MD3 TJ134M4MD3 TJ34400TMD3 $1007.00 TJ34M4TMD3 $1007.00
J Frame — 600 Amperes Maximum, Interchangeable Trip3
600 900 3000 TJ136600MD3 TJ136M6MD3 TJ136FMD $4636.00 TJ36600TMD3 $1071.00 TJ36M6TMD3 $1671.00
K Frame — 800 Amperes Maximum, Interchangeable Trip3
300 900 3000 TK138600MD3 TK38300TMD3 $1815.00 ——
400 1250 3000 TK138400MD4 TK38400TMD4 $1815.00 ——
600 1250 3000 TK138600MD4 TK138FMD $5296.00 TK38600TMD4 $2813.00 ——
600 2000 4000 TK138600MD5 TK38600TMD5 $2813.00 ——
800 1250 3000 TK138800MD4 TK13M8MD4 TK38800TMD4 $2813.00 TK38M8TMD4 $2813.00
800 2000 4000 TK138800MD5 TK13M8MD5 TK38800TMD5 $2813.00 TK38M8TMD5 $2813.00
K Frame — 1200 Amperes Maximum, Interchangeable Trip3,4
800 2000 4000 TK13A10MD5 TK13AFMD $7600.00 TK3A10TMD5 $5923.00 ——
800 2000 4000 TK13A12MD5 TK13M12MD5 TK3A12TMD5 $5923.00 TK3M12TMD5 $5923.00
1The lugs recommended for use with all Mine Duty breakers are copper for use with copper cable. Select from page 3-101.
2Applies only to magnetic-only breakers.
3Order frame plus trip unit; not available as complete breaker.
4Not suitable for use on dc.
Accessories: See pages 3-85 to 3-104.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-77
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
TB1, 150A Frame, Noninterchangeable Trip (Includes line and load lugs) GO-135B
Tri-Break—Including Lugs2Replacement
Current Limiters1Current Limiters1
Adjustable Instantaneous Three-Pole Product No. Trip Units3Standard Optional1
Ampere Trip Amperes Range Product List and Wire Sizes List Product List Product List Product List
Rating Low High Number Price (order 2 per pole) Price Number Price Number Price Number Price
15 Fixed TB13015BWE05 $2680.004
20 Fixed TB13020BWE05 $2680.004TCAL14
25 Fixed TB13025BWE05 $2680.004#14-8 Lugs
30 Fixed TB13030BWE05 $2680.004Cu-Al Furnished
TB4E05 $280.004Not
35 Fixed TB13035BWE05 $2680.004with Available
40 Fixed TB13040BWE05 $2680.004
TCAL 12 Breaker
45 Fixed TB13045BWE05 $2680.004
#14-2/0
50 Fixed TB13050BWE09 $2680.004
Cu-Al
60 Fixed TB13060BWE09 $2680.004
70 Fixed TB13070BWE09 $2680.004Lugs
80 Fixed TB13080BWE09 $2680.004TCAL 12 Furnished TB7E09 $360.004TB4E05 $280.004
90 Fixed TB13090BWE09 $2680.004#14-2/0 with
100 Fixed TB13100BWE09 $2680.004Cu-Al Breaker
100NA TB13BYWE095,6 $2680.004
Replacement Breakers
TriBreak
Internally Fused
TB4, 400A Frame, Interchangeable Trip (Without line or load lugs) GO-135B
Tri-Break—Including Lugs2Replacement
Current Limiters1Current Limiters1
Adjustable Instantaneous Three-Pole Product No. Trip Units3Standard Optional1
Ampere Trip Amperes Range Product List and Wire Sizes List Product List Product List Product List
Rating Low High Number Price (order 2 per pole) Price Number Price Number Price Number Price
125 375 1250 TB43125AF14 $4079.00 TB43T125 $473.00
150 450 1500 TB43150AF14 $4079.00 $14.00 TB43T150 $473.00
175 525 1750 TB43175AF14 $4079.00 TB43T175 $473.00
200 600 2000 TB43200AF14 $4079.00 TCAL43 TB43T200 $473.00 TB3F05 $401.00
225 675 2250 TB43225AF14 $4079.00 (1) 6-600 kcmil TB43T225 $473.00 TB10F14 $377.00 or
250 750 2500 TB43250AF14 $5542.00 or TB43T250 $1931.00 TB6F09 $377.00
300 900 3000 TB43300AF14 $5542.00 (2) 2/0-250 kcmil TB43T300 $1931.00
350 1050 3500 TB43350AF14 $5542.00 TB43T350 $1931.00
400 1200 3500 TB43400AF14 $5542.00 TB43T400 $1931.00
400NA TB43AYW F145,6 $4802.00 ––––
1Standard current limiters (bolt on: TB1, TB6, TB8 and plug-in: TB4) have been selected based upon recommended coordination with thermal
magnetic trip characteristics of the breaker. Optional current limiters are not UL listed in combination with breaker except TB4 with
TB3F05 or TB6F09, 250A maximum.
2For optional lugs, see page 3-101.
3Trip units fit 2 and 3 pole frames.
4GO-148D.
5Molded case switch. Includes dummy trip, line and load lugs.
6Not UL listed.
TCAL43
(1) 6-600 kcmil
or
(2) 2/0-250 kcmil
$14.00
TB1 TB4 TB6
Prices and data subject to change without notice
3-78 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
TB6, 600A Frame, Interchangeable Trip (Without line or load lugs) GO-135B
Tri-Break—Including Lugs2Replacement
Current Limiters1Current Limiters1
Adjustable Instantaneous Three-Pole Product No. Trip Units3Standard Optional1
Ampere Trip Amperes Range Product List and Wire Sizes List Product List Product List Product List
Rating Low High Number Price (order 2 per pole) Price Number Price Number Price Number Price
300 1200 3500 TB63300BJ14 $7123.00 TB63T300 $2334.00
350 1200 3500 TB63350BJ14 $7123.00 TCAL61 TB63T350 $2334.00 TB3BJ05 $579.00
400 1200 3500 TB63400BJ14 $7123.00 (2) 2/0-500 TB63T400 $2334.00 TB10BJ14 $543.00 or
500 1200 3500 TB63500BJ14 $7123.00 kcmil 40.00 TB63T500 $2334.00 TB6BJ09 $543.00
600 1200 3500 TB63600BJ14 $7123.00 TB63T600 $2334.00
600NA TB63BYWJ144$6894.00 ––––
TCAL61
(2) 2/0-500 kcmil $40.00
TB8, 800A Frame, Interchangeable Trip (Without line or load lugs) GO-135B
Tri-Break—Including Lugs2Replacement
Current Limiters1Current Limiters1
Adjustable Instantaneous Three-Pole Product No. Trip Units3Standard Optional1
Ampere Trip Amperes Range Product List and Wire Sizes List Product List Product List Product List
Rating Low High Number Price (order 2 per pole) Price Number Price Number Price Number Price
600 1800 3000 TB83600BK22 $8204.00 TB83T600 $2334.00 TB6BJ095$543.00
700 2100 4000 TB83700BK22 $8204.00 TB83T700 $2334.00 TB15K22 543.00 or
800 2400 4000 TB83800BK22 $8204.00 TB83T800 $2334.00 TB10BJ145$543.00
800NA TB83AYWK224,5 $8204.00 ––––
Old Style (Plug-in) Replacement Limiters
Breaker Ampere Replacement Limiter1
Type Range Standard Optional1
TB1 15-45 TB3E05
TB1 50-100 TB6E09 TB3E05
TB1 110-150 TB7E10 TB7E09
TB6 300-600 TB10J14 TB3J05 TB6J09
TB8 600-800 TB15K18 - -
1Standard current limiters (bolt on: TB1, TB6, TB8 and plug-in: TB4) have been selected
based upon recommended coordination with thermal magnetic trip characteristics of
the breaker. Optional current limiters are not UL listed in combination with breaker
except TB4 with TB3F05 or TB6F09, 250A maximum.
2For optional lugs, see page 3-101.
3Trip units fit 2 and 3 pole frames.
4Molded case switch. Includes dummy trip, line and load lugs.
5Not UL listed.
6GO-135S.
Replacement Breakers
TriBreak
Internally Fused
TCAL81
(3) 250-500 kcmil $47.00
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-79
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Replacement Breakers
THLC Current Limiting
Unfused
15-400 Amperes
20kAIC @ 240 Vac max.
20kAIC @480 Vac max.
50kAIC @600 Vac max.
THLC1, 150A Frame, 15-150 Amperes,
Noninterchangeable Trip with Line and Load Lugs GO-135B
Ampere Rating 3-Pole Product Number List Price
15 THLC136015WL $2910.00
20 THLC136020WL $2910.00
30 THLC136030WL $2910.00
40 THLC136040WL $2910.00
50 THLC136050WL $2910.00
60 THLC136060WL $2910.00
70 THLC136070WL $2910.00
80 THLC136080WL $2910.00
90 THLC136090WL $2910.00
100 THLC1360100WL $2910.00
125 THLC1360125WL $5520.00
150 THLC1360150WL $5520.00
Internal accessories for THLC1 are same as Type TED accessories. Refer to pages 3-86 to
3-91.
THLC2, 225A Frame, 125-225 Amperes,
Noninterchangeable Trip with Line and Load Lugs GO-135B
Adjustable Trip
Range Amperes
Ampere Rating Low High 3-Pole Product Number List Price
125 550 1250 THLC236125WL $5540.00
150 675 1500 THLC236150WL $5540.00
175 775 1750 THLC236175WL $5540.00
200 900 2000 THLC236200WL $5540.00
225 1000 2500 THLC236225WL $5540.00
Internal accessories for THLC2 and THLC4 are same as Type TFK accessories. Refer to
pages 3-87 to 3-91. Accessory must have code date 535+ or later.
THLC4, 400A Frame, 250-400 Amperes,
Noninterchangeable Trip without Line and Load Lugs1GO-135B
Adjustable Trip
Range Amperes
Ampere Rating Low High 3-Pole Product Number List Price
250 1175 2500 THLC436250 $7450.00
300 1400 3000 THLC436300 $7450.00
350 1650 3500 THLC436350 $7450.00
400 1870 4000 THLC436400 $7450.00
1Lug kit for THLC4 for line or load end. Order Product Number TCLK43, List Price $49.00,
GO-135B. Consists of three-pole assembly. Wire range (1) 3/0-500 or (2) 3/0-250 Cu-Al.
THLC1
THLC2
THLC4
Prices and data subject to change without notice
3-80 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Long-Time 2
Delay (Seconds)
Pick-Up (Multiple of
Current Setting) (C) Delay (Seconds)
Pick-Up (Multiple of
Sensor Ampere Rating) (S) Delay (Seconds)
I
2
t in;
3
.44
1.5, 2.0, 3.0, 5.0, 7.0, 9.0,
10.0 without short-time
I
2
t in;
4
.44
I
2
t out:
5
.10, .21, .35
1.5, 2.0, 3.0, 5.0, 7.0,
9.0, 10.0, 13.0, 15.0
6
with short-time
I
2
t out:
5
.10, .21, .35
4
Time delay at 200% of pick-up setting at lower limit of band.
X = rating plug amperes
S = sensor ampere rating
C = current setting
2
Pick-up fixed at 1.1C.
6
J600 frame with 600 amp sensor for high IC 65kA rating (TJL) limited to 10X
.
5
Time delay shown at lower limit of each band. Pick-up tolerances
±
10%. Ground fault pick-up not to exceed 1200 amperes.
3
Time delay at 600% of current setting at lower limit of band.
1.0, .95, .90, .85,
.80, .70, .60, .50
2.4, 4.9, 9.8, 20
at 600% of current
setting at lower
limit of each band
1.5, 2.0, 2.5, 3.0,
4.0, 6.0, 7.0, 9.0
.20, .25, .30,
.35, .40, .45, .50, .60
Current Setting
(Multiple of rating
plug ampere) (X)
Short-Time Adjustable
Instantaneous Pick-Up
(Multiple of Rating
Plug Amperes) (X)
Ground Fault
MicroVersaTrip Plus Trip Unit Characteristics
Circuit Breaker Frame Selection (less lugs) GO-135D
Replacement Breakers
J and K Frame Circuit Breakers with MicroVersaTrip Plus Trip Units
For Replacement Use Only
For New Breaker Designs, use Spectra RMS Breakers with MicroVersaTrip Plus
How To Order
—Determine the required breaker frame (i.e. 600 or 1200 amperes),
IC rating, and load requirements (UL Standard or 100%). Select
frame product number and list price from table below.
—Select and price the appropriate trip unit from table below.
—Select and price the required rating plug from table below. The
sensor rating of frame must match the sensor rating of the rating
plug in table.
—Select and price lugs and lug covers as required from pages 3-101
and 3-102.
—When ordering, specify separate product numbers as follows.
The trip unit will be installed in the frame. Rating plugs and lugs/lug
covers will be shipped unassembled.
—Frame
—Trip Unit
—Rating plug
—Lugs/Lug covers
—Other accessories (assembled or separate items)
Pricing Example
J600 frame, 300 ampere sensor, 250 ampere rating plug, 35kAIC,
480 Vac, IC 100% rated, trip unit functions to include long-time (L),
short-time (S), instantaneous (I), ground fault (G), trip targets (T2),
ground fault/short-time zone selective interlocking (Z2),
3-phase/3-wire system.
Product List Price,
Description Number GO-135D
Frame TJH3SS $4774.00
Trip Unit and Suffix Adder TS20LSIGT2Z2 $4915.00
Rating Plug TR3S250J $106.00
Zone Interlock Module (120 Vac) TIM1 $402.001
Neutral Current Sensor TSRG203 $532.002
1GO-245B.
2GO-135S.
