___________________ Preface 1 ___________________ General technical data SIMATIC S7-300 S7-300 Module data Manual 2 ___________________ Power supply modules 3 ___________________ Digital modules Principles of analog value 4 ___________________ processing 5 ___________________ Principles of analog modules 6 ___________________ Analog modules 7 ___________________ Other signal modules 8 ___________________ Interface modules Parameter sets of signal A ___________________ modules Diagnostics data of signal B ___________________ modules C ___________________ Dimensional drawings Spare parts and accessories D ___________________ for S7-300 modules Directive on handling Electrostatic-Sensitive Devices (ESD) E ___________ F ___________________ Service & support G ___________________ Safety-relevant symbols 06/2017 A5E00105505-AJ H ___________________ List of abbreviations Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by (R) are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Division Digital Factory Postfach 48 48 90026 NURNBERG GERMANY A5E00105505-AJ 07/2017 Subject to change Copyright (c) Siemens AG 2001 - 2017. All rights reserved Preface Purpose of the manual The information contained in this manual can be used as a reference to operating, to functions, and to the technical data of the signal modules, power supply modules and interface modules of the S7-300. Refer to the relevant S7-300 or ET 200M manuals to find out how to assemble and wire the modules.for system installation. Basic knowledge required This manual presumes general knowledge in the field of automation engineering. Range of validity of this manual The manual describes the components based on the data valid at the time of its release. SIEMENS reserves the right to include product information for each new module of a later version. Changes compared to the previous version Changes / enhancements compared to the previous version described in this manual: Comments on the previous version of this manual are included in the current edition. Position in the overall documentation structure The following documentation is part of the S7-300 documentation package. You can find this on the Internet (http://support.automation.siemens.com/WW/view/en/10805159/133300) and the corresponding entry ID. Name of the manual Description Manual Control and display elements, communication, memory concept, cycle and reaction times, technical data CPU 31xC and CPU 31x, technical data Entry ID: 12996906 Operating Instructions S7-300, CPU 31xC and CPU 31x: Installation Entry ID: 13008499 Project design, installation, wiring, addressing, commissioning, maintenance and test functions, diagnostics and troubleshooting. System Manual Basic description of PROFINET: PROFINET system description Network components, data exchange and communication, PROFINET IO, Component-based Automation, application example of PROFINET IO and Component-based Automation. Entry ID: 19292127 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 3 Preface Name of the manual Description Programming manual Guideline for migration from PROFIBUS DP to PROFINET IO. Migration from PROFIBUS DP to PROFINET IO Entry ID: 19289930 Manual * CPU 31xC: Technological functions Entry ID: 12429336 * CD containing examples YOU ARE CURRENTLY READING the Manual S7-300 Automation System: Module Data Description of the technological functions: positioning, counting, point-to-point coupling, loop control. The CD contains examples of the technological functions. Description of the functions and technical data of signal/ power supply/ interface modules. Entry ID: 8859629 Instructions List * CPU 31xC, CPU 31x, IM151-7 CPU, IM154-8 CPU, BM 147-1 CPU, BM147-2 CPU List of the CPU's instruction set and corresponding execution times. List of executable blocks (OBs, SFCs, SFBs) and their execution times. Entry ID: 13206730 * CPU 312, CPU 314, CPU 315-2 DP CPU 315-2 PN/DP, CPU 317-2 PN/DP, CPU 319-3 PN/DP as of V3.0 Entry ID: 31977679 Getting Started Available anthology of Getting Started manuals: * S7-300 Getting Started * PROFINET Getting Started Collection Using concrete examples, the Getting Started documentation provides step-by-step instructions focused on commissioning a fully functional application. Entry ID: 15390497 Entry ID: 19290251 S7-300 Module data 4 Manual, 06/2017, A5E00105505-AJ Preface Other manuals on S7-300 and ET 200M Name of the manual Description Reference Manual Control and display elements, communication, memory concept, cycle and reaction times, technical data * CPU Data: CPU 312 IFM - 318-2 DP * Entry ID: 8860591 Software Installation Manual S7-300 Automation System: Installation: CPU 312 IFM - 318-2 DP Project design, installation, wiring, addressing, commissioning, maintenance and test functions, diagnostics and troubleshooting. Entry ID: 15390415 Configuration manual ET 200M signal modules for process automation Entry ID: 7215812 Manual Distributed I/O Device ET 200M Description of integration in process automation, parameter configuration using SIMATIC PDM, digital input modules, digital output modules. Description of configuration and commissioning of HART analog modules. HART analog modules Entry ID: 22063748 Manual Description of configuration, assembly and wiring. Distributed I/O Device ET 200M Entry ID: 1142798 Manual SM 335 - High-speed analog mixed module for SIMATIC S7-300 Entry ID: 1398483 Description of how to use the SM 335 module in a SIMATIC S7-300. Overview of operations, descriptions of functions, and technical data relating to the SM 335. Sign posts The manual contains various features supporting quick access to specific information: At the beginning of the manual, you will find a complete table of contents. Key terms are explained in the glossary. You can use the index to find the key parts of the manual. Approvals See section Standards and approvals (Page 14). CE approval See section Standards and approvals (Page 14). RCM (C-Tick) Declaration of conformity for Australia/New Zealand See section Standards and approvals (Page 14). S7-300 Module data Manual, 06/2017, A5E00105505-AJ 5 Preface Standards See section Standards and approvals (Page 14). Recycling and disposal Since the S7-300 components only contain low levels of harmful substances, they are suitable for recycling. For ecologically compatible recycling and disposal of your old device, contact a certificated disposal service for electronic scrap. Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial security concept. Siemens' products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks. Systems, machines and components should only be connected to the enterprise network or the internet if and to the extent necessary and with appropriate security measures (e.g. use of firewalls and network segmentation) in place. Additionally, Siemens' guidance on appropriate security measures should be taken into account. For more information about industrial security, please visit (http://www.siemens.com/industrialsecurity). Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends to apply product updates as soon as available and to always use the latest product versions. Use of product versions that are no longer supported, and failure to apply latest updates may increase customer's exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under (http://www.siemens.com/industrialsecurity). S7-300 Module data 6 Manual, 06/2017, A5E00105505-AJ Table of contents Preface ................................................................................................................................................... 3 1 2 3 General technical data .......................................................................................................................... 14 1.1 Standards and approvals ........................................................................................................14 1.2 Electromagnetic compatibility .................................................................................................19 1.3 Shipping and storage conditions for modules and backup batteries ......................................21 1.4 Mechanical and climatic environmental conditions for S7-300 operation...............................23 1.5 Specification of dielectric tests, protection class, degree of protection, and rated voltage of S7-300 ....................................................................................................................25 1.6 Rated voltages of S7-300 .......................................................................................................25 1.7 SIPLUS S7-300 Modules ........................................................................................................26 1.8 Environmental conditions for the operation of SIPLUS S7-300 modules ...............................30 Power supply modules .......................................................................................................................... 32 2.1 Power supply module PS 307; 2 A; (6ES7307-1BA01-0AA0) ................................................33 2.2 Power supply module PS 307; 5 A; (6ES7307-1EA01-0AA0) ................................................36 2.3 Power supply module PS 307; 10 A; (6ES7307-1KA02-0AA0) ..............................................39 2.4 Power supply module PS 305; 2 A; (6AG1305-1BA80-2AA0) ...............................................42 2.5 Power supply module PS 307; 5 A; (6AG1307-1EA80-2AA0) ...............................................45 Digital modules ..................................................................................................................................... 48 3.1 3.1.1 3.1.2 3.1.3 3.1.4 Module overview .....................................................................................................................49 Digital input modules:..............................................................................................................49 Digital output modules ............................................................................................................52 Relay output modules .............................................................................................................55 Digital IO modules ...................................................................................................................56 3.2 Steps in selecting and commissioning the digital module ......................................................57 3.3 Programming digital modules .................................................................................................58 3.4 Diagnostics of digital modules ................................................................................................59 3.5 How to protect digital modules from inductive overvoltage ....................................................61 3.6 Digital input module SM 321; DI 64 x DC 24 V, sinking/sourcing; (6ES7321-1BP000AA0) ......................................................................................................................................63 3.7 Digital input module SM 321; DI 32 x DC 24 V; (6ES7321-1BL00-0AA0)..............................70 3.8 Digital output module SM 321; DI 32 x AC 120 V; (6ES7321-1EL00-0AA0)..........................73 3.9 Digital input module SM 321; DI 16 x DC 24 V; (6ES7321-1BH02-0AA0) .............................76 3.10 Digital input module SM 321; DI 16 x DC 24 V High Speed; (6ES7321-1BH10-0AA0) .........78 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 7 Table of contents 3.11 3.11.1 3.11.2 3.11.3 3.11.4 3.11.5 3.12 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH01-0AB0) ........................................................................................................ 80 Isochronous mode ................................................................................................................. 85 SM 321; DI 16 x DC 24 V - Parameters ................................................................................. 86 SM 321; DI 16 x DC 24 V - Diagnostics ................................................................................. 88 SM 321; DI 16 x DC 24 V - Behavior ..................................................................................... 90 SM 321; DI 16 x DC 24 V - Interrupts .................................................................................... 91 3.12.1 3.12.2 3.12.3 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES7321-7EH00-0AB0)........................................................................................ 94 Parameters of SM 321; DI 16 x DC 24/125 V ........................................................................ 98 Diagnostics of SM 321; DI 16 x DC 24/125 V ........................................................................ 99 Interrupts of SM 321; DI 16 x DC 24/125 V ......................................................................... 100 3.13 Digital input module SM 321; DI 16 x DC 24 V; source input; (6ES7321-1BH50-0AA0) .... 103 3.14 Digital input module SM 321; DI 16 x UC 24/48 V; (6ES7321-1CH00-0AA0) ..................... 105 3.15 Digital input module SM 321; DI 16 x DC 48-125 V; (6ES7321-1CH20-0AA0) ................... 108 3.16 Digital input module SM 321; DI 16 x AC 120/230 V; (6ES7321-1FH00-0AA0) ................. 111 3.17 Digital input module SM 321; DI 8 x AC 120/230 V; (6ES7321-1FF01-0AA0) .................... 114 3.18 Digital input module SM 321; DI 8 x AC 120/230 V ISOL; (6ES7321-1FF10-0AA0)........... 117 3.19 Digital output module SM 322; DO 64 x DC 24 V/0.3 A sourcing; (6ES7322-1BP00-0AA0) ...................................................................................................... 120 3.20 Digital output module SM 322; DO 64 x DC 24 V/0.3 A Sinking (6ES7322-1BP50-0AA0) ...................................................................................................... 128 3.21 Digital output module SM 322; DO 32 x DC 24 V/ 0.5 A; (6ES7322-1BL00-0AA0) ............ 135 3.22 Digital output module SM 322; DO 32 x AC 120/230 V/1 A; (6ES7322-1FL00-0AA0)........ 139 3.23 Digital output module SM 322; DO 16 x DC 24 V/ 0.5 A; (6ES7322-1BH01-0AA0)............ 143 3.24 3.24.1 3.24.2 3.24.3 3.24.4 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0)............. 147 Parameters of digital output modules .................................................................................. 152 Diagnosis of digital output modules ..................................................................................... 153 Firmware update via HW Config .......................................................................................... 154 I&M identification data .......................................................................................................... 155 3.25 Digital output module SM 322; DO 16 x DC 24 V/0.5 A High Speed; (6ES7322-1BH10-0AA0) ...................................................................................................... 157 3.26 3.26.1 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0) ................. 161 Parameters of digital output module SM 322 DO 16 x UC24/48 V ...................................... 165 3.27 Digital output module SM 322; DO 16 x AC 120/230 V/1 A; (6ES7322-1FH00-0AA0) ....... 167 3.28 Digital output module SM 322; DO 8 x DC 24 V/2 A; (6ES7322-1BF01-0AA0) .................. 170 3.29 3.29.1 3.29.2 3.29.3 3.29.4 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) ...................................................................................................... 174 SM 322; DO 8 x DC 24 V/0.5 A - Parameters ..................................................................... 178 SM 322; DO 8 x DC 24 V/0.5 A - Diagnostics ..................................................................... 179 SM 322; DO 8 x DC 24 V/0.5 A - Behavior .......................................................................... 181 SM 322; DO 8 x DC 24 V/0.5 A - Interrupts ......................................................................... 182 3.30 Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0)........ 183 S7-300 Module data 8 Manual, 06/2017, A5E00105505-AJ Table of contents 3.31 Digital output module SM 322;DO 8 x AC 120/230 V/2 A; (6ES7322-1FF01-0AA0) ...........187 3.32 3.32.1 3.32.2 3.32.3 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF000AB0) ....................................................................................................................................191 Parameters of SM 322; DO 8 x AC 120/230 V/2 A ISOL .....................................................195 SM 322; DO 8 x AC 120/230 V/2 A ISOL - Diagnostics .......................................................196 SM 322; DO 8 x AC 120/230 V/2 A ISOL - Interrupts ...........................................................196 3.33 Relay output module SM 322; DO 16 x Rel. AC 120/230 V; (6ES7322-1HH01-0AA0) .......198 3.34 Relay output module SM 322; DO 8 x Rel. AC 230 V; (6ES7322-1HF01-0AA0) .................203 3.35 3.35.1 3.35.2 3.35.3 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0) .............208 Parameters of SM 322; DO 8 x Rel. AC 230V/5A ................................................................214 SM 322; DO 8 x Rel. AC 230V/5A - Diagnostics ..................................................................214 SM 322; DO 8 x Rel. AC 230V/5A - Interrupts .....................................................................215 3.36 Relay output module SM 322; DO 8 x Rel. AC 230 V/5 A; (6ES7322-1HF10-0AA0) ..........216 3.37 Digital IO module SM 323; DI 16/DO 16 x DC 24 V/0.5 A; (6ES7323-1BL00-0AA0) ...........222 3.38 Digital IO module SM 323; DI 8/DO 8 x DC 24 V/0.5 A; (6ES7323-1BH01-0AA0) ..............227 3.39 Programmable digital IO module SM 327; DI 8/DO 8 x DC 24 V/0.5 A (6ES7327-1BH00-0AB0) ......................................................................................................231 Parameters of SM 327; DI 8/DO 8 x 24 VDC/0.5 A ..............................................................235 Structure of data record 1 of SM 327; DI 8/DO 8 x DC 24 V/0.5 A ......................................236 3.39.1 3.39.1.1 4 5 Principles of analog value processing .................................................................................................. 238 4.1 Overview ...............................................................................................................................238 4.2 4.2.1 4.2.2 Wiring and connecting transducers to analog inputs ............................................................239 Wiring and connecting electrically isolated transducers .......................................................240 Wiring non-isolated transducers ...........................................................................................241 4.3 Wiring and connecting voltage transducers ..........................................................................244 4.4 Wiring and connecting current transducers ..........................................................................245 4.5 Wiring and connecting resistance thermometers and resistors ............................................247 4.6 4.6.1 4.6.2 Wiring and connecting thermocouples ..................................................................................249 Wiring and connecting thermocouples with internal compensation ......................................253 Wiring and connecting thermocouples with external compensation .....................................254 4.7 4.7.1 4.7.2 Wiring and connecting loads/actuators to analog outputs ....................................................257 Wiring and connecting loads/actuators to voltage outputs ...................................................258 Wiring and connecting loads/actuators to current outputs....................................................260 Principles of analog modules............................................................................................................... 261 5.1 Representation of the values for analog input channels .......................................................262 5.2 Representation of analog values for analog output channels...............................................279 5.3 Setting the measuring method and ranges of analog input channels ..................................282 5.4 5.4.1 5.4.2 5.4.3 Response of the analog modules .........................................................................................285 Influence of the power supply and operating state ...............................................................285 Influence of the range of analog values ................................................................................287 Influence of operational limits and basic error limits .............................................................288 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 9 Table of contents 6 5.5 Conversion and cycle times of analog modules .................................................................. 289 5.6 Settling and response times of analog output channels ...................................................... 293 5.7 5.7.1 Programming analog modules ............................................................................................. 294 Parameters of analog input modules ................................................................................... 294 5.8 5.8.1 5.8.2 5.8.3 5.8.4 Diagnostics of analog modules ............................................................................................ 295 Diagnostics messages of analog input modules .................................................................. 296 Diagnostic messages of analog output modules ................................................................. 296 Causes of error and troubleshooting at analog input modules ............................................ 297 Causes of error and troubleshooting at analog output modules .......................................... 