General Purpose IEC Fuses
General Purpose IEC Fuses
GPEU56
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 2 and 3
from 125 to 630 A
• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR OR TRIP-INDICATOR
• COMPLYING WITH IEC 269.1 AND 2.1, NF EN 60269.1 & 2 NF C 63210 - 63211 AND DIN 43620
• DIMENSIONS:
L
N
DG
B
F
D1
A
K
HC
J
D2
M
e
L
N
DG
B
D1
A
HC
J
M
e
Accessories: Neutral link BS2 Reference Number J097712 - BS3 Reference Number K097713
Pull-out handle - PMP Reference Number P215592
With trip-indicator With blown fuse indicator
Size A B C D D1 D2* F* G H J K L M N e Wgt.
2 60 64 72 74 50 50 14 3 28 19 14,5 150 10 14,5 6 590g
3 75 61 88 75 70 64 14 2,5 36 23 14,5 150 10 18 6 850g
* For fuses with trip-indicator
2
3
500
500
aM 2 /125
aM 2 /160
aM 2 /200
aM 2 /250
aM 2 /315
aM 2 /400
aM 2 /500
aM 3 /315
aM 3 /400
aM 3 /500
aM 3 /630
P095210
Q095211
R095212
Q095142
R095143
S095144
W088523
J095182
D095154
E095155
F095156
Z095196
S095213
F095340
H095342
J095343
K095344
L095345
Q095073
W095354
X095355
Y095356
Watts
loss
(W) Designation Ref. Number
Catalog Number
8,5
11,5
13,5
17
24
28
34
24
28
34
41
125
160
200
250
315
400
500
315
400
500
630
Size
Voltage
rating
(VAC)
Current
rating
IN(A)
aM 2 /125 P
aM 2 /160 P
aM 2 /200 P
aM 2 /250 P
aM 2 /315 P
aM 2 /400 P
aM 2 /500 P
aM 3 /315 P
aM 3 /400 P
aM 3 /500 P
aM 3 /630 P
Designation Ref. Number
With blown fuse indicator With trip-indicator
Catalog Number
NH2AM50V125-3
NH2AM50V160-3
NH2AM50V200-3
NH2AM50V250-3
NH2AM50V315-3
NH2AM50V400-3
NH2AM50V500-3
NH3AM50V315-3
NH3AM50V400-3
NH3AM50V500-3
NH3AM50V630-3
NH2AM50V125-4
NH2AM50V160-4
NH2AM50V200-4
NH2AM50V250-4
NH2AM50V315-4
NH2AM50V400-4
NH2AM50V500-4
NH3AM50V315-4
NH3AM50V400-4
NH3AM50V500-4
NH3AM50V630-4
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 2 and 3
GPEU57
General Purpose IEC Fuses
General Purpose IEC Fuses
from 125 to 630 A
Rating (A)
103
104
105
106
107
108
125 160 200 250 315 400 500 630
I
2
t (A
2
S)
b: total clearing I2t@ 500 V
a: pre-arcing I2t
1 10 100 Ip (kA)
10
100
Ic (kA)
Ic = Peak let-through current
Ip = Available fault current
630
500
400
315
250
200
160
125
10 100 1 000 10 000 Ip (A)
10-1
10-2
1
10
102
103
t (s)
t (s) = Pre-arcing duration
160 250 315 500
125 200 400 630
Ip (A) = R.M.S.
AVAILABLE
FAULT CURRENT
Breaking
capacity
100 kA
Total Clearing I2t
Time VS. Current Characteristics
Current Limitation Cur ves