SPECIFICATION
240W Single Output Industrial DIN RAIL NDR-240 series
File Name:NDR-240-SPEC 2015-05-04
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE Note.4
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1500ms, 100ms/230VAC 3000ms, 100ms/115VAC at full load
28ms/230VAC 22ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
2.5A/115VAC 1.3A/230VAC
29 ~ 33V
88.5%
56 ~ 65V
90%
20A/115VAC 35A/230VAC
<1mA / 240VAC
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
UL508, TUV EN60950-1 approved
Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
-20 ~ +70 (Refer to "Derating Curve")℃
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH℃
±℃ ℃0.03%/ (0 ~ 50 )
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
230.2K hrs min. MIL-HDBK-217F (25 )℃
63*125.2*113.5mm (W*H*D)
1Kg; 12pcs/13Kg/1.1CUFT
NDR-240-24 NDR-240-48
24V 48V
10A 5A
0 ~ 10A 0 ~ 5A
240W 240W
150mVp-p 150mVp-p
24 ~ 28V 48 ~ 55V
±1.0% ±1.0%
±0.5% ±0.5%
±1.0% ±1.0%
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH℃
ENVIRONMENT
SAFETY &
EMC
(Note 4)
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltage. Please check the derating curve for more details.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
EMC IMMUNITY
EMC EMISSION
105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
POWER FACTOR (Typ.) PF>0.98/115VAC, PF>0.95/230VAC at full load