297 5.9 Interrupts of analog modules ............................................................................................... 298 Analog modules ...................................................................................................................................300 6.1 Analog module selection and commissioning sequence ..................................................... 301 6.2 6.2.1 6.2.2 6.2.3 Module overview .................................................................................................................. 302 Analog input modules .......................................................................................................... 302 Analog output modules ........................................................................................................ 305 Analog I/O modules ............................................................................................................. 306 6.3 6.3.1 6.3.2 6.3.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) ................................ 307 Measurement types and ranges .......................................................................................... 313 Programmable parameters .................................................................................................. 314 Additional information on SM 331; AI 8 x 16 Bit .................................................................. 315 6.4 6.4.1 6.4.2 6.4.3 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) ................................ 318 Measurement types and measuring ranges ........................................................................ 323 Programmable parameters .................................................................................................. 324 Additional information for SM 331; AI 8 x 16 Bit .................................................................. 325 6.5 6.5.1 6.5.2 6.5.3 6.5.4 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) ...................................................................................................... 329 Measurement types and measuring ranges ........................................................................ 334 Programmable parameters .................................................................................................. 336 Isochronous mode ............................................................................................................... 337 Additional information on SM 331; AI 8 x 14 Bit High Speed, isochrone ............................. 339 6.6 6.6.1 6.6.2 6.6.3 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) ................................ 340 Measurement types and measuring ranges ........................................................................ 348 Programmable parameters .................................................................................................. 348 Additional information on SM 331; AI 8 x 13 Bit .................................................................. 350 6.7 6.7.1 6.7.2 6.7.3 6.7.4 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) ................................. 353 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) ................................. 353 Measurement types and ranges .......................................................................................... 362 Programmable parameters .................................................................................................. 364 Additional information on SM 331; AI 8 x 12 Bit .................................................................. 366 6.8 6.8.1 6.8.2 6.8.3 6.8.4 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) ................................ 367 Analog input module SM 331; AI 2 x 12-bit; (6ES7331-7KB02-0AB0) ................................ 367 Measurement types and measuring ranges ........................................................................ 376 Programmable parameters .................................................................................................. 378 Additional information on SM 331; AI 2 x 12 Bit .................................................................. 379 S7-300 Module data 10 Manual, 06/2017, A5E00105505-AJ Table of contents 7 6.9 6.9.1 6.9.2 6.9.3 6.9.4 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) ...................................380 Analog input module SM 331; AI 8 x RTD (6ES7331-7PF01-0AB0) ....................................380 Measurement types and measuring ranges .........................................................................387 Programmable parameters ...................................................................................................389 Additional information on SM 331; AI 8 x RTD .....................................................................391 6.10 6.10.1 6.10.2 6.10.3 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) .....................................396 Measurement types and measuring ranges .........................................................................404 Adjustable parameters ..........................................................................................................405 Additional information on SM 331; AI 8 x TC ........................................................................407 6.11 6.11.1 6.11.2 6.11.3 6.11.4 6.11.5 6.11.6 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0).........................412 Measurement types and measuring ranges .........................................................................423 Programmable parameters ...................................................................................................424 Additional information relating to SM 331; AI 6 x TC ............................................................425 Firmware update via HW Config for analog input module SM 331; AI 6 x TC .....................431 I&M data for identifying the analog input module SM 331; AI 6 x TC ...................................433 Calibration of analog input module SM 331; AI 6 x TC .........................................................434 6.12 6.12.1 6.12.2 6.12.3 Analog output module SM 332; AO 8 x 12 bit; (6ES7332-5HF00-0AB0) .............................442 SM 332; AO 8 x 12 Bit - Output ranges ................................................................................447 Programmable parameters ...................................................................................................448 Additional information on SM 332; AO 8 x 12 Bit .................................................................449 6.13 6.13.1 6.13.2 6.13.3 6.13.4 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) ...........450 SM 332; AO 4 x 16 Bit - Output ranges ................................................................................456 Programmable parameters ...................................................................................................457 Isochronous mode ................................................................................................................458 Additional information on SM 332; AO 4 x 16 Bit .................................................................459 6.14 6.14.1 6.14.2 6.14.3 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0) ............................460 Output ranges of SM 332; AO 4 x 12 Bit ..............................................................................465 Programmable parameters ...................................................................................................466 Additional information on SM 332; AO 4 x 12 Bit .................................................................467 6.15 6.15.1 6.15.2 6.15.3 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0) ............................468 Output ranges of SM 332; AO 2 x 12 Bit ..............................................................................473 Programmable parameters ...................................................................................................474 Additional information on SM 332; AO 2 x 12 Bit .................................................................475 6.16 6.16.1 6.16.2 6.16.3 6.16.4 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) ..........................476 SM 334; AI 4/AO 2 x 8/8 Bit - Function principle ..................................................................482 Measurement and output type of SM 334; AI 4/AO 2 x 8/8 bit .............................................482 Measurement and output ranges of SM 334; AI 4/ AO 2 x 8/8 bit ........................................483 Additional information on SM 334; AI 4/AO2 x 8/8 Bit ..........................................................483 6.17 6.17.1 6.17.2 6.17.3 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) ............................484 Programmable parameters ...................................................................................................490 Measurement types and ranges ...........................................................................................490 Additional information on SM 334; AI 4/ AO 2 x 12 bit .........................................................492 Other signal modules .......................................................................................................................... 493 7.1 Module overview ...................................................................................................................493 7.2 Simulator module SM 374; IN/OUT 16; (6ES7374-2XH01-0AA0) .......................................494 7.3 Dummy module DM 370; (6ES7370-0AA01-0AA0) ..............................................................496 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 11 Table of contents 7.4 7.4.1 7.4.2 7.4.3 7.4.3.1 7.4.3.2 7.4.3.3 7.4.3.4 7.4.4 7.4.5 7.4.6 7.4.7 7.4.8 8 A B Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) ........................ 499 Isochronous mode ............................................................................................................... 500 Wiring and block diagrams ................................................................................................... 501 Functions of SM 338; POS-INPUT; encoder value acquisition ........................................... 502 Encoder value acquisition .................................................................................................... 502 Gray code/binary code converter ......................................................................................... 502 Transferred encoder value and scaling ............................................................................... 503 Freeze function .................................................................................................................... 504 Parametrization SM 338 POS-INPUT .................................................................................. 505 Addressing SM 338 POS-INPUT ......................................................................................... 507 Diagnostics of SM 338; POS-INPUT ................................................................................... 509 SM 338; POS INPUT - Interrupts ......................................................................................... 511 Technical data of SM 338; POS-INPUT .............................................................................. 512 Interface modules ................................................................................................................................515 8.1 Module overview .................................................................................................................. 515 8.2 Interface module IM 360; (6ES7360-3AA01-0AA0) ............................................................. 516 8.3 Interface module IM 361; (6ES7361-3CA01-0AA0)............................................................. 518 8.4 Interface module IM 365; (6ES7365-0BA01-0AA0) ............................................................. 520 Parameter sets of signal modules ........................................................................................................522 A.1 Principles of programming signal modules in the user program .......................................... 522 A.2 Parameters of digital IO modules......................................................................................... 524 A.3 Parameters of the digital input module SM 321; DI 16 x DC 24/125 V................................ 526 A.4 Parameters of digital output modules .................................................................................. 528 A.5 Settings from the digital output module SM 322; DO 16 x DC 24 V/0.5 A (6ES7322-8BH10-0AB0) ...................................................................................................... 530 A.6 Parameters of analog input modules ................................................................................... 534 A.7 Parameters of analog input module SM 331; AI 8 x RTD .................................................... 538 A.8 Parameters of SM 331; AI 8 TC ........................................................................................... 548 A.9 Parameters of analog input module SM 331; AI 8 x 13 Bit .................................................. 557 A.10 Setting of the analog input module SM 331; AI 8 x 16 Bit (6ES7331-7NF10-0AB0) ........... 560 A.11 Parameters of analog input module SM 331; AI 6 x TC isolated ......................................... 567 A.12 Parameters of analog output modules ................................................................................. 574 A.13 Parameters of analog output module SM 332; AO 8 x 12 Bit .............................................. 577 A.14 Parameters of analog IO modules ....................................................................................... 580 Diagnostics data of signal modules ......................................................................................................583 B.1 Evaluating diagnostic data of signal modules in the user program ..................................... 583 B.2 Structure and content of diagnostics data, byte 0 and up ................................................... 584 B.3 Channel-specific diagnostics data ....................................................................................... 588 B.4 Diagnosis data from the SM 322; DO 16 x DC24 V/0.5 A (6ES7322-8BH10-0AB0) .......... 590 S7-300 Module data 12 Manual, 06/2017, A5E00105505-AJ Table of contents C B.5 Diagnostics data of SM 331; AI 6 x TC isolated ...................................................................593 B.6 Diagnostics data of SM 338; POS-INPUT ............................................................................596 Dimensional drawings ......................................................................................................................... 598 C.1 C.1.1 Dimensional drawings of the mounting rails .........................................................................599 Bus modules .........................................................................................................................605 C.2 Dimensional drawings of the power supply modules ............................................................606 C.3 Dimensional drawings of the interface modules ...................................................................610 C.4 Dimensional drawings of the signal modules .......................................................................612 C.5 Dimensional drawings of accessories...................................................................................614 D Spare parts and accessories for S7-300 modules ................................................................................ 616 E Directive on handling Electrostatic-Sensitive Devices (ESD) ................................................................ 619 F E.1 Definition of ESD...................................................................................................................619 E.2 Electrostatic charging of the body .........................................................................................620 E.3 Basic protective measures against electrostatic discharge ..................................................621 Service & support................................................................................................................................ 622 F.1 G H Service & support..................................................................................................................622 Safety-relevant symbols ...................................................................................................................... 623 G.1 Safety-related symbols for devices without Ex protection ....................................................623 G.2 Safety-related symbols for devices with Ex protection .........................................................624 List of abbreviations ............................................................................................................................ 626 H.1 List of abbreviations ..............................................................................................................626 Glossary ............................................................................................................................................. 628 Index................................................................................................................................................... 638 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 13 1 General technical data 1.1 Standards and approvals Introduction Contents of general technical data: standards and test values satisfied by modules of the S7-300 automation system test criteria of S7-300 modules. Note Information on the nameplate You will find the current labels and approvals on the nameplate of the respective modules. Safety guidelines WARNING Personal injury and damage to property may occur. In potentially explosive environments, there is a risk of injury or damage if you disconnect any connectors while the S7-300 is in operation. Always isolate the S7-300 operated in such areas before you disconnect and connectors. WARNING Explosion hazard If you replace components, compliance with Class I, DIV 2 may become invalid. WARNING The S7-300 module is only suitable for use in Class I, Div. 2, Group A, B, C, D, or in nonhazardous areas. S7-300 Module data 14 Manual, 06/2017, A5E00105505-AJ General technical data 1.1 Standards and approvals Test symbols and their significance The test symbols and their meanings are described in the following section. CE Label The S7-300 automation system satisfies the requirements and protection goals of the following EC directives, and conforms with the harmonized European standards (EN) for programmable logic controllers announced in the Official Journals of the European Community: 2014/35/EU "Electrical equipment designed for use within certain voltage limits" (Low-Voltage Directive) 2014/30/EU "Electromagnetic Compatibility" (EMC Directive) 2014/34/EU "Equipment and protective systems intended for use in potentially explosive atmospheres" (Explosion Protection Directive) 2011/65/EU "Restriction of the use of certain hazardous substances in electrical and electronic equipment" (RoHS Directive) The EC declaration of conformity is held on file available to competent authorities at: Siemens Aktiengesellschaft Digital Factory Factory Automation DF FA AS SYS P.O. Box 1963 D-92209 Amberg, Germany You can also download this under the keyword "Declaration of conformity" on the Internet (http://support.automation.siemens.com/WW/view/en/37217116/134200). UL approval Underwriters Laboratories Inc., complyling with UL 508 (Industrial Control Equipment) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 15 General technical data 1.1 Standards and approvals CSA approval Canadian Standards Association to C22.2 No. 142 (Process Control Equipment) or cULus approval Underwriters Laboratories Inc. complying with UL 508 (Industrial Control Equipment) CSA C22.2 No. 142 (Process Control Equipment) or cULus HAZ. LOC. approval Underwriters Laboratories Inc., complying with UL 508 (Industrial Control Equipment) UL 1604 (Hazardous Location) CSA C22.2 No. 142 (Process Control Equipment) CSA C22.2 No. 213 (Hazardous Location) APPROVED for use in Class I, Division 2, Group A, B, C, D Tx; Class I, Zone 2, Group IIC Tx S7-300 Module data 16 Manual, 06/2017, A5E00105505-AJ General technical data 1.1 Standards and approvals FM approval Factory Mutual Research (FM) in accordance with Approval Standard Class Number 3611, 3600, 3810 APPROVED for use in Class I, Division 2, Group A, B, C, D Tx; Class I, Zone 2, Group IIC Tx ATEX approval In accordance with EN 60079-15 (Electrical Apparatus for Potentially Explosive Atmospheres; Type of Protection "n") and EN 60079-0 (Electrical apparatus for potentially explosive gas atmospheres - Part 0: General Requirements) RCM (C-Tick) Declaration of conformity for Australia/New Zealand The automation system S7-300 fulfills the requirements of the standards AS/NZS 61000.6.4 IEC 61000-6-4. IEC 61131 The automation system S7-300 fulfills the requirements and criteria of the IEC 61131-2 standard (Programmable Controllers, Part 2: Equipment requirements and tests). S7-300 Module data Manual, 06/2017, A5E00105505-AJ 17 General technical data 1.1 Standards and approvals Marine approval Classification societies: ABS (American Bureau of Shipping) BV (Bureau Veritas) DNV-GL (Det Norske Veritas-Germanischer Lloyd) LRS (Lloyds Register of Shipping) Class NK (Nippon Kaiji Kyokai) CCS (China Classification Society) Use in industrial environments SIMATIC products are designed for industrial applications. Table 1- 1 Use in industrial environments Field of applica- Noise emission requirements tion Noise immunity requirements Industry EN 