Frame Sensor Rating 65 kAIC List 100% 65 kAIC List Hi-Break List 100% Hi-Break7List
Type (Amperes) Product Number Price Product Number Price Product Number Price Product Number Price
150TJL1S $5149.00 TJL1SS $5919.00 TJH1S $4151.00 TJH1SS $4774.00
J600 300 TJL3S $5149.00 TJL3SS $5919.00 TJH3S $4151.00 TJH3SS $4774.00
400 TJL4S $5149.00 TJL4SS $5919.00 TJH4S $4151.00 TJH4SS $4774.00
600 TJL6S $6222.00 TJL6SS $7155.00 TJH6S $5018.00 TJH6SS $5771.00
K1200 800 TKL8S $8603.00 TKL8SS $9892.00 TKH8S $6935.00 TKH8SS $7975.00
1200 TKL12S $12536.00 TKL12SS $14414.00 TKH12S $10108.00 TKH12SS $11624.00
7100% supplied with back-connected assembly which increases breaker depth. Refer to outline drawing 139C4335 Sh7 for details.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-81
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
MicroVersaTrip Trip Unit Selection GO-135D
J/K Rating Plug Selection—All plugs List Price, $106.00 GO-135D
Replacement Breakers
J and K Frame Circuit Breakers with MicroVersaTrip Trip Units
For Replacement Use Only
For New Breaker Designs, use Spectra RMS Breakers with MicroVersaTrip Plus
Frame Sensor Rating Current Rating Rating Plug Frame Sensor Rating Current Rating Rating Plug
Type (Amperes) (Amperes) Product Number Type (Amperes) (Amperes) Product Number
60 TR1S60J 300 TR6S300J
80 TR1S80J 400 TR6S400J
150100 TR1S100J J600 600 450 TR6S450J
125 TR1S125J 500 TR6S500J
150 TR1S150J 600 TR6S600J
150 TR3S150J 300 TR6S300K
200 TR3S200J 400 TR6S400K
J600 300 225 TR3S225J K800 800 500 TR6S500K
250 TR3S250J 600 TR6S600K
300 TR3S300J 700 TR6S700K
150 TR4S150J 800 TR6S800K
200 TR4S200J
400 225 TR4S225J 600 TR12S600K
250 TR4S250J K1200 1200 800 TR12S800K
300 TR4S300J 1000 TR12S1000K
400 TR4S400J 1200 TR12S1200K
Trip Unit Function Definitions
Long-Time (L) Adjustable current setting
Adjustable long-time delay
Short-Time (S) Adjustable short-time pick-up
Adjustable short-time delay with l2t
Adjustable short-time delay without l2t
Instantaneous (I) Adjustable pick-up
Ground Fault (G) Adjustable ground fault pick-up
Adjustable ground fault delay with l2t
Adjustable ground fault delay without l2t
Trip Indication Target (T1, T2) Overload/short circuit targets (T1)
Overload/short circuit/ground fault targets (T2)
Zone Selective Interlock (Z1, Z2) Ground fault (Z1)
Ground fault/short-time (Z2)
Ta rgets Zone Interlock
Trip Unit List Long-Time Short-Time Instantaneous Ground Fault1OL, SC OL, SC, GF GF GF, ST
Suffix Price (L) (S) (I) (G) (T1) (T2) (Z1) (Z2)
TS20LIT1 $755.00 •–
TS20LSIT1 $2120.00 ••
TS20LIGT2 $2380.00 •–
TS20LSIGT2 $3745.00 ••
TS20LIGT2Z1 $3965.00 •–
TS20LSIGT2Z1 $4330.00 ••
TS20LSIGT2Z2 $4915.00 ••
1For single-phase, 3-wire or three-phase, 4-wire applications select appropriate neutral-current sensor from page 3-103.
Prices and data subject to change without notice
3-82 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Power+ Trip Unit Characteristics
Select trip unit product number from specific circuit breaker pages—J and K frames, page 3-81.
(X) Fixed Sensor
Sensor Current
Ratings (Amperes)
Pick-up
(Multiple of
Current
Setting) (C)
Delay 3
(Seconds)
Pick-up
(Multiple of
Current
Setting) (C)
I2t
Delay Ramp3
(Seconds)
Pick-Up
(Multiple of
Sensor Current
Rating) (X)
Delay 4
(Seconds)
J600 600
150, 200
300, 400,
500, 600
K1200 1200 800, 1000, 1200
X = sensor current rating
C = current setting
3
Time delay shown at 600% of current setting at lower limit of each band.
4
Time delay shown at lower limit of each band. All pick-up tolerances are
±
10%. Ground Fault Pick-up not to exceed 1200 amperes.
1
When optional adjustable short-time pick-up is provided, instantaneous is fixed at 15X. Short-time and fixed instantaneous are not available on TJL
with 500A and 600A sensors.
2
Delay Curve = I
2
t in, I
2
t out
Ground Fault2
.5, .6, .7, .8,
.9, .95, 1.0 (X)
.5, .6, .7, .8,
.9, .9.5, 1.0
3, 6, 12, 25
Bands 1, 2, 3, 4
1.5, 2, 2.5, 3,
4, 5, 7, 9 (C)
.13, .26, .42
(Min, Int, Max)
1.5, 2, 3, 4,
5, 7, 9, 10 (X)
.2, .25, .3, .35,
.4, .45, .5, .6 (X)
0.10, 0.21
0.35
(Min, Int, Max)
Frame
Type
Max.
Amperes
Current Setting
(Multiple of
Sensor Current
Rating) (X)
Adjustable
Instantaneous
Pick-Up1
(Multiple of
Sensor Current
Rating (X)
Long-Time Short-Time 1,2
None N G NG
150 TJL4V2601A $4242.00 $4242.00 $5448.00 $5448.00
200 TJL4V2602A $4242.00 $4242.00 $5448.00 $5448.00
300 TJL4V2603A $4242.00 $4242.00 $5448.00 $5448.00
400 TJL4V2604A $4242.00 $4242.00 $5448.00 $5448.00
500 TJL4V2605A
2
$5071.00
7
$6275.00
7
600 TJL4V2606A
2
$5071.00
7
$6275.00
7
800 TKL4V4608A $5658.00 $5658.00 $6864.00 $6864.00
1000 TKL4V4610A $9154.00 $9154.00 $10360.00 $10360.00
1200 TKL4V4612A $9154.00 $9154.00 $10360.00 $10360.00
65 kAIC Breaker
Base
Product No.
List Price, GO-148D with Suffix
Frame
Type
Current
Sensor
Ampere
J600
K1200
5
For single-phase, 3-wire or three phase, 4-wire applications, select
appropriate neutral-current sensor from page 3-103.
6
• = Function included.
Select and price lugs and lug covers as required from pages 3-101 and 3-102.
None N G NG None N G NG
150 TJ4V2601A $2703.00 $2703.00 $3909.00 $3909.00 THJ4V2601A $3858.00 $3858.00 $5064.00 $5064.00
200 TJ4V2602A $2703.00 $2703.00 $3909.00 $3909.00 THJ4V2602A $3858.00 $3858.00 $5064.00 $5064.00
300 TJ4V2603A $2703.00 $2703.00 $3909.00 $3909.00 THJ4V2603A $3858.00 $3858.00 $5064.00 $5064.00
400 TJ4V2604A $2703.00 $2703.00 $3909.00 $3909.00 THJ4V2604A $3858.00 $3858.00 $5064.00 $5064.00
500 TJ4V2605A $3657.00 $3657.00 $4863.00 $4863.00 THJ4V2605A $4611.00 $4611.00 $5816.00 $5816.00
600 TJ4V2606A $3657.00 $3657.00 $4863.00 $4863.00 THJ4V2606A $4611.00 $4611.00 $5816.00 $5816.00
800 TK4V4608A $4694.00 $4694.00 $5900.00 $5900.00 ————
1000 TK4V4610A $8183.00 $8183.00 $9389.00 $9389.00 ————
1200 TK4V4612A $8183.00 $8183.00 $9389.00 $9389.00 ————
List Price, GO-148D with Suffix
Frame
Type
Current
Sensor
Ampere
Standard Circuit Breaker Hi-Break
J600
K1200
Base
Product No.
Base
Product No.
List Price, GO-148D with Suffix
None GWNG
Adjustable Current Setting
••
Fixed Long-Time Pick-Up
••
Fixed Long-Time Delay
••
Long-Time Timing Light
••
Adj. Short-Time Pick-Up
Fixed Short-Time Delay I
2
t Ramp
Adj. Instantaneous Pick-Up
Fixed Instantaneous Pick-Up
7
Adj. Ground Fault Pick-Up
Zero Sequence ——
••
••
Adj. Ground Fault Delay ——
Trip Unit
Functions
Suffix
Long-Time
Short-Time
Instantaneous
Ground Fault
5
7
TJL4V with 500 and 600A sensors available with adjustable
instantaneous only.
Replacement Breakers
J and K Frame Circuit Breakers with Power+ 4 Trip Unit
Power+ 4 Trip Unit Selection
Circuit Breaker Product Number Selection (less lugs)5
Circuit Breaker Product Number Selection (less lugs) 5,6
Part Number Selection Instructions
1. Select product number of circuit breaker, including trip unit suffix.
2. Select lugs, internal/external accessories and neutral current sensor, as required from pages 3-85 through 3-104.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-83
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Internal Accessories
Spectra RMS Circuit Breakers
Voltage Current (mA) Product List
ac dc Inrush Cont Number Price
120 125 500 6.0 SAST1 $363.00
240 250 400 5.0 SAST2 $363.00
12 12 1000 800 SAST51$363.00
24 24 300 10.0 SAST3 $363.00
48 48 300 10.0 SAST4 $363.00
1Not suitable for use with ground fault sensing and relaying equipment.
Note: UL listed at 200,000 AIC without internal accessories, 100,000 AIC with internally mounted accessories.
Auxiliary Switch GO-135S
Auxiliary switches provide remote indication of whether the circuit breaker main contacts
are opened or closed via open or closed SPDT switch elements.
Switch Number of Auxiliary Switch List
Rating Switch Elements Product Number Price
5A @240 Vac/ 1 form C SAUXPAB1 $149.00
0.5A @ 125 Vdc 2 form C SAUXPAB2 $295.00
Gold-Plated Contacts 1 form C SAUXGAB1 $149.00
0.5A @ 30V 2 form C SAUXGAB2 $295.00
One each 2 form C SAUXGPAB2 $295.00
of above types
Universal Field-Installable Internal Accessories
All Spectra RMS circuit breakers from the SE150 through the SK1200, including
instantaneous-trip Mag Break motor circuit protectors and molded case switches, use
the same UL listed, field-installable internal accessories that do not require cover removal
to install.
Accessory Mounting
All accessories mount in pouches accessible from a front cover. All breakers have a left-side
pouch and right-side pouch. The following combinations may be installed:
Left-Side Pouch—either shunt trip or undervoltage release plus bell alarm.
Right-Side Pouch—auxiliary switch (single or double pole).
Shunt Trip GO-135S
For remote tripping of breaker, use with momentary close contact. Not recommended for
use with latching relay contact since electronics in shunt trip will pulse power to the coil
if continuously energized, and breaker shunt tripping upon reclosure will be delayed 1-2
seconds at rated control voltage. (A short-circuit trip would be instantaneous.)
If maintained (latching relay) contact must be used and delayed shunt tripping is not
acceptable, use small bell alarm in series with control power for SE150 and SF250 frames
and auxiliary switch for SG600 and SK1200 breakers.
These devices are suitable for use with ground fault sensing and relaying equipment.
Maximum VA is 75. AC devices are UL listed for 50-60 Hz.
Auxilliary Switch
Shunt Trip
Red
White
Brown/white
Black
Black
All accessory contacts shown
with the circuit breaker in
tripped position.
All accessory contacts shown
with the circuit breaker in
tripped position.
Left Side Pouch
Right Side Pouch
Prices and data subject to change without notice
3-84 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Voltage Peak Current Product List
ac dc (mA) Number Price
120 125 200 SAUV1 $363.00
240 250 200 SAUV2 $363.00
24 24 100 SAUV3 $363.00
48 48 100 SAUV4 $363.00
120125 SPUVTD $430.001
1GO-245B.
Switch Number of Product List
Rating Switch Elements Number Price
5A @ 240 Vac/ 1 form C SABAP1 $154.00
0.5A @ 125 Vdc
Gold-Plated Contacts 1 form C SABAG1 $154.00
0.5A @30V
Note: UL listed at 200,000 AIC without internal accessories, 100,000 AIC with internally mounted accessories.
Bell Alarm Switch GO-135S
The bell alarm switch provides remote indication of whether the circuit breaker has been
tripped via open or closed SPDT switch elements, but remains unchanged during "On/Off"
circuit breaker operation and during operation by the "Push-to-Trip" button.
Undervoltage Release
Undervoltage Release GO-135S
The undervoltage release provides automatic circuit breaker tripping when there is a
power loss or major dip (to 35%-70% of rated voltage) in accessory control voltage. AC
devices are UL listed for 50-60 Hz. Product number SAUV1 may be used with time delay
unit SPUVTD (List Price $430.00, GO-245B) (delay 0.1 to 1.0 seconds), 120 Vac input, 125 Vdc
output.
Bell Alarm Switch
Internal Accessories
Spectra RMS Circuit Breakers
Purple
Yellow
Brown
Blue
Blue
All accessory contacts shown
with the circuit breaker in
tripped position.
All accessory contacts shown
with the circuit breaker in
tripped position.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-85
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Internal Accessories
Molded Case Circuit Breakers
Accessory Devices and Ratings
Internally mounted accessories can be either factory or field
installed, but should be factory installed when UL listing is required.
F225 frame accessories, including THLC2, and THLC4 are UL listed
for field installation1.
Factory installed devices with leads exiting from the side are UL
listed, but when leads exit from the back the UL listing is void.
For accessory installation combinations refer to table below.
“Mounting Pole” refers to left-, center- or right-hand pole as seen
when facing the front of the breaker. Control leads may exit the
breaker from its side (S) or back (B)2.
Nonautomatic circuit breakers (molded case switches) require
dummy trip units if internal accessories are to be field installed
(refer to page 3-91).
J Frame Circuit Breaker with Internal
Accessories Mounted in Each Pole
LCR LRLRLR
TQB, THQB,
THHQB, TXQB,
TQL, THQL,
THHQL, TXQL,
TQC, THQC,
THHQC, TXQC
————UL ——————
One accessory only. Mounts
in a one-inch frame and
increase overall breaker size
by one pole. May be applied
to 1-, 2-, or 3-pole breakers.
TQD, THQD —————
UL ——————
One accessory only
E150 TEB,
TEC, TED,
THED,
THLC1,
TB1
5,6,8
7
UL —UL4576
7
4
4
UL UL
3418
Aux
3416
S.T.
—UL3417
8
UL 3434
2-pole circuit breaker—any
one 3-pole circuit breaker—
any two except UVR and
3-coil shunt trip
F225
9
TFC, TFJ, TFK,
THFK, THLC2,
THLC4, TLB2,
TLB4
——UL 4620 UL UL 4653 UL UL 4653
8
UL UL 4622 any two
J600 TJC,
TJD, TJJ,
TJK, THJK,
TB4
5
, TBC4
5
8
UL 3320 UL UL
3321
Aux
3435
S.T.
—UL5407
8
UL 3346
Any two plus belt alarm except
TB4, TBC4 any one plus bell
alarm.
K1200 TKC,
TKM, THKM
TB6
5
, TBC6
5
,
TB8, TBC8
8
8
UL 4305 UL UL
3321
Aux
3344
S.T.
—UL5408
8
UL 3346 Any two plus bell alarm
TJ4V, TKL4V,
TJH6S, TKL12S
solid-state trips
—UL—4626 UL
4623
Aux
4623
S.T.
—UL4623 Any one plus bell alarm
Total Number of
Accessories Within any
One Circuit Breaker
Inst.
Sheet
GEH-
Inst.
