Technical Specifications
CONTROL
Control type Single-setpoint control
On-Off control
Control algorithm
Hysteresis Adjustable between 0.1 ... 20.0°C.
OUTPUT
COMPRESSOR For Relay: 250V AC, 8A ( ), NO+NC;
1/2 HP 240V AC ( )
EDT1411-NTC-XX ; for resistive load
for inductive load
Cos = 0.4F
For Mechanical 30.000.000; Electrical 100.000operation.EDT1411-NTC-XX ;
Life expectancy for relay
ENVIRONMENTAL CONDITIONS
Height Max. 2000m
80 , up to 40% 31°C decreasing linearly 50% at °C
Ambient/storage temperature
Max. relative humidity
0 ... +50°C/-25 ... 70°C (with no icing)
Rated pollution degree According to EN 60529 Front panel : IP60
Rear panel : IP20
Do not use the device in locations subject to corrosive and flammable gasses.
HOUSING
Housing type Suitable for panel mounting.
Dimensions W77xH34xD70mm
Weight Approx. 250g ( )after packing the device and a probe
Enclosure material Self extinguishing plastics
CAL EDT1411 THERMOSTAT
Thank you for choosing the CAL EDT1411 thermostat.
* 34 x 77mm sized.
* On-Off control.
* CE marked according to European Norms.
NTC NTC
* Single contact output for cooling control.
* probe input for cold room temperature.
* Offset value can be entered for probe.
* Compressor protection parameters can be entered.
* In the case of probe failure, output state can be
selected on or off or periodical running.
* Upper and lower limits of the setpoint can be adjusted.
* Defrosting duration and interval can be adjusted.
* 16 different warning tones.
* Upper and lower limits of the alarm value can be adjusted depending on the setpoint value.
Connection Diagram
CAL EDT1411 is intended for installation in control panels. Make sure that the device is used
only for intended purpose. The electrical connections must be carried out by qualified staff
and must be according to the relevant locally applicable regulations. During an installation, all of the
cables that are connected to the device must be free of electrical power. The device must be
protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation
temperature is not exceeded. The cables should not be close to the power cables or components.
1/3
Panel cut-out
Dimensions
Note :1) Panel thickness
should be maximum
7 mm.
2) If there is no 60mm
free space at the back
side of the device, it
would be difficult to
remove it from the
anelp
EDT1411-E-06
Holding screw
0.4-0.5Nm.
Equipment is protected throughout
by DOUBLE INSULATION
70mm 8mm
71mm
29mm
mounting
clamp
mounting
clamp
Depth
Rubber
gasket
Panel
For removing mounting clamps:
Push out the mounting clamp
in direction as shown
in the figure below. Then, pull
out the clamp in direction
1
2.
2
1
While cleaning the device, solvents (thinner, benzine, acid etc.) or must not be used.corrosive materials
7
8
SUPPLY:
NOTE:
184-253V AC
50/60Hz 3VA
Line
Neutral
230V AC
Supply
Switch
Note:
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
34mm
85mm
°C
SET
EDT1411
CAL
°F
°C
SET
EDT1411
CAL
°F
COMPRESSOR
1/2HP 240V AC Cos = 0.4
8 A 250V AC Cos = 1
F
F
SN: XXXXXXXXX
123456789
10 11 12
EDT1411-NTC-230VAC
DIGITAL DEFROST THERMOSTAT
NTC
SENSOR
RW
230V AC +10% -20%
50/60Hz 3VA
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
For Relay: 240V AC, 16A ( ), NO;
1
EDT1411-NTC-XXP; for resistive load
HP 230V AC (for inductive load)
Cos = 0.5F
For Mechanical 30.000.000; Electrical 30.000operation.EDT1411-NTC-XXP;
SN: XXXXXXXXX
123456789
10 11 12
EDT1411-NTC-24
DIGITAL DEFROST THERMOSTAT
NTC
SENSOR
R
W
24V AC/DC 10%
50/60Hz 3VA
±
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
SN: XXXXXXXXX
123456789
10 11 12
EDT1411-NTC-230VAC
DIGITAL DEFROST THERMOSTAT
NTC
SENSOR
R
W
230V AC +10% -20%
50/60Hz 3VA
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
SN: XXXXXXXXX
123456789
10 11 12
EDT1411-NTC-230VAC-P
DIGITAL DEFROST THERMOSTAT
NTC
SENSOR
R
W
230V AC +10% -20%
50/60Hz 3VA
COMPRESSOR
250V AC 16A
RESISTIVE LOAD
Order Code : EDT1411-NTC--
12
1 - Supply Voltage
230VAC...230V AC
24............24V AC/DC
12............12V AC/DC
2 - Output
P..........Relay-16A
None...Relay-8A
Please read this document carefully before using this product. The guarantee will be
invalidated if the device is damaged by not following instructions detailed in the
manual. CAL Controls shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.