61000-6-2: 2005 EN 61000-6-4: 2007 Use in residential areas / mixed areas Note The S7-300 automation system is intended for use in industrial areas; use in residential areas / mixed areas may have an impact on radio/TV reception. If you use the S7-300 in residential areas / mixed areas, you must ensure observance of the Class B radio interference limit in accordance with EN 55022 regarding the emission of radio interferences. Suitable measures for achieving the required Class B radio interference level include, for example: S7-300 installation in grounded switch cabinets / cubicles Use of noise filters in the supply lines S7-300 Module data 18 Manual, 06/2017, A5E00105505-AJ General technical data 1.2 Electromagnetic compatibility 1.2 Electromagnetic compatibility Definition Electromagnetic compatibility (EMC) is the ability of an electrical installation to function satisfactorily in its electromagnetic environment without interfering with that environment. The S7-300 modules also satisfy requirements of EMC legislation for the European domestic market. Compliance of the S7-300 system with specifications and directives on electric design is prerequisite. Pulseshaped disturbance The table below shows the EMC compatibility of S7 modules in areas subject to pulseshaped disturbance. Pulse-shaped disturbance Electrostatic discharge to IEC 61000-4-2 Burst pulses (high-speed transient disturbance) to IEC 61000-4-4. Test voltage corresponds with degree of severity Air discharge: 8 kV 3 Contact discharge 4 kV 2 2 kV (power supply lines) 2 kV (signal lines > 3 m) 1 kV (signal lines < 3 m) 3 3 High-energy single pulse (surge) to IEC 61000-4-5 External protective circuit required (refer to S7-300 Automation System, Hardware and Installation, Chapter "Lightning and overvoltage protection") * asymmetric coupling 2 kV (power supply lines) DC with protective elements 3 2 kV (signal/ data line only > 3 m), with protective elements as required * symmetric coupling 1 kV (power supply lines) DC with protective elements 1 kV (signal/ data line only > 3 m), with protective elements as required S7-300 Module data Manual, 06/2017, A5E00105505-AJ 19 General technical data 1.2 Electromagnetic compatibility Sinusoidal disturbance The table below shows the EMC compatibility of S7-300 modules in areas subject to sinusoidal disturbance. HF radiation HF radiation according to IEC 61000-4-3 Corresponds with degree of severity Electromagnetic HF field, amplitude-modulated 80 MHz to 1,000 MHz; 1.4 GHz to 2 GHz 2.0 GHz to 2.7 GHz 10 V/m 3, 2, 1 1 V/m 80% AM (1 kHz) HF coupling HF coupling according to IEC 61000-4-6 Corresponds with degree of severity 0.15 MHz to 80 MHz 3 10 Vrms unmodulated 80% AM (1 kHz) 150 source impedance Emission of radio interference Electromagnetic interference to EN 55016: Limit Value Class A (measured at a distance of 10 m). Frequency Noise emission 30 MHz to 230 MHz < 40 dB (V/m)Q 230 MHz to 1000 MHz < 47 dB (V/m)Q 1 GHz - 3 GHz < 76 dB (V/m) peak < 56 dB (V/m) average 3 GHz - 6 GHz < 80 dB (V/m) peak < 60 dB (V/m) average Noise emission via AC mains to EN 55016: Limit value class A, Group 1. Frequency Noise emission From 0.15 to 0.5 MHz < 79 dB (V/m)Q < 66 dB (V/m)M 0.5 MHz to 5 MHz < 73 dB (V/m)Q < 60 dB (V/m)M 5 MHz to 30 MHz < 73 dB (V/m)Q < 60 dB (V/m)M S7-300 Module data 20 Manual, 06/2017, A5E00105505-AJ General technical data 1.3 Shipping and storage conditions for modules and backup batteries 1.3 Shipping and storage conditions for modules and backup batteries Introduction S7-300 modules exceed the specifications regarding transport and storage conditions pursuant to IEC 61131-2. The following information applies to modules that are transported and stored in their original packaging. The climatic conditions for temperature and humidity meet: IEC 60721-3-3, Class 3K7 for storage. IEC 60721-3-2, Class 2K4 for transport. The mechanical conditions for individual parameters meet IEC 60721-3-2, Class 2M2. Shipping and storage conditions for modules Type of condition Permissible range Free fall (in shipping package) 1m Temperature - 40 C to + 70 C Barometric pressure from 1140 to 660 hPa (corresponds to an elevation of -1000 to 3500 m) Relative humidity 10% to 95%, no condensation Sinusoidal oscillation to IEC 60068-2-6 5 Hz to 9 Hz: 3.5 mm 9 Hz to 150 Hz: 9.8 m/s2 Shock to IEC 60068-2-29 250 m/s2, 6 ms, 1000 shocks Shipment of backup batteries Backup batteries should always be shipped in their original package. Note the regulations governing the transport of hazardous goods. The backup battery has a lithium content of approx. 0.25 g. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 21 General technical data 1.3 Shipping and storage conditions for modules and backup batteries Storing backup batteries Always store backup batteries in a cool and dry place. The maximum storage period is 5 years WARNING Handling backup batteries Improper handling of backup batteries can result in injury and damage to property. Improperly handled backup batteries may explode or cause severe burns. Observe the following rules when handling the backup batteries used in the S7-300 automation system: * Never charge the batteries * Never heat the batteries * Never throw the batteries in an open fire * Never damage the batteries mechanically (drill, squeeze, etc.) Note Backup batteries Do not dispose of batteries through household waste! Batteries are recyclable! S7-300 Module data 22 Manual, 06/2017, A5E00105505-AJ General technical data 1.4 Mechanical and climatic environmental conditions for S7-300 operation 1.4 Mechanical and climatic environmental conditions for S7-300 operation Operating conditions S7-300 systems are designed for stationary use in weather-proof locations. The operating conditions are based on the requirements of DIN IEC 60721-3-3: Class 3M3 (mechanical requirements) Class 3K3 (climatic requirements) Use with additional measures The S7-300 may not be used under the conditions outlined below without taking additional measures: at locations with a high degree of ionizing radiation in aggressive environments caused, for example, by - the development of dust - corrosive vapors or gases - strong electric or magnetic fields in installations requiring special monitoring, for example - elevators - electrical plants in potentially hazardous areas Mechanical environmental conditions The table below shows the mechanical environmental conditions in the form of sinusoidal oscillations. Frequency band Continuous Infrequently 10 Hz f 58 Hz 0.0375 mm amplitude 0.75 mm amplitude 58 Hz f 150 Hz 0.5 g constant acceleration 1 g constant acceleration Reducing vibrations If your S7-300 modules are exposed to severe shock or vibration, take appropriate measures to reduce acceleration or the amplitude. We recommend the installation of the S7-300 on damping materials (for example, rubberbonded-to-metal mounting.) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 23 General technical data 1.4 Mechanical and climatic environmental conditions for S7-300 operation Test of mechanical environmental conditions The table below provides important information with respect to the type and scope of the test of ambient mechanical conditions. Condition tested Test Standard Comment Vibration Vibration test to Type of oscillation: Frequency sweeps with a rate of change of 1 ocIEC 60068-2-6 (sinusoidal) tave/minute. 5 Hz f 9 Hz, constant amplitude 3.5 mm 9 Hz f 150Hz, constant acceleration 1 g Duration of oscillation: 10 frequency sweeps per axis at each of three vertically aligned axes Shock Shock, tested to IEC 60068-2-27 Type of shock: half-sine Severity of shock: 15 g peak value, 11 ms duration Direction of shock: 3 shocks in each direction (+/-) at each of three vertically aligned axes Climatic environmental conditions The S7-300 may be operated on following environmental conditions: Environmental conditions Permitted range Temperature: horizontal mounting position: vertical mounting position: Comments 0C to 60C 0C to 40C Relative humidity 10 % to 95 % No condensation, corresponds to relative humidity (RH) Class 2 to IEC 61131, Part 2 Barometric pressure from 1140 to 795 hPa Corresponds with an altitude of -1000 m to 2000 m Concentration of pollutants SO2: < 0.5 ppm; RH < 60 %, no condensation H2S: < 0.1 ppm; RH < 60 %, no condensation Test: 10 ppm; 4 days ISA-S71.04 severity level G1; G2; G3 - - Test: 1 ppm; 4 days S7-300 Module data 24 Manual, 06/2017, A5E00105505-AJ General technical data 1.5 Specification of dielectric tests, protection class, degree of protection, and rated voltage of S7-300 1.5 Specification of dielectric tests, protection class, degree of protection, and rated voltage of S7-300 Isolation The isolation is designed in accordance with the requirements of EN 61131-2. Pollution degree/overvoltage category according to IEC 61131-2: 2007 Proof of dielectric strength must be provided in the type test at a test voltage according to IEC 61131-2: Pollution degree 2 Overvoltage category: II Protection class in accordance with IEC 61131-2: 2007 The automation system S7-300 meets Protection Class I and contains parts of Protection Classes II and III. Degree of protection IP20 Degree of protection IP 20 in accordance with IEC 60529 for all modules of the S7-300 automation system, i.e.: Protection against contact with standard test finger Protection against foreign objects with diameters greater than 12.5 mm No protection against water 1.6 Rated voltages of S7-300 Rated operating voltages The S7-300 modules operate at different rated voltages. The table shows the rated voltages and corresponding tolerances. Rated voltages Tolerance 24 VDC 20.4 VDC to 28.8 VDC 120 VAC 93 VAC to 132 VAC 230 VAC 187 VAC to 264 VAC S7-300 Module data Manual, 06/2017, A5E00105505-AJ 25 General technical data 1.7 SIPLUS S7-300 Modules 1.7 SIPLUS S7-300 Modules Definition SIPLUS S7-300 modules can be used under extended environmental conditions. Meaning of "extended environmental conditions": Extended temperature range of - 25 C to + 60 C/70C Moisture condensation/condensation permissible increased mechanical stress permissible Comparison with "standard" modules The functional scope and technical data of SIPLUS S7-300 modules and of "standard" modules are identical, with the exception of the environmental conditions. SIPLUS S7-300 modules have a separate order number (see the table below.) The mechanical/climatic environmental conditions and the method of testing these have changed. The SIPLUS S7-300 modules are specified: For deployment in harsh environmental conditions, For use in hostile environments. For extreme temperature ranges. For more on this, read section Environmental conditions for the operation of SIPLUS S7-300 modules (Page 30). Project design in STEP 7 SIPLUS S7-300 modules are not included in the hardware catalog. Please design your plant based on the relevant "standard" modules shown in the table below. S7-300 Module data 26 Manual, 06/2017, A5E00105505-AJ General technical data 1.7 SIPLUS S7-300 Modules SIPLUS S7-300 Modules This following table contains all SIPLUS S7-300 modules available at the time of publication. In addition, we included the order numbers of the corresponding "standard" modules to support project design. You can refer to specifications and technical data in the special "standard" module section. Youll find more information on SIPLUS and contact partners in the Internet (http://www.siemens.com/siplus-extreme). Table 1- 2 Comparison of SIPLUS S7-300 modules and S7-300 "Standard" module Module type SIPLUS S7-300 modules for the use under extended environmental conditions "Standard" modules as of order no. Power supply PS 305; 2A 6AG1305-1BA80-2AA0 6ES7305-1BA80-0AA0 PS 307; 5A 6AG1307-1EA80-2AA0 6ES7307-1EA80-0AA0 PS 307; 10A 6AG1307-1KA02-7AA0 6ES7307-1KA02-0AA0 IM 153-1 6AG1153-1AA03-2XB0 6ES7153-1AA03-0XB0 IM 365 6AG1365-0BA01-2AA0 6ES7365-0BA01-0AA0 Separator module 6AG1195-7KF00-2XA0 6ES7195-7KF00-0XA0 Interface module S7-300 Module data Manual, 06/2017, A5E00105505-AJ 27 General technical data 1.7 SIPLUS S7-300 Modules Module type SIPLUS S7-300 modules for the use under extended environmental conditions "Standard" modules as of order no. Central module CPU 312C (EN50155) 6AG1312-5BF04-2AY0 6ES7312-5BF04-0AB0 CPU 312C 6AG1312-5BF04-7AB0 6ES7312-5BF04-0AB0 CPU 313C (EN50155) 6AG1313-5BG04-2AY0 6ES7313-5BG04-0AB0 CPU 313C 6AG1313-5BG04-7AB0 6ES7313-5BG04-0AB0 CPU 313C-2DP (EN50155) 6AG1313-6CG04-2AY0 6ES7313-6CG04-0AB0 CPU 313C-2DP 6AG1313-6CG04-7AB0 6ES7313-6CG04-0AB0 CPU 314 (EN50155) 6AG1314-1AG14-2AY0 6ES7314-1AG14-0AB0 CPU 314 6AG1314-1AG14-7AB0 6ES7314-1AG14-0AB0 CPU 314C 6AG1314-6BH04-7AB0 6ES7314-6BH04-0AB0 CPU 314C-2DP (EN50155) 6AG1314-6CH04-2AY0 6ES7314-6CH04-0AB0 CPU 314C-2DP 6AG1314-6CH04-7AB0 6ES7314-6CH04-0AB0 CPU314C-2PN/DP 6AG1314-6EH04-7AB0 6ES7314-6EH04-0AB0 CPU 315-2DP (EN50155) 6AG1315-2AH14-2AY0 6ES7315-2AH14-0AB0 CPU 315-2DP 6AG1315-2AH14-7AB0 6ES7315-2AH14-0AB0 CPU 315-2PN/DP (EN50155) 6AG1315-2EH14-2AY0 6ES7315-2EH14-0AB0 CPU 315-2PN/DP 6AG1315-2EH14-7AB0 6ES7315-2EH14-0AB0 CPU 315F-2PN/DP 6AG1315-2FJ14-2AB0 6ES7315-2FJ14-0AB0 CPU 315F-2PN/DP (EN50155) 6AG1315-2FJ14-2AY0 6ES7315-2FJ14-0AB0 CPU 315F-2DP 6AG1315-6FF04-2AB0 6ES7315-6FF04-0AB0 CPU 315F-2DP (EN50155) 6AG1315-6FF04-2AY0 6ES7315-6FF04-0AB0 CPU 317-2PN/DP (EN50155) 6AG1317-2EK14-2AY0 6ES7317-2EK14-0AB0 CPU 317-2PN/DP 6AG1317-2EK14-7AB0 6ES7317-2EK14-0AB0 CPU 317F-2PN/DP 6AG1317-2FK14-2AB0 6ES7317-2FK14-0AB0 CPU 317F-2PN/DP (EN50155) 6AG1317-2FK14-2AY0 6ES7317-2FK14-0AB0 CPU 317F-2DP 6AG1317-6FF04-2AB0 6ES7317-6FF04-0AB0 SM 321; DI 16 x DC 24V 6AG1321-1BH02-2AA0 6ES7321-1BH02-0AA0 SM 321; DI 32 x DC 24V 6AG1321-1BL00-2AA0 6ES7321-1BL00-0AA0 SM 321; DI 16 x DC 24V 6AG1321-7BH01-2AB0 6ES7321-7BH01-0AB0 SM 321; DI 8 x AC 120/230V 6AG1321-1FF10-7AA0 6ES7321-1FF10-0AA0 SM 321; DI 16 x DC 48 V-125V 6AG1321-1CH20-2AA0 6ES7321-1CH20-0AA0 SM 321; DI 8 x AC 120/220 V 6AG1321-1FF01-2AA0 6ES7321-1FF01-0AA0 SM 321; DI 4 NAMUR 6AG1321-7RD00-4AB0 6ES7321-7RD00-0AB0 SM 321; DI 16 x DC 24V 6AG1321-7TH00-4AB0 6ES7321-7TH00-0AB0 Digital input module S7-300 Module data 28 Manual, 06/2017, A5E00105505-AJ General technical data 1.7 SIPLUS S7-300 Modules Module type SIPLUS S7-300 modules for the use under extended environmental conditions "Standard" modules as of order no. Digital output module SM 322; DO 16 x DC 24V/0.5A 6AG1322-1BH01-2AA0 6ES7322-1BH01-0AA0 SM 322; DO 8 x Rel. 230 V AC / 5A 6AG1322-1HF10-2AA0 6ES7322-1HF10-0AA0 SM 322, DO 8 x DC 48-125 V/1.5 A 6AG1322-1CF00-7AA0 6ES7322-1CF00-0AA0 SM 322; DO 8 x AC 120/230V/2A 6AG1322-1FF01-7AA0 6ES7322-1FF01-0AA0 SM 322; DO 8 x DC 24V/0.5A 6AG1322-8BF00-2AB0 6ES7322-8BF00-0AB0 SM 322; DO 8 x DC 24V 6AG1322-1BF01-2XB0 6ES7322-1BF01-0AA0 SM 322; DO 32 x DC 24 V/0.5 A 6AG1322-1BL00-2AA0 6ES7322-1BL00-0AA0 SM 322; DO 16 x AC 120/230V/1 A 6AG1322-1FH00-7AA0 6ES7322-1FH00-0AA0 SM 322; DO 16 RELAY 6AG1322-1HH01-2AA0 6ES7322-1HH01-0AA0 SM 322; DO 8 x AC 120/230 V, 2 A 6AG1322-5FF00-4AB0 6ES7322-5FF00-0AB0 SM 322; DO 8 RELAY 6AG1322-5HF00-4AB0 6ES7322-5HF00-0AB0 SM 322; DO 16 x DC 24V 6AG1322-8BH10-7AB0 6ES7322-8BH10-0AB0 6AG1323-1BH01-2AA0 6ES7323-1BH01-0AA0 SM 331; AI 2 x 12Bit 6AG1331-7KB02-2AB0 6ES7331-7KB02-0AB0 SM 331; AI 8 x 13 Bit 6AG1331-1KF02-4AB0 6ES7331-1KF02-0AB0 SM 331; AI 8 x 13 Bit 6AG1331-1KF02-7AB0 6ES7331-1KF02-0AB0 SM 331; AI 8 x 12 Bit 6AG1331-7KF02-2AB0 6ES7331-7KF02-0AB0 SM 331; AI 8 x 16 Bit 6AG1331-7NF00-2AB0 6ES7331-7NF00-0AB0 SM 331; AI 8 x 16 Bit 6AG1331-7NF10-2AB0 6ES7331-7NF10-0AB0 SM 331; AI 8 x 13 Bit 6AG1331-7PF11-4AB0 6ES7331-7PF11-0AB0 SM 331; AI 8 x 13-bit 6AG1331-7PF01-4AB0 6ES7331-7PF11-0AB0 SM 331; AI 4 x 0/4-20 mA 6AG1331-7RD00-2AB0 6ES7331-7RD00-0AB0 SM 331; AI 8 Thermo / AI 4 PT 100 6AG1331-7SF00-4AB0 6ES7331-7SF00-0AB0 SM 331; AI 2 HART 6AG1331-7TB00-7AB0 6ES7331-7TB00-0AB0 SM 331; AI 8 x 0/4 to mA HART 6AG1331-7TF01-7AB0 6ES7331-7TF01-0AB0 SM 332; AO 2 x 12 bit 6AG1332-5HB01-2AB0 6ES7332-5HB01-0AB0 SM 332; AO 4 x 12 bit 6AG1332-5HD01-7AB0 6ES7332-5HD01-0AB0 SM 332; AO 8 x 12 bit 6AG1332-5HF00-2AB0 6ES7332-5HF00-0AB0 SM 332; AO 8 x 0/4 - 20 mA HART 6AG1332-8TF01-2AB0 6ES7332-8TF01-0AB0 SM 332; AO 4 x 16 bit 6AG1332-7ND02-4AB0 6ES7332-7ND02-0AB0 6AG1334-0KE00-7AB0 6ES7334-0KE00-0AB0 Digital I/O module SM 323; DI8/DO8 x DC 24V/0.5A Analog input module Analog output module Analog IO module SM 334; AI 4/AO 2 x 12 Bit S7-300 Module data Manual, 06/2017, A5E00105505-AJ 29 General technical data 1.8 Environmental conditions for the operation of SIPLUS S7-300 modules 1.8 Environmental conditions for the operation of SIPLUS S7-300 modules Mechanical environmental conditions Application class: according to IEC 721-3-3, Class 3M4. Test of mechanical environmental conditions The table provides information on the type and scope of the test of mechanical environmental conditions for SIPLUS S7-300 modules. Table 1- 3 SIPLUS S7-300 Modules: Test of mechanical environmental conditions Condition tested Test Standard Remarks Vibration Vibration test acc. to IEC 60068-2-6 (sinusoidal) Type of oscillation: Frequency sweep at a rate of change of 1 octave/minute. 5 Hz f 9 Hz, constant Amplitude 3.5 mm 9 Hz f 150 Hz, constant Acceleration 1 g duration of oscillation: 10 frequency sweeps at each of three vertically aligned axes Shock Shock, tested acc. to Type of shock: Half-sine IEC 60068-2-27 Severity of shock: 15 g peak value, 11 ms duration Direction of shock: 3 shocks each in +/- direction in each of the three vertically aligned axes S7-300 Module data 30 Manual, 06/2017, A5E00105505-AJ General technical data 1.8 Environmental conditions for the operation of SIPLUS S7-300 modules Environmental conditions Operating category: to IEC 721 -3-3, Class 3K5. The SIPLUS S7-300 modules may also be used under the following climatic, chemical, biological and mechanical environmental conditions: Table 1- 4 SIPLUS S7-300 Modules: Environmental conditions Environmental conditions Permitted range Temperature: Horizontal mounting position: -25 C to +60 C/70C Vertical mounting position: 0C to +40 C Relative humidity 5 ... 100 %, condensation / condensation allowed Resistance against biologically active substances Conformity with EN 60721-3-3, Class 3B2 mildew, fungi and sponge spores (excluding fauna) Resistance against chemically active substances Conformity with EN 60721-3-3, Class 3C4 incl. salt mist and ISA -S71.04 severity level G1; G2; G3; GX 1)2) Resistance against mechanically active substances Conformity with EN 60721-3-3, Class 3S4 incl. conductive sand, dust 2) Air pressure in relation to ambient temperature - air pressure - installation altitude - 25 ... +60/70 C at 1140 ... 795 hPa -1000 ... +2000 m - 25 ... +50/60C at 795 ... 658 hPa +2000 ... +3500 m - 25 ... +40/50C at 658 ... 540 hPa +3500 ... +5000 m Certificate of suitability as approval for rail application --> Partly EN 50155 T1 Cat1 Cl A/B 1) ISA -S71.04 severity level GX: Dauerbelastung/long-term load: SO2 < 4.8 ppm; H2S < 9.9 ppm; Cl < 0.2 ppm; HCl < 0.66 ppm; HF < 0.12 ppm; NH < 49 ppm; O3 < 0.1 ppm; NOX < 5.2 ppm limit value (max. 30 min/d): SO2 < 14.8 ppm; H2S < 49.7 ppm; Cl < 1.0 ppm; HCl < 3.3 ppm; HF < 2.4 ppm; NH < 247 ppm; O3 < 1.0 ppm; NOX < 10.4 ppm 2) When operated in harmful gas environments, the supplied plug covers must remain on the non-used port. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 31 2 Power supply modules Introduction Various 24-VDC power supply modules are available for your S7-300 PLC and the sensors/actuators. Power supply modules This chapter contains the technical data of the S7-300 power supply modules. In addition to technical data, this chapter describes: The characteristics Wiring diagram Block Diagram Line protection Reaction to atypical operating conditions S7-300 Module data 32 Manual, 06/2017, A5E00105505-AJ Power supply modules 2.1 Power supply module PS 307; 2 A; (6ES7307-1BA01-0AA0) 2.1 Power supply module PS 307; 2 A; (6ES7307-1BA01-0AA0) Order number 6ES7307-1BA01-0AA0 Properties Properties of the PS 307; 2 A power supply module: Output current 2 A Output voltage 24 V DC; short circuit-proof, open circuit-proof Connection to singlephase AC mains (rated input voltage 120/230 V AC, 50/60 Hz) safe electrical isolation in accordance with EN 60 950 (SELV) May be used as load power supply Wiring diagram of PS 307; 2 A "24 V DC output voltage present" display 24 V DC On/Off switch Mains and protective conductor terminals Terminals for 24 V DC output voltage Strain-relief S7-300 Module data Manual, 06/2017, A5E00105505-AJ 33 Power supply modules 2.1 Power supply module PS 307; 2 A; (6ES7307-1BA01-0AA0) Schematic circuit diagram of PS 307; 2 A Figure 2-1 Schematic circuit diagram of power supply module PS 307; 2 A Line protection The mains supply of the PS 307; 2A power supply module should be protected with a miniature circuit-breaker (for example Siemens 5SN1 series) of the following rating: Rated current at 230 V AC: 3 A Tripping characteristics (type): C. Reaction to atypical operating conditions Table 2- 1 Reaction of the PS 307; 2A power supply module to atypical operating conditions If ... ... then ... 