Sheet
GEH-
Inst.
Sheet
GEH-
Mounting Pole
Undervoltage
Release
Mounting Pole
Three Coil
Shunt Trip
Breaker Type
Mounting Pole
Bell Alarm Switch
Mounting Pole
Auxiliary Switch3
or Shunt Trip
Inst.
Sheet
GEH-
9
UL listed interrupting capacity with accessories: 10 kAIC at 600 Vac, 22 kAIC at 480 Vac, 22 kAIC at 240 Vac.
10
Leads are #18 125
°
C Vulkene insulated.
3
600 Vac auxiliary switches are not UL listed.
4
Accessories are factory installed only.
5
UL listed at 200 AIC without internal accessories, 100 AIC with internally mounted accessories.
6
Accessories not available for single-pole TEB/TED frame. Use two-pole circuit breaker.
1
Except TFC and TFJ, F225 line model 4 frames and trips (mfg. code date J101+ (1981 or later), and THLC2, THLC4, TLB4 are UL listed for
field installation of most accessories.
2
Not UL listed.
7
Left pole mounting not available for two-pole TEB, TED.
8
Not available with lead exit from the back of breaker.
Accessory-Lead
Color Coding
10
All accessory contacts shown
with the circuit breaker in
tripped position.
Shunt TripBell Alarm Switch Undervoltage Release Three-Coil Shunt Trip
Auxiliary Switch
Purple
Yellow
Brown
Red
White
Brown/white
Black
Black
Blue
Blue
Red
Brown/white
Blue
White
Yellow
Black
Pole Positions
L—Left
C—Center
R—Right
Lead Wire Exit
S—Side
B—Back
Prices and data subject to change without notice
3-86 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Internal Accessories
Internally Mounted Signaling and Controlling Functions
Mine Duty Circuit Breaker Undervoltage Release GO-135A
Factory Installed1
Circuit Breaker Control Product Number List Field Replacement List
Frame Voltage Premium Duty Price Product Number2Price
24 Vac TEDMDVAS $485.00 TEMDVAS $485.00
120 Vac TEDMDVBS $485.00 TEMDVBS $485.00
E240 Vac TEDMDVCS $485.00 TEMDVCS $485.00
12 Vdc TEDMDVDS $485.00 TEMDVDS $485.00
24 Vdc TEDMDVES $485.00 TEMDVES $485.00
60 Vdc TEDMDVFS $485.00 TEMDVFS $485.00
24 Vac TJMDVAS $509.00 TJRMDVA $526.00
120 Vac TJMDVBS $509.00 TJRMDVB $526.00
230 Vac TJMDVCS $509.00 TJRMDVC $526.00
J12 Vdc TJMDVDS $509.00 TJRMDVD $526.00
24 Vdc TJMDVES $509.00 TJRMDVE $526.00
60 Vdc TJMDVFS $509.00 TJRMDVF $526.00
24 Vac TKMDVAS $509.00 TKRMDVA $526.00
120 Vac TKMDVBS $509.00 TKRMDVB $526.00
240 Vac TKMDVCS $509.00 TKRMDVC $526.00
K12 Vdc TKMDVDS $509.00 TKRMDVD $526.00
24 Vdc TKMDVES $509.00 TKRMDVE $526.00
60 Vdc TKMDVFS $509.00 TKRMDVF $526.00
1Mounts in right pole only. "S" suffix–wires out the side of breaker.
2Replacement for standard and premium duty mine duty UVR, both old and new design.
How to Order
For factory installation, specify breaker product number, accessory base number, and
appropriate suffix. (Example: Product Number TJK436125WL, TJUV1RS, TJKASA2AB2LS
specifies a type TJK breaker with factory installed undervoltage release in the right-hand
pole and an auxiliary switch in the left-hand pole.)
For field replacement, order the accessory by the base number only.
Where this number ends in "R" or "L" right-hand and left-hand devices are physically
different. Specify only one suffix letter per accessory product number when option is
available.
Nonautomatic circuit breakers require dummy trip units if internal accessories are
to be mounted.
Undervoltage Release
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-87
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Auxiliary Switches GO-135B
Unless otherwise noted switch is SPDT rated 6 amperes at rated ac voltage, 1/2 amperes at 125 Vdc, 1/4 amperes at 250 Vdc.
Control Voltage 240 Vac, 250 Vdc Maximum Control Voltage 600 Vac, 250 Vdc Maximum
UL Listed When Factory Installed Suffix1Not UL Listed Suffix1
Number of Add to Base Product Add to Base Product
SPDT Switch Base Number for Factory List Base Number for Factory List
Breaker Type Elements Number Installation Price Number Installation Price
TQB, THQB, THHQB, TXQB, TQL,213TQAS2A145
$64.50 ––
THQL, THHQL, TXQL
TQC, THQC, THHQC, TXQC213TQCAS2A145
$77.50 ––
TQD, THQD 1 TQDAS2AB1RS N/A $148.006––
TEB, TEC, TB1 1 TEDAS2AB1R,L7, 8 S$148.00 TEDAS6AB1R,L7, 8 S$179.00
TED, THED,THLC182TEDAS2AB2R,L7, 8 S$295.00 TEDAS6AB2R,L7, 8 S$360.00
TFC, TFJ, TFK, THFK,91TFKASA2AB110 RS or LS $148.00 TFKASA6AB110 RS $167.00
THLC2, THLC4, TLB2, TLB4 2 TFKASA2AB210 RS or LS $295.00 TFKASA6AB210 RS $360.00
1TJKASA2AB1R,L S $148.00 TJKASA6AB1R,L S $179.00
2TJKASA2AB2R,L S $295.00 TJKASA6AB2R,L S $360.00
TJC, TJD, TJJ, TJK, THJK 3TJKASA2AB3R,L S $439.00 TJKASA6AB3R,L S $530.00
4TJKASA2AB4R,L S $598.00 TJKASA6AB4R,L S $712.00
1TB4ASA2AB1R,L S $148.00 TB4ASA6AB1R,L S $179.00
2TB4ASA2AB2R,L S $295.00 TB4ASA6AB2R,L S $360.00
TB4, TBC4 3TB4ASA2AB3R,L S $439.00 TB4ASA6AB3R,L S $530.00
4TB4ASA2AB4R,L S $598.00 TB4ASA6AB4R,L S $712.00
1TKMAAS2AB1 RS or LS $148.00 TKMAAS6AB1 RS or LS $179.00
TKM, THKM, TKC, TB6, 2 TKMAAS2AB2 RS or LS $295.00 TKMAAS6AB2 RS or LS $360.00
TB8, TBC6, TBC8 3 TKMAAS2AB3 RS or LS $439.00 TKMAAS6AB3 RS or LS $530.00
4TKMAAS2AB4 RS or LS $598.00 TKMAAS6AB4 RS or LS $712.00
TJ4V/TJL, TK4V/TKL 2TVAS2AB2R10 S$297.0011 TVAS6AB2R S $341.0011
4TVAS2AB4R10 S$553.0011 TVAS6AB4R S $657.0011
1TPAS2AB110 S$251.0012 TPAS6AB1 S $251.0012
2TPAS2AB210 S$503.0012 TPAS6AB2 S $503.0012
3TPAS2AB310 S$534.0012 TPAS6AB3 S $534.0012
4TPAS2AB410 S$562.0012 TPAS6AB4 S $562.0012
5TPAS2AB510 S$623.0012 TPAS6AB5 S $623.0012
TRL/TRP 6 TPAS2AB610 S$680.0012 TPAS6AB6 S $680.0012
R Frame 7 TPAS2AB7S10 Must be Factory Installed $924.0012 TPAS6AB7S Must be Factory Installed $924.0012
8TPAS2AB8S10 Must be Factory Installed $1180.0012 TPAS6AB8S Must be Factory Installed $1180.0012
9TPAS2AB9S10 Must be Factory Installed $1215.0012 TPAS6AB9S Must be Factory Installed $1215.0012
10 TPAS2AB10S10 Must be Factory Installed $1240.0012 TPAS6AB10S Must be Factory Installed $1240.0012
11 TPAS2AB11S10 Must be Factory Installed $1300.0012 TPAS6AB11S Must be Factory Installed $1300.0012
12 TPAS2AB12S10 Must be Factory Installed $1365.0012 TPAS6AB12S Must be Factory Installed $1365.0012
1"S" suffix for wires out the side of breaker. For lead exit from back of breaker, replace suffix "S" with "B"" and multiply list price by 1.25. "B" suffix not UL listed. Not available with
leads out the back for "Q Line".
2Not available on GFCI (5 ma) or Equipment Ground Fault (30 ma) breakers.
3Switch is SPST. Operates like "A" side of an "AB" contact and is rated six amperes at 120 Vac and three amperes at 24 Vac.
4Accessories mounted in a one-inch frame and increase overall breaker size by one pole added to left side. May be applied to 1-, 2-, or 3-pole breakers. Must be factory installed.
Maximum total breaker width is four poles.
5To order, specify both the accessory and breaker product number, e.g. THQL2130, TQASA1 identifies a 30 ampere, 2-pole plug-in breaker with a factory installed SPST
auxiliary switch.
6GO-135F.
7Auxiliary switch mounts in right pole only on two-pole TEB, TED breakers. (Factory installed only.)
8Not available with “B” suffix–leads out back.
9Changes circuit breaker interrupting capacity to 10kAIC, 600 Vac; 22 kAIC, 240 and 480 Vac.
10UL listed for field installation.
11GO-135C.
12GO-145A.
Internal Accessories
Internally Mounted Signaling and Controlling Functions
Prices and data subject to change without notice
3-88 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Shunt Trip GO-135B
Product Number1,2 — UL Listed When Factory Installed
Suffix Number3
Accessory Voltage Base Number Add to Base Product Number List
Breaker Type Vac Vdc for Field Replacement for Factory Installation Price
TQB, THQB, THHQB, TXQB, 120-240 TQSTA14,5,6,7 10 $95.50
TQL, THQL, THHQL, TXQL 12 TQSTA74,6,7 10 $95.50
24-48 TQSTA84,6,7 10 $95.50
120-240 TQCSTA14,6 10 $112.00
TQC, THQC, THHQC, TXQ 12 TQCSTA74,6 10 $112.00
24 TQCSTA84,6 10 $112.00
120 TQDSTA8,9 10 $178.00
240 TQDSTA2910 $178.00
TQD, THQD 12 TQDSTA7910 $178.00
24 TQDSTA8910 $178.00
120 TEDST12 RS or LS8,12 $363.00
240 TEDST12 RS or LS8,12 $363.00
480 TEDST13 RS or LS8,12 $363.00
TEB, TEC, TB1-B,11 600 TEDST13 RS or LS8,12 $363.00
TED, THED, THLC1 12 TEDST7 RS or LS8,12 $363.00
24 TEDST8 RS or LS8,12 $363.00
48 TEDST9 RS or LS8,12 $363.00
125 TEDST12 RS or LS8,12 $363.00
250 TEDST11 RS or LS8,12 $363.00
120 TFKSTA121RS or LS $363.00
240 TFKSTA121RS or LS $363.00
480 TFKSTA131RS or LS $363.00
TFC, TFJ, TFK, THFK, THLC2, 600 TFKSTA131RS or LS $363.00
THLC4, TLB2, TLB4 12 TFKSTA71RS or LS $363.00
24 TFKSTA81RS or LS $363.00
48 TFKSTA91RS or LS $363.00
125 TFKSTA121RS or LS $363.00
250 TFKSTA111RS or LS $363.00
1UL listed for field installation on TFC, TFJ, TFK, and THFK model 4 frames and trips (mfg. Code date J101 or later) and on THLC2, THLC4, TLB4.
2For replacement voltage suppressor on 120 Vac UVRs for F225 line, order Product Number 286A8062G1. for 120 Vac UVRs on all other breaker lines, order Product Number
192A8300G1.
3"S" suffix for wires out the side of the breaker. For lead exit from back of breaker, replace suffix "S" with "B", and multiply "S" accessory List Price by 1.25. "B" suffix not UL listed.
Not available with leads out the back on "Q Line."
4Mounts on a one-inch frame and increases overall breaker size by one pole added to left side. May be applied to 1-, 2-, or 3-pole breakers. Maximum total breaker width is 4-pole.
Must be factory installed.
5A selective listing of breaker product numbers that include 120 Volt ac shunt trip appears on page 3-14.
6Not available on GFCI (5 ma) or Equipment Ground Fault (30 ma) breakers.
7TQST shunt trips not available on breakers over 100 A.
8Not available with “B” suffix–leads out back.
9Must be factory installed, right pole only.
10To order, specify both the accessory and breaker product number =, e.g.THQL2130, TQST1 identifies a 30 A, 2-pole plug-in breaker with a factory installed 120 Vac shunt trip.
11For TB1 with bolt-on limiters.
12Mounts in the right pole only on 2-pole TEB, TED breakers.
How to Order
For field replacement, order base number only. For factory installation, order base number
plus appropriate suffix. For a nonautomatic breaker (molded case switch) a dummy trip is
required when installing either a shunt trip or UVR.
Shunt Trip
Remote Tripping – Trips breaker by remote control. Trip coil de-energized when breaker
opens. Device meets UL requirements for service to ground fault system.
Undervoltage Release
Undervoltage release automatically trips breaker when applied coil voltage drops to 30 to 70
percent of rated value. Time-delay unit prevent nuisance tripping due to momentary loss of
voltage. Separate externally mounted unit has 120 Vac input and 125 Vdc output. Used in
conjunction with 125 Vdc undervoltage release which must be ordered separately. Product
number SPUVTD for adjustable delay .1 to 1.0 seconds. List Price $430.00 GO-245B.