www.cal-controls.com www.cal-controls.com www.cal-controls.com
www.cal-controls.com
CAL CONTROLS LTD
Tel : +44 (0) 1462 436161 Fax : +44 (0) 1462 451801
e-mail: sales@cal-controls.co.uk Web : www.cal-controls.com
Bury Mead Road, Hitchin, Herts, SG5 1RT, UK.
Supply voltage 230V AC +%10 -%20, 50/60Hz or 24V AC/DC ±%10, 50/60Hz or 12V AC/DC ±%10, 50/60Hz.
Power consumption Max. 3VA
2.5mm² screw-terminal connections.
( %1-15sec) for hour unit, ( %1-1sec) for minute unit±±
4 digits, 12mm, 7 parts yellow LED
Wiring
Scale
Sensitivity
/Accuracy
Time Accuracy
Indicator
EMC
Safety requirements
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
The device is designed to operate in controlled electromagnetic environment)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
ELECTRICAL CHARACTERISTICS
-50.0 ... +110.0°C (-58.0 ... +230.0°F)
0.1°C / °C
±1
A.lol
A.uPl
A.Set
A.dpo
The lower limit
of the setpoint.
Delay time for the compressor
after power is on.
Defrosting duration. Limit for
lower alarm level.
Limit for
upper alarm level.
Alarm configuration
Time delay to display
alarm message after
power is on.
The upper limit
of the setpoint.
Delay time required for
the compressor to restart
following a stop.
Continuous-on mode duration
for the compressor.
Switch hysteresis
for compressor.
on time for the compressor
output in the case of
probe failure.
The offset value
for the refrigeration.
Display resolution
oFF time for the compressor
output in the case of
probe failure.
D.dur
D.int
While holding key COMPRESSOR setpoint value appears and by using and keys
the value can be adjusted.
C.pon
C.ppn
C.Con
C.Fos
C.ppF
Interval between
defrost cycles.
Programming Mode
Run Mode
Process
Value -30.0 -29.9 -30.0
R.lol
R.uPl
R.Hys
R.off
DrES
1000
EDT1411-E-06
SET
SET
If both keys are pressed and held for 3 seconds,
programming mode is entered.
-22.0
SET
Temperature unit
Unit
Display configuration
during defrost
D.dsp
D.drE Delay time for display
real temperature after
defrost is over.
Defrosting after
power is on.
D.Pon
D.dPo
Delay time for defrosting
after power is on.
A.dFl Time delay to display
alarm message after
alarm is on.
A.HYS Switch hysteresis
for alarm.
Security parameter
for menu of compressor control
Security parameter
for menu of defrost control
Security parameter
for menu of alarm control
Security parameter
for refrigeration setpoint value
A. re-
A. al-
A. de-
A. Cp-
A.rE.S.
Security parameter
for refrigeration menu
If both keys are pressed,
run mode is entered.
RE CP DE Al SE
Used for adjusting the value of the setpoint in the run mode and for adjusting the selected parameter in the programming mode. While holding key, setpoint value of the selected parameter appears and by
using and keys the value can be adjusted.
When held down for 3 second in the run mode, manual defrost starts. After the specified time with parameter manual defrost finishes. When held down for 3 second manual defrost finishes before the
specified time ends. Used for selecting menu and increasing setpoint value of the parameters in the programming mode and for increasing the setpoint value in the run mode When held down for a few
seconds, the change rate accelerates.
D.dur
.
When held down for 3 second in the run mode continuous mode starts. After the specified time with parameter this mode finishes. When held down for 3 second continuous mode finishes before the
specified time ends. Used for selecting parameters and decreasing the setp in the programming mode and for decreasing the setpoint value in the run mode When held down for a few seconds, the
change rate accelerates.
C.Con
oint value .
DEFROST
LED
COMPRESSOR
LED
FAHRENHEIT
LED Displayed process value in the run mode, parameter name or value in programming mode.
2/3
SET
Means, thermostat probe is short circuit or temperature value is
higher than the scale.
Error Messages
Pfa
Psc
Means, thermostat probe is broken or temperature value is
lower than the scale.
EDT1411
°C
SET
CAL
°F
S.Cod
Access code for security menu.