24 V DC LED the output circuit is overloaded: * * I > 2.6 A (dynamic) Flashing Voltage dip, automatic voltage recovery Voltage drop, reduction of service life 2 A < I 2.6 A (static) short-circuit at the output Output voltage 0 V; automatic voltage recovery after shortcircuit is eliminated off overvoltage on primary side risk of destruction - undervoltage on primary side Automatic shutdown; automatic voltage recovery off S7-300 Module data 34 Manual, 06/2017, A5E00105505-AJ Power supply modules 2.1 Power supply module PS 307; 2 A; (6ES7307-1BA01-0AA0) Technical specifications of the PS 307; 2 A (6ES7307-1BA01-0AA0) Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 120 Weight ca. 400 g Input parameters Input voltage * Rated value Mains frequency * Rated value * Permitted range 120/230 V AC (automatic switching) 50 Hz or 60 Hz 47 Hz to 63 Hz Rated input current * at 230 V * at 120 V 0.5 A 0.9 A Inrush current (at 25 C) 22 A I2t (at inrush current) 1 A2s Output parameters Output voltage * Rated value * Permitted range * Rampup time 24 V DC 24 V 3 %, open-circuit test max. 2.5 s Output current * Rated value 2 A, parallel wiring supported Short-circuit protection electronic, non-latching 1.1 to 1.3 x IN Residual ripple max. 150 mVpp Characteristics Safety class to IEC 536 (DIN VDE 0106, Part 1) I, with protective conductor Isolation rating * Rated isolation voltage (24 V to L1) * Test voltage Safety isolation Buffering of power supply failure (at 93 V or 187 V) * Repeat rate 250 V AC 4200 V DC SELV circuit min. 20 ms min 1 s Efficiency 84 % Power consumption 57 W Power loss Typ. 9 W Diagnostics "Output voltage present" display yes, green LED S7-300 Module data Manual, 06/2017, A5E00105505-AJ 35 Power supply modules 2.2 Power supply module PS 307; 5 A; (6ES7307-1EA01-0AA0) 2.2 Power supply module PS 307; 5 A; (6ES7307-1EA01-0AA0) Order number 6ES7307-1EA01-0AA0 Properties Properties of the PS 307; 5 A power supply module: Output current 5 A Output voltage 24 V DC; short circuit-proof, open circuit-proof Connection to singlephase AC mains (rated input voltage 120/230 V AC, 50/60 Hz) safe electrical isolation in accordance with EN 60 950 (SELV) May be used as load power supply Wiring diagram of PS 307; 5 A Display for "Output voltage DC 24 V present" 24 V DC On/Off switch Mains and protective conductor terminals Terminals for 24 V DC output voltage Strain-relief S7-300 Module data 36 Manual, 06/2017, A5E00105505-AJ Power supply modules 2.2 Power supply module PS 307; 5 A; (6ES7307-1EA01-0AA0) Block diagram PS 307; 5 A Figure 2-2 Block diagram of the PS 307; 5 A power supply module Line protection The mains supplies of the PS 307; 5 A power supply module should be protected with a miniature circuit-breaker (for example Siemens 5SN1 series) of the following rating: Rated current at 230 V AC: 6 A Tripping characteristics (type): C. Reaction to atypical operating conditions Table 2- 2 Reaction to atypical operating conditions of the PS 307; 5 A power supply module If ... ... then ... DisplayDC 24 V Voltage dip, automatic voltage recovery flashes the output circuit is overloaded: * * I > 6.5 A (dynamic) Voltage drop, reduction of service life 5 A < I 6.5 A (static) short-circuit at the output Output voltage 0 V; automatic voltage recovery after short-circuit is eliminated off overvoltage on primary side risk of destruction - undervoltage on primary side Automatic shutdown; automatic voltage recovery off S7-300 Module data Manual, 06/2017, A5E00105505-AJ 37 Power supply modules 2.2 Power supply module PS 307; 5 A; (6ES7307-1EA01-0AA0) Technical specifications of PS 307; 5 A (6ES7307-1EA01-0AA0) Technical specifications Dimensions and weight Dimensions W x H x D (mm) 60 x 125 x 120 Weight ca. 600 g Input parameters Input voltage * Rated value 120/230 V AC (automatic switching) Mains frequency * Rated value * Permitted range 50 Hz or 60 Hz 47 Hz to 63 Hz Rated input current * at 120 V * at 230 V 2.3 A 1.2 A Inrush current (at 25 C) 20 A I2 t 1.2 A2s (at inrush current) Output parameters Output voltage * Rated value * Permitted range * Rampup time 24 V DC 24 V 3 %, open circuit-proof max. 2.5 s Output current * Rated value Short-circuit protection 5 A, parallel wiring is available electronic, non-latching 1.1 to 1.3 x IN Residual ripple max. 150 mVpp Characteristics Safety class to IEC 536 (DIN VDE 0106, Part 1) I, with protective conductor Isolation rating * Rated isolation voltage (24 V to L1) 250 V AC * Test voltage 4200 V DC Safety isolation SELV circuit Buffering of power supply failure (at 93 V or 187 V) Min. 20 ms * Repeat rate min 1 s Efficiency 87 % Power consumption 138 W Power loss typ. 18 W Diagnostics "Output voltage present" display yes, green LED S7-300 Module data 38 Manual, 06/2017, A5E00105505-AJ Power supply modules 2.3 Power supply module PS 307; 10 A; (6ES7307-1KA02-0AA0) 2.3 Power supply module PS 307; 10 A; (6ES7307-1KA02-0AA0) Order number 6ES7307-1KA02-0AA0 Properties Properties of the PS 307; 10 A power supply module: Output current 10 A Output voltage 24 V DC; short circuit-proof, open circuit-proof Connection to singlephase AC mains (rated input voltage 120/230 V AC, 50/60 Hz) safe electrical isolation in accordance with EN 60 950 (SELV) May be used as load power supply Block diagram of PS 307; 10 A Display for "Output voltage DC 24 V present" Terminals for 24 V DC output voltage Strain-relief Mains and protective conductor terminals 24 V DC On/Off switch S7-300 Module data Manual, 06/2017, A5E00105505-AJ 39 Power supply modules 2.3 Power supply module PS 307; 10 A; (6ES7307-1KA02-0AA0) Block diagram PS 307; 10 A Figure 2-3 Block diagram of the PS 307; 10 A power supply module Line protection The mains supplies of the PS 307;10 A power supply module should be protected with a miniature circuit-breaker (for example Siemens 5SN1 series) of the following rating: Rated current at 230 V AC: 10 A Tripping characteristics (type): C. Reaction to atypical operating conditions Table 2- 3 Reaction to atypical operating conditions of the PS 307; 10 A power supply module If ... Module reaction DisplayDC 24 V .output circuit is overloaded: * I > 13 A (dynamic) Voltage dip, automatic voltage recovery Voltage drop (reduction of service life) flashes short-circuit at the output Output voltage 0 V; automatic voltage recovery after short-circuit is eliminated off overvoltage on primary side risk of destruction - undervoltage on primary side Automatic shutdown; automatic voltage recovery off * 10 A < I 13 A (static) S7-300 Module data 40 Manual, 06/2017, A5E00105505-AJ Power supply modules 2.3 Power supply module PS 307; 10 A; (6ES7307-1KA02-0AA0) Technical specifications of PS 307; 10 A (6ES7307-1KA02-0AA0) Technical specifications Dimensions and weight Dimensions W x H x D (mm) 80 x 125 x 120 Weight 800 g Input parameters Input voltage * Rated value 120/230 V AC (automatic switching) Mains frequency * Rated value * Permitted range 50 Hz or 60 Hz 47 Hz to 63 Hz Rated input current * at 230 V * at 120 V 1.9 A 4.2 A Inrush current (at 25 C) 55 A I2 t 3.3 A2s (at inrush current) Output parameters Output voltage * Rated value * Permitted range * Rampup time 24 V DC 24 V 3 %, open-circuit test max. 2.5 s Output current * Rated value Short-circuit protection 10 A, parallel wiring is available electronic, non-latching 1.1 to 1.3 x IN Residual ripple max. 150 mVpp Characteristics Safety class to IEC 536 (DIN VDE 0106, Part 1) I, with protective conductor Isolation rating * Rated isolation voltage (24 V to L1) * Test voltage 250 V AC 4200 V DC Safety isolation SELV circuit Buffering of power supply failure (at 93 V or 187 V) Min. 20 ms * Repeat rate min 1 s Efficiency 90 % Power consumption 267 W Power loss typ. 27 W Diagnostics "Output voltage present" display yes, green LED S7-300 Module data Manual, 06/2017, A5E00105505-AJ 41 Power supply modules 2.4 Power supply module PS 305; 2 A; (6AG1305-1BA80-2AA0) 2.4 Power supply module PS 305; 2 A; (6AG1305-1BA80-2AA0) Order number "SIPLUS S7-300 module" 6AG1305-1BA80-2AA0 Properties Properties of the PS 305 power supply module (2 A): Output current 2 A Output voltage 24 V DC; short circuit-proof, open circuit-proof Connection to DC power supply (rated input voltage 24/48/72/96/110 V DC) safe electrical isolation in accordance with EN 60 950 (SELV) May be used as load power supply Wiring diagram of PS 305; 2 A "24 V DC output voltage present" display Terminals for 24 V DC output voltage Strain relief Mains and protective conductor terminals 24 V DC On/Off switch S7-300 Module data 42 Manual, 06/2017, A5E00105505-AJ Power supply modules 2.4 Power supply module PS 305; 2 A; (6AG1305-1BA80-2AA0) Schematic circuit diagram of PS 305; 2 A Figure 2-4 Schematic circuit diagram of power supply module PS 305; 2 A Line protection The mains supply of the PS 305 power supply module (2 A) should be protected with a miniature circuit-breaker (for example Siemens 5SN1 series) of the following rating: Rated current at 110 V DC: 10 A Tripping characteristics (type): C. Reaction to atypical operating conditions Table 2- 4 Reaction of the PS 305;(2 A) power supply module to atypical operating conditions If ... ... then ... 24 V DC LED ... the output circuit is overloaded: Voltage dip, automatic voltage recovery Flashing * I > 3.9 A (dynamic) * 3 A < I 3.9 A (static) Voltage drop, reduction of service life ... short-circuit at the output Output voltage 0 V; automatic voltage recovery after short-circuit is eliminated off overvoltage on primary side risk of destruction - undervoltage on primary side Automatic shutdown; automatic voltage recovery off S7-300 Module data Manual, 06/2017, A5E00105505-AJ 43 Power supply modules 2.4 Power supply module PS 305; 2 A; (6AG1305-1BA80-2AA0) Technical specifications of the PS 305; 2 A (6AG1305-1BA80-2AA0) Technical specifications Dimensions and weight Dimensions W x H x D (mm) 80 x 125 x 120 Weight ca. 740 g Input parameters Input voltage * Rated value * Voltage range 24/48/72/96/110 V DC 16.8 to 138 V DC Rated input current * at 24 V * at 48 V * at 72 V * at 96 V * at 110 V 2.7 A 1.3 A 0.9 A 0.65 A 0.6 A Inrush current (at 25 C) 20 A I2t (at inrush current) 5 A2s Output parameters Output voltage * Rated value * Permitted range * Rampup time 24 V DC 24 V 3 %, open circuit-proof max. 3 s Output current * 2 A; 1) parallel connection supported Rated value Short-circuit protection electronic, non-latching, 1.65 to 1.95 x IN Residual ripple max. 150 mVpp Characteristics Safety class to IEC 536 (DIN VDE 0106, Part 1) I, with protective conductor Isolation rating * Rated isolation voltage (24 V to input) 150 V AC * Test voltage 2800 V DC Safety isolation SELV circuit Buffering of power supply failure (at 24/48/72/96/110 V) * > 10 ms min. 1 s Repeat rate Efficiency 75% Power consumption 64 W Power loss 16 W Diagnostics "Output voltage present" display 1) At yes, green LED a limited input voltage range > 24 V (24 to 138 V DC), PS 305 can be loaded to 3 A. S7-300 Module data 44 Manual, 06/2017, A5E00105505-AJ Power supply modules 2.5 Power supply module PS 307; 5 A; (6AG1307-1EA80-2AA0) 2.5 Power supply module PS 307; 5 A; (6AG1307-1EA80-2AA0) Order number "SIPLUS S7 module" 6AG1307-1EA80-2AA0 Properties Properties of the PS 307; 5 A power supply module: Output current 5 A Output voltage 24 V DC; short circuit-proof, open circuit-proof Connection to singlephase AC mains (rated input voltage 120/230 V AC, 50/60 Hz) safe electrical isolation in accordance with EN 60 950 (SELV) May be used as load power supply Wiring diagram of PS 307; 5 A "24 V DC output voltage present" display Terminals for 24 V DC output voltage Strain relief Mains and protective conductor terminals 24 V DC On/Off switch Mains selector switch S7-300 Module data Manual, 06/2017, A5E00105505-AJ 45 Power supply modules 2.5 Power supply module PS 307; 5 A; (6AG1307-1EA80-2AA0) Schematic circuit diagram of PS 307; 5 A Figure 2-5 Schematic circuit diagram of power supply module PS 307; 5 A Line protection To protect the mains supply line of the PS 307; 5 A power supply module, you should install a miniature circuit-breaker (for example Siemens 5SN1 series) of the following rating: Rated current at 230 V AC: 10 A Tripping characteristics (type): C. Reaction to atypical operating conditions Table 2- 5 Reaction of the PS 307; 5A power supply module to atypical operating conditions If ... ... then ... 24 V DC LED the output circuit is overloaded: Voltage dip, automatic voltage recovery Flashing * I > 6.5 A (dynamic) * 5 A < I 6.5 A (static) Voltage drop, reduction of service life short-circuit at the output Output voltage 0 V; automatic voltage recovery after short-circuit is eliminated off overvoltage on primary side risk of destruction - undervoltage on primary side Automatic shutdown; automatic voltage recovery off S7-300 Module data 46 Manual, 06/2017, A5E00105505-AJ Power supply modules 2.5 Power supply module PS 307; 5 A; (6AG1307-1EA80-2AA0) Technical specifications of the PS 307; 5 A (6AG1307-1EA80-2AA0) Technical specifications Dimensions and weight Dimensions W x H x D (mm) 80 x 125 x 120 Weight ca. 570 g Input parameters Input voltage * Rated value 120/230 V DC Mains frequency * Rated value * Permitted range 50 Hz or 60 Hz 47 Hz to 63 Hz Rated input current * at 120 V * at 230 V 2.1 A 1.2 A Inrush current (at 25 C) 45 A I2 t 1.8 A2s (at inrush current) Output parameters Output voltage * Rated value * Permitted range * Rampup time 24 V DC 24 V 3 % max. 3 s Output current * Rated value Short-circuit protection 5 A; parallel wiring not supported electronic, non-latching 1.1 to 1.3 x IN Residual ripple max. 150 mVpp Characteristics Safety class to IEC 536 (DIN VDE 0106, Part 1) I, with protective conductor Isolation rating * Rated isolation voltage (24 V to L1) * Test voltage 250 V AC 2800 V DC Safety isolation SELV circuit Buffering of power supply failure (at 93 V or 187 V) min. 20 ms * Repeat rate min. 1 s Efficiency 84 % Power consumption 143 W Power loss 23 W Diagnostics "Output voltage present" display yes, green LED S7-300 Module data Manual, 06/2017, A5E00105505-AJ 47 3 Digital modules Chapter layout Topical structure of this chapter: 1. Chapter overview of which modules are available and described here 2. Overview of essential module properties 3. Steps in selecting and commissioning the digital module 4. General information, i.e. global data applicable to all digital modules (parameter assignment and diagnostics, for example) 5. Module-specific information (properties, connection and block diagrams, technical data and special features of the module): a) for digital input modules b) for digital output modules c) for relay output modules d) for digital IO modules Installation and wiring For information on installation and wiring, refer to the S7-300, CPU 31xC, and CPU 31x Operating Instructions: Installation. The operating instructions are available on the Internet (http://support.automation.siemens.com/WW/view/en/13008499). Further information The structure of parameter sets (data records 0, 1 and 128) is described in the system data section of the appendix. You must be familiar with this structure if you want to modify module parameters in the STEP 7 user program. The structure of diagnostic data (data records 0 and 1) is described in the system data section of the appendix. You must be familiar with this structure if you want to analyze diagnostics data of the modules in the STEP 7 user program. See also Principles of programming signal modules in the user program (Page 522) Evaluating diagnostic data of signal modules in the user program (Page 583) S7-300 Module data 48 Manual, 06/2017, A5E00105505-AJ Digital modules 3.1 Module overview 3.1 Module overview Introduction The tables below summarize the essential properties of the digital modules. This overview supports you in selecting a module to suit your requirements. 3.1.1 Digital input modules: Overview of properties The table below shows essential properties of the digital input modules Table 3- 1 Digital input modules: Module Properties SM 321; DI 64 x 24V; Sinking/Sourcing SM 321; DI 32 x DC24V SM 321; DI 32 x AC120V SM 321; DI 16 x DC24V (-1BP00-) (-1BL00-) (-1EL00-) (-1BH02-) Number of inputs 64 DO; isolated in groups of 16 32 DI; isolated in groups of 16 32 DI; isolated in groups of 8 16 DI; isolated in groups of 16 Rated input voltage 24 VDC 24 VDC 120 VAC 24 VDC Suitable for... - 2-wire, 3-wire and 4-wire proximity switches (BEROs) Supports isochronous mode No No No No Programmable diagnostics No No No No Diagnostic interrupt No No No No Edge-triggered hardware interrupt No No No No Adjustable input delays No No No No Special features - - - - S7-300 Module data Manual, 06/2017, A5E00105505-AJ 49 Digital modules 3.1 Module overview Table 3- 2 Digital input modules (continued) Module Properties Number of inputs SM 321; DI 16 x DC24V High Speed SM 321; DI 16 x DC24V with process and diagnostic interrupts SM 321; DI 16 x DC 24V/125V with process and diagnostic interrupts SM 321; DI 16 x DC24V; (-1BH10-) (-7BH01-) (-7EH00-) (-1BH50-) (-1CH00-) 16 DI; electrically isolated in groups of 16 16 DI; electrically isolated in groups of 16 16 DI; isolated in groups of 16 16 DI, source input, electrically isolated in groups of 16 16 DI; isolated in groups of 1 24 VDC 24 VDC - 125 VDC 24 VDC 24 VDC to 48 VDC Rated input voltage 24 VDC Suitable for... SM 321; DI 16 x UC24/48V source input 24 VAC to 48 VAC Switches; 2-wire, 3-wire and 4-wire proximity switches (BEROs) Supports isochronous mode Yes Yes No No No Programmable diagnostics No Yes Yes No No Diagnostic interrupt No Yes Yes No No Edge-triggered hardware interrupt No Yes Yes No No Adjustable input delays No Yes Yes No No Special features Fast module; especially for isochronous mode 2 short-circuitproof sensor supplies for 8 channels each; --- --- --- External redundant sensor supply is supported S7-300 Module data 50 Manual, 06/2017, A5E00105505-AJ Digital modules 3.1 Module overview Table 3- 3 Digital input modules (continued) Module SM 321; Properties SM 321; SM 321; DI 16 x DC48-125V DI 16 x AC120/230 DI 16 x NAMUR V SM 321; DI 8 x AC 120/230V SM 321; DI 8 x AC 120/230 V ISOL (-1CH20-) (-1FH00-) (-7TH00-) * (-1FF01-) (-1FF10-) 16 DI; isolated in groups of 4 16 DI; isolated in groups of 4 16 DI; isolated in groups of 2 8 DI; isolated in groups of 2 8 DI; isolated in groups of 2 Rated input voltage 120/230 VAC 120/230 VAC 24 VDC 120/230 VAC 120/230 VAC Suitable for... Switches; 2-wire / 3-wire AC proximity switches NAMUR encoder Switches; 2-wire / 3-wire AC proximity switches Number of inputs Switches; 2-wire, 3-wire and 4-wire proximity switches (BEROs) Supports isochronous mode No No No No No Programmable diagnostics No No No No No Diagnostic interrupt No No Yes No No Edge-triggered hardware interrupt No No No No No Adjustable input delays No No No No No Special features --- --- Module with single --channel diagnostics and extensive control functions --- * This module is described in the ET 200M Signal Modules for Process Automation manual. You can find the manual on the Internet (http://support.automation.siemens.com/WW/view/en/7215812). S7-300 Module data Manual, 06/2017, A5E00105505-AJ 51 Digital modules 3.1 Module overview 3.1.2 Digital output modules Overview of properties The table below shows the essential properties of the digital output modules Table 3- 4 Digital output modules Module Properties SM 322; DO 64 x DC24V/0,3A Sourcing SM 322; DO 64 x DC 24V/0,3A Sinking SM 322; DO 32 x DC24V/0,5A SM 322; DO 32 x AC120/230V/1A SM 322; DO 16 x DC24V/0,5A (-1BP00-) (-1BP50-) (-1BL00-) (-1FL00-) (-1BH01-) Number of outputs 64 DO; isolated in 64 DO; isolated in 32 DO; isolated in groups of 16 groups of 16 groups of 8 32 DO; isolated in 16 DO; isolated in groups of 8 groups of 8 Output current 0.3 A 0.3 A 0.5 A 1.0 A 0.5 A Rated load voltage 24 V DC 24 V DC 24 V DC 24 V DC 24 V DC Suitable for... solenoid valves, DC contactors and signal lamps Supports isochronous mode no no No No No Programmable diagnostics No No No No no Diagnostic interrupt No No No No No Substitute value output No No No No No Special features - S7-300 Module data 52 Manual, 06/2017, A5E00105505-AJ Digital modules 3.1 Module overview Table 3- 5 Digital output modules (continued) Module Properties SM 322; DO 16 x SM 322; DO 16 x DC24V/0,5A High UC24/48 V Speed SM 322; DO 16 x AC120/230V/1A (-1BH10-) (-1FH00-) (-5GH00-) SM 322; DO 16 x DC24V/0,5A SM 322; DO 8 x DC24V/2A (-8BH00-)* (-8BH01-) * (-1BF01-) (-8BH10-) Number of outputs 16 DO; isolated in 16 DO; isolated in 16 DO; isolated in 16 DO; isolated in 8 DO; isolated in groups of 8 groups of 1 groups of 8 groups of 4 groups of 4 Output current 0.5 A 0.5 A 1A 0.5 A 2A Rated load voltage 24 V DC 24 to 48 V DC 120/230 V AC 24 V DC 24 V DC 24 to 48 V AC Suitable for... solenoid valves, DC contactors and signal lamps Supports isochronous mode Yes no no no no Programmable diagnostics No Yes no yes no Diagnostic interrupt no Yes No Yes No Yes No Fast module; especially for isochronous mode - - Redundant load control is supported; extensive control functions - Substitute value output Special features S7-300 Module data Manual, 06/2017, A5E00105505-AJ 53 Digital modules 3.1 Module overview Table 3- 6 Digital output modules (continued) Module SM 322; DO 8 x DC24V/0,5A with diagnostics interrupt SM 322; DO 8 x DC48-125V/1,5A SM 322; DO 8 x AC120/230 V/2A SM 322;DO 8 x AC120/230 V/ 2A ISOL (-8BF00-) (-1CF00-) (-1FF01-) (-5FF00-) Number of outputs 8 DO; isolated in groups of 8 8 DO; electrically isolated in groups of 4, with reverse polarity protection 8 DO; isolated in groups of 4 8 DO; isolated in groups of 1 Output current 0.5 A 1.5 A 2A 2A Rated load voltage 24 V DC 48 to 125 V DC 120/230 V AC 120/230 V AC Suitable for... solenoid valves, DC contactors and signal lamps AC solenoid valves, contactors, motor starters, FHP motors and signal lamps. Supports isochronous mode No No No No Programmable diagnostics Yes No no yes Diagnostic interrupt Yes No no yes Substitute value output Yes No no yes Special features - Fuse blown display. Replaceable fuse for each group - Properties Redundant load control is supported * This module is described in the ET 200M Signal Modules for Process Automation manual. You can find the manual on the Internet (http://support.automation.siemens.com/WW/view/en/7215812). S7-300 Module data 54 Manual, 06/2017, A5E00105505-AJ Digital modules 3.1 Module overview 3.1.3 Relay output modules Overview of properties The table below shows the essential properties relay output modules Table 3- 7 Relay output modules Properties Module SM 322; DO 16 x Rel. AC 120 V SM 322; DO 8 x Rel. AC 230 V SM 322; DO 8 x Rel. AC 230 V/ 5 A SM 322; DO 8 x Rel. AC 230 V/ 5 A (-1HH01-) (-1HF01-) (-5HF00-) (-1HF10-) Number of outputs 16 outputs, electrically isolated in groups of 8 8 outputs, electrically isolated in groups of 2 8 outputs, electrically isolated in groups of 1 8 outputs, electrically isolated in groups of 1 Rated load voltage 24 VDC to 120 