Internal Accessories
Internally Mounted Signaling and Controlling Functions
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-89
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Shunt Trip (continued) GO-135B
Product Number1,2 — UL Listed When Factory Installed
Suffix Number3
Accessory Voltage Base Number Add to Base Product Number List
Breaker Type Vac Vdc for Field Replacement for Factory Installation Price
120TJKSTA12R,L S $363.00
240 TJKSTA12R,L S $363.00
480 TJKSTA13R,L S $363.00
600 TJKSTA13R,L S $363.00
TJC, TJD, TJJ, TJK, THJK 12 TJKSTA7R,L S $363.00
24 TJKSTA8R,L S $363.00
48 TJKSTA9R,L S $363.00
125TJKSTA12R,L S $363.00
250 TJKSTA11R,L S $363.00
120 TB4STA12R,L S $363.00
240 TB4STA12R,L S $363.00
480 TB4STA13R,L S $363.00
600 TB4STA13R,L S $363.00
TB4, TBC4 12 TB4STA7R,L S $363.00
24 TB4STA8R,L S $363.00
48 TB4STA9R,L S $363.00
125 TB4STA12R,L S $363.00
250 TB4STA11R,L S $363.00
120 TKMASTA12R,L S $363.00
240 TKMASTA12R,L S $363.00
480 TKMASTA13R,L S $363.00
600 TKMASTA13R,L S $363.00
TKC, TKM, THKM, TB6, 12 TKMASTA7R,L S $363.00
TB8, TBC6, TBC8424 TKMASTA8R,L S $363.00
48 TKMASTA9R,L S $363.00
125 TKMASTA12R,L S $363.00
250 TKMASTA11R,L S $363.00
120 TVST12R S $363.005
240 TVST12R S $363.005
480 TVST13R S $363.005
TJ4V, TKL4V, 600 TVST13R S $363.005
TJH6S, TKL12S 12 TVST7R S $363.005
24 TVST8R S $363.005
48 TVST9R S $363.005
125 TVST12R S $363.005
250 TVST11R S $363.005
120 TPST12R S $630.006
240 TPST12R S $630.006
480 TPST13R S $630.006
R Frame 600 TPST13R S $630.006
TRL, TRP 12 TPST7R S $630.006
24 TPST8R S $630.006
48 TPST9R S $630.006
125 TPST12R S $630.006
250 TPST11R S $630.006
1UL listed for field installation on TFC, TFJ, TFK, and THFK model 4 frames and trips (mfg. Code date J101 or later) and on THLC2, THLC4, TLB4.
2For replacement voltage suppressor on 120 Vac UVRs for F225 line, order Product Number 286A8062G1. for 120 Vac UVRs on all other breaker lines, order Product Number
192A8300G1.
3"S" suffix for wires out the side of the breaker. For lead exit from back of breaker, replace suffix "S" with "B", and multiply "S" accessory List Price by 1.25. "B" suffix not UL listed. Not
available with leads out the back on "Q Line."
4Not UL listed.
5GO-135C UL listed for field installation.
6GO-145A UL listed for field installation.
Internal Accessories
Internally Mounted Signaling and Controlling Functions
Prices and data subject to change without notice
3-90 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Internal Accessories
Internally Mounted Signaling and Controlling Functions
UnderVoltage Release GO-135B
Product Number1,2 — UL Listed When Factory Installed
Suffix Number3
Accessory Voltage Base Number Add to Base Product Number List
Breaker Type Vac Vdc for Field Replacement for Factory Installation Price
120 TEDUV1 RS8$363.00
240 TEDUV2 RS8$363.00
480 TEDUV4 RS8$363.00
TEB, TEC, TB1-B5600 TEDUV6 RS8$363.00
TED, THED, THLC1 12 TEDUV7 RS8$363.00
24 TEDUV8 RS8$363.00
48 TEDUV9 RS8$363.00
125 TEDUV10 RS8$363.00
250 TEDUV11 RS8$363.00
120 TFKUVA11RS or LS $363.00
240 TFKUVA2 RS or LS $363.00
480 TFKUVA4 RS or LS $363.00
600 TFKUVA6 RS or LS $363.00
TFC, TFJ, TFK, THFK, THLC2, 12 TFKUVA7 RS or LS $363.00
THLC4, TLB2, TLB4 24 TFKUVA8 RS or LS $363.00
48 TFKUVA9 RS or LS $363.00
125 TFKUVA10 RS or LS $363.00
250 TDKUVA11 RS or LS $363.00
120TJUV1R S $363.00
240 TJUV2R S $363.00
480 TJUV4R S $363.00
600 TJUV6R S $363.00
TJC, TJD, TJJ, TJK, THJK 12 TJUV7R S $363.00
24 TJUV8R S $363.00
48 TJUV9R S $363.00
125TJUV10R S $363.00
250 TJUV11R S $363.00
120 TKUV1R S $363.00
240 TKUV2R S $363.00
480 TKUV4R S $363.00
TKC, TKM, THKM, TB6, 600 TKUV6R S $363.00
TB8, TBC6, TBC8612 TKUV7R S $363.00
24 TKUV8R S $363.00
48 TKUV9R S $363.00
125 TKUV10R S $363.00
250 TKUV11R S $363.00
120 TVUV1R S $363.007
240 TVUV2R S $363.007
480 TVUV4R S $363.007
600 TVUV6R S $363.007
TJ4V, TKL4V, 12 TVUV7R S $363.007
TJH6S, TKL12S5
24 TVUV8R S $363.007
48 TVUV9R S $363.007
125 TVUV10R S $363.007
250 TVUV11R S $363.007
380 TVUV3R S $363.007
120 TPUV1 S $630.008
240 TPUV2 S $630.008
480 TPUV4 S $630.008
R Frame 600 TPUV6 S $630.008
TRL, TRP512 TPUV7 S $630.008
24 TPUV8 S $630.008
48 TPUV9 S $630.008
125 TPUV10 S $630.008
250 TPUV11 S $630.008
1UL listed for field installation on TFC, TFJ, TFK, and THFK model 4 frames and trips (mfg. Code date J101 or later) and on THLC2, THLC4, TLB4.
2For replacement voltage suppressor on 120 Vac UVRs for F225 line, order Product Number 286A8062G1 for 120 Vac UVRs on all other breaker lines, order Product Number
192A8300G1.
3"S" suffix for wires out the side of the breaker. For lead exit from back of breaker, replace suffix "S" with "B", and multiply "S" accessory List Price by 1.25. "B" suffix not UL listed. Not
available with leads out the back on "Q Line."
4For TB1 with bolt-on limiters.
5Not available with “B” suffix – leads out back.
6Not UL listed.
7GO-135C UL listed for field installation.
8GO-145A UL listed for field installation.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-91
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Internal Accessories
Internally Mounted Signaling and Controlling Functions
Heavy-Duty Undervoltage Release1GO-135B
Automatically trips breaker when an undervoltage or power outage
condition occurs. Special PUSH-TO-TRIP/PUSH-TO-RESET button is
used to manually trip the breaker (E-frame only). On J and K frames,
the UVR is handle resettable with a cover-mounted button to provide
local mechanical tripping.
The Heavy-Duty Undervoltage Release (UVR) is designed for
applications where repeated UVR trips are anticipated. The manual
reset feature prevents breaker reset or possible contact kiss until
power is available and reset button is depressed.
Mounts in right pole of breaker only. Must be factory installed to
incorporate special breaker frame modifications.2Motor-operated
mechanism cannot be provided when heavy-duty UVR is installed.
Voltage
Breaker Type ac dc Product Number3List Price
24 TEDXUVARS13 $543.00
120–TEDXUVBRS13 $543.00
240 TEDXUVCRS13 $543.00
TEB, TED, THED, –12TEDXUVDRS13 $543.00
TEC,TB14,5 –24TEDXUVERS13 $543.00
–60TEDXUVFRS13 $543.00
–125 TEDXUVGRS13 $543.00
24 TJMDVAS $509.007
120 TJMDVBS $509.007
TJ J, TJK, THJK, TJD, 240 TJMDVCS $509.007
TJC, TB4, TBC4 12 TJMDVDS $509.007
–24TJMDVES $509.007
–60TJMDVFS $509.007
24 TKMDVAS $509.007
120–TKMDVBS $509.007
TKM, THKM, TKC, 240 TKMDVCS $509.007
TB6,TB8, TBC66, –12TKMDVDS $509.007
TBC86–24TKMDVES $509.007
–60TKMDVFS $509.007
1Not UL listed when field installed.
2For replacement purposes, order from page 3-84 using field replacement Product
Number.
3Add "B" suffix for leads exit from back of breaker; for price, multiply List Price by 1.25.
4For TB1 with bolt-on limiters.
5Not available with “B” suffix – leads out back.
6Not UL listed.
7GO-135A.
8Not available for two-pole TEB, TED. Order TEDBAR.
9Changes circuit breaker interrupting capacity to: 10kA @ 600 Vac, 22kA @ 480 Vac,
22kA @ 240 Vac, for TFC, TFJ, TFK and THFK only.
10UL listed for field installation.
11Mounts in center pole with leads out left side.
12GO-135C.
13GO-145A.
Dummy Trip1GO-135B
Breaker Type Product Number List Price
E150 Internal accessories for these noninterchangeable No
FJ225 breakers require factory-installed dummy trips. Charge
JJ400 Automatically supplied when accessories are ordered.
FK225 TFKYT2 (two-pole) $148.00
FK225 TFKYT3 (three-pole) $208.00
JK400 TJKYT3 (two-pole, three-pole) $212.00
JK600 TJKYT36 (two-pole, three-pole) $212.00
KM800 TKMAYT3 (two-pole, three-pole) $261.00
KM1200 TKMA3YT12 (two-pole, three-pole) $424.00
Bell Alarm Switches GO-135B
Product Number
Breaker UL Listed When Factory Installed
Type Base No. Suffix List Price
TEB, TEC, TB1 TEDBAR or S$154.00
TED, THED, THLC1 TEDBAL5,8 $154.00
TFC, TFJ, TFK, THFK, TFKBAAR9,10 S$154.00
THLC2, THLC4, TLB4
TJC, TJJ, TJK, THJK TJKBAAL11 S$156.00
TB4, TBC4, TJD
TKC, TKM, THKM, TKMABAAL11 S$141.00
TB6, TBC6, TBC8, TB8
TJL, TKL TJVBALS S $156.0012
TKVBALS $156.0012
(R Frame) TPSBAS S $259.0013
TRL, TRP
Blown Fuse Detector-Three-Coil Shunt Trip GO-135B
Product Number
Breaker UL Listed When Factory Installed
Type Base No. Suffix List Price
TED, THED, TEC5TEDST316 RS $672.00
TFJ, TJK, THFK, TFC TFKBFD316 LS or RS $672.00
TJ J, TJK, THJK, TJD, TJC TJKST316 LS $672.00
TKM, THKM, TKC TKMAST316 LS $672.00
(R Frame) TRL, TRP TPST316 S $1530.0013
Prices and data subject to change without notice
3-92 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Spectra Flex Cable Operators
—UL Listed—File E–57253
—Reduced installation costs:
—Simpler, faster installation
—No special alignment required
—Optimized panel layout:
—Breaker mounting position is independent of flange-mounted
handle location
—Covers a full spectrum of enclosure types and sizes:
—Flange-mounted handle for NEMA Types 1, 3R, 12 and 13
enclosures
—Flange-mounted handle for NEMA 4/4X enclosures—optional
—Broad range of enclosure sizes and breaker mounting
configurations
—8 different operating cable lengths available from 3 to 10 feet
—For circuit breaker types E150, SE150, SF250, SG600 and SK1200
—Force and motion transmitted independently of breaker
mounting plane or position relative to handle location
—Common breaker mounted operator for SE150 and SF250 frames
Spectra Flex cable operating mechanisms are suitable for
application with GE circuit breakers mounted in a wide variety of
flanged enclosure types and sizes.
Flange-mounted handle mechanisms are available for NEMA Types
1, 12 or 13 enclosures in either 6 inch (Model SCH1) or 10 inch
(Model SCH2) handle lengths. Corresponding mechanisms, SCH1X
and SCH2X, are available for NEMA Type 4/4X enclosures. Handle
mechanisms are suitable for either left or right flange operation.
The handle mechanism is combined with one of eight operating
cables, with lengths from 3 to 10 feet, to cover a broad range of
possible breaker mounting locations in the enclosure. The cable
links the handle mechanism to the breaker-mounted operating
mechanism and transmits the mechanical force and motion of the
handle mechanism to the breaker mounted mechanism. The force
and motion is transmitted independently of the breaker mounting
plane or location relative to the location of the handle mechanism,
provided only that the bending radius of the cable is not less than
3inches. No mounting reinforcement of the breaker or enclosure
flange is required.
The breaker-operating mechanism mounts directly to the face of
the breaker and does not involve any mounting interface with the
enclosure. A standard breaker mounting screw kit for tapped holes
is furnished with each mechanism to mount the breaker in the
enclosure.
See page 3-93 for ordering and pricing information.
External Accessories
Cable Operators
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-93
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
How to order
Use the circuit breaker mounting zone dimension table to determine the correct cable length
for the application and ensure that the 3-inch minimum bending radius is not violated. Select
the breaker mounted mechanism, operating cable and handle mechanism below. Order as
separate components.
Publication References
Breaker types E150, SE150, SF250, SG600 GEH-6290
Breaker type SK1200 GEH-6291
See Section 21 for publication ordering information.
Maximum Dimensions in Inches
To determine the maximum mounting dimensions for 60-through 120-inch-long operating
cables, add the respective additional lengths to the 48-inch cable maximum dimensions.
(Example: Add 12 inches to E, F and G dimensions for 60-inch cable length.) When cable is
installed, the minimum cable bend radius should not be less than 3 inches. The minimum
cable bending requirement must be met to ensure a safe operating environment.
External Accessories
Cable Operators
Circuit Breaker Mounting Zone Dimensions
Maximum Mounting Dimensions (in.)
Box 36" Cable 48" Cable
Depth E1FGE
1FG
8" 13.5 4.0 15.0 25.5 16.0 27.0
10"13.0 5.0 14.8 25.0 17.0 26.8
12"12.8 6.0 14.5 24.8 17.0 26.5
16"10.5 4.5 14.2 22.5 16.5 26.2
18" 8.5 3.5 12.6 20.5 15.5 24.6
20" 0.5 10.0 22.0 15.0 24.0
24" 19.5 14.0 22.0
1Maximum E Dimension only if F = 4.5"
Breaker and Handle Mechanisms
Flange-Mounted Handle Mechanism
Breaker Mounted NEMA Enclosure Type 1, 3R, 12, 13 NEMA Enclosure Type 4, 4X
Circuit Mechanism 6" 10" 6" 10"
Breaker Product List Price Product List Price Product List Price Product List Price Product List Price
Type Number GO-144A Number GO-144A Number GO-144A Number GO-144A Number GO-144A
E150 SCOM1A $96.00
SE150 SCOM1EF $133.00 SCH1 $188.00 SCH2 $322.00 SCH1X $258.00 SCH2X $373.00
SF250 SCOM1EF $133.00
SG600 SCOM1G $148.00
SK1200 SCOM1K $149.00 ––SCH2K $322.00 ––SCH2KX $373.00
Operating Cables GO-144A
Circuit Breaker Type
E150, SE150, SF250, SG600 SK1200
Cable Product List Product List
Length Number Price Number Price
3' SC3L $91.00 SC3H $119.00
4' SC4L $108.00 SC4H $141.00
5' SC5L $119.00 SC5H $163.00
6' SC6L $134.00 SC6H $185.00
7' SC7L $148.00 SC7H $207.00
8' SC8L $163.00 SC8H $229.00
9' SC9L $196.00 SC9H $251.00
10' SC10L $211.00 SC10H $273.00
Prices and data subject to change without notice
3-94 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Operating Mechanism Selection GO-144A
Circuit Breaker Flange Handle Operating Mechanism List
Type Product Number Product Number Price
SE150 SDOM1A $67.00
SF250 SDOM3 $76.50
SG600 SDOM4 $194.00
SK12001STDA3, 3X SDOM61$303.00
TEB, TED, THED, TEC SDOM1A $67.00
TB1 (150A), SDOM1A $67.00
TEC with TECL SDOM1AP $15.00
THLC1 (150A) TDOM1D $252.00
TFJ, TFK, TFC (225A) TDOM32$76.50
J-Frames, TJC
(400, 600A)3TDOM4 $194.00
TB4 (400A) TJH/TJL4
(600A Max) TDOM5 $265.00
K-Frames, TKC
(800A, 1200A)5,TDOM6 $303.00
THLC2 (225A), THLC4
TLB4 (400A)
TB6 (600A), TB8 (800A)
TKH/TKLD6(1200A Max) TDOM7 $303.00
1Requires STDA3 or STDA3X (10 inch, SK1200 only).