This parameter should be 321 .
Type of buzzer
sound.
SonD
23.5 If process value flashes and warning tone sounds, means,
measured value exceeds the adjusted alarm limit.
*Note: To stop warning tone, press any key.
Menu of Refrigeration control parameters
Menu of Defrost control parameters
Menu of Alarm control parameters
R.HYS
R.LoL
R.uPL
R.oFF
C.pon
A. rE-
C.FoS
A. CP-
C.PPn
A. AL-
C.PPF
A.rE.S.
D.dur
D.int
D.dSP
D.drE
D.Pon
D.dPo
A.LoL
A.uPL
A.dFL
A.HYS
A.SEt
Switch hysteresis for compressor.
Alarm configuration ( = Absolute alarm. Alarm values are and .
= Relative alarm. Alarm values are - and + .)
A.Abs A.LoL A.uPL
A.rEF SET A.LoL SET A.uPL
The lower limit of the setpoint.
The upper limit of the setpoint.
The offset value for the refrigeration.
Delay time for the compressor after power is on.
Security parameter for refrigeration menu (NonE P.yes P.no= menu is invisible, = Parameters of menu are changeable, = Parameters of menu are only visible.)
Security parameter for refrigeration setpoint value (= Setpoint value is invisible., = Setpoint value is only visible.)P.yes P.no
Security parameter for menu of compressor control (NonE P.yes P.no= menu is invisible, = Parameters of menu are changeable, = Parameters of menu are only visible.)
Security parameter for menu of defrost control (NonE P.yes P.no= menu is invisible, = Parameters of menu are changeable, = Parameters of menu are only visible.)
Security parameter for menu of alarm control (NonE P.yes P.no= menu is invisible, = Parameters of menu are changeable, = Parameters of menu are only visible.)
Delay time required for the compressor to restart following a stop.
on time for the compressor output in the case of probe failure.
oFF time for the compressor output in the case of probe failure.
Defrosting duration.(If =0, then defrost is disable.)d.dur
Interval between defrost cycles.
Display configuration during defrost ( = Real temperature is displayed during defrost.
= message is displayed during defrost.)
rEAL
dEF dEF
Defrosting after power is on.( =Defrosting begins when power is on, =Defrosting doesn’t begin when power is on.)yn
Delay time for defrosting after power is on.
Delay time for display real temperature after defrost is over.
Limit for lower alarm level.
Limit for upper alarm level.
Switch hysteresis for alarm.
Time delay to display alarm message after alarm is on.
-50.0 °C -50.0R.uPL
-20.0 20.0 °C 0.0
0.1 20.0 °C 0.1
-50.0 °C -50.0A.uPL
110.0 °C 110.0A.LoL
0 255 min. 0
0 255 min. 1
1 120 h. 1
REAL DEF
Y
DEF
N
N
0 255 min. 1
015 2°C
A.AbS A.rEF A.AbS
MÝN MAX UNIT DEF.SET
EDT1411-E-06
A.dPo Time delay to display alarm message after power is on.
Unit
Temperature unit
DrES
Display resolution ( = no decimal point, = with decimal point.)ny
0 23.5 hr. 0.3
0 30 min. 1
0 255 min. 1
°C °F °C
YN
N
R.LoL 110.0 °C 110.0
0 255 min. 1
C.Con
A. DE-
Continuous-on mode duration for the compressor.
0 255 min. 0
0 255 min. 1
0.0 24.0 h. 0.1
Menu of Compressor control parameters
Menu of Parameter security
EDT1411 OUTPUT AND PARAMETER TABLE
CP
Al
DE
SE
RE
3/3
Defrost
LED
Compressor
LED
Power
D.int
(if = ,
then
timer runs)
D.dPo
d.Pon y
d.dPo
D.dur
C.Pon
Compressor
Output
C.Con
Continuous mode
Defrost mode
NOTE : Variables for lower and upper alarm level are determined according to parameter. If = ,then = & = .
If = , then = SET- & = SET+ .
A.SEt A.SEt A.AbS A.LoL A.LoL A.uPL A.uPL
A.SEt A.LoL ALoL A.uPL A.uPLA.rEF
A.uPl
SET
A.uPl A.HYS-
SET+ r.HYS
A.LoL
A.LoL A.HYS+
A.dPo
A.dFL
Alarm
status
AHi enable AHi abledis Alo enable Alo abledis
Sond
Type of buzzer sound ( 16 different warning tones can be selectable. If =0, then warning tone is disable.)Sond
016 0