IB IL AI 2/SF Order No.: 2726285
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726285
PHOENIX CONTACT Inc., USA Page 2 / 6
http://www.phoenixcon.com Feb 7, 2011
- Measurement value acquisition with a resolution of 16 bits
It goes without saying that you also have advantages in handling with the analog Inline input terminals, such as multi-
wire connection or the automatic contact with the grounding conductor when the terminal is snapped onto the DIN rail.
The Inline terminals can be labeled using hinged labeling fields. The fields have insert cards that can be labeled
individually to suit the application. Additionally, there is the proven ZBFM-6... Zack strip for labeling the terminal points.
Technical data
General data
Width 12.2 mm
Height 119.8 mm
Depth 71.5 mm
Weight 47 g
Mounting type DIN rail
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Test section 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
7.5 V supply (bus logic), 24 V supply UANA / I/O 500 V AC 50 Hz 1
min
7.5 V supply (bus logic), 24 V supply UANA/functional earth ground
500 V AC 50 Hz 1 min
I/O / functional earth ground 500 V AC 50 Hz 1 min
Interface
Name Inline local bus
Type of connection Inline data jumper
Transmission speed 500 kbps
500 kBit/s
Transmission physics Copper