2Not suitable for left hand mounting.
3Includes TJ/THJ/TJL with MicroVersaTrip R trip unit.
4Use TDOM5 for TJH/TJL with MicroVersaTrip R RMS-9 trip unit.
5Includes TK/TKL with MicroVersaTrip R trip unit.
6Use TDOM7 for TKH/TKL with MicroVersaTrip R trip unit.
STDA1, 1X (6 inch)
or
STDA2, 2X (10-inch)
STDA1, 1X (6 inch)
or
STDA2, 2X (10-inch)
External Accessories
Flange-Mounted Operators
Type STDA Flange Handles and Variable Depth Operating
Mechanisms
—Designed to meet automotive duty specifications
—NEMA 12/13 and 4/4X UL Component Recognized components,
File E-57253l CSA LR 10263
—For right or left hand flange mounting – field convertible
—Mounting dimensions to fit standard flange enclosures 8 inches –
24 inches deep
—Detailed installation instructions
—Superior strength
Flange Handle Construction
—Rugged die cast housing with provisions for locking in OFF position
with up to three 3/16-inch to 5/16-inch padlocks
—O-ring seals for dirt-tight/oil-tight duty
—Gusseted, 3/32-inch thick double-sided steel handle with large,
red-black self-extinguishing grade plastic grip.
Flange Handle Selection GO-144A
Product Number STDA1 (6 inch) and STDA2 (10 inch) flange series
handles are interchangeable. While the SE150 through SG600
operating mechanisms can be easily operated with the 6-inch STDA1
handle, the 10-inch STDA2 may be used to obtain lower operating
force and/or to provide a proportionally larger handle on large
enclosures. STDA3 and STDA3X can be used only with SDOM6 (for
SK1200) operating mechanism.
NEMA 12/13 NEMA 4/4X Nominal Installation Drilling
Flange Handle List Flange Handle List Length Instruction Template
Product Number Price Product Number Price Inches Number Number
STDA1 $82.50 STDA1X $148.00 6
STDA2 $94.50 STDA2X $165.00 10 GEH-5314 GEH-5314
STDA3 $94.50 STDA3X $165.00 10
Flange Stiffener Kit or Extended Length Drive Rod,
Product Number TDSR GO-144A
Provides rigid 3/8-inch diameter rod between STDA handle mounting
surface (flange or center mullion) and operating mechanism when
STDA handle would otherwise not be rigidly supported.
Rod length is 22 inches and my be cut to appropriate length. Also
used as extended-length drive rod for SDOM1A and SDOM3 when
standard 16 inch rod is not long enough. (Operating mechanism
Product Number SDOM6 for SK1200 includes two 22" unique
3/8-16x22 inch flange stiffener rods, Product Number TDSR and
drive rod.)
Operating Flange Extended
Mechanism Stiffener Kit Drive Rod List
Product Number Product Number Product Number Price
SDOM1A, SDOM3,
TDOM1A through TDOM3 TDSR TDSR $29.50
SDOM4, TDSR
TDOM4 through TDOM7 (16" supplied with TDSR1 $28.00
operating mechanism)
Extended Drive Stud, Product Number TDS1, TDS2 GO-144A
This optional drive study permits locating the operating mechanism
1-5/16 inches farther to the left (When flange handle is on right side)
or to the right (when handle is on the left side) to accommodate
specific mounting restrictions. Not suitable for use with SDOM4,
SDOM6, TDOM4 and TDOM5 operating mechanisms.
Operating Mechanism Extended Drive Stud List
Product Number Product Number Price
SDOM1A, SDOM3,
TDOM1A through TDOM3 TDS1 $29.50
TDOM6, TDOM7 TDS2 $29.50
Door Hardware NEMA 12/13 and 4/4X GO-144A
Type TDV door hardware provides sealing and interlocking of 3/4-inch
nominal door depth hinged on left or right. Interlocking design
requires use of screwdriver to release. When used with an STDA
flange handle and operating mechanisms, disconnect or circuit
breaker cannot be turned on unless door and door hardware have
been closed. For noninterlocking type, one bracket in kit is not used.
Use of third point latch recommended for doors 40 inches or longer.
Door Hinged Door Hinged
on Left on Right List
Description Product Number Product Number Price
NEMA 12/13 two point
interlocking door hardware kit TDV1 TDV1L $134.00
NEMA 4/4X two point
interlockingdoor hardware kit TDV1X TDV1LX $174.00
Third point latch kit for above TDV3 TDV3L $29.50
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-95
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Publication References
Instructions:
Door Hardware GEH-5322
Auxiliary Contact Kit GEH-5323
Flange Stiffener Kit or Extended Length Drive Rod GEH-5324
Extended Drive Stud GEH-5325
Operating Mechanism:
SDOM1A through SDOM4, SDOM6 GEH-5684
TDOM1A through TDOM1D GEH-5315
TDOM3 GEH-5317
TDOM4 and TDOM5 GEH-5318
TDOM6 and TDOM7 GEH-5319
See Section 21 for publication ordering information.
Auxiliary Contact Kits GO-144A
Available SPDT and DPDT and actuated by operating mechanism yoke.
When STDA Auxiliary Contact Kit
Used With handle is on SPDT DPDT
Operating Mechanism Right Left Product List Product List
Product Number Flange Flange Number Price Number Price
SDOM1A,
SDOM3 •TDAS1L1 $71.00 TDAS1L2 $134.00
SDOM4
TDOM1A, JA
TDOM1B, JB
TDOM1C •TDAS1R1 $71.00 TDAS1R2 $134.00
TDOM1D
TDOM3
SDOM6
TDOM4 TDAS2L1 $71.00 TDAS2L2 $134.00
TDOM5
TDOM6 •TDAS1R1 $71.00 TDAS1R2 $134.00
TDOM7
External Accessories
Flange-Mounted Operators
Prices and data subject to change without notice
3-96 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
External Accessories
Door-Mounted Operators
TDM Operating Handle, Fixed or Adjustable Shaft
TDM Handle Operating Mechanisms, Door Mounted GO-144A
Complete mechanism with handle UL listed, E-57253
Operating mechanism only, UL Component Recognized, E-57253
Complete Mechanism1Operating Handle Only
with NEMA 1, 3R, 12 Handle Mechanism Only NEMA 1, 3R, 12 NEMA 4/4X
Breaker Box Depth Product List Product List Product List Product List
Type in Inches Number Price Number Price Number Price Number Price
Shallow Mount TQDHM1 $69.00 TQDOM1 $42.00
TQD, THQD 3 7/16
Extended Shaft TQDHM2 $82.00 TQDOM22$55.00
4 5/16 - 14 5/16
Shallow Mount TEFHM1 $69.00 TEFOM1 $42.00
4 3/16
TEB, TEC, TB1, Extended Shaft TEFHM3 $82.00 TEFOM3 $55.00 TH1 $27.00
TED, THED 5-1/8 - 5 7/32
5 1/8 - 5 13/16 TEFHM4 $82.00 TEFOM4 $55.00
5 1/8 - 15 TEFHM2 $82.00 TEFOM2 $55.00
Shallow Mount TFKHM1 $103.50 TFKOM1 $76.50 THCH453,4 $303.00
TFC, TFJ, 5 7/8
TFK, THFK Extended Shaft TFKHM2 $107.50 TFKOM22$80.50
6 7/8 - 15 1/2
TJC, TJD, TJJ, Shallow Mount TJKHM1 $143.00 TJ K OM1 $102.00
TJK, THJK, 5 7/8
TB4, TBC4 Extended Shaft TJKHM2 $147.00 TJ K OM24$106.00
5 5/8 - 15 5/8
Shallow Mount TKMHM1 $143.00 TKMOM1 $102.00TKC, TKM, 7 7/16
THKM, TB6, Extended Shaft TKMHM2 $147.00 TKMOM24$106.00TBC6, TB8, TBC8 7 1/32 - 17 5/16
TJ4V, TJL Shallow TJVHM1 $143.00 TJ VOM1 $102.00 ––
Extended TJVHM2 $147.50 TJ V OM2 $106.00 ––
TK4V, TKL Shallow TKVHM1 $143.00 TKVOM1 $102.00 ––
Extended TKVHM2 $147.00 TKVOM2 $106.00 ––
SE150 (GEH-5611)54 3/16 SEFHM1 $79.00 SEFOM1 $52.00
6 1/8 - 15 SEFHM2 $81.50 SEFOM22$55.00 TH1 $7.00
SF250 (GEH-5611)55 7/8 SEFHM1 $79.00 SEFOM1 $52.00
7 3/4 - 15 1/2 SEFHM2 $81.50 SEFOM22$55.00 THCH453,4 $303.00
SG600 (GEH-5653)55 7/8 SGHM1 $143.00 SGOM1 $102.00
5 5/8 - 15 5/8 SGHM2 $147.00 SGOM24$106.00 TH2 $41.00
SK1200 (GEH-5612)56SKHM1 $143.00 SKOM1 $102.00
7SKHM2 $147.00 SKOM24$106.00
1Handle assembly and operating mechanism separately packaged.
2For 15-inch long shaft order Product Number 788A831G10, List Price, $40.00, GO-135B. For 20-inch long shaft order Product Number 788A831G21 List Price $40.00, GO-135B.
3Provides interlocking for J600, SG600 SK1200, and K1200 breakers when used with the extended shaft operating mechanism. For interlocking with E150/SE150, F225 and SF250 order
special shaft Product Number 788A832G1, List Price, $40.00, GO-135B.
4For 15-inch long shaft order Product Number 788A832G2, List Price $40.00, GO-135B. For 20-inch long shaft order Product Number 788A832G5, List Price $40.00, GO-135B.
5Installation instructions publication number.
6MOD 1 is 7 7/16; MOD 2 is 8 3/32.
7MOD 1 is 7 3/16 - 17 3/16; MOD 2 is 7 15/16 - 17 15/16.
TH2 $41.00
Handle Accessories for TDM Operating Mechanisms GO-139
Device Product Number List Price
Replacement neoprene gaskets
for NEMA 1, 3R and 12 enclosures
Use with TH1 788A742P3 $2.80
Use with TH2 788A742P4 $6.10
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-97
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
External Accessories
Door-Mounted Operators
TDR Handle on TEC Mag-Break
TDR Integral Handle Mechanism1Suitable for NEMA 12 Applications2GO-144
Handle Door Ring - Interlock Catch Kit NEMA 12 Gasket Kit
Vertical Mounting Horizontal Mounting List Ship Product List Product List
Breaker Type Product Number Product Number Price Weight Number Price Number Price
TEB, TEC, TB1-B, TED, THED TEFR1B TEFR1HB $65.50 173SEFRDRCK $11.25
THLC1 TLC1RB TLC1RHB $65.50 173––SEFRGSK $4.00
TFC, TFJ, TFK, THFK TFKR1B TFKR1HB $78.50 223343L483G5 $11.25
THLC2, 4; TLB4 TLC4RB TLC4RHB $78.50 3343L483G9 $11.25 ––
TJD, TJC, TJJ, TJK, THJK, TB4, TBC4 TJR1B TJR1HB $78.50 5343L483G2 $20.25 SGRGSK $11.00
TKC, TKM, THKM, TB6, TB8, TBC6, TBC8 TKMR1B TKMR1HB $128.00 5 SKRDRCK $21.75 SKRGSK $11.00
TJ4V, TJL TJVR1B TJVR1HB $78.50 5343L483G7 $20.25 SGRGSK $11.00
TJVR1BKLP4TJVR1HBKLP4$524.00
TKL TKVR1B TKVR1HB $128.00 5343L483G8 $21.75 SKRGSK $11.00
TKVR1BKLP4TKVR1HBKLP4$572.00
SE150, SF250 (GEH-5609)6SEFR15SEFR1H5$65.50 173SEFRDRCK $11.25 SEFRGSK $4.00
SG600 (GEH-5654)6SGR1 SGR1H $78.50 5 SGRDRCK $20.25 SGRGSK $11.00
SK1200 (GEH-5610)6SKR1 SKR1H $128.00 5 SKRDRCK $21.75 SKRGSK $11.00
1Not suitable for use with mine duty or heavy duty UVR breakers.
2Requires Gasket kit.
3Shipped 12 per pack.
4With provision for Kirk Key Interlock. Lock supplied by customer (type FN with one-inch bolt projection - bolt extended, key removable with breaker open).
5For F250 Frame also order adapter bracket, Product Number SFRAK, no charge when ordered with handle.
6Installation instructions publication number. See Section 21 for publication ordering information.