VDC, 24 VDC to 120 VDC, 24 VDC to 120 VDC, 24 VDC to 120 VDC, 48 VAC to 230 VAC 48 VAC to 230 VAC 24 VAC to 230 VAC 48 VAC to 230 VAC Suitable for... AC/DC solenoid valves, contactors, motor starters, FHP motors and signal lamps Supports isochronous mode no no no no Programmable diagnostics function no no yes no Diagnostics interrupt no no yes no Substitution value output no no yes no Special features - S7-300 Module data Manual, 06/2017, A5E00105505-AJ 55 Digital modules 3.1 Module overview 3.1.4 Digital IO modules Overview of properties The table below shows the essential properties of digital IO modules Table 3- 8 Digital IO modules Properties Module SM 323; DI 16/DO 16 x DC 24 V/ 0,5 A SM 323; DI 8/DO 8 x DC 24 V/0,5 A SM 327; DI 8/DX 8 x DC 24 V/0,5 A, Programmable (-1BL00-) (-1BH01-) (-1BH00-) Number of inputs 16 inputs, electrically isolated in groups of 16 8 inputs, electrically isolated 8 digital inputs, plus 8 sepain groups of 8 rately programmable inputs/outputs, electrically isolated in groups of 16 Number of outputs 16 outputs, electrically isolated in groups of 8 8 outputs, electrically isolated in groups of 8 Rated input voltage 24 VDC 24 VDC 24 VDC Output current 0.5 A 0.5 A 0.5 A Rated load voltage 24 VDC 24 VDC 24 VDC Inputs suitable for... Switches and 2-/3-/4-wire proximity switches (BEROs). Outputs suitable for... solenoid valves, DC contactors and signal lamps Supports isochronous mode no no no Programmable diagnostics no no no Diagnostic interrupt no no no Edge-triggered hardware interrupt no no no Programmable input delay no no no Substitution value output no no no Special features - 8 individually configurable input or outputs; Reading back of inputs is possible, for example, for diagnoses S7-300 Module data 56 Manual, 06/2017, A5E00105505-AJ Digital modules 3.2 Steps in selecting and commissioning the digital module 3.2 Steps in selecting and commissioning the digital module Introduction The table below contains the steps required to successfully complete commission of digital modules. You do not strictly have to adhere to this suggested sequence, that is, you can complete other tasks such as installing or commissioning other modules, or program the module at an earlier or later time. Step sequence Table 3- 9 Steps in selecting and commissioning the digital module Step Procedure See... 1. Selecting the module Chapter Modules overview (Page 49)and the specific module chapter 2. Installing the module in the SIMATIC S7 system Installation chapter in the relevant AS Installation Manual: * S7-300 Automation System, Hardware and Installation, or S7400 / M7-400 Automation System, Hardware and Installation or * Distributed I/O Device ET 200M 3. Assigning module parameters Chapter Diagnostics of digital modules (Page 59) 4. Commission the configuration Commissioning chapter in the relevant installation manual:of the AS used: * S7-300 Automation System, Hardware and Installation, or S7400 / M7-400 Automation System, Hardware and Installation or * 5. ET 200M distributed I/O device Analysis the configuration if commission- Chapter Diagnostics of digital modules (Page 59) ing was not successful. See also Programming digital modules (Page 58) Parameters of digital output modules (Page 528) Module overview (Page 49) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 57 Digital modules 3.3 Programming digital modules 3.3 Programming digital modules Introduction Digital modules may have different properties. You can program the properties of certain modules. All information in this chapter applies only to programmable digital modules: Digital input module SM 321; DI 16 x DC 24 V with process and diagnostic interrupts, isochronous; (6ES7321-7BH01-0AB0) Digital input module SM 321; DI 16 x DC 24 V/125 V with process and diagnostic interrupts (6ES7321-7EH00-0AB0) Digital output module SM 322; DO 16 x DC 24 V/0,5 A (6ES7322-8BH10-0AB0) Digital output module SM 322; DO 8 x DC 24 V/0,5 A with diagnostic interrupt (6ES7322-8BF00-0AB0) Digital output module SM 322; DO 8 x AC120/230 V /2A ISOL (6ES7322-5FF00-0AB0) Digital output module SM 322; DO 8 x Rel. AC230V /5A (6ES7322-5HF00-0AB0) Digital input/output module SM 327; DI 8/DO 8 x DC 24 V/0,5 A (6ES7327-1BH00-0AB0) Programming tools Only program the digital modules in STEP 7 while the CPU is in STOP. After you defined all parameters, download these from your PG to the CPU. During its STOP RUN transition, the CPU transfers the parameters to the relevant digital modules. Static and dynamic parameters Parameters are organized by static and dynamic properties. Set the static parameters while the CPU is in STOP, as described earlier. You may also edit dynamic parameters in the active user program of an S7 PLC using SFCs. However, the parameters set in STEP 7 will be applied again after a RUN STOP, STOP RUN transition of the CPU. The appendix Parameter sets of the signal modules (Page 522) describes the assignment of module parameters in the user program. Parameters programmable using CPU operating state static PG (STEP 7 HW CONFIG) STOP dynamic PG (STEP 7 HW CONFIG) STOP SFC55 in the user program RUN Parameters of digital modules Information on programmable parameters is available in the module-specific chapter. See also Parameters of digital IO modules (Page 524) S7-300 Module data 58 Manual, 06/2017, A5E00105505-AJ Digital modules 3.4 Diagnostics of digital modules 3.4 Diagnostics of digital modules Introduction The information provided in this chapter applies only to S7-300 digital modules with diagnostics functions. Digital input module SM 321; DI 16 x DC 24 V with process and diagnostic interrupts, isochronous; (6ES7321-7BH01-0AB0) Digital input module SM 321; DI 16 x DC 24 V/125 V with process and diagnostic interrupts (6ES7321-7EH00-0AB0) Digital output module SM 322; DO 16 x UC 24/48 V (6ES7322-5GH00-0AB0) Digital output module SM 322; DO 16 x DC 24 V/0,5 A (6ES7322-8BH10-0AB0) Digital output module SM 322; DO 8 x DC 24 V/0,5 A with diagnostic interrupt (6ES7322-8BF00-0AB0) Digital output module SM 322; DO 8 x AC120/230 V /2A ISOL (6ES7322-5FF00-0AB0) Digital output module SM 322; DO 8 x Rel. AC230V /5A (6ES7322-5HF00-0AB0) Programmable and non-programmable diagnostics messages We distinguish between programmable and non-programmable diagnostics messages. You only obtain programmable diagnostics messages if you have enabled diagnostics at the relevant parameters. Program the "Diagnostics" parameter block in STEP 7. Digital modules always return non-programmable diagnostics messages, irrespective of diagnostics being enabled. Reactions to diagnostics message in STEP 7 Actions initiated by diagnostics messages: The diagnostics message will be entered in the diagnostics data of the digital module, and is then passed to the CPU. The SF LED on the digital module is lit. When "Enable Diagnostics Interrupt" is set in STEP 7, the system triggers a diagnostics interrupt and calls OB82. Reading diagnostics messages You can read detailed diagnostics messages using SFCs in the user program (refer to the appendix Diagnostics data of signal modules (Page 583)). In STEP 7, you can view the cause of error by reading the module diagnostics data (refer to the STEP 7 Online Help.) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 59 Digital modules 3.4 Diagnostics of digital modules Diagnostics message using the SF LED Digital modules with diagnostics function indicate errors at their SF LED (group error LED.) The SF LED lights up when the digital module generates a diagnostics message. It goes dark after all error states are cleared. The SF LED also lights up to indicate external errors (short-circuit at the sensor supply), regardless of the CPU operating state (at POWER ON.) Diagnostics messages and interrupt processing of digital modules For information on diagnostics messages, their possible causes, troubleshooting measures, and possible interrupts refer to the specific module chapter. S7-300 Module data 60 Manual, 06/2017, A5E00105505-AJ Digital modules 3.5 How to protect digital modules from inductive overvoltage 3.5 How to protect digital modules from inductive overvoltage Inductive overvoltage Overvoltage occurs when an inductance is deactivated. Examples of this are relay coils and contactors. Integrated overvoltage protection The digital output modules of S7-300 have integrated overvoltage protection equipment. Extra overvoltage protection Inductances should only be configured with extra overvoltage protection equipment in the following instances: If SIMATIC output current circuits can be deactivated by extra fitted contacts (e.g. relay contacts). If the inductive reactances are not activated by SIMATIC modules. Note: Ask the suppliers of inductive reactances what size of overvoltage protection equipment should be used. Example The following diagram shows an output current circuit which make extra overvoltage protection equipment necessary. Contact in output current circuit Inductive reactance needs a protective circuit Figure 3-1 Relay contact for emergency stop in output current circuit S7-300 Module data Manual, 06/2017, A5E00105505-AJ 61 Digital modules 3.5 How to protect digital modules from inductive overvoltage Configuration of coils operated with direct current Coils operated with direct current are shown in the following diagram and configured with diodes or Z diodes. with diode with Z diode Figure 3-2 Configuration of coils operated with direct current Properties of the diode/Z diode circuit: Cut-off currents can be avoided. Z diode withstands a higher cut-off voltage. High cut-off delay (6 to 9 times higher compared to non-protective cidrcuits). Faster cut-off of the Zener diode compared to the diode circuit. Connection of AC-operated coils The operation of AC coils with varistors or RC elements is shown in the diagram. with varistor with RC element Figure 3-3 Connection of AC-operated coils Properties of a circuit with varistor: The amplitude of the cut-off current is limited but not attenuated. The steepness of the overvoltage remains the same. Low cut-off delay. Properties of acircuit with RC elements: Reduction of the amplitude and steepness of the cut-off current. Low cut-off delay. S7-300 Module data 62 Manual, 06/2017, A5E00105505-AJ Digital modules 3.6 Digital input module SM 321; DI 64 x DC 24 V, sinking/sourcing; (6ES7321-1BP00-0AA0) 3.6 Digital input module SM 321; DI 64 x DC 24 V, sinking/sourcing; (6ES7321-1BP00-0AA0) Order number 6ES7321-1BP00-0AA0 Properties Properties of SM 321; DI 64 x DC 24 V, Sinking/Sourcing: 64 inputs, isolated in 4 groups of 16 Rated input voltage 24 V DC Wiring and block diagram of SM 321; DI 64 x DC 24 V, Sinking/Sourcing Channel number Status display - green Backplane bus interface Terminal for "sinking" operating mode Terminal for "sourcing" operating mode S7-300 Module data Manual, 06/2017, A5E00105505-AJ 63 Digital modules 3.6 Digital input module SM 321; DI 64 x DC 24 V, sinking/sourcing; (6ES7321-1BP00-0AA0) Terminal assignment of SM 321; DI 64 x DC 24 V, Sinking/Sourcing The figure below shows how channels are assigned to addresses (input byte x up to input byte x+7). 40-pin terminal block SM321; DI 64 X DC 24 V Sinking/Sourcing features two terminal blocks for connecting actuators and sensors to the module front connector. A connecting cable is used to establish the module connections. S7-300 Module data 64 Manual, 06/2017, A5E00105505-AJ Digital modules 3.6 Digital input module SM 321; DI 64 x DC 24 V, sinking/sourcing; (6ES7321-1BP00-0AA0) The table below shows how channel terminals are assigned to the terminal block for module SM321; DI 64 X DC 24 V Sinking/Sourcing. Terminal Function Terminal Function 1 I x.0 2 I x+2.0 3 I x.1 4 I x+2.1 5 I x.2 6 I x+2.2 7 I x.3 8 I x+2.3 9 I x.4 10 I x+2.4 11 I x.5 12 I x+2.5 13 I x.6 14 I x+2.6 15 I x.7 16 I x+2.7 17 COM 0 18 COM 1 19 I x+1.0 20 I x+3.0 21 I x+1.1 22 I x+3.1 23 I x+1.2 24 I x+3.2 25 I x+1.3 26 I x+3.3 27 I x+1.4 28 I x+3.4 29 I x+1.5 30 I x+3.5 31 I x+1.6 32 I x+3.6 33 I x+1.7 34 I x+3.7 35 COM 0 36 COM 1 37 Not connected 38 Not connected 39 Not connected 40 Not connected Note The COM x terminals must be connected on the terminal block. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 65 Digital modules 3.6 Digital input module SM 321; DI 64 x DC 24 V, sinking/sourcing; (6ES7321-1BP00-0AA0) Technical specifications of SM 321; DI 64 x DC 24 V, Sinking/Sourcing Technical specifications Dimensions and weight Dimensions (W x H x D) (mm) 40 x 125 x 112 (including protective barrier, required for connections which are not in use) Weight ca. 230 g Module-specific data Supports isochronous mode No Number of inputs 64 Cable length * Unshielded * Shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Number of simultaneously controlled inputs * Horizontal installation to 40 C to 60 C * 64 32 (50% derating per group) 32 (50% derating per group) Vertical installation to 40 C Electrical isolation * between channels and the backplane bus * Between channels Yes Yes 16 in groups of Isolation test voltage 500 VDC Current consumption * from the backplane bus Power loss of the module Max. <100 mA Typ. 7 W Status, interrupts, diagnostics Status display Green LED (per channel) Interrupts none Diagnostic functions none S7-300 Module data 66 Manual, 06/2017, A5E00105505-AJ Digital modules 3.6 Digital input module SM 321; DI 64 x DC 24 V, sinking/sourcing; (6ES7321-1BP00-0AA0) Technical specifications Encoder selection data Input voltage * Rated value * "1" signal * "0" signal 24 V DC -13 V to -30 V, 13 V to 30 V - 5 V to + 5 V Input current * Typ. 4.2 mA "1" signal Input delay * "0" to "1" transition * "1" to "0" transition 1.2 ms to 4.8 ms 1.2 ms to 4.8 ms Input characteristics to IEC 61131, type 1 Connection of 2-wire BEROs not supported Input type Sinking/sourcing input Wiring of the signal transmitters Two 40-pin terminal blocks STEP 7 integration 64-channel I/O modules are integrated with the HSP 2019 V 1.0. The HSP forms part of STEP 7 V 5.4 SP2 and can be installed from STEP 7 V 5.4 and higher. GSD/GSDML files The 64-channel I/O modules are supported by the ET 200M versions listed below. Download the corresponding GSD/GSDML files from the following link: on the Internet (http://www.siemens.com/automation/service). To search for PROFIBUS GSD files, type in the entry ID 113498. To search for PROFINET GSDML files, type in the entry ID: 25057900. PROFIBUS IM 153-1, as of 6ES7153-1AA03-0XB0, E12 with GSD file SI01801D.*, version V 1.5 IM 153-2, as of 6ES7153-2BA02-0XB0, E01 with GSD file SI04801E.*, version V 1.0 PROFINET IM 153-4 PN, as of 6ES7153-4AA00-0XB0 with GSDML file version V 2.1 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 67 Digital modules 3.6 Digital input module SM 321; DI 64 x DC 24 V, sinking/sourcing; (6ES7321-1BP00-0AA0) Using the module in S7-300 and ET 200M If the station is configured with STEP 7, you can use the SM 321 digital input module with all CPUs in the following tables. Startup cannot be performed if no configuration is loaded. C-CPUs (compact CPUs) CPU 312C CPU 313C Order number 6ES7312-5BD0x-0AB0 6ES7312-5BE03-0AB0 6ES7312-5BF04-0AB0 6ES7313-5BE0x-0AB0 CPU 313C-2 DP 6ES7313-5BF03-0AB0 6ES7313-5BG04-0AB0 6ES7313-6CE0x-0AB0 CPU313C-2 PtP 6ES7313-6CF03-0AB0 6ES7313-6CG04-0AB0 6ES7313-6BE0x-0AB0 6ES7313-6BF03-0AB0 CPU 314C-2 DP 6ES7313-6BG04-0AB0 6ES7314-6CF0x-0AB0 6ES7314-6CG03-0AB0 CPU 314C-2 PtP 6ES7314-6CH04-0AB0 6ES7314-6BF0x--0AB0 6ES7314-6BG03--0AB0 CPU314C-2 PN/DP M-CPUs CPU 312 CPU 314 CPU 315-2 DP CPU 316-2 DP CPU 317-2 DP CPU 315-2 PN/DP CPU 317-2 PN/DP CPU 319-3 PN/DP 6ES7314-6BH04-0AB0 6ES7314-6EH04-0AB0 Order number 6ES7312-1AD1x-0AB0 6ES7312-1AE13-0AB0 6ES7312-1AE14-0AB0 6ES7314-1AF1x-0AB0 6ES7314-1AG13-0AB0 6ES7314-1AG14-0AB0 6ES7315-2AF0x-0AB0 6ES7315-2AG10-0AB0 6ES7315-2AH14-0AB0 6ES7316-2AG00-0AB0 6ES7317-2AJ10-0AB0 6ES7317-2AK14-0AB0 6ES7315-2EG10-0AB0 6ES7315-2EH13-0AB0 6ES7315-2EH14-0AB0 6ES7317-2EJ10-0AB0 6ES7317-2EK13-0AB0 6ES7317-2EK14-0AB0 6ES7318-3EL00-0AB0 6ES7318-3EL01-0AB0 S7-300 Module data 68 Manual, 06/2017, A5E00105505-AJ Digital modules 3.6 Digital input module SM 321; DI 64 x DC 24 V, sinking/sourcing; (6ES7321-1BP00-0AA0) F-CPUs Order number CPU 315F-2 DP 6ES7315-6FF0x-0AB0 CPU 317F-2 DP 6ES7317-6FF0x-0AB0 CPU 315F-2 PN/DP 6ES7315-2FH1x-0AB0 6ES7315-2FJ14-0AB0 CPU 317F-2 PN/DP 6ES7317-2FJ10-0AB0 6ES7317-2FK13-0AB0 6ES7317-2FK14-0AB0 CPU 319F-3 PN/DP 6ES7318-3FL00-0AB0 6ES7318-3FL01-0AB0 T-CPUs Order number CPU 315T-2 DP 6ES7315-6TG10-0AB0 CPU315T-3 PN/DP 6ES7315-7TJ10-0AB0 CPU 317T-2 DP 6ES7317-6TJ10-0AB0 CPU317TF-2 DP 6ES7317-6TF14-0AB0 CPU317T-3 PN/DP 6ES7317-7TK10-0AB0 CPU317TF-3 PN/DP 6ES7317-7UL10-0AB0 C7-CPUs Order number C7-613 6ES7613-1CA01-0AE3 C7-635 Touch 6ES7635-2EB01-0AE3 C7-635 Key 6ES7635-2EC01-0AE3 C7-636 Touch 6ES7636-2EB00-0AE3 C7-636 Key 6ES7636-2EC00-0AE3 WARNING Use of the module This module must be configured in a STEP 7 project in which the correct address assignment and allocation of the input/output point is ensured. Using the module without having first carried out this configuration work can lead to machines or processes operating in an unexpected manner. If machines or processes do run in an unexpected manner, this can result in death, serious injury, and/or material damage. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 69 Digital modules 3.7 Digital input module SM 321; DI 32 x DC 24 V; (6ES7321-1BL00-0AA0) 3.7 Digital input module SM 321; DI 32 x DC 24 V; (6ES7321-1BL00-0AA0) Order number: "Standard module" 6ES7321-1BL00-0AA0 Order number: "SIPLUS S7-300 module" 6AG1321-1BL00-2AA0 Properties Properties of SM 321; DI 32 x DC 24 V: 32 inputs, isolated in groups of 16 Rated input voltage 24 V DC Suitable for switches and 2-/3-/4-wire proximity switches (BEROs) Wiring and block diagram of SM 321; DI 32 x DC 24 V Channel number Status display - green Backplane bus interface S7-300 Module data 70 Manual, 06/2017, A5E00105505-AJ Digital modules 3.7 Digital input module SM 321; DI 32 x DC 24 V; (6ES7321-1BL00-0AA0) Terminal assignment of SM 321; DI 32 x DC 24 V The figure below shows how channels are assigned to addresses (input byte x up to input byte x+3). Technical specifications of SM 321; DI 32 x DC 24 V Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 120 Weight ca. 260 g Module-specific data Supports isochronous mode No Number of inputs 32 Cable length * Unshielded * Shielded Front connector Max. 600 m Max. 1000 m 40-pin Voltages, currents, potentials Number of simultaneously controlled inputs * Horizontal mounting position to 40 C to 60 C * Vertical arrangement 32 16 32 to 40 C Electrical isolation * between channels and the backplane bus * Between channels - in groups of Isolation test voltage yes Yes 16 500 V DC S7-300 Module data Manual, 06/2017, A5E00105505-AJ 71 Digital modules 3.7 Digital input module SM 321; DI 32 x DC 24 V; (6ES7321-1BL00-0AA0) Technical specifications Current consumption * From the backplane bus Power loss of the module Max. 15 mA Typ. 6.5 W Status, interrupts, diagnostics Status display Green LED per channel Interrupts None Diagnostic functions None Encoder selection data Input voltage * Rated value * "1" signal * "0" signal 24 V DC 13 to 30 V - 30 to + 5 V Input current * "1" signal Typ. 7 mA Input delay * "0" to "1" transition * "1" to "0" transition 1.2 ms to 4.8 ms 1.2 ms to 4.8 ms Input characteristics to IEC 61131, type 1 Connection of 2-wire BEROs Supported * Permissible quiescent current Connection of the signal transmitters Max. 1.5 mA Using a 40-pin front connector S7-300 Module data 72 Manual, 06/2017, A5E00105505-AJ Digital modules 3.8 Digital output module SM 321; DI 32 x AC 120 V; (6ES7321-1EL00-0AA0) 3.8 Digital output module SM 321; DI 32 x AC 120 V; (6ES7321-1EL00-0AA0) Order number 6ES7321-1EL00-0AA0 Properties Properties of SM 321; DI 32 x AC 120 V: 32 inputs, electrically isolated in groups of 8 Rated input voltage 120 VAC Suitable for switches and 2-/3-wire AC proximity switches Wiring and block diagrams SM 321; DI 32 x AC 120 V Channel number Status display - green Backplane bus interface S7-300 Module data Manual, 06/2017, A5E00105505-AJ 73 Digital modules 3.8 Digital output module SM 321; DI 32 x AC 120 V; (6ES7321-1EL00-0AA0) Terminal assignment The figure below shows the channel addressing (input byte x up to input byte x +3). Technical specifications of SM 321; DI 32 x AC 120 V Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 300 g Module-specific data Supports isochronous mode no Number of inputs 32 Cable length * * unshielded shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Number of simultaneously controlled inputs * horizontal mounting position to 40 C to 60 C * vertical mounting position to 40 C 32 24 32 Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of 8 Maximum potential difference * between Minternal and inputs 120 VAC * between inputs of different groups 250 VAC Isolation test voltage 2500 VDC S7-300 Module data 74 Manual, 06/2017, A5E00105505-AJ Digital modules 3.8 Digital output module SM 321; DI 32 x AC 120 V; (6ES7321-1EL00-0AA0) Technical specifications Current consumption * from the backplane bus Power loss of the module max. 16 mA typ. 4 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none Transducer selection data Input voltage * Rated value * "1" signal * "0" signal * Frequency band 120 VAC 74 V to 132 V 0 V to 20 V 47 Hz to 63 Hz Input current * "1" signal typ. 21 mA Input delay * "0" to "1" transition * "1" to "0" transition max. 15 ms max. 25 ms Input characteristics to IEC 61131, type 2 Connection of 2-wire BEROs supported * Permissible quiescent current Wiring the signal transducers max. 4 mA using a 40pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 75 Digital modules 3.9 Digital input module SM 321; DI 16 x DC 24 V; (6ES7321-1BH02-0AA0) 3.9 Digital input module SM 321; DI 16 x DC 24 V; (6ES7321-1BH02-0AA0) Order number: "Standard module" 6ES7321-1BH02-0AA0 Order number: "SIPLUS S7-300 module" 6AG1321-1BH02-2AA0 Properties Properties of SM 321; DI 16 x DC 24 V: 16 inputs, electrically