06/30/2015 229748 - HPL-ED2015 V13.0 EN 1 / 3
Palm�switch,�1N/O+1N/C,�emergency�switching�off,�surface�mounting
Part�no. FAK-R/V/KC11/IY
Article�no. 229748
Catalog�No. FAK-R-V-KC11-IY
Delivery�programme
Product range Foot and palm switches
Basic function Basic devices
Single unit/Complete unit Complete unit
Function maintained
Description Pull to release
Emergency stop pushbutton tamper-proof to ISO13850/EN418
Contacts
N/O = Normally open 1 N/O
N/C = Normally closed 1 NC
Notes = safety function, by positive opening to IEC/EN 60947-5-1
Enclosure�color
Colour Enclosure base RAL 9005, black
Operator only RAL 1004, yellow
yellow
Contact sequence
Colour
Button Red
Gehäuseoberteil Yellow
Gehäuseunterteil Black
06/30/2015 229748 - HPL-ED2015 V13.0 EN 2 / 3
Approval
Connection to SmartWire-DT no
Technical�data
General
Lifespan, mechanical Operations x 106> 0.1
Operating frequency Operations/h 600
Actuating force N 40 - 60
Degree of protection, IEC/EN 60529 IP67, IP69K
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature °C
Open °C -25 - +40
Mounting position As required
Mechanical shock resistance g > 15
Shock duration 11 ms
Sinusoidal
according to IEC 60068-2-27
Design�verification�as�per�IEC/EN�61439
Technical data for design verification
Rated operational current for specified heat dissipation InA 6
Heat dissipation per pole, current-dependent Pvid W 0.11
Equipment heat dissipation, current-dependent Pvid W 0
Static heat dissipation, non-current-dependent Pvs W 0
Heat dissipation capacity Pdiss W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 40
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Please enquire
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
06/30/2015 Eaton Industries GmbH
http://www.eaton.eu
© 06/2015 by Eaton Industries GmbH
229748 - HPL-ED2015 V13.0 EN
3 / 3
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical�data�ETIM�6.0
Low-voltage industrial components (EG000017) / Foot-/palm switch complete (EC000231)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Command and alarm device / Foot, palm switch (ecl@ss8.1-27-37-12-17 [AKF035011])
Unlocking method Pull release
Colour cap Red
Number of contacts as normally open contact 1
Number of contacts as normally closed contact 1
Switching function latching Yes
Spring-return No
Hole diameter mm 0
Degree of protection (IP) IP67
Approvals
Product Standards IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94-91; CE marking
UL File No. E29184
UL Category Control No. NKCR
CSA File No. 012528
CSA Class No. 3211-03
North America Certification UL listed, CSA certified
Degree of Protection UL/CSA Type 3R, 4X, 12, 13
Dimensions
3 x M20 (PG 13.5) on the side
1 x M16 in the base
Additional�product�information�(links)
IL04716006Z�(AWA1160-1696)�Indicator�light
IL04716006Z (AWA1160-1696) Indicator light ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL04716006Z2011_02.pdf
IL04716017Z�(AWA1160-1467)�Foot�and�palm�switches
IL04716017Z (AWA1160-1467) Foot and palm
switches
ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL04716017Z2011_02.pdf