Prices and data subject to change without notice
3-98 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
External Accessories
Motor Operators and Plug-in Hardware
Motor Operated Mechanism
on SF-Frame breaker
Motor Mounted Mechanism GO-135S
UL Listed
Voltage
Vac Product List Installation
Breaker Type 50/60 Hz Vdc Number Price Instructions
TEB,1 TEC, TED,1–24TEDMOMA8 $1572.006
THED, TB1, THLC121203TEDMOMA1 $710.006
2404,5 TEDMOMA2 $710.006
–24TFKMOMA8 $1692.006
TFC, TFJ, TFK, THFK –48TFKMOMA9 $1692.006
120125 TFKMOMA1 $1692.006
2404,5 250 TFKMOMA2 $1692.006
–24TJKMOMA8 $2160.006
TJC, TJJ, TJD, TJK, 48 TJKMOMA9 $2160.006
THJK, TB4, TBC4 120 125 TJKMOMA1 $2160.006
2404,5 250 TJKMOMA2 $2160.006
–24TKMMOMA8 $2340.006
TKC, TKM, THKM, TB6, 48 TKMMOMA9 $2340.006
TB8, TBC6, TBC8 120 125 TKMMOMA1 $2340.006
2404,5 250 TKMMOMA2 $2340.006
120125 SEMOM1 $710.00
SE150 2404SEMOM2 $710.00 GEH-5613
–24SEMOM8 $710.00
–48SEMOM9 $710.00
120125 SFMOM1 $1692.00
SF250 2404SFMOM2 $1692.00 GEH-5613
–24SFMOM8 $1692.00
–48SFMOM9 $1692.00
120125 SGMOM1 $2160.00
SG600 2404250 SGMOM2 $2160.00 GEH-5657
–24SGMOM8 $2160.00
–48SGMOM9 $2160.00
120125 SKMOM1 $2340.00
SK1200 2404250 SKMOM2 $2340.00 GEH-5614
–24SKMOM8 $2340.00
–48SKMOM9 $2340.00
For TJ4V, TJL, TKL, TK4V ONLY 7GO-135B
Mechanism Mounting Plate
Breaker Type Volts Product Number Product Number List Price
120 Vac TJKMOMA1 286A7558G8 $2160.00
125 Vdc
TJ4V, TJL 240 Vac4,5 TJKMOMA2 286A7558G8 $2160.00
250 Vdc
24 Vdc TJKMOMA8 286A7558G8 $2160.00
48 Vdc TJKMOMA9 286A7558G8 $2160.00
120 Vac TKMMOMA1 286A7558G7 $2340.00
125 Vdc
TKL, TK4V 240 Vac4,5 TKMMOMA2 286A7558G7 $2340.00
250 Vdc
24 Vdc TKMMOMA8 286A7558G7 $2340.00
48 V TKMMOMA9 286A7558G7 $2340.00
Mounting Screw Kit for Motor-Operated Mechanism 8GO-148B
Breaker Type Mounting Screw Kit Product Number List Price
TED, TB1 343L564G7 $33.506
TFJ, TFK 343L564G1 $8.706
TJ J, TJK, TB4 343L564G2 $87.00
SG600 SGMSKMOM $87.009
TKM, TB6, TB8, SK 343L564G3 $121.00
1For use on 3-pole breaker only.
2Motor-operated mechanisms must have Code Date 506 + or later for use with THLC1.
3TEDMOMA1 not rated at 50 hertz.
4Suitable for use at 208 Vac.
5Not UL listed.
6GO-135B.
7Requires mounting plate which is supplied at no charge when ordered with mechanism.
Order both items.
8Required with plug-in mounting base assembly when used with motor-operating
mechanisms or TDR integral-handle kits. Furnished no charge when ordered with
mounting base.
9GO-135S.
Mounting Screw Kit for TDR Integral Handle GO-135B
Mounting Screw Kit
Breaker Type Product Number List Price
TFC,TFJ,TFK 343L564G4 $8.60
TEC,TED,TB1-B, TJC, TJJ,
TJK, TB4, TBC, TKC, TKM, No Special Mounting
TB6, TB8, TBC6, TBC8 Screw Required
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-99
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
External Accessories
Mechanical Interlocks and Locking Devices
Mechanical Interlocks
Walking Beam Type Externally Mounted—UL Component Recognized
Requires Breaker with
Special Factory Drilling.
Panel Order 2 Breakers per Interlock,
Thickness Specifying "Drilled for Mech. Interlock" List Price
Breaker Type in Inches Product Number GO-135B
E-150, TB1 .25-1.0 TEDMI $341.00
F225 .25-1.0 TFKMI $341.00
TJ J, TJK, TJ4V, 0.38 TJKMIB $341.00
THJ4V, TB4 1.0 TJKMIE $341.00
TKM, TK4V, TB6, TB8 .75-1.0 TKMMI $341.001
These face-mounted interlocks prevent two adjacent breakers from
being in the ON position at the same time.
Adapter Kit Required
when using handle
Face-mounted operator (TDM) or
Spectra RMS Interlock List Price motor operator. List Price
Breaker Type Product Number GO-135S Order separately. GO-135S
SE150, SF250 SEFFMI $341.00 SEFFMIAK2$33.50
SG600 SGFMI $683.00 SGFMIAK3$42.00
SK1200 SKFMI $683.00 SKFMIAK $59.50
Handle-Locking, Handle-Extension Devices GO-135B
Breaker Type Device Product Number List Price
TQB, TQC, TQL Handle locking THL103 $6.504
TQB, TQC, TQL Snap-on handle tie - trip indicating TQHT1 $2.304
TQL Snap-on handle tie - solid THT104 $2.304
TEY Handle locking TEYLD1 $5.00
E150 Line Handle locking TLD3 $5.00
F225 Line,
THLC2, 4 Handle locking TFKLD1 $6.00
SE150, SF250 Handle locking SBD1 $4.705
SK1200 Handle extension - replacement SKHDLEXT $96.505
Q Line, TEY Mounting Accessories GO-135B
Description Breaker Type Product Number List Price
Back Mounting plates 1-pole THQC TQCBMPA1 $8.30
Screw Type 2-pole THQC TQCBMPA2 $9.80
THQC Breaker held to 3-pole THQC TQCBMPA3 $12.00
Mounting Plate by screw clip 10-pole THQC TQCBMPA10 $32.00
Snap In 1-pole TQCGFBMPA1 $6.106
THQC, THQC-GF 2-pole TQCGFBMPA2 $7.606
snaps in to spring retaining clip 3-pole TQCGFBMPA3 $9.106
10-pole TQCGFBMPA10 $25.006
Bolt-on Base for THQB, TEY 3-pole TEY3B $31.50
1-pole THQC TQCFMP1 $8.30
Front-mounting Plates72-pole THQC TQCFMP2 $9.80
3-pole THQC TQCFMP3 $12.00
10-pole THQC TQCFMP10 $14.00
3-pole Plug-in Mounting Base (70 Amp) 3-pole TQL 571B595DDG2 $32.008
2-pole Plug-in Mounting Base (70 Amp) 2-pole TQL 571B595DDG1 $23.758
3-pole Plug-in Mounting Base (100 Amp) 3-pole TQL 565B837G1 $38.008
2-pole Plug-in Mounting Base (100 Amp) 2-pole TQL 565B837G2 $23.758
Pack of 48 Front/Rear Mounting Clips 1 & 2-pole THQCFMK $48.009
15-60A THQC
Pack of 24 DIN rail clips DIN rail THQC THQCDIN $24.009
1GO-144.
2Not suitable with THCH45 handle.
3Compatible with motor operator only. Product Number SGFMI cannot be used with the
handle operator.
4GO-137A.
5GO-135S.
6GO-133.
7Not UL listed.
8GO-134A.
9Price is per pack.
10Suitable for circuit breakers used in group mounted panelboard construction only except
for J600, K1200, SE150/SF250, SG600 and SK1200 which screw down to face of breaker.
11Field installable.
Standard Padlocking Devices10 GO-135B
Breaker Type Device Product Number List Price
TQC TQPLD1 $4.70
TQD TQDPLD1 $20.754
TQDL TQDLPDL1 $17.754
TQB, TQL THP100 $6.504
TEY TEYPLD1 $9.00
E150, TB1 TEFPLD1 $8.00
THLC1 TLC1PLD1 $17.00
F225 TFKPLD1 $4.00
THLC2, THLC4, TLB4 TLC4PLD1 $22.00
J600 Line TJKPLD1 $8.00
K1200 Line TKMPLD1 $28.50
SE150, SF250 SEPLD $8.705
SG600 SGPLD $15.005
SK1200 SKPLD $28.505
EUSERC Approved—Factory Installed Only GO-135B
Breaker Type Product Number List Price
TQD TQDPLD2 $32.00
E150 TEDPLD2 $32.00
SE150, SF25011 SEFPLD2 $32.005
SG600 SGPLD2 $48.005
J600 TJKPLD2 $48.00
SK1200 SKPLD2 $60.005
THLC1 THLC1PLD2 $48.00
THLC2/4 THLC4PLD2 $48.00
PowerMark Gold Main Circuit Breaker Kit GO-138M
Description Product Number List Price
Order appropriate TQMH000 $10.50
THQL (10 kAIC) or THHQL
breakers separately.
Prices and data subject to change without notice
3-100 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
External Accessories
Breaker Mounting Hardware and Kits
Breaker Mounting Screw Kits GO-135S
Spectra RMS Kit Screw Size
Application Breaker Type Product Number (inches) List Price
SE150 SEMSK1 10-33x2 7/8 (std.) $2.10
For use on mounting SEMSK3 8-32x2 7/8 (opt.) $2.10
plates with tapped SF250 SFGMSK1 12-24x3 3/4 (std.) $6.10
holes (4 screws SFMSK1 10-32x3 3/4 (opt.) $6.10
and lockwashers) SG600 SFGMSK1 12-24x3 3/4 $6.10
SK1200 SKMSK1 5/16-18x1 1/4 $8.70
SE150 SEMSK2 10-32x3 (std.) $2.10
For use on mounting SEMSK4 8-32x3 (opt.) $2.10
plates with clearance SF250 SFGMSK2 12-24x4 (std.) $6.10
holes (4 screws, SFMSK2 10-32x4 (opt.) $6.10
lockwashers and nuts) SG600 SFGMSK2 12-24x4 $6.10
SK1200 SKMSK2 5/16-18x1 3/4 $8.70
Breaker Mounting Screw Kits GO-135B
Application Breaker Type Product Number List Price
1-pole E150 343L162G1 $0.85
2- and 3-pole E150 SEMSK4 $2.101
For use on mounting THLC1 343L162G22 $2.10
plates with clearance F225 SFGMSK2 $6.101
holes THLC2, 4, TLB4 343L162G24 $5.70
J600 343L162G20 $4.50
K1200 SKMSK2 $8.701
1-pole TE, E150 343L162G7 $0.85
2- and 3-pole E150 SEMSK3 $2.101
THLC1 343L162G23 $2.10
For use on mounting 2- and 3-pole TQD/THQD 343L184G18 $4.402
plates with tapped holes F225 SFGMSK1 $6.101
THLC2, 4, TLB4 343L162G25 $5.70
J600 343L162G11 $4.50
K1200 SKMSK1 $8.701
24 mounting screws for TQBS1
connecting low tab to THQB (packaged 24/kit) $6.003
panel board
Cup washer E150 254V644P1 $0.10
(for mounting 1-pole breakers) (2 req'd per breaker)
Back-Connected Line and Load Studs GO-135B
Length,
Back of Breaker Product
Breaker Type Amperes in Inches Std Pkg Number List Price
50 2 25/32 (short) 1 TEF1 $27.00
E1504, TB14,4 13/32 (long) 1 TEF2 $27.00
THLC141503 13/32 (short) 1 TEF3 $28.00
5 25/32 (long) 1 TEF4 $31.50
TFJ4, TFK4, 225 2 23/32 (short) 1 TFK1 $38.50
THFK45 31/32 (long) 1 TFK2 $59.50
J600, TJ4V, 400 5 17/32 1 TJK1 $83.50
TB4, TJL 600 5 17/32 1 TJK2 $119.00
K1200, 1200 5 1/2 2 TKM11 $220.00
TB6, TB8 8 2 TKM12 $242.00
50 2 25/32 (short) 1 TEF1 $27.00
SE150 4 13/32 (long) 1 TEF2 $27.00
150 3 13/32 (short) 1 TEF3 $28.00
5 25/32 (long) 1 TEF4 $31.50
SF250 250 2 23/32 (short) 1 TFK1 $38.50
5 31/32 (long) 1 TFK2 $59.50
SG600 600 2 13/16 (short) 2 SGBCS1 $119.001
6 1/16 (long) 2 SGBCS2 $119.001
SK1200 1200 5 1/2 2 TKM11 $220.00
82TKM12 $242.00
Back-Connected Center Studs
for Dual Voltage Applications GO-135B
3-pole only. Order frame and trip unit separately. Not UL listed.
Breaker frame can be supplied with center stud connections permit-
ting operation at both voltages with one trip unit rating. At the higher
voltage, connection is made at the line and load terminals only and
thus the trip unit carries all the load current. At the lower voltage,
where current is double, connection is also made through the center
studs permitting half the current to bypass the trip unit. At either
voltage, full-load current is carried by the breaker contacts.
Trip Unit Dual Voltage
Maximum Frame Maximum Frame Only
Ampere Rating Ampere Rating Product Number List Price5
225A 110 TFK236F000DV $1244.00
400A 200 TJK436F000DV $2364.00
600A 300 TJK636F000DV $2576.00
800A 400 TKM836F000DV $3095.00
1200A600 TKM3FDV $4064.00
1GO-135S.
2GO148C.
3Price is per screw. Packaged in quantity of 24. Must be ordered in multiples of 24.
4For proper clearance between poles, a short and long stud must be assembled adjacent
to each other.
5Price includes center studs, but does not include line and load back-connected studs or
trip unit.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-101
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
External Accessories
Lugs and Associated Hardware
Breaker with Line and Load Studs
Lugs, Line Shields, Covers and Bus Connectors GO-135B
Accessory Wire Size For Use With Product Number List Price
Copper-Aluminum Lugs #14-6 Cu, #12-2 Al TQC (15-60A) (Non DIN Rail) TQAL3 $1.50
#4-1/0 Cu-Al TQC (70-100A) TQAL4 $1.50
#1-300 kcmil Cu-Al TQD TCAL25 $8.001
#14-8 E150, THLC1, TB1, (15-30A) TCAL14 $3.00
#14-3 Cu, #12-1 Al E150, THLC1, TB1, (15-60A) TCAL12 $3.00
#6-2/0 Cu, #4-2/0 Al E150, THLC1, TB1, (70-90A) TCAL12A $3.00
#3-3/0 Cu, #1-3/0 Al E150, THLC1, TB1, (100-150A) TCAL15 $3.00
#4-300kcmil Cu-Al F225 TCAL24 $8.00
#4-300kcmil Cu-Al THLC2 TCAL27 $10.00
(1) 6-600kcmil or (2) 2/0-250kcmil Cu-Al J400, TB4, J600 (Thru 400A), TJD TCAL43 $14.00
(2) 4/0-350kcmil Cu or (2) 300-500kcmil Al J600 (450-600A) TCAL63 $23.00
(1) 750 kcmil Cu-Al J400, TJD TCAL47 $26.00
(1) 3/0-500kcmil or (2)3/0-250kcmil Cu-Al TLB4, THLC4 TCLK43 $49.00
(2) 1/0-250kcmil or (1) #4-600 kcmil Cu-Al K1200, TB6 (300-400A) TCAL41 $38.00
(2) 2/0-500 kcmil Cu-Al K1200, TB6, (500-600A) TCAL61 $40.00
(3) 3/0-500 kcmil Cu-Al K1200 (700-1000A), TB8 TCAL812$47.003
(3) 3/0-500 kcmil Cu-Al TK4V - Load end TCAL912$47.003
(4) 250-350 kcmil Cu or (4) 250-500 kcmil Al K1200 (1200A) TCAL1214$76.003
(3) 750 kcmil Cu-Al TCAL122 $103.005
(4) 250-350 kcmil Cu or (4) 250-500 kcmil Al TK4V - Load end TCAL1314$76.003
Copper Only Lugs #14-2/0 E150, TB1 (thru 150A) TC012 $6.00
With Follower and Extra Plating (1) 6-600 kcmil or (2) 1/0-250 kcmil Cu J400, TB4 TC043 $21.00
(2) 250-350 kcmil Cu J600 TC063 $34.00
(1) 1/0-600kcmil or (2) 1/0-250 kcmil Cu K1200, TB6 (300-400A) TC0415$38.00
(2) 2/0-500 kcmil Cu K1200, TB6, (500-600A) TC061 $40.00
(3) 3/0-500 kcmil Cu K1200 (700-1000A), TB8 TC081A $53.003
(3) 3/0-500 kcmil Cu TK4V - Load end TC091 $53.003
(4) 250-400kcmil Cu K1200 (1200A) TC0121 $80.003
(4) 250-400kcmil Cu TK4V - Load end TC0131 $80.003
Line Shield TEB, TEC, TED, THED TEDLS $5.10
TFJ, TFK, TFC TFKLS $16.25
TJ J, TJK, TJC TJKLS $14.25
Lug Cover, TKM Breaker TC041, TCAL41 Lugs 789A448G36$35.00
(two per breaker) TC061, TCAL61, TCAL81 Lugs, TC081A 789A448G1 $35.00
TC0121; TCAL121 Lugs 789A448G2 $35.00
TH4V, THK9V 286A8066G1 $33.503
Connector (back strap) TKM TKMC1 $38.00
Line voltage control wire kit J600 TJLVK7$9.00
for terminating control wire at breaker lugs K1200 SKLVK7$12.003
1GO-135F.
2Not suitable for 100 A aluminum conductor.
3GO-135S.
4Suitable for 500 kcmil copper for voltage drop considerations.
5Not UL listed.
6End cover supplied with 800A frame is used as lug cover.
73-pole kit.
Prices and data subject to change without notice
3-102 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
External Accessories
Lugs and Associated Hardware
Spectra RMS Lugs, Lug Covers, and Bus Lugs GO-135S
Wire Range (Qty.)
Accessory For Use With Copper Aluminum Product Number Description Ampacity Range1List Price
SE150 #12-3/0 #12-3/0 TCAL18 Single lug 15-150 $3.00
SF250 #8-350 kcmil #8-350 kcmil TCAL29 Single lug 70-250 $8.00
SG600 (2)2/0-500 kcmil or (2)2/0-500 kcmil or TCLK265 2-pole lug kit2125-600 $28.00
Plated extruded aluminum (1)#8-600 kcmil (1)#8-600 kcmil TCLK365 3-pole lug kit2125-600 $42.00
lugs for terminating
(3)300-750 kcmil (3)300-750 kcmil TCAL124 Single lug Cu 275-1200 $103.00
copper or aluminum cables
SK1200 Al 225-1100 $103.00
(3)3/0-500 kcmil (3)3/0-500 kcmil TCAL81 Single lug 300-800 $47.00
(4)250-3503kcmil (4)250-500 kcmil TCAL1253Single lug 600-1200 $76.00
SE150 SE3LCK Three lug covers for $5.10
upper (line) end
SF250 SF3LCK Three lug covers for $9.80
upper (line) end
Replacement Lug Covers SG1LCK 3-pole lug cover for $21.25
and End Covers SG600 upper (line) or lower (load) end
SG1BCK 3-pole lug cover for $37.00
upper (line) or lower (load) end7
SK1200 SK1LCK Lug cover for upper (line) $33.50
or lower (load) end4
SE150 #12-3/0 TCO18 Single lug 15-150 $6.00
SF250 #8-350 kcmil TCO19 Single lug 70-250 $21.25
SG600 (2)2/0-500 kcmil or TCOK265 2-pole lug kit 125-600 $42.00
Plated Copper Lugs (1)#8-600 kcmil TCOK365 3-pole lug kit 125-600 $63.00
(3)250-500 kcmil TCO81A Single lug 300-800 $53.00
SK1200 (4)250-400 kcmil TCO121 Single lug 600-1200 $80.00
(3)250-750 kcmil TCO124 Single lug 600-1200 $155.00
SE150 #12-3/0 #12-3/0 TCAL18LV Single lug with .25 15-150 $6.60
Line voltage control wire kit Quick Connect
for terminating control wire SF250 #8-350 kcmil #8-350 kcmil TCAL29LV for Control Voltage 70-250 $17.75
at breaker lugs SG600 SGLVK 3-pole kit $9.00
SK1200 SKLVK 3-pole kit $12.00
Replacement cover
SPCOV1 for MicroVersaTrip Plus $13.25
Clear rating plug cover and MicroVersaTrip PM
with provision for wire seal SG600 / SK1200 SPCOV2 Cover with access to $13.25
instantaneous set point
SPCOV3 Cover with no access $13.25
to instantaneous set point
Lugs and Lug Covers for J and K Frames with MVT-4 and RMS-9 Trip Units GO-135S
Standard Lugs Optional Lugs Lug Covers5End Covers5
Sensor Rating Cu/Al List Cu Only List Product List Product List
Breaker Type (Amps) Product Number Price Product Number Price Number Price Number Price
150
200 TCAL43 $14.006TCO43 $21.006––
TJ, TJL with RMS-9 or MVT-4 300
400
500 TCAL63 $23.006TCO63 $34.006––
600
400
600 TCAL81 $47.00 TCO81A $53.00 286A8066G3 $33.50 286A8066G2 $33.50
TKH, TKL with RMS-9 800
1000 TCAL1213$76.00 TCO121 $80.00 286A8066G1 $33.50 286A8066G2 $33.50
1200
400 TCAL81-Line3$47.00 TCO81A-Line $53.00
600
TCAL91-Load3$47.00 TCO91-Load $53.00
286A8066G3 $33.50 286A8066G2 $33.50
K with MVT-4 TRIP UNIT 800
1000 TCAL121-Line3$76.00 TCO121-Line $80.00 286A8066G1 $33.50 286A8066G2 $33.50
1200 TCAL131-Load3$76.00 TCO131-Load $80.00
1Both copper and aluminum cables may not cover full ampacity range.
2With lug cover for line or load end.
3500 kcmil acceptable for voltage drop considerations.
4100kA, 480 Vac (SKPA) uses longer lug cover/arc shield on upper end. Use Product Number SKPSHLD for replacement. May be used on other SK1200 devices.
5Breakers supplied less lugs with end covers. When ordering K-frame breaker and lugs, order appropriate lug covers.
6GO-135B.
7Required for line end bus connection.
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-103
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
External Accessories
Neutral Grounds and Sensors
Power Distribution Lugs GO-135
Breaker Type Max Amperes Wire Range Product Number List Price
SE, TED 125 (2) 4-14 or TCAL19PD3 $50.00
(1) 2/0-4 Cu only
SF 250 (6) 4-14 Cu only TCAL28PD3 $75.00
SG 400 (12) 4-14 Cu only TCAL40PD3 $88.00
Neutral Current Sensors GO-135S
For grounded neutral system ground fault applications
Breaker Type Ampere Rating Product Number List Price
150 TSRG201 $532.00
200 TSRG202 $532.00
300 TSRG203 $532.00
J400 TSRG204 $532.00
500 TSRG205 $532.00
600 TSRG206 $532.00
800 TSKG408 $532.00
K1000 TSKG410 $532.00
1200 TSKG412 $532.00
Fungus and Moisture Proofing GO-135B
Q Line E150 F225 J600 K1200 TB-1 TB-4 TB-6, 8
Poles List Price List Price List Price List Price List Price List Price List Price List Price
1, 2 $8.90 $28.50 $84.00 $84.00 $216.00 $62.50 $231.00 $295.00
and 3 $22.25 $62.50
Test Set for MicroVersaTrip Plus, MicroVersaTrip PM
and MicroVersaTrip RMS-9 Trip Units GO-245B
Description Product Number List Price
Portable Test Set TVRMS2 $3000.00
Rating Plug Removal Tool GO-135S
Product Number List Price
TRTOOL $12.00
"Naval Use" Molded Case Circuit Breakers
The following molded case circuit breaker types are optionally
available as UL listed per Standard 489, Supplement SB for naval use:
—THQB
—THQC
—SE150
—SF250
—SG600
—SK1200
Contact GE sales office for price and delivery.
Special Calibration
Contact GE sales office for availability. May void UL listing status.
Neutral Current Sensor
Power Distribution Lugs
Prices and data subject to change without notice
3-104 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
External Accessories
Plug-in Hardware
Plug-In Mounting Base Assembly GO-135B
Plug-In Mounting Bases - 2 Required Per Breaker
Ampere Breaker Stud Configuration Product Optional Mounting Base
Rating Type No. Poles PD1 PD2 Number List Price Product Number List Price
E15012OLS SLO TE12PD1,2 $250.00 TMP1 $40.00
150 TB1 3 SLS LSL TE13PD1,2 $375.00 TMP5 $40.00
SE150 3 SLS LSL TE13PD1,2 $375.00 TMP1 $40.00
225 F225 2SOS LOL TF22PD1,2 $300.00 TMP2 $40.00
3SLS LSL TF23PD1,2 $450.00 TMP2 $40.00
250 SF250 2SOS LOL TF22PD1,2 $300.00 TMP2 $40.00
3SLS LSL TF23PD1,2 $450.00 TMP2 $40.00
J400 2SOS LOL TJ42PD1A,2A $400.00 TMP3 $40.00
3SLS LSL TJ43PD1A,2A $600.00 TMP3 $40.00
400 TB4 2SOS LOL TJ42PD1A,2A $400.00 TMP6 $50.00
3SLS LSL TJ43PD1A,2A $600.00 TMP6 $50.00
SG400 3 SLS2LSL2SGPC1, SGPC2 $600.003SMP3 $40.003
J600, TJ4V, TJL 2SOS LOL TJ62PD1A,2A $500.00 TMP3 $40.00
3SLS LSL TJ63PD1A,2A $750.00 TMP3 $40.00
K1200, TKL, TK4V 2SOS LOL TK62PD1A,2A $500.00 TMP4 $50.00
600 3 SLS LSL TK63PD1A,2A $750.00 TMP4 $50.00
TB6 2SOS LOL TK62PD1A,2A $500.00 TMP7 $50.00
3SLS LSL TK63PD1A,2A $750.00 TMP7 $50.00
SG600 3 SLS2LSL2SGPC1, SGPC2 $600.003SMP3 $40.003
K1200, TK4V, TKL 2SOS LOL TK82PD1A,2A $600.00 TMP4 $50.00
3SLS LSL TK83PD1A,2A $900.00 TMP4 $50.00
800 TB8 2SOS LOL TK82PD1A,2A $600.00 TMP7 $50.00
3SLS LSL TK83PD1A,2A $900.00 TMP7 $50.00
SK800 3 SLS LSL TK83PD1A,2A $900.00 TMP4 $50.00
K1200, TK4V, TKL 2SOS LOL TK102PD1A,2A $700.00 TMP4 $50.00
1000 3 SLS LSL TK103PD1A,2A $1050.00 TMP4 $50.00
SK1200 3 SLS LSL TK103PD1A,2A $1050.00 TMP4 $50.00
K1200, TK4V, TKL 2SOS LOL TK122PD1A,2A $800.00 TMP4 $50.00
1200 3 SLS LSL TK123PD1A,2A $1200.00 TMP4 $50.00
SK1200 3 SLS LSL TK123PD1A,2A $1200.00 TMP4 $50.00
1Order 3-pole base for use with 2-pole Hi Break and 600 Vac breakers.
2Vertical studs only for SG600 frame.
3GO-135S.
Each plug-in mounting base assembly includes all mounting
hardware, studs, and male or female connectors for attachment to
one end of breaker. Studs are of different length so by using proper
combinations of PD1 and PD2 units, adequate electrical spacing will
be assured between adjacent breakers, i.e., a short-long-short (SLS)
unit must be used adjacent to a long-short-long (LSL) unit. Two-pole
breakers of the E150 line require an open-long-short (OLS) unit on
one end of the breaker and a short-long-open (SLO) on the other
since these breakers are built with the normal left pole missing
while the mounting bases are built from standard three-pole
molded supports.
Spectra RMS and all other two-pole breakers are basically three-pole
devices with the center pole omitted. When these breakers are to be
mounted side by side, a short-open-short (SOS) unit must be used on
one end and a long-open-long (LOL) on the other. Horizontal studs are
normally supplied with the flat surface of studs at right angles to the
long axis of the breaker. If vertical studs are desired, substitute "C" for
"D" in the product number, e.g., TE13PC1 (vertical)
or TE13PD1 (horizontal).
The optional mounting plate (TMP1, etc.) accurately locates and
supports the pair of line and load plug-in mounting-base assemblies
and provides a convenient means to attach the entire unit to a
metal structure, and serves as a dead front barrier. New drawings
are available for customers who prefer to fabricate their own
mounting plates.
Plug-in Mounting Base with Hardware
Product Number TF23PD2 shown
Plug-in Mounting Base
Product Number TK123PD2A shown
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-105
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
External Accessories
R-Frame
Ground Fault Neutral Sensors GO-245B
Current Sensor Rating Neutral Sensor Product Number List Price
1000A TSVG810A $266.00
1600A TSVG816A $266.00
2000A TSVG820A $266.00
T-Studs GO-145A
Studs mount to breaker or adapter kit. Studs may be rotated for either vertical or
horizontal bus. Product number includes 1 stud.
Maximum Breaker Ampacity Product Number List Price
1600A TP16FCA $113.00
2000A TP20FCA $113.00
1600A Power Break
with TPLUGA16 Adapter and 6 TPLUG108 Lugs
Type TP16FCA T-Stud
Type TPLUG408 Lug Kit
Lug Kits GO-245B
Kits accept Cu/Al wire and are suitable for direct mounting to breaker. Order one kit per line
or load pole. TPLUG108 is suitable for use only with the adapter kits described below.
Circuit Breaker Maximum Product Lugs Maximum Cables Wire Range
Frame Size Ampere Rating Number per Kit per Pole Cu/Al List Price
1000-1600 1600 TPLUG408 1 4 500-800 kcmil $39.00
TPLUG401 1 6 250-800 kcmil $23.00
Lug Adapter Kits GO-245B
Premounts to bus structure allowing cabling or bussing to be
completed prior to breaker mounting. Accepts either lugs or crimp
type connector terminals. Product number includes adapter and
hardware for three-pole line side or three-pole load side connection.
Kits include a set of three corresponding T-studs and are suitable for
use with from 1 to 6 TPLUG108 lugs per pole or with from 1 to 6 Crimp
Lugs (Anderson No. VCEL-075-12H1 or equivalent) per pole.
