Technical data
Coil side
Typical input current at UN3.5 mA (at UN = 120 V AC)
3 mA (at UN = 110 V DC)
Typical response time 6 ms
Typical release time 15 ms
Operating voltage display Yellow LED
Protective circuit Bridge rectifier Bridge rectifier
Contact side
Contact type 1 PDT
Contact material AgSnO
Maximum switching voltage
250 V AC/DC (The separating plate PLC-ATP should be installed for
voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in
adjacent modules. Potential bridging is then carried out with FBST 8-PLC...
or ...FBST 500...)
Minimum switching voltage 5 V (at 100 mA)
Maximum inrush current on request
Min. switching current 10 mA (at 12 V)
Limiting continuous current 6 A
Interrupting rating (ohmic load) max. 140 W (at 24 V DC)
20 W
General
Test voltage relay winding/relay contact 4 kV AC (50 Hz, 1 min.)
Operating mode 100% operating factor
Mechanical service life 2 x 107 cycles
Inflammability class according to UL 94 V0
Pollution degree 3
Surge voltage category III
UL, USA Class I, Zone 2, AEx nA nC IIC T6
UL, USA / Canada Class I, Div. 2, Groups A, B, C, D
UL, Canada Class I, Zone 2, Ex nA nC IIC Gc T6 X
Mounting position any
Assembly instructions In rows with zero spacing
Connection data
Connection method Screw connection
Stripping length 8 mm
Conductor cross section stranded min. 0.14 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section solid min. 0.14 mm²