isolated in groups of 16 Rated input voltage 24 V DC suitable for switches and 2- /3-/4-wire proximity switches (BEROs) Wiring and block diagram of SM 321; DI 16 x DC 24 V Channel number Status display - green Backplane bus interface S7-300 Module data 76 Manual, 06/2017, A5E00105505-AJ Digital modules 3.9 Digital input module SM 321; DI 16 x DC 24 V; (6ES7321-1BH02-0AA0) Technical specifications of SM 321; DI 16 x DC 24 V Technical specifications Dimensions and weight Dimensions W x H x D (mm) Weight Module-specific data Supports isochronous mode Number of inputs Cable length * unshielded * shielded 40 x 125 x 117 ca. 200 g no 16 max. 600 m max. 1000 m Voltages, currents, electrical potentials Number of simultaneously controlled inputs * horizontal mounting position to 60 C * vertical mounting position 16 16 to 40 C Electrical isolation * between channels and the backplane bus * between channels * in groups of Isolation test voltage Current consumption * from the backplane bus yes yes 16 500 V DC max. 10 mA Power loss of the module typ. 3.5 W Status, interrupts, diagnostics Status display Interrupts green LED per channel none Diagnostic functions Encoder selection data Input voltage * Rated value * "1" signal * "0" signal none 24 V DC 13 V to 30 V - 30 V to + 5 V Input current * "1" signal typ. 7 mA Input delay * "0" to "1" transition * "1" to "0" transition Input characteristics Connection of 2-wire BEROs * Permissible quiescent current Wiring of the signal transmitters 1.2 ms to 4.8 ms 1.2 ms to 4.8 ms to IEC 61131, type 1 supported max. 1.5 mA using a 20-pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 77 Digital modules 3.10 Digital input module SM 321; DI 16 x DC 24 V High Speed; (6ES7321-1BH10-0AA0) 3.10 Digital input module SM 321; DI 16 x DC 24 V High Speed; (6ES7321-1BH10-0AA0) Order number 6ES7321-1BH10-0AA0 Properties Properties of SM 321; DI 16 x DC 24 V High Speed: 16 inputs, electrically isolated in groups of 16 Rated input voltage 24 V DC suitable for switches and 2- /3-/4-wire proximity switches (BEROs) Supports isochronous mode Wiring and block diagram of SM 321; DI 16 x DC 24 V High Speed Channel number Status display - green Backplane bus interface S7-300 Module data 78 Manual, 06/2017, A5E00105505-AJ Digital modules 3.10 Digital input module SM 321; DI 16 x DC 24 V High Speed; (6ES7321-1BH10-0AA0) Technical specifications of SM 321; DI 16 x DC 24 V High Speed Technical specifications Dimensions and weight Dimensions W x H x D (mm) Weight Module-specific data Supports isochronous mode Number of inputs Cable length * unshielded * shielded 40 x 125 x 117 ca. 200 g yes 16 max. 600 m max. 1000 m Voltages, currents, electrical potentials Number of simultaneously controlled inputs * horizontal mounting position * to 60 C vertical mounting position to 40 C Electrical isolation * between channels and the backplane bus Maximum potential difference * between channels - in groups of Isolation test voltage Current consumption * from the backplane bus Power loss of the module Status, interrupts, diagnostics Status display Interrupts Diagnostic functions Encoder selection data Input voltage * Rated value * "1" signal * "0" signal Input current * "1" signal Input delay * "0" to "1" transition * "1" to "0" transition Input characteristics Connection of 2-wire BEROs * Permissible quiescent current Wiring of the signal transmitters 16 16 yes yes 16 500 V DC max. 110 mA typ. 3.8 W green LED per channel none none 24 V DC 13 V to 30 V - 30 V to + 5 V typ. 7 mA 25 s to 75 s 25 s to 75 s to IEC 61131, type 1 supported max. 1.5 mA using a 20-pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 79 Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH010AB0) 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH01-0AB0) Order number: "Standard module" 6ES7321-7BH01-0AB0 Order number: "SIPLUS S7-300 module" 6AG1321-7BH01-2AB0 Properties Properties of SM 321; DI 16 x DC 24 V with hardware and diagnostic interrupts: 16 inputs, electrically isolated in groups of 16 Rated input voltage 24 V DC Input characteristics to IEC 61131, Type 2 suitable for switches and 2- /3-/4-wire proximity switches (BEROs) 2 short circuitproof sensor supplies for each group of 8 channels external redundant sensor supply is supported "Sensor supply (Vs)" status display Group error display (SF) Supports isochronous mode Supports parameter reassignment in RUN Programmable diagnostics Programmable diagnostic interrupt Programmable hardware interrupts Programmable input delays S7-300 Module data 80 Manual, 06/2017, A5E00105505-AJ Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH01-0AB0) Wiring and block diagram of SM 321; DI 16 x DC 24 V Channel number Status displays - green Error displays - red Sensor supply VS -green Backplane bus interface Wire-break detection Wiring diagram of the redundant sensor supply The figure below shows how an additional redundant voltage source can be used to power sensors using Vs. Figure 3-4 Wiring diagram of the redundant supply of sensors of SM 321; DI 16 x DC 24 V S7-300 Module data Manual, 06/2017, A5E00105505-AJ 81 Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH010AB0) Wiring diagram of the shunt circuit of the sensors For wire-break detection, it is necessary to connect a shunt resistor to the transducer contacts. Figure 3-5 Wiring diagram of the shunt circuit of transducers of SM 321; DI 16 x DC 24 V S7-300 Module data 82 Manual, 06/2017, A5E00105505-AJ Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH01-0AB0) Technical specifications of SM 321; DI 16 x DC 24 V Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 200 g Module-specific data Supports isochronous mode yes Supports parameter reassignment in RUN yes * Response of non-programmed inputs Number of inputs return the process value which was valid before configuration 16 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated supply voltage L+ for the electronic system and sensors * Reverse polarity protection 24 V DC yes Number of simultaneously controlled inputs * horizontal mounting position to 60 C * vertical mounting position to 40 C 16 16 Electrical isolation * between channels and the backplane bus * between channels - yes 16 In groups of Isolation test voltage 500 V DC Current consumption * from the backplane bus max. 130 mA * from load voltage L + (without sensor supply VS) max. 90 mA Power loss of the module typ. 4 W S7-300 Module data Manual, 06/2017, A5E00105505-AJ 83 Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH010AB0) Technical specifications Status, interrupts, diagnostics Status display * Inputs green LED per channel * Sensor supplies (Vs) green LED per output Interrupts * Hardware interrupt * Diagnostic interrupt Diagnostic functions programmable programmable programmable * Group error display red LED (SF) * Reading diagnostic information supported Monitoring for * wirebreak yes, sensing I < 1 mA Sensor supply outputs Number of outputs 2 Output voltage * on load min. L+ (- 2.5 V) Output current * Rated value * Permitted range 120 mA 0 mA to 150 mA Additional (redundant) supply supported Short-circuit protection yes, electronic Encoder selection data Input voltage * Rated value * "1" signal * "0" signal 24 V DC 13 V to 30 V -30 V to + 5 V Input current * "1" signal typ. 7 mA Input characteristics to IEC 61131, type 2 Connection of 2-wire BEROs supported * Permissible quiescent current max. 2 mA Wiring of the signal transmitters using a 20-pin front connector Shunt circuit of the sensor for wire-break detection 10 kohms to 18 kohms S7-300 Module data 84 Manual, 06/2017, A5E00105505-AJ Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH01-0AB0) Technical specifications Time/frequency Internal preparation time for diagnostics (in non-isochronous mode) * Enabling of process and diagnostic interrupts max. 40 ms Input delay * programmable * Rated value yes typ. 0.1/0.5/3/15/20 ms Configuration in RUN Special considerations must be given if you use the Configuration in RUN function. SF LED is lit: Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or module), although diagnostics are no longer pending and the module is operating correctly. Solution: Only change the configuration when no diagnostics are pending for the module or Pulling and plugging the module. 3.11.1 Isochronous mode Properties Reproducible reaction times (i.e. of the same length) are achieved in a SIMATIC system by means of a constant DP bus cycle, and synchronization of the single cyclic processes outlined below: Independent user program cycle. The length of the cycle time may vary due to non-cyclic program branching. Independent and variable DP cycle on the PROFIBUS subnet Cyclic operation of the backplane bus of the DP slave. Cyclic signal conditioning and conversion at the electronic modules of the DP slave. The constant DP cycle runs in synchronism and at the same length. The CPU run levels (OB61 to OB64) and isochronous IO are synchronized with this cycle. I/O data are therefore transferred at defined and constant intervals (isochronous mode.) Requirements The DP master and slave must support isochronous mode. STEP 7 V5.2 or higher. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 85 Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH010AB0) Operating mode: Isochronous mode Conditions of isochronous mode: Filtering and processing time TWE between reading actual values and writing these to the transfer buffer(the value defined for TWE applies, irrespective of the enable status of diagnostics) 255 s to 345 s includes an input delay time of 100 s TDPmin 2.5 ms Diagnostic interrupt max. 4 x TDP Note In "isochronous" mode, the input delay is automatically set to 100 s, regardless of the input delay setting in STEP 7 Further information You can find additional information on isochronous mode in the online help for STEP 7 and in the operating instructions Distributed I/O System ET 200M. (http://support.automation.siemens.com/WW/view/en/1142798) 3.11.2 SM 321; DI 16 x DC 24 V - Parameters Programming The general procedure of programming digital modules is described in the chapter Programming digital modules (Page 58). Parameters of SM 321; DI 16 x DC 24 V The table below shows an overview of configurable parameters and their default settings for SM 321; DI 16 x DC 24 V. S7-300 Module data 86 Manual, 06/2017, A5E00105505-AJ Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH01-0AB0) The default settings apply if you have not set any parameters in STEP 7. Table 3- 10 Parameters of SM 321; DI 16 x DC 24 V Parameters Range of values Default Parameter type Scope Yes/No No dynamic Module Yes/No No 0.1 ms (DC) (DC) static Module Yes/No No static Channel group Yes/No No Yes/No No dynamic Channel group Yes/No No Enable * * Diagnostic interrupt Hardware interrupt Input delay/voltage type 0.5 ms (DC) 3 ms (DC) 15 ms (DC) 20 ms (DC/AC) Diagnosis encoder supply missing * Wire break Hardware interrupt trigger * * Positive edge Negative edge Allocating the sensor supplies to channel groups The module's two sensor supplies power the two channel groups: Inputs 0 to 7 and inputs 8 to 15. You also configure the diagnostics for the encoder supply in these channel groups. Assigning interrupt parameters to channel groups The table below shows which channels you can group for interrupt processing. The channel group number is required to program SFC parameters in the user program. Table 3- 11 Assigning interrupt parameters to the inputs of SM 321; DI 16 x DC 24 V Parameters... * * * Programmable in the following channel groups Channel group number Hardware interrupt (triggered at the positive, negative, or both edges) 0 and 1 0 2 and 3 1 Diagnostic interrupt for wire break 4 and 5 2 6 and 7 3 8 and 9 4 10 and 11 5 12 and 13 6 14 and 15 7 0 to 7 - Diagnostic interrupt for missing encoder supply 8 to 15 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 87 Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH010AB0) Tolerances of the programmable input delays Table 3- 12 Tolerances of the input delays at SM 321; DI 16 x DC 24 V Programmed input delay Tolerance 0.1 ms 60 s to 140 s 0.5 ms 400 s to 900 s 3 ms (default) 2.6 ms to 3.3 ms 15 ms 12 ms to 15 ms 20 ms 17 ms to 23 ms 3.11.3 SM 321; DI 16 x DC 24 V - Diagnostics Diagnostic messages of SM 321; DI 16 x DC 24 V The table below shows an overview of the diagnostic messages of SM 321; DI 16 x DC 24 V. Table 3- 13 Diagnostic messages of SM 321; DI 16 x DC 24 V Diagnostic message LED Scope of diagnostics Sensor supply missing SF Channel group Wire break SF Channel group Module not programmed SF Channel group External auxiliary voltage missing SF Module Internal auxiliary voltage missing SF Module Fuse blown SF Module Incorrect module parameters SF Module Watchdog time-out SF Module EPROM fault SF Module RAM fault SF Module Hardware interrupt lost SF Module programmable yes no Note A prerequisite for detecting faults indicated by programmable diagnostic messages is an appropriate configuration of the digital module in STEP 7. S7-300 Module data 88 Manual, 06/2017, A5E00105505-AJ Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH01-0AB0) Note Wire break diagnostics Wire break diagnostics is always used for one channel group with two channels. It is only possible to determine that one of the two channels has suffered a wire break; it is not possible to identify which one. When operated with PCS7, only one channel of the group can be used at any time for an exact diagnosis. Causes of error and troubleshooting Table 3- 14 Diagnostics Messages of the SM 321; DI 16 x DC 24 V, causes of error and troubleshooting Diagnostic message Possible cause of error To correct or avoid error Sensor supply missing Overload at sensor supply Eliminate overload Short-circuit to M at sensor supply Eliminate the short-circuit External auxiliary voltage missing Power supply L+ to module missing Feed supply L+ Internal auxiliary voltage missing Power supply L+ to module missing Feed supply L+ Fuse blown in module Replace the module Fuse blown Fuse blown in module Replace the module Incorrect module parameters Implausible parameter or combination thereof Program the module Watchdog timeout Infrequent high electromagnetic interference Eliminate the interference Module defective Replace the module Infrequent high electromagnetic interference Eliminate interference and cycle the power supply of CPU off/on. Module defective Replace the module Infrequent high electromagnetic interference Eliminate interference and cycle the power supply of CPU off/on. Module defective Replace the module The module can not output an interrupt, because the previous interrupt was not acknowledged; possibly a configuration error Change interrupt processing in the CPU, and reprogram the module as required EPROM fault RAM fault Hardware interrupt lost Module not programmed Startup error The error persists until the module is assigned new parameters Program the module S7-300 Module data Manual, 06/2017, A5E00105505-AJ 89 Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH010AB0) 3.11.4 SM 321; DI 16 x DC 24 V - Behavior Influence of the operating state and supply voltage on input values The SM 321; DI 16 x DC 24 input values are determined by the CPU's operating state and the module's power supply. Table 3- 15 Dependency of input values on the CPU's operating state, and on the L+ power supply of SM 321; DI 16 x DC 24 V CPU operating state POWER ON RUN STOP POWER OFF - Power supply L+ at digital module input value of the digital module L+ present Process value L+ missing 0 signal L+ present Process value L+ missing 0 signal L+ present - L+ missing - Reaction to power failure Failure of the SM 321; DI 16 x DC 24 power supply is always indicated by the module's SF LED. This information is also available on the module. The input value is initially held for the duration of 20 ms to 40 ms before the zero signal is transferred to the CPU. Supply voltage dips <20 ms do not influence the process value (see the table above.) Triggering of diagnostic interrupts is determined by the parameter settings (see chapter Interrupts of SM 321; DO 16 x DC 24 V (Page 91)). Power supply failure with redundant external sensor supply Note When an external redundant power source is connected in parallel to the sensor supply (Vs) and the L+ power supply fails, the module does not report failure of the sensor supply, but rather the failure of the internal and/or external auxiliary voltage, and/or a blown fuse. Short-circuit at the sensor supply Vs The relevant Vs LED goes dark if a short-circuit is detected at the sensor supply Vs, irrespective of parameter settings. S7-300 Module data 90 Manual, 06/2017, A5E00105505-AJ Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH01-0AB0) 3.11.5 SM 321; DI 16 x DC 24 V - Interrupts Introduction This chapter describes the interrupt reaction of SM 321; DI 16 x DC 24 V. Always distinguish between the following interrupts: Diagnostic interrupt Hardware interrupt For detailed information on the OBs and SFCs mentioned below, refer to the STEP 7 Online Help. Enabling interrupts There is no default interrupt setting, i.e. interrupts are disabled if parameters are not set accordingly. You can enable interrupts in STEP 7 (see the chapter Parameters of SM 321; DI 16 x DC 24 V (Page 86)). S7-300 Module data Manual, 06/2017, A5E00105505-AJ 91 Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH010AB0) Diagnostic interrupt When diagnostic interrupts are enabled, incoming error events (initial occurrence) and outgoing error events (error is cleared) are reported by means of an interrupt. The CPU interrupts user program execution in order to process diagnostic interrupt OB82. You can call SFC51 or 59 in OB82 in the user program to view detailed diagnostics data output by the module. Diagnostics data remain consistent until the program exits OB82. The module acknowledges the diagnostic interrupt when the program exits OB82. Hardware interrupt SM 321; DI 16 x DC 24 V can trigger a hardware interrupt for each channel group at the positive, negative, or both edges of a signal transition. Program each channel group separately. The parameters can be changed at any time (in RUN mode in the user program.) Active hardware interrupts trigger hardware interrupt processing in the CPU (OB40) and interrupt execution of the user program or of object classes with lower priority in the CPU. You can define the response of the AS to signal edge transitions in the user program of hardware interrupt OB40. The module acknowledges the hardware interrupt when the program exits the hardware interrupt OB. The module can save one interrupt per channel to the stack. If no higher priority classes are pending processing, the CPU processes the buffered interrupts (of all modules) in the order of their occurrence. Hardware interrupt lost A "Hardware interrupt lost" diagnostic interrupt is generated if a successive interrupt is triggered at the channel previously saved to the stack and which has not yet been processed by the CPU. The CPU does not register any further interrupts at this channel unless it has completed processing of the queued interrupts of the same channel. Interrupt-triggering channels The relevant hardware interrupt-triggering channel is logged in the OB40_POINT_ADDR variable of the start information of OB40. The figure shows the bit assignments of DWORD 8 in the local data. Byte Variable Data type 6/7 OB40_MDL_ADDR WORD B#16#0 Description Address of the interrupt-triggering module starting at 8 OB40_POINT_ADDR DWORD see the figure below Indication of the interrupt-triggering inputs S7-300 Module data 92 Manual, 06/2017, A5E00105505-AJ Digital modules 3.11 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts (6ES7321-7BH01-0AB0) Figure 3-6 Start Information of OB40: which event has triggered the hardware interrupt S7-300 Module data Manual, 06/2017, A5E00105505-AJ 93 Digital modules 3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES73217EH00-0AB0) 3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES7321-7EH00-0AB0) Order number: 6ES7321-7EH00-0AB0 Properties Properties of SM 321; DI 16 x DC 24 V/125 V; with hardware and diagnostic interrupts: 16 inputs, electrically isolated in groups of 16 Rated input voltage 24 to 125 V DC Input characteristics to IEC 61131, Type 1 suitable for switches and 2- /3-/4-wire proximity switches (BEROs) Group error display (SF) Supports parameter reassignment in RUN Channel-based configurable diagnostics Programmable diagnostic interrupt Channel-based configurable hardware interrupts Programmable input delays WARNING * Electrical hazard arises with electric circuits operated with voltages - >30 Veff and 42.4 Vpeak - 60 VDC. * It is not permitted to mix electrically safe and dangerous contact input voltages on the 16 inputs of the same module. S7-300 Module data 94 Manual, 06/2017, A5E00105505-AJ Digital modules 3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES7321-7EH00-0AB0) Wiring and block diagram of SM 321; DI 16 x DC 24 V/125 V Channel number Status displays - green Error displays - red Backplane bus interface Wiring diagram of the shunt circuit of the sensors For wire-break detection, it is necessary to connect a shunt resistor to the transducer contacts. Figure 3-7 Wiring diagram of the shunt circuit of transducers of SM 321; DI 16 x DC 24 V/125 V S7-300 Module data Manual, 06/2017, A5E00105505-AJ 95 Digital modules 3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES73217EH00-0AB0) The resistance used depends on the module's rated input voltage Table 3- 16 Dependence on rated input voltage and resistance Rated input voltage L+ Resistance Rs 24 V DC 43 k 48 V DC 100 k 125 V DC 300 k SM 321; DI 16 x DC 24 V/125V - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight approx. 