Maximum Breaker Ampacity Product Number List Price
1000/1600 A TPLUGA16 $389.00
2000 A TPLUGA20 $486.50
Kirk Key Provision (Factory Installation Only) GO-145A
Equips the breaker to accept a zero bolt projection Kirk Key device
(supplied by customer) to permit sequencing of breaker operations
with other key-type devices. The key remains captured in the breaker
frame except when the breaker has been locked in the open position.
Not compatible with door interlock and padlock device.
Number of Locks Product Number List Price
1TPK01 (Type F) $817.00
2TPK02 (Type M2F) $817.00
3TPK03 (Type M3F) $817.00
4TPK04 (Type M4F) $817.00
Terminal Block (Factory Installed Only) GO-145A
Offers an external means of terminating accessory leads at the
breaker. A maximum of 18 terminals can be supplied on each side
of the breaker (36 terminals total). For stationary breakers only.
Terminal blocks are rated 10 amperes at 600 Vac.
Factory Installed Product Numbers
Breaker Envelope Size (Amps)
Breaker Terminals 1000, 1600 and 20001List Price
6TPTB1R,L $158.00
12 TPTB2R,L $221.00
TRL/TRP 18 TPTB3R,L $286.00
R Frame 24 TPTB4L $444.00
30 TPTB5L $508.00
36 TPTB6L $573.00
1Limited to left side only.
Walking Beam Interlock—Not UL listed GO-145A
Product Number List Price
TPWB $525.00
Prices and data subject to change without notice
3-106 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Power Management System Accessories
Spectra RMS Circuit Breakers with MicroVersaTrip Plus and MicroVersaTrip PM Trip Units
All Devices UL Listed for Factory or Field Installation (UL File No. E-57253)
Required Accessories
Type Accessories
Standard
Ground Fault Option with 3-phase, 4-wire Neutral Current Sensor and Terminal Block
MicroVersaTrip Plus Trip Unit or 1-phase, 3-wire service or Neutral Current Sensor and Junction Box
Control Power Option Power Supply Plate or Voltage Module1or Power Supply Assembly2
Power Supply Plate and Voltage Conditioner Plate or Voltage Module1
Standard or with Protective Relaying or Power Supply Assembly2and Voltage Conditioner Assembly2
MicroVersaTrip PM Trip Unit Junction Box, Cable Harness and Auxiliary Switch
Ground Fault Option with 3-phase, 4-wire Neutral Current Sensor
or 1-phase, 3-wire service
1For installation into GE Spectra Series Switchboards only.
2Requires fuse protection and other components; refer to accessory detail for additional information.
Power Supply Plate GO-135PM
The Power Supply Plate is used to provide +24 Vdc control power to Spectra RMS Molded Case Circuit
Breakers with MicroVersaTrip PM or MicroVersaTrip Plus trip systems via the Distribution Cable System.
The Power Supply Plate includes the Power Supply Assembly (product number SPSAA) as an integral com-
ponent and also includes fuse protection for AC source input. Supplemental +24 Vdc input terminals are
provided for backup control power applications. Five versions are available. Not suitable for 400 Hz.
Description Voltage Rating Product Number List Price
The Power Supply Plate is rated 24 watts 120 Vac SPSA120 $1215.00
(+24 Vdc at 1.0 amperes) and has the maximum 208 Vac SPSA208 $1215.00
capacity to power a distribution Cable System 240 Vac SPSA240 $1215.00
consisting of 20 breakers and has a maximum 480 Vac SPSA480 $1215.00
system cable length of 40 feet. 600 Vac SPSA600 $1215.00
Voltage Conditoner Plate GO-135PM
The Voltage Conditioner Plate is used to provide voltage sensing signals to Spectra RMS Molded Case
Circuit Breakers with MicroVersaTrip PM Trip Units via the Distribution Cable System. The Voltage
Conditioner Plate includes the Voltage Conditioner Assembly (product number SVCAA) as an integral
component and also includes fuse protection for the AC source input terminals and three 1-VA high
accuracy potential transformers.
The Voltage Conditioner Plate requires a control power source of +24 Vdc to operate properly (the Power
Supply Assembly or Power Supply Plate can provide this required input). The unit also requires AC direct
voltage inputs from the AC source. A GE POWER LEADER network (commnet) connection is provided.
Seven versions are available. Not suitable for 400 Hz.
Voltage Rating and Service Type Comments Product Number List Price
120 Vac Wye system Phase to Neutral potential SVCA120Y $1000.00
208 Vac Wye system Phase to Phase potential SVCA208Y $1000.00
240 Vac Delta system Phase to Phase potential SVCA240D $1000.00
277 Vac Wye system Phase to Neutral potential SVCA277Y $1000.00
480 Vac Wye system Phase to Phase potential SVCA480Y $1000.00
480 Vac Delta system Phase to Phase potential SVCA480D $1000.00
600 Vac Delta system Phase to Phase potential SVCA600D $1000.00
Note: The Voltage Conditoner Plate has the maximum capacity to power a Distribution Cable System consisting of
20 breakers and has a maximum system cable length of 40 feet.
Distribution Cable Junction Box GO-135PM
The Distribution Cable Junction Box is a modular connector used to provide quick, easy and reliable
attachment of Spectra RMS Molded Case Circuit Breakers with MicroVersaTrip Plus trip systems or
MicroVersaTrip PM trip systems to the Distribution Cable System. The Junction Box contains two
Distribution Cable Harness plugs, one breaker plug and a terminal block for the connection of a neutral
current sensor and an auxiliary switch. Product number SDCJBA is for general purpose OEM applica-
tions. Product number SDCJBB is designed for mounting in Spectra Series Panelboards.
Description Product Number List Price
Distribution Cable Junction Box SDCJBA $155.00
Distribution Cable Junction Box SDCJBB $155.00
Distribution Cable Harness3GO-135PM
The Distribution Cable Harness is a modular connector used to carry electronic signals and/or control
power between Spectra RMS Molded Case Circuit Breakers with MicroVersaTrip Plus or MicroVersaTrip
PM Trip Units and Distribution Cable accessories. The harnesses come in three lengths.
Description Harness Length Product Number List Price
Distribution Cable Harness 11 inches SDCHA11 $70.00
Distribution Cable Harness 30 inches SDCHA30 $80.00
Distribution Cable Harness 60 inches SDCHA60 $100.00
3Cannot be connected together. Use 30 inch Distribution Cable Extension (SDCEA30) to extend.
Power Supply Plate
Voltage Conditioner Plate
Distribution Cable Junction Box
Distribution Cable Harness
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-107
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Power Management System Accessories
Spectra RMS Circuit Breakers with MicroVersaTrip Plus and MicroVersaTrip PM Trip Units
All Devices UL Listed for Factory or Field Installation (UL File No. E-57253)
Distribution Cable Extension GO-135PM
The Distribution Cable Extension is used to provide modular expansion of the Distribution
Cable System.
Description Harness Length Product Number List Price
Distribution Cable Extension 30 inches SDCEA30 $80.00
Distribution Cable Terminal Block GO-135PM
The Distribution Cable Terminal Block is a modular attachment primarily used to provide an
alternate means of input to Spectra RMS Molded Case Circuit Breakers with MicroVersaTrip
Plus or MicroVersaTrip PM Trip Units. The Terminal Block plugs into the breaker distribution
cable receptacle allowing the direct connection of breaker signals via screw terminals. This
allows point-to-point wiring of breakers instead of using the Distribution Cable System.
Description Product Number List Price
Distribution Cable Terminal Block SDCTBA11 $110.00
Power Supply Assembly GO-135PM
The Power Supply Assembly is used to provide +24 Vdc Control Power to Spectra RMS
Molded Case Circuit Breakers with MicroVersaTrip Plus or MicroVersaTrip PM trip systems
via the Distribution Cable System. The assembly requires a minimum input voltage of 85 Vac
to operate properly (the maximum voltage rating is 240 Vac). Supplemental +24 Vdc input ter-
minals are provided for backup control power applications. The input must be fused with 1/2
ampere class CC fuses (not included). Not suitable for 400 Hz.
Description Voltage Rating Product Number List Price
The Power Supply Assembly is rated 24 watts 85 - 240 Vac SPSAA $1000.00
(+24 Vdc @ 1.0 ampere) and has the maximum
capacity to power a Distribution Cable System
consisting of 20 breakers and has a maximum
system cable length of 40 feet.
Voltage Conditioner Assembly GO-135PM
The Voltage Conditioner Assembly is used to provide voltage sensing signals to Spectra RMS
Molded Case Circuit Breakers with MicroVersaTrip PM Trip Units via the Distribution Cable
System. The Voltage Conditioner Assembly requires a control power source of +24 Vdc to
operate properly (the Power Supply Assembly or Power Supply Plate can provide this
required input). The unit also requires 120 Vac voltage inputs from the secondary of three 1-
VA high accuracy potential transformers (not included). The primary side of the potential
transformers must be fused with three, 1/2 ampere class CC fuses (not included). A GE
POWER LEADER network (commnet) connection is provided. Not suitable for 400 Hz.
Description Voltage Rating Product Number List Price
Requires 120 Vac voltage inputs from the 120 Vac SVCAA $680.00
secondary of three 1.0 VA high accuracy
potential transformers
Note: the Voltage Conditioner Assembly has the maximum capacity to power a Distribution Cable System consisting of
20 breakers and has a maximum system cable length of 40 feet.
Distribution Cable Extension
Distribution Cable Terminal Block
Power Supply Assembly
Voltage Conditioner Assembly
Required Accessories
Type Accessories
Standard
Ground Fault Option with 3-phase, 4-wire Neutral Current Sensor and Terminal Block
MicroVersaTrip Plus Trip Unit or 1-phase, 3-wire service or Neutral Current Sensor and Junction Box
Control Power Option Power Supply Plate or Voltage Module1or Power Supply Assembly2
Power Supply Plate and Voltage Conditioner Plate or Voltage Module1
Standard or with Protective Relaying or Power Supply Assembly2and Voltage Conditioner Assembly2
MicroVersaTrip PM Trip Unit Junction Box, Cable Harness and Auxiliary Switch
Ground Fault Option with 3-phase, 4-wire Neutral Current Sensor
or 1-phase, 3-wire service
1For installation into GE Spectra Series Switchboards only.
2Requires fuse protection and other components; refer to accessory detail for additional information.
Prices and data subject to change without notice
3-108 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Power Management System Accessories
Spectra RMS Circuit Breakers with MicroVersaTrip Plus and
MicroVersaTrip PM Trip Units
All Devices UL Listed for Factory or Field Installation (UL File No. E-57253)
Voltage Modules GO-135PM
The Voltage Module is used primarily as a Spectra Series Switchboard component to provide
+24 Vdc Control Power to Spectra RMS Molded Case Circuit Breakers with MicroVersaTrip
Plus or MicroVersaTrip PM Trip Units via the Distribution Cable System. The Module also pro-
vides voltage sensing signals to Spectra RMS Molded Case Circuit Breakers with
MicroVersaTrip PM Trip Units on the same Distribution Cable System. The Module contains
both a Power Supply Plate and a Voltage Conditioner as integral components. It also includes
fuse protection for the AC source input terminals (the modules pressure connectors which
mate with the switchboard interior bus bars). A GE POWER LEADER Network (commnet) con-
nection is provided as well as supplemental 24 Vdc input terminals for backup control power
applications. Seven versions are available. Not suitable for 400 Hz.
Voltage Rating and Service Type Comments Product Number List Price
120 Vac Wye system Phase to Neutral potential ADSVMA120Y $2350.00
208 Vac Wye system Phase to Phase potential ADSVMA208Y $2350.00
240 Vac Delta system Phase to Phase potential ADSVMA240D $2350.00
277 Vac Wye system Phase to Neutral potential ADSVMA277Y $2350.00
480 Vac Wye system Phase to Phase potential ADSVMA480Y $2350.00
480 Vac Delta system Phase to Phase potential ADSVMA480D $2350.00
600 Vac Delta system Phase to Phase potential ADSVMA600D $2350.00
Note: The Voltage Module has the maximum capacity to power a Distribution Cable System consisting of 20 breakers
and has a maximum system cable length of 40 feet.
Voltage Module Exterior View Voltage Module Interior View
Publications and Reference: See Section 21
for a list of additional product-related publications
Prices and data subject to change without notice
www.geindustrial.com BuyLog Catalog 3-109
Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
Neutral Current Sensor GO-135S
The neutral current sensor is used in conjunction with breakers that have a MicroVersaTrip
Plus or MicroVersaTrip PM Trip Unit with the optional ground fault function and the breaker is
connected to a grounded neutral service (3-phase, 4-wire or 1-phase, 3-wire). The neutral
current sensor provides an input signal to the breaker trip unit. Breakers connected to a
service without a neutral (3-phase, 3-wire) require no external connection or shorting of the
breaker cable connector for ground fault to function properly.
Breaker Type Sensor Rating (S) Product Number List Price
SG 150 TSRG201 $532.00
SG 400 TSRG204 $532.00
SG 600 TSRG206 $532.00
SK 800 TSKG408 $532.00
SK 1200 TSKG412 $532.00
MicroVersaTrip Rating Plug Removal Tool GO-135S
Product Number List Price
TRTOOL $12.00
MicroVersaTrip Portable Power Pack GO-245A
The hand-held MicroVersaTrip portable battery pack provides an independent power source
for MicroVersaTrip Plus and MicroVersaTrip PM trip units as an alternative to the TVRMS test
set. The power pack is used to power up the trip unit to set or adjust trip set points when the
breaker is on the bench or otherwise not powered up. It connects to the trip unit through the
rating plug test jack. It requires three standard 9 Vdc alkaline batteries (not included).
Description Product Number List Price
Portable Power Pack TVPBP $75.00
MicroVersaTrip Portable Test Set GO-245A
The portable, battery-powered test kit provides for RMS-9, Plus, or PM trip unit self-tests and
functional trip/no trip tests. It also provides defeat of the ground fault function and can be
used in conjunction with high current test equipment. Interface is via a plug on the front of
the trip unit and tests can be conducted with breaker in service. Kit uses six rechargeable
ni-cad or standard alkaline "D" cells supplied by customer. Kit can also be powered by 120
Vac source.
Description Product Number List Price
Portable Test Set2TVRMS2 $3000.00
2May also be used to temporarily defeat ground fault function when using primary injection (high current test set).
Note: This test kit is for use with MicroVersaTrip RMS-9, Plus, or PM Trip Units only. Not for use with MicroVersaTrip
4- or 9-Function Trip Units.
Accessories–Other
Spectra RMS Circuit Breakers with MicroVersaTrip Plus and MicroVersaTrip PM Trip Units
All Devices UL Listed for Factory or Field Installation Except Where Noted
Prices and data subject to change without notice
3-110 BuyLog Catalog www.geindustrial.com Rev. 12/04
Molded Case Circuit Breakers
3
MOLDED CASE
CIRCUIT BREAKERS
NOTES: