54
PRODUCT CATALOGUE - STEGOCOOLING
FILTER FAN PLUS
FPI/FPO 018 | up to 727 m³/h (291 x 291 mm)
TECHNICAL DATA
Axial fan, ball bearing service life L10 at +40 °C (+104 °F): min. 76,000 h
rotor metal
Connection 3-pole clamp for 2.5 mm², clamping torque 0.8 Nm max.
Casing, hood, flaps plastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out 291 x 291+1 mm
Mounting frame 4 built-in ratchet braces for mounting
(6 notches for wall thickness 1 4 mm).
Additional use of screws possible if needed1.
Filter mat G3 acc. to DIN EN 779, average arrestance Aa 84 %
Filter material synthetic fibre with progressive construction,
temperature resistant to +100 °C, self-extinguishing class F1,
moisture resistant to 100 % RH, reusable
Operating temperature 50 Hz: -25 to +55 °C (-13 to +131 °F)
60 Hz: -25 to +35 °C (-13 to +95 °F)
Storage temperature -40 to +70 °C (-40 to +158 °F)
Operating/Storage humidity max. 75 % RH (non-condensing)
Protection type/Protection class IP54 / I (earthed)
Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
Approvals VDE, UL File No. E234324, EAC
Note other voltages on request
AIRFLOW DIRECTION "IN": FILTER FAN FPI 018
Art. No. Operating voltage Air volume,
free flow
Air volume
with exit filter
Current consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01874.0-30 AC 230 V, 50/60 Hz 433 m³/h 373 m³/h 400/480 mA 95 W 62 db (A) 160 mm 3.1 kg G3
01874.9-30 AC 115 V, 50/60 Hz 394 m³/h 339 m³/h 660/800 mA 90 W 61 db (A) 160 mm 3.1 kg G3
AIRFLOW DIRECTION "IN": EXIT FILTER FPI 118
Art. No. Depth in enclosure Weight (approx.) Air outlet
11874.0-00 50 mm 1.0 kg air-flap outlet technology
1 Drilling marks for screw mounting are indicated on mounting frame.
Filter fans are used to provide an optimum climate in enclosures and cabinets with electrical/electronic components.
The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure
thus expelling heated internal air. The resulting airflow prevents formation of localised hot pockets in installations
and protects electronic components from overheating.
The Filter Fan Plus series uses a new air-flap outlet technology for the air outlet and thus reaches a high degree
of airflow. A ratchet mechanism is used for mounting and provides high stability and tightness. Depending on the
application there are two systems that are available – the FPI or FPO system. The FPI system is a standard installation
with a filter fan in the lower part of the enclosure which ensures that fresh air is fed into the enclosure (airflow
direction "In"). This system consists of a filter fan and exit filter. Whereas in the FPO system, the filter fan is located
in the upper area of the enclosure to avoid heat buildups (airflow direction "Out"). The FPO system is composed of
an intake filter and exit filter fan. The Filter Fan Plus series has been designed for indoor use.
> New air-flap outlet technology for
high airflow
> Easy mounting
> Protection type test/Environmental
rating by independent testing institutes
(VDE and UL)
> Two systems for optimal airflow
(FPI/FPO)
> Standard enclosure cut-out sizes
(5 sizes)
> One filter mat
warmcold
Exit Filter FPI 118
Filter Fan FPI 018
Air-flaps
Filter mat
SYSTEM FPI
19.03.2019 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application. www.stego.de | www.stego.co.uk | www.stegonorden.se
54TECHNICAL DATASHEET
5555
FPI 118FPI 018 FPO 118FPO 018
322
291
160 29
291
2950
322
291
160 29
291
2950
322
291
160 29
291
29
25
322
291
160 29
291
29
25
291
+1
0
291
+1
0
STEGO - PRODUCT CATALOGUE COOLING
FILTER MAT FM 086
Filter class 283 x 283 mm Average arrestance Aa1 packing unit
G3 acc. to DIN EN 779 Art. No. 08637.0-00 84 % 5 pieces
TECHNICAL DRAWINGS
AIRFLOW DIRECTION "OUT": INTAKE FILTER FPO 118
Art. No. Depth in enclosure Weight (approx.) Filter mat
11884.0-30 25 mm 0.8 kg G3 acc. to DIN EN 779, average arrestance Aa 84 %
AIRFLOW DIRECTION "OUT": FILTER FAN FPO 018
Art. No. Operating voltage Air volume,
free flow
Air volume
with intake filter
Current consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01884.0-00 AC 230 V, 50/60 Hz 727 m³/h 413 m³/h 400/480 mA 95 W 63 db (A) 160 mm 3.2 kg air-flaps
01884.9-00 AC 115 V, 50/60 Hz 703 m³/h 391 m³/h 660/800 mA 90 W 62 db (A) 160 mm 3.2 kg air-flaps
warmcold
Filter Fan FPO 018
Intake Filter FPO 118
Air-flaps
Filter mat
SYSTEM FPO
ENCLOSURE CUT-OUT ENCLOSURE CUT-OUT
19.03.2019 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application. www.stego.de | www.stego.co.uk | www.stegonorden.se