200 g Module-specific data Supports isochronous mode No Supports parameter reassignment in RUN Yes * Response of non-programmed inputs return the process value which was valid before configuration Accuracy of the time stamp > 5 ms* Number of inputs 16 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Number of simultaneously controlled inputs * * Horizontal mounting position to 60 C - L+ = 146 VDC - L+ = 125 VDC - L+ = 100 VDC Vertical mounting position to 40 C - L+ = 146 VDC - L+ = 125 VDC - L+ = 100 VDC 8 12 16 8 12 16 Electrical isolation * between channels and the backplane bus * between channels Yes No Maximum potential difference * between different circuits Isolation test voltage 300 V DC / 250 V AC 3500 VDC S7-300 Module data 96 Manual, 06/2017, A5E00105505-AJ Digital modules 3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES7321-7EH00-0AB0) Technical specifications Current consumption * from the backplane bus max. 90 mA Power loss of the module * L+ = 24 V * L+ = 100 V typ. 2 W typ. 6.5 W Status, interrupts, diagnostics Status displays green LED per channel Interrupts * Hardware interrupt * Diagnostic interrupt * Wire break Diagnostic functions programmable programmable programmable programmable * Group error display red LED (SF) * Reading diagnostics information supported Monitoring for * Wire break yes, sensing I < 1 mA Encoder selection data Input voltage * Rated value * "1" signal * "0" signal From 15 to 146 V from -146 V to + 5 V Input current * "1" signal Typ. 3.5 mA Input characteristics to IEC 61131, Type 1 Connection of 2-wire BEROs supported * Permissible quiescent current Wiring of the signal transmitters max. 1 mA with 40-pin front connector Time/frequency Input delay * programmable * Rated value Yes typ. 0.1/0.5/3/15/20 ms** Fixed current limitation of the sensor for wire-break detection See previous table for dependence on rated input voltage and resistance Overvoltage protection Dehnconnect RK DCO RK ME110; Art. No. 919 923 * To obtain a time stamp accuracy of < 1 ms, the input delay must be configured to 0.1 ms. ** To obtain a high immunity to interference, use a shielded cable and set input delay to 0.1 ms. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 97 Digital modules 3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES73217EH00-0AB0) Configuration in RUN Special considerations must be given if you use the Configuration in RUN function. SF LED is lit: Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or module), although diagnostics are no longer pending and the module is operating correctly. Solution: Only change the configuration when no diagnostics are pending for the module or Pulling and plugging the module. 3.12.1 Parameters of SM 321; DI 16 x DC 24/125 V Programming The general procedure of programming digital modules is described in the chapter Programming digital modules. Parameters of SM 321; DI 16 x DC 24 V/125 V The table below shows an overview of configurable parameters and their default settings for SM 321; DI 16 x DC 24 V/125V. The default settings apply if you have not set any parameters in STEP 7. Table 3- 17 Parameters of SM 321; DI 16 x DC 24 V/125 V Parameters Range of values Default Parameter type Efficiency range Yes/No No dynamic Module Yes/No No 0.1 ms (DC) 3 ms (DC) static Module Yes/No No static Channel Yes/No No dynamic Channel Yes/No No Enable * * Diagnostic interrupt Hardware interrupt Input delay/voltage type 0.5 ms (DC) 3 ms (DC) 15 ms (DC) 20 ms (DC/AC) Diagnostics * Wire break Hardware interrupt trigger * Positive edge * Negative edge S7-300 Module data 98 Manual, 06/2017, A5E00105505-AJ Digital modules 3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES7321-7EH00-0AB0) Tolerances of the programmable input delays Table 3- 18 Tolerances of the input delays of SM 321; DI 16 x DC 24 V/125 V Programmed input delay Tolerance 0.1 ms 80 s to 200 s 0.5 ms 580 s to 700 s 3 ms (default) 3.1 ms to 3.7 ms 15 ms 15.1 ms to 18.1 ms 20 ms 20.1 ms to 24.1 ms Note The timers for the input delay are only valid for reading in the status. In the case of wirebreak, "Wire-break diagnostics" is only triggered approx. 40 ms after the reading in of the value. 3.12.2 Diagnostics of SM 321; DI 16 x DC 24/125 V Diagnostic messages of SM 321; DI 16 x DC 24 V/125 V The table below shows an overview of the diagnostic messages of SM 321; DI 16 x DC 24 V/125 V. Table 3- 19 Diagnostic messages of SM 321; DI 16 x DC 24 V/125 V Diagnostic message LED Scope of diagnostics Wire break SF Channel No channel parameters SF Channel No/incorrect parameters in module SF Module Time monitoring activated (watchdog) SF Module EPROM fault SF Module RAM fault SF Module Hardware interrupt lost SF Module programmable Yes No Note To detect the errors indicated by programmable diagnostic messages, you must have programmed the digital module accordingly in STEP 7. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 99 Digital modules 3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES73217EH00-0AB0) Special features of diagnostics The SM 321; DI 16 x DC 24 V/125 V supplies 9-byte diagnostic data (diagnostic data set 0 with a length of 4 bytes and the diagnostic data set 1 with a length of 9 bytes). The wire-break diagnostics is only reported in the channel error vector of the data set 1 (bytes 7 and 8). Each channel that reports an error in the channel errror vector has a wirebreak. You can find additional information, in chapter Structure and content of diagnostics data, byte 0 and up (Page 584). Causes of error and troubleshooting Table 3- 20 Diagnostics messages of SM 321; DI 16 x DC 24 V/125V, causes of error and troubleshooting Diagnostic message Possible cause of error Incorrect module parameters Implausible parameter or combination thereof Program the module Time monitoring activated (watchdog) Infrequent high electromagnetic interference Eliminate the interference Module defective Replace the module EPROM fault Infrequent high electromagnetic interference Eliminate interference and cycle the power supply of CPU off/on. Module defective Replace the module Infrequent high electromagnetic interference Eliminate interference and cycle the power supply of CPU off/on. Module defective Replace the module The module can not output an interrupt, because the previous interrupt was not acknowledged; possibly a configuration error Change interrupt processing in the CPU, and reprogram the module as required RAM fault Hardware interrupt lost Module not programmed 3.12.3 Startup error To correct or avoid error The error persists until the module is assigned new parameters Program the module Interrupts of SM 321; DI 16 x DC 24/125 V Introduction This chapter describes the interrupt reaction of SM 321; DI 16 x DC 24 V/125V. Always distinguish between the following interrupts: Diagnostic interrupt Hardware interrupt For detailed information on the OBs and SFCs mentioned below, refer to the STEP 7 Online Help. S7-300 Module data 100 Manual, 06/2017, A5E00105505-AJ Digital modules 3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES7321-7EH00-0AB0) Enabling interrupts There is no default interrupt setting, i.e. interrupts are disabled if parameters are not set accordingly. You can enable interrupts in STEP 7 (see the chapter Parameters of SM 321; DI 16 x DC 24 V ). Diagnostic interrupt When diagnostic interrupts are enabled, incoming error events (initial occurrence) and outgoing error events (error is cleared) are reported by means of an interrupt. The CPU interrupts user program execution in order to process diagnostic interrupt OB82. You can call SFC51 or 59 in OB82 in the user program to view detailed diagnostics data output by the module. Diagnostics data remain consistent until the program exits OB82. The module acknowledges the diagnostic interrupt when the program exits OB82. Hardware interrupt SM 321; DI 16 x DC 24 V/125V can trigger a hardware interrupt for each channel group at the positive, negative, or both edges of a signal transition. You perform parameter assignment for each channel separately. The parameters can be changed at any time (in RUN mode in the user program.) Active hardware interrupts trigger hardware interrupt processing in the CPU (OB40) and interrupt execution of the user program or of object classes with lower priority in the CPU. You can define the response of the AS to signal edge transitions in the user program of hardware interrupt OB40. The module acknowledges the hardware interrupt when the program exits the hardware interrupt OB. The module can save one interrupt per channel to the stack. If no higher priority classes are pending processing, the CPU processes the buffered interrupts (of all modules) in the order of their occurrence. Hardware interrupt lost A "Hardware interrupt lost" diagnostic interrupt is generated if a successive interrupt is triggered at the channel previously saved to the stack and which has not yet been processed by the CPU. The CPU does not register any further interrupts at this channel unless it has completed processing of the queued interrupts of the same channel. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 101 Digital modules 3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES73217EH00-0AB0) Interrupt-triggering channels The relevant hardware interrupt-triggering channel is logged in the OB40_POINT_ADDR variable of the start information of OB40. The figure shows the bit assignments of DWORD 8 in the local data. Byte Variable Data type 6/7 OB40_MDL_ADDR WORD B#16#0 Address of the interrupt-triggering module starting at 8 OB40_POINT_ADDR DWORD see the figure below Indication of the interrupt-triggering inputs Figure 3-8 Description Start Information of OB40: which event has triggered the hardware interrupt S7-300 Module data 102 Manual, 06/2017, A5E00105505-AJ Digital modules 3.13 Digital input module SM 321; DI 16 x DC 24 V; source input; (6ES7321-1BH50-0AA0) 3.13 Digital input module SM 321; DI 16 x DC 24 V; source input; (6ES7321-1BH50-0AA0) Order number 6ES7321-1BH50-0AA0 Properties Properties of SM 321; DI 16 x DC 24 V; source input: 16 inputs, source input, electrically isolated in groups of 16 Rated input voltage 24 V DC Suitable for switches and 2- /3-/4-wire proximity switches (BEROs) Wiring and block diagram of SM 321; DI 16 x DC 24 V Channel number Status display - green Backplane bus interface S7-300 Module data Manual, 06/2017, A5E00105505-AJ 103 Digital modules 3.13 Digital input module SM 321; DI 16 x DC 24 V; source input; (6ES7321-1BH50-0AA0) SM 321; DI 16 x DC 24 V - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) Weight Module-specific data Supports isochronous mode Number of inputs Cable length * unshielded * shielded 40 x 125 x 117 ca. 200 g no 16 max. 600 m max. 1000 m Voltages, currents, electrical potentials Number of simultaneously controlled inputs * horizontal mounting position 16 to 60 C * vertical mounting position 16 to 40 C Electrical isolation * between channels and the backplane bus yes * between channels in groups of yes 16 Isolation test voltage Current consumption 500 V DC * from the backplane bus max. 10 mA Power loss of the module Status, interrupts, diagnostics typ. 3.5 W Status display Interrupts Diagnostic functions green LED per channel none none Encoder selection data Input voltage (reference potential L+) * Rated value * "1" signal * "0" signal 24 V DC -13 V to -30 V +30 V to -5 V Input current * "1" signal typ. 7 mA Input delay * "0" to "1" transition * "1" to "0" transition Input characteristics Connection of 2-wire BEROs * Permissible quiescent current Wiring of the signal transmitters 1.2 ms to 4.8 ms 1.2 ms to 4.8 ms to IEC 61131, type 1 supported max. 1.5 mA using a 20-pin front connector S7-300 Module data 104 Manual, 06/2017, A5E00105505-AJ Digital modules 3.14 Digital input module SM 321; DI 16 x UC 24/48 V; (6ES7321-1CH00-0AA0) 3.14 Digital input module SM 321; DI 16 x UC 24/48 V; (6ES7321-1CH00-0AA0) Order number 6ES7321-1CH00-0AA0 Properties Properties of SM 321; DI 16 x UC24/48 V: 16 inputs, electrically isolated Electrical isolation between channels of 120 V AC Rated input voltage 24 VDC/VAC to 48 VDC/VAC Inputs are autarkic and can be wired to suit any configuration Wiring and block diagram of SM 321; DI 16 x UC 24/48 V Channel number Status display - green Backplane bus interface S7-300 Module data Manual, 06/2017, A5E00105505-AJ 105 Digital modules 3.14 Digital input module SM 321; DI 16 x UC 24/48 V; (6ES7321-1CH00-0AA0) SM 321; DI 16 x UC 24/48 V - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D 40 x 125 x 117 Weight ca. 260 g Module-specific data Supports isochronous mode no Number of inputs 16 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Number of simultaneously controlled inputs * horizontal mounting position up to 60 C 16 * other mounting positions up to 40 C 16 Electrical isolation * Between channels and the backplane bus Yes * between channels Yes In groups of 1 Maximum potential difference * Between channels and the backplane bus 170 VDC, 120 VAC * between inputs of different groups 170 VDC, 120 VAC Isolation test voltage * Between channels and the backplane bus 1500 VAC * between inputs of different groups 1500 VAC Current consumption * from the backplane bus 100 mA max. Power loss of the module * Operation with 24 V * Operation with 48 V typ. 1.5 W typ. 2.8 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none S7-300 Module data 106 Manual, 06/2017, A5E00105505-AJ Digital modules 3.14 Digital input module SM 321; DI 16 x UC 24/48 V; (6ES7321-1CH00-0AA0) Technical specifications Sensor selection data Input voltage * Rated value 24 VDC/VAC or 48 VDC/VAC * "1" signal 14 V to 60 V * "0" signal * Frequency band -5 V to 5 V 0 Hz to 63 Hz Input current * "1" signal * "0" signal typ. 2.7 mA -1 mA to +1 mA Input delay * "0" to "1" transition * "1" to "0" transition max. 16 ms max. 16 ms Input characteristics to IEC 61131, type 1 Connection of 2-wire BEROs supported * Permissible quiescent current Wiring of the signal sensors max. 1 mA using a 40-pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 107 Digital modules 3.15 Digital input module SM 321; DI 16 x DC 48-125 V; (6ES7321-1CH20-0AA0) 3.15 Digital input module SM 321; DI 16 x DC 48-125 V; (6ES7321-1CH20-0AA0) Order number: "Standard module" 6ES7321-1CH20-0AA0 Order number: "SIPLUS S7-300 module" 6AG1321-1CH20-2AA0 Properties Properties of SM 321; DI 16 x DC 48-125 V: 16 inputs, electrically isolated in groups of 8 Rated input voltage 48 VDC to 125 VDC suitable for switches and 2- /3-/4-wire proximity switches (BEROs) Wiring and block diagram of SM 321; DI 16 x DC 48-125 V Channel number Status display - green Backplane bus interface S7-300 Module data 108 Manual, 06/2017, A5E00105505-AJ Digital modules 3.15 Digital input module SM 321; DI 16 x DC 48-125 V; (6ES7321-1CH20-0AA0) SM 321; DI 16 x DC 48-125 V - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 120 Weight ca. 200 g Module-specific data Supports isochronous mode no Number of inputs 16 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Number of simultaneously controlled inputs per group at UI * horizontal mounting position to 50 C to 60 C * vertical mounting position to 60 V to 146 V 8 8 8 6 8 8 to 40 C Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of 8 Maximum potential difference * between different circuits Isolation test voltage 146 VDC / 132 VAC 1500 VDC Current consumption * from the backplane bus Power loss of the module max. 40 mA typ. 4.3 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none S7-300 Module data Manual, 06/2017, A5E00105505-AJ 109 Digital modules 3.15 Digital input module SM 321; DI 16 x DC 48-125 V; (6ES7321-1CH20-0AA0) Technical specifications Sensor selection data Input voltage * Rated value 48 VDC to 125 VDC * "1" signal 30 V to 146 V * "0" signal -146 V to 15 V Input current * "1" signal typ. 3.5 mA Input delay * "0" to "1" transition * "1" to "0" transition 0.1 ms to 3.5 ms 0.7 ms to 3.0 ms Input characteristics to IEC 61131, type 1 Connection of 2-wire BEROs supported * Permissible quiescent current Wiring the signal transducers max. 1 mA using a 20-pin front connector S7-300 Module data 110 Manual, 06/2017, A5E00105505-AJ Digital modules 3.16 Digital input module SM 321; DI 16 x AC 120/230 V; (6ES7321-1FH00-0AA0) 3.16 Digital input module SM 321; DI 16 x AC 120/230 V; (6ES7321-1FH00-0AA0) Order number 6ES7321-1FH00-0AA0 Properties Properties of SM 321, DI 16 x AC 120/230 V: 16 inputs, electrically isolated in groups of 4 Rated input voltage 120/230 VAC Suitable for switches and 2-/3-wire proximity switches (AC) Wiring and block diagrams of SM 321; DI 16 x AC 120/230 V Channel number Status display - green Backplane bus interface S7-300 Module data Manual, 06/2017, A5E00105505-AJ 111 Digital modules 3.16 Digital input module SM 321; DI 16 x AC 120/230 V; (6ES7321-1FH00-0AA0) SM 321; DI 16 x AC 120/230 V- Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D 40 x 125 x 117 Weight ca. 240 g Module-specific data Supports isochronous mode no Number of inputs 16 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L1 120/230 V All load voltages must be connected to a common phase Number of simultaneously controlled inputs * Horizontal mounting position to 60 C 16 * Vertical mounting position to 40 C 16 Electrical isolation * Between channels and the backplane bus Yes * between channels Yes in groups of 4 Maximum potential difference * between Minternal and inputs 230 VAC * between inputs of different groups 500 VAC Isolation test voltage 4000 VDC Current consumption * from the backplane bus Power loss of the module max. 29 mA typ. 4.9 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none S7-300 Module data 112 Manual, 06/2017, A5E00105505-AJ Digital modules 3.16 Digital input module SM 321; DI 16 x AC 120/230 V; (6ES7321-1FH00-0AA0) Technical specifications Sensor selection data Input voltage * Rated value * "1" signal * "0" signal * Frequency band 120/230 VAC 79 V to 264 V 0 V to 40 V 47 Hz to 63 Hz Input current * "1" signal 120 V, 60 Hz 230 V, 50 Hz typ. 6.5 mA typ. 16.0 mA Input delay * "0" to "1" transition * "0" to "1" transition max. 25 ms max. 25 ms Input characteristics to IEC 61131, type 1 Connection of 2-wire BEROs supported * Permissible quiescent current Wiring the signal transducers max. 2 mA using a 20-pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 113 Digital modules 3.17 Digital input module SM 321; DI 8 x AC 120/230 V; (6ES7321-1FF01-0AA0) 3.17 Digital input module SM 321; DI 8 x AC 120/230 V; (6ES7321-1FF01-0AA0) Order number: "Standard module" 6ES7321-1FF01-0AA0 Order number: "SIPLUS S7-300 module" 6AG1321-1FF01-2AA0 Properties Properties of SM 321, DI 8 x AC 120/230 V: 8 inputs, electrically isolated in groups of 2 Rated input voltage 120/230 VAC suitable for switches and 2-/3-wire AC proximity switches Wiring and block diagram of SM 321; DI 8 x AC 120/230 V Channel number Status display - green Backplane bus interface S7-300 Module data 114 Manual, 06/2017, A5E00105505-AJ Digital modules 3.17 Digital input module SM 321; DI 8 x AC 120/230 V; (6ES7321-1FF01-0AA0) SM 321; DI 8 x AC 120/230 V - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 240 g Module-specific data Supports isochronous mode no Number of inputs 8 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Number of simultaneously controlled inputs * horizontal mounting position 8 to 60 C * vertical mounting position 8 to 40 C Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of 2 Maximum potential difference * between Minternal and inputs 230 VAC * between inputs of different groups 500 VAC Isolation test voltage 4000 VDC Current consumption * from the backplane bus Power loss of the module max. 29 mA typ. 4.9 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none S7-300 Module data Manual, 06/2017, A5E00105505-AJ 115 Digital modules 3.17 Digital input module SM 321; DI 8 x AC 120/230 V; (6ES7321-1FF01-0AA0) Technical specifications Sensor selection data Input voltage * Rated value * "1" signal * "0" signal * Frequency band 120/230 VAC 79 V to 264 V 0 V to 40 V 47 Hz to 63 Hz Input current * "1" signal 120 V, 60 Hz 230 V, 50 Hz typ. 6.5 mA typ. 11 mA Input delay * "0" to "1" transition * "1" to "0" transition max. 25 ms max. 25 ms Input characteristics to IEC 61131, type 1 Connection of 2-wire BEROs supported * Permissible quiescent current Wiring of the signal transducers max. 2 mA using a 20-pin front connector S7-300 Module data 116 Manual, 06/2017, A5E00105505-AJ Digital modules 3.18 Digital input module SM 321; DI 8 x AC 120/230 V ISOL; (6ES7321-1FF10-0AA0) 3.18 Digital input module SM 321; DI 8 x AC 120/230 V ISOL; (6ES7321-1FF10-0AA0) Order number 6ES7321-1FF10-0AA0 Properties Properties of the digital input module SM 321; DI 8 x AC 120/230 V ISOL: 8 inputs, electrically isolated in groups of 1 Rated input voltage 120/230 VAC Suitable for switches and 2-/3-/4-wire AC proximity switches Wiring and block diagrams of SM 321; DI 8 x AC 120/230 V ISOL Channel number Status display - green Backplane bus interface S7-300 Module data Manual, 06/2017, A5E00105505-AJ 117 Digital modules 3.18 Digital input module SM 321; DI 8 x AC 120/230 V ISOL; (6ES7321-1FF10-0AA0) SM 321; DI 8 x AC 120/230 V ISOL - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D 40 x 125 x 117 Weight ca. 240 g Module-specific data Supports isochronous mode no Number of inputs 8 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L1 120/230 VAC All load voltages must be connected to a common phase Number of simultaneously controlled inputs * Horizontal mounting position to 60 C 8 * Vertical mounting position to 40 C 8 Electrical isolation * Between channels and the backplane bus Yes * between channels Yes in groups of 1 Maximum potential difference * between Minternal and inputs 230 VAC * between inputs of different groups 500 VAC Isolation test voltage * between Minternal and inputs 1500 VAC * between inputs of different groups 2000 VAC Current consumption * from the backplane bus Power loss of the module max. 100 mA typ. 4.9 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none S7-300 Module data 118 Manual, 06/2017, A5E00105505-AJ Digital modules 3.18 Digital input module SM 321; DI 8 x AC 120/230 V ISOL; (6ES7321-1FF10-0AA0) Technical specifications Sensor selection data Input voltage * Rated value * "1" signal * "0" signal * Frequency band 120/230 VAC 79 V to 264 V 0 V to 40 V 47 Hz to 63 Hz Input current * "1" signal 120 V, 60 Hz 230 V, 50 Hz typ. 7.5 mA typ. 17.3 mA Input delay * "0" to "1" transition * "0" to "1" transition max. 25 ms max. 25 ms Input characteristics to IEC 61131, type 1 Connection of 2-wire BEROs supported * Permissible quiescent current Wiring of the signal sensors max. 2 mA using a 40-pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 119 Digital modules 3.19 Digital output module SM 322; DO 64 x DC 24 V/0.3 A sourcing; (6ES7322-1BP00-0AA0) 3.19 Digital output module SM 322; DO 64 x DC 24 V/0.3 A sourcing; (6ES7322-1BP00-0AA0) Order number 6ES7322-1BP00-0AA0 Properties Properties of SM 322; DO 64 x DC 24 V/0,3 A Sourcing: 64 outputs, isolated in 4 groups of 16 Rated load voltage 24 V DC Wiring and block diagram of SM 322; DO 64 x DC 24 V/0,3 A Sourcing Channel number Status display - green Backplane bus interface S7-300 Module data 120 Manual, 06/2017, A5E00105505-AJ Digital modules 3.19 Digital output module SM 322; DO 64 x DC 24 V/0.3 A sourcing; (6ES7322-1BP00-0AA0) Terminal assignment of SM 322; DO 64 x DC 24 V/0,3 A Sourcing The figure below shows how channels are assigned to addresses (output byte x up to output byte x+7). 40-pin terminal block SM 322; DO 64 x DC 24 V/0,3 A Sourcing features two terminal blocks for connecting actuators and sensors to the module front connector. A connecting cable is used to establish the module connections. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 121 Digital modules 3.19 Digital output module SM 322; DO 64 x DC 24 V/0.3 A sourcing; (6ES7322-1BP00-0AA0) The table below shows how channel terminals are assigned to the connector for module SM 322; DO 64 x DC 24 V/0,3 A Sourcing. Terminal Function Terminal Function 1 O x.0 2 O x+2.0 3 O x.1 4 O x+2.1 5 O x.2 6 O x+2.2 7 O x.3 8 O x+2.3 9 O x.4 10 O x+2.4 11 O x.5 12 O x+2.5 13 O x.6 14 O x+2.6 15 O x.7 16 O x+2.7 17 1M 18 2M 19 1L+ 20 2L+ 21 O x+1.0 22 O x+3.0 23 O x+1.1 24 O x+3.1 25 O x+1.2 26 O x+3.2 27 O x+1.3 28 O x+3.3 29 O x+1.4 30 O x+3.4 31 O x+1.5 32 O x+3.5 33 O x+1.6 34 O x+3.6 35 O x+1.7 36 O x+3.7 37 1M 38 2M 39 1L+ 40 2L+ Note Connections x M and x L+ must be connected to a channel group. S7-300 Module data 122 Manual, 06/2017, A5E00105505-AJ Digital modules 3.19 Digital output module SM 322; DO 64 x DC 24 V/0.3 A sourcing; (6ES7322-1BP00-0AA0) Technical specifications of SM 322, DO 64 x DC 24 V, 0,3 A Sourcing Technical specifications Dimensions and weight Dimensions (W x H x D) (mm) 40 x 125 x 112 (including protective barrier, required for connections which are not in use) Weight ca. 260 g Module-specific data Supports isochronous mode No Number of outputs 64 Cable length * Unshielded * Shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L+ 24 V DC Total current of outputs (per group) For horizontal installation * Up to 25 C * to 40 C * to 60 C max. 2.0 A max. 1.6 A max. 1.2 A For vertical installation * to 40 C * Up to 25 C max. 1.6 A max. 2.0 A Electrical isolation * Between channels and the backplane bus * Between channels - In groups of Isolation test voltage Yes Yes 16 500 VDC Current consumption * From the backplane bus * From the user 24 V (L+) (separately for each group; no load) Power loss of the module Max. 100 mA Max. 75 mA Typ. 6.0 W S7-300 Module data Manual, 06/2017, A5E00105505-AJ 123 Digital modules 3.19 Digital output module SM 322; DO 64 x DC 24 V/0.3 A sourcing; (6ES7322-1BP00-0AA0) Technical specifications Status, interrupts, diagnostics Status display Green LED per channel Interrupts None Diagnostic functions None Actuator selection data Output type M switching Output voltage 24 V DC * L+ (-0.5 V) "1" signal Output current * * "1" signal - Rated value - Permitted range Typ. 0.3 A 2.4 mA to 0.36 A <100 A "0" signal (residual current) Output delay (resistive load) * "0" to "1" transition * "1" to "0" transition <550 s <550 s Load resistance range 80 to 10 k Lamp load Max. <5 W Wiring two outputs in parallel * For redundant load control * For performance increase supported (with external diode) not supported Control of a digital input supported Switching frequency * with resistive load * With inductive load to IEC 947-5-1, DC * With lamp load 131 Max. <100 Hz Max. <0.5 Hz Max. <10 Hz Internal limiting of the inductive shutdown voltage to: 53 V typ. Short-circuit-proof output Yes, electronic * Response threshold: Wiring of the actuators 1 For 0.7 A to 1.9 A typ. Two 40-pin terminal blocks loads above 200 mA, a terminal diode is required for the inductive load. STEP 7 integration 64-channel I/O modules are integrated with the HSP 2019 V 1.0. The HSP forms part of STEP 7 V 5.4 SP2 and can be installed from STEP 7 V 5.4 and higher. S7-300 Module data 124 Manual, 06/2017, A5E00105505-AJ Digital modules 3.19 Digital output module SM 322; DO 64 x DC 24 V/0.3 A sourcing; (6ES7322-1BP00-0AA0) GSD/GSDML files The 64-channel I/O modules are supported by the ET 200M versions listed below. Download the corresponding GSD/GSDML files from the following link: on the Internet (http://www.siemens.com/automation/service). To search for PROFIBUS GSD files, type in the entry ID 113498. To search for PROFINET GSDML files, type in the entry ID: 25057900. PROFIBUS IM 153-1, as of 6ES7153-1AA03-0XB0, E12 with GSD file SI01801D.*, version V 1.5 IM 153-2, as of 6ES7153-2BA02-0XB0, E01 with GSD file SI04801E.*, version V 1.0 PROFINET IM 153-4 PN, as of 6ES7153-4AA00-0XB0 with GSDML file version V 2.1 IM153-4 PN IO HF, as of 6ES7153-4BA00-0XB0 with GSDML file version V2.1 Using the module in S7-300 and ET 200M If the station is configured with STEP 7, you can use the digital output module SM 322 with all CPUs in the following table. Startup cannot be performed if no configuration is loaded. C-CPUs (compact CPUs) Order number CPU 312C 6ES7312-5BD0x-0AB0 6ES7312-5BE03-0AB0 6ES7312-5BF04-0AB0 CPU 313C 6ES7313-5BE0x-0AB0 6ES7313-5BF03-0AB0 6ES7313-5BG04-0AB0 CPU 313C-2 DP 6ES7313-6CE0x-0AB0 6ES7313-6CF03-0AB0 6ES7313-6CG04-0AB0 CPU313C-2 PtP 6ES7313-6BE0x-0AB0 6ES7313-6BF03-0AB0 6ES7313-6BG04-0AB0 CPU 314C-2 DP 6ES7314-6CF0x-0AB0 6ES7314-6CG03-0AB0 6ES7314-6CH04-0AB0 CPU 314C-2 PtP 6ES7314-6BF0x--0AB0 6ES7314-6BG03--0AB0 6ES7314-6BH04-0AB0 CPU314C-2 PN/DP 6ES7314-6EH04-0AB0 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 125 Digital modules 3.19 Digital output module SM 322; DO 64 x DC 24 V/0.3 A sourcing; (6ES7322-1BP00-0AA0) M-CPUs Order number CPU 312 6ES7312-1AD1x-0AB0 6ES7312-1AE13-0AB0 6ES7312-1AE14-0AB0 CPU 314 6ES7314-1AF1x-0AB0 6ES7314-1AG13-0AB0 6ES7314-1AG14-0AB0 CPU 315-2 DP 6ES7315-2AF0x-0AB0 6ES7315-2AG10-0AB0 6ES7315-2AH14-0AB0 CPU 316-2 DP 6ES7316-2AG00-0AB0 CPU 317-2 DP 6ES7317-2AJ10-0AB0 CPU 315-2 PN/DP 6ES7315-2EG10-0AB0 6ES7317-2AK14-0AB0 6ES7315-2EH13-0AB0 6ES7315-2EH14-0AB0 CPU 317-2 PN/DP 6ES7317-2EJ10-0AB0 6ES7317-2EK13-0AB0 6ES7317-2EK14-0AB0 CPU 319-3 PN/DP 6ES7318-3EL00-0AB0 6ES7318-3EL01-0AB0 F-CPUs Order number CPU 315F-2 DP 6ES7315-6FF0x-0AB0 CPU 317F-2 DP 6ES7317-6FF0x-0AB0 CPU 315F-2 PN/DP 6ES7315-2FH1x-0AB0 6ES7315-2FJ14-0AB0 CPU 317F-2 PN/DP 6ES7317-2FJ10-0AB0 6ES7317-2FK13-0AB0 6ES7317-2FK14-0AB0 CPU 319F-3 PN/DP 6ES7318-3FL00-0AB0 6ES7318-3FL01-0AB0 S7-300 Module data 126 Manual, 06/2017, A5E00105505-AJ Digital modules 3.19 Digital output module SM 322; DO 64 x DC 24 V/0.3 A sourcing; (6ES7322-1BP00-0AA0) T-CPUs Order number CPU 315T-2 DP 6ES7315-6TG10-0AB0 CPU315T-3 PN/DP 6ES7315-7TJ10-0AB0 CPU 317T-2 DP 6ES7317-6TJ10-0AB0 CPU317TF-2 DP 6ES7317-6TF14-0AB0 CPU317T-3 PN/DP 6ES7317-7TK10-0AB0 CPU317TF-3 PN/DP 6ES7317-7UL10-0AB0 C7-CPUs Order number C7-613 6ES7613-1CA01-0AE3 C7-635 Touch 6ES7635-2EB01-0AE3 C7-635 Key 6ES7635-2EC01-0AE3 C7-636 Touch 6ES7636-2EB00-0AE3 C7-636 Key 6ES7636-2EC00-0AE3 WARNING Use of the module This module must be configured in a STEP 7 project in which the correct address assignment and allocation of the input/output point is ensured. Using the module without having first carried out this configuration work can lead to machines or processes operating in an unexpected manner. If machines or processes do run in an unexpected manner, this can result in death, serious injury, and/or material damage. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 127 Digital modules 3.20 Digital output module SM 322; DO 64 x DC 24 V/0.3 A Sinking (6ES7322-1BP50-0AA0) 3.20 Digital output module SM 322; DO 64 x DC 24 V/0.3 A Sinking (6ES7322-1BP50-0AA0) Order number 6ES7322-1BP50-0AA0 Properties Characteristics of the SM 322; DO 64 x DC 24 V, 0,3 A Sinking digital output module: 64 outputs, isolated in 4 groups of 16 Rated load voltage 24 V DC Wiring and block diagram of SM 322; DO 64 x DC 24 V, 0,3 A Sinking Channel number Status display - green Backplane bus interface S7-300 Module data 128 Manual, 06/2017, A5E00105505-AJ Digital modules 3.20 Digital output module SM 322; DO 64 x DC 24 V/0.3 A Sinking (6ES7322-1BP50-0AA0) Terminal assignment of SM 322; DO 64 x DC 24 V, 0,3 A Sinking The figure below shows how channels are assigned to addresses (output byte x to output byte x+7). 40-pin terminal block SM 322; DO 64 x DC 24 V/0,3 A Sinking features two terminal blocks for connecting actuators and sensors to the module front connector. A connecting cable is used to establish the module connections. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 129 Digital modules 3.20 Digital output module SM 322; DO 64 x DC 24 V/0.3 A Sinking (6ES7322-1BP50-0AA0) The table below shows how channel terminals are assigned to the terminal block for module SM 322; DO 64 x DC 24 V/0,3 A Sinking.. Terminal Function Terminal Function 1 O x.0 2 O x+2.0 3 O x.1 4 O x+2.1 5 O x.2 6 O x+2.2 7 O x.3 8 O x+2.3 9 O x.4 10 O x+2.4 11 O x.5 12 O x+2.5 13 O x.6 14 O x+2.6 15 O x.7 16 O x+2.7 17 1M 18 2M 19 1L+ 20 2L+ 21 O x+1.0 22 O x+3.0 23 O x+1.1 24 O x+3.1 25 O x+1.2 26 O x+3.2 27 O x+1.3 28 O x+3.3 29 O x+1.4 30 O x+3.4 31 O x+1.5 32 O x+3.5 33 O x+1.6 34 O x+3.6 35 O x+1.7 36 O x+3.7 37 1M 38 2M 39 1L+ 40 2L+ Note Terminals x M and x L+ must be connected on the terminal block. Technical specifications of SM 322, DO 64 x DC 24 V, 0,3 A (Sinking) Technical specifications Dimensions and weight Dimensions (W x H x D) (mm) 40 x 125 x 112 (including protective barrier, required for connections which are not in use) Weight ca. 260 g Module-specific data Supports isochronous mode No Number of outputs 64 Cable length * Unshielded * Shielded Max. 600 m Max. 1000 m S7-300 Module data 130 Manual, 06/2017, A5E00105505-AJ Digital modules 3.20 Digital output module SM 322; DO 64 x DC 24 V/0.3 A Sinking (6ES7322-1BP50-0AA0) Technical specifications Voltages, currents, electrical potentials Rated load voltage L+ 24 V DC Total current of outputs (per group) For horizontal installation * Up to 25 C * to 40 C * to 60 C max. 2.0 A max. 1.6 A max. 1.2 A For vertical installation * to 40 C * Up to 25 C max. 1.6 A max. 2.0 A Electrical isolation * Between channels and the backplane bus * Between channels In groups of Isolation test voltage Yes Yes 16 500 VDC Current consumption * From the backplane bus * From load voltage L+ (no load) Power loss of the module max. 100 mA max. 75 mA Typ. 6.0 W Status, interrupts, diagnostics Status display Green LED per channel Interrupts None Diagnostic functions None Actuator selection data Output type Sinking Output voltage 24 V DC * "1" signal M+ (0.5 V) at full load Output current "1" signal * Rated value * Permitted range "0" signal (residual current) Typ. 0.3 A 2.4 mA to 0.36 A <100 A Output delay (resistive load) * "0" to "1" transition * "1" to "0" transition <450 s <450 s Load resistance range 80 to 10 k Lamp load Max. 5 W Wiring two outputs in parallel * for redundant load control * for performance increase supported (with external diode) not supported S7-300 Module data Manual, 06/2017, A5E00105505-AJ 131 Digital modules 3.20 Digital output module SM 322; DO 64 x DC 24 V/0.3 A Sinking (6ES7322-1BP50-0AA0) Technical specifications Control of a digital input supported Switching frequency * With resistive load * With inductive load to IEC 947-5-1, DC 131 * With lamp load Max. 100 Hz Max. 0.5 Hz Max. 10 Hz Internal limiting of the inductive shutdown voltage to: Typ. 45 V Short-circuit protection of the output Yes, electronic * Response threshold Wiring of the actuators 1 For 1.7 A to 3.5 A typ. Two 40-pin terminal blocks loads above 200 mA, a terminal diode is required for the inductive load. Recommended fuse Groups of outputs must be protected by a 4 A/125 V fast-blow fuse (recommended: Littelfuse 235 004P 125 V 4 A). If the fuse is installed in a danger zone in accordance with the National Electric Code (NEC), you must always use a suitable tool to remove it. Before removing or replacing the fuse, you must determine whether or not you are dealing with a danger zone. STEP 7 integration 64-channel I/O modules are integrated with the HSP 2019 V 1.0. The HSP forms part of STEP 7 V 5.4 SP2 and can be installed from STEP 7 V 5.4 and higher. GSD/GSDML files The 64-channel I/O modules are supported by the ET 200M versions listed below. Download the corresponding GSD/GSDML files from the following link: on the Internet (http://www.siemens.com/automation/service). To search for PROFIBUS GSD files, type in the entry ID 113498. To search for PROFINET GSDML files, type in the entry ID: 25057900. PROFIBUS IM 153-1, as of 6ES7153-1AA03-0XB0, E12 with GSD file SI01801D.*, version V 1.5 IM 153-2, as of 6ES7153-2BA02-0XB0, E01 with GSD file SI04801E.*, version V 1.0 PROFINET IM 153-4 PN, as of 6ES7153-4AA00-0XB0 with GSDML file version V 2.1 IM153-4 PN IO HF, as of 6ES7153-4BA00-0XB0 with GSDML file version V2.1 S7-300 Module data 132 Manual, 06/2017, A5E00105505-AJ Digital modules 3.20 Digital output module SM 322; DO 64 x DC 24 V/0.3 A Sinking (6ES7322-1BP50-0AA0) Using the module in S7-300 and ET 200M If the station is configured with STEP 7, you can use the digital output module SM 322 with all CPUs in the following table. Startup cannot be performed if no configuration is loaded. C-CPUs (compact CPUs) CPU 312C CPU 313C Order number 6ES7312-5BD0x-0AB0 6ES7312-5BE03-0AB0 6ES7312-5BF04-0AB0 6ES7313-5BE0x-0AB0 CPU 313C-2 DP 6ES7313-5BF03-0AB0 6ES7313-5BG04-0AB0 6ES7313-6CE0x-0AB0 CPU313C-2 PtP 6ES7313-6CF03-0AB0 6ES7313-6CG04-0AB0 6ES7313-6BE0x-0AB0 6ES7313-6BF03-0AB0 CPU 314C-2 DP 6ES7313-6BG04-0AB0 6ES7314-6CF0x-0AB0 6ES7314-6CG03-0AB0 CPU 314C-2 PtP 6ES7314-6CH04-0AB0 6ES7314-6BF0x--0AB0 6ES7314-6BG03--0AB0 CPU314C-2 PN/DP M-CPUs CPU 312 CPU 314 CPU 315-2 DP CPU 316-2 DP CPU 317-2 DP CPU315-2 PN/DP CPU317-2 PN/DP CPU 319-3 PN/DP 6ES7314-6BH04-0AB0 6ES7314-6EH04-0AB0 Order number 6ES7312-1AD1x-0AB0 6ES7312-1AE13-0AB0 6ES7312-1AE14-0AB0 6ES7314-1AF1x-0AB0 6ES7314-1AG13-0AB0 6ES7314-1AG14-0AB0 6ES7315-2AF0x-0AB0 6ES7315-2AG10-0AB0 6ES7315-2AH14-0AB0 6ES7316-2AG00-0AB0 6ES7317-2AJ10-0AB0 6ES7317-2AK14-0AB0 6ES7315-2EG10-0AB0 6ES7315-2EH13-0AB0 6ES7315-2EH14-0AB0 6ES7317-2EJ10-0AB0 6ES7317-2EK13-0AB0 6ES7317-2EK14-0AB0 6ES7318-3EL00-0AB0 6ES7318-3EL01-0AB0 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 133 Digital modules 3.20 Digital output module SM 322; DO 64 x DC 24 V/0.3 A Sinking (6ES7322-1BP50-0AA0) F-CPUs Order number CPU 315F-2 DP 6ES7315-6FF0x-0AB0 CPU 317F-2 DP 6ES7317-6FF0x-0AB0 CPU315F-2 PN/DP 6ES7315-2FH1x-0AB0 6ES7315-2FJ14-0AB0 CPU 317F-2 PN/DP 6ES7317-2FJ10-0AB0 6ES7317-2FK13-0AB0 6ES7317-2FK14-0AB0 CPU 319F-3 PN/DP 6ES7318-3FL00-0AB0 6ES7318-3FL01-0AB0 T-CPUs Order number CPU 315T-2 DP 6ES7315-6TG10-0AB0 CPU315T-3 PN/DP 6ES7315-7TJ10-0AB0 CPU317T-2 DP 6ES7317-6TJ10-0AB0 CPU317TF-2 DP 6ES7317-6TF14-0AB0 CPU317T-3 PN/DP 6ES7317-7TK10-0AB0 CPU317TF-3 PN/DP 6ES7317-7UL10-0AB0 C7-CPUs Order number C7-613 6ES7613-1CA01-0AE3 C7-635 Touch 6ES7635-2EB01-0AE3 C7-635 Key 6ES7635-2EC01-0AE3 C7-636 Touch 6ES7636-2EB00-0AE3 C7-636 Key 6ES7636-2EC00-0AE3 WARNING Use of the module This module must be configured in a STEP 7 project in which the correct address assignment and allocation of the input/output point is ensured. Using the module without having first carried out this configuration work can lead to machines or processes operating in an unexpected manner. If machines or processes do run in an unexpected manner, this can result in death, serious injury, and/or material damage. S7-300 Module data 134 Manual, 06/2017, A5E00105505-AJ Digital modules 3.21 Digital output module SM 322; DO 32 x DC 24 V/ 0.5 A; (6ES7322-1BL00-0AA0) 3.21 Digital output module SM 322; DO 32 x DC 24 V/ 0.5 A; (6ES7322-1BL00-0AA0) Order number 6ES7322-1BL00-0AA0 Properties Properties of SM 322; DO 32 x DC 24 V/0.5 A: 32 outputs, electrically isolated in groups of 8 Output current 0.5 A Rated load voltage 24 V DC Suitable for solenoid valves, DC contactors and signal lamps Use of the module with high-speed counters Please note when using the module in combination with high-speed counters: Note When using a mechanical contact to switch on the 24-V power supply to SM 322; DO 32 x DC 24 V/0.5 A, its outputs will carry "1" signal for the duration of ca. 50 s due to the circuit structure. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 135 Digital modules 3.21 Digital output module SM 322; DO 32 x DC 24 V/ 0.5 A; (6ES7322-1BL00-0AA0) Wiring and block diagram of SM 322; DO 32 x DC 24 V/ 0.5 A Channel number Status display - green Backplane bus interface Terminal assignment The figure below shows the channel addressing (output byte x to output byte x+3). S7-300 Module data 136 Manual, 06/2017, A5E00105505-AJ Digital modules 3.21 Digital output module SM 322; DO 32 x DC 24 V/ 0.5 A; (6ES7322-1BL00-0AA0) SM 322; DO 32 x DC 24 V/ 0.5 A - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 260 g Module-specific data Supports isochronous mode no Number of outputs 32 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L+ 24 V DC Total current of outputs (per group) * horizontal mounting position to 40 C to 60 C * vertical mounting position max. 4 A max. 3 A max. 2 A to 40 C Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of Isolation test voltage 8 500 V DC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 110 mA max. 160 mA typ. 6.6 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none S7-300 Module data Manual, 06/2017, A5E00105505-AJ 137 Digital modules 3.21 Digital output module SM 322; DO 32 x DC 24 V/ 0.5 A; (6ES7322-1BL00-0AA0) Technical specifications Actuator selection data Output voltage * "1" signal min. L + (- 0.8 V) Output current * "1" signal Rated value Permitted range * "0" signal (residual current) 0.5 A 5 mA to 0.6 A max. 0.5 mA Output delay (resistive load) * "0" to "1" transition max. 100 s * "1" to "0" transition max. 500 s Load resistance range 48 to 4 k Lamp load max. 5 W Wiring two outputs in parallel * For redundant load control supported (only outputs of the same group) * For performance increase Not supported Control of a digital input Supported Switching frequency * with resistive load max. 100 Hz * with inductive load to IEC 947-5-1, DC 13 max. 0.5 Hz * with lamp load max. 10 Hz Internal limiting of the inductive shutdown voltage to Short-circuit protection of the output * Threshold Wiring of the actuators typ. L + (-53 V) yes, electronic typ. 1 A using a 40-pin front connector S7-300 Module data 138 Manual, 06/2017, A5E00105505-AJ Digital modules 3.22 Digital output module SM 322; DO 32 x AC 120/230 V/1 A; (6ES7322-1FL00-0AA0) 3.22 Digital output module SM 322; DO 32 x AC 120/230 V/1 A; (6ES7322-1FL00-0AA0) Order number 6ES7322-1FL00-0AA0 Properties Properties of SM 322; DO 32 x AC 120/230 V/1 A: 32 outputs, fused and electrically isolated in groups of 8 Output current 1.0 A Rated load voltage 120/230 VAC Blown fuse indicator for each group Suitable for AC solenoids, contactors, starters, FHP motors and signal lamps Group error display (SF) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 139 Digital modules 3.22 Digital output module SM 322; DO 32 x AC 120/230 V/1 A; (6ES7322-1FL00-0AA0) Wiring and block diagram of SM 322; DO 32 x AC 120/230 V/1 A Channel numbers Status display - green Error LED - red Backplane bus interface S7-300 Module data 140 Manual, 06/2017, A5E00105505-AJ Digital modules 3.22 Digital output module SM 322; DO 32 x AC 120/230 V/1 A; (6ES7322-1FL00-0AA0) Terminal assignment The figure below shows the channel addressing (output byte x to output byte x+3). SM 322; DO 32 x AC 120/230 V/1 A - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 80 x 125 x 117 Weight ca. 500 g Module-specific data Supports isochronous mode no Number of outputs 32 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L1 * Maximum frequency range 120/230 VAC 47 Hz to 63 Hz Total current of outputs (per group) * horizontal mounting position to 60 C to 40 C * vertical mounting position * to 40 C max. 3 A max. 4 A max. 4 A Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of 8 Maximum potential difference * between Minternal and outputs 250 VAC * between outputs of different groups 250 VAC S7-300 Module data Manual, 06/2017, A5E00105505-AJ 141 Digital modules 3.22 Digital output module SM 322; DO 32 x AC 120/230 V/1 A; (6ES7322-1FL00-0AA0) Technical specifications Isolation test voltage 4000 VDC Current consumption * from the backplane bus * from load voltage L1 (no-load) Power loss of the module max. 190 mA max. 10 mA typ. 25 W Status, interrupts, diagnostics Status display green LED per channel Interrupts no Diagnostic functions yes * Group error display red LED (SF) Actuator selection data Output voltage * min. L1 (-0.8 V) "1" signal Output current * "1" signal 1A Rated value 10 mA to 1 A Permitted range 10 A (for two AC cycles) Maximum inrush current (per group) * "0" signal (residual current) max. 2 mA Output delay (resistive load) * "0" to "1" transition 1 AC cycle * "1" to "0" transition 1 AC cycle Blocking voltage zero transition max. 60 V Size of the motor starter max. size 4 to NEMA Lamp load max. 50 W Wiring two outputs in parallel * for redundant load control supported (only outputs of the same group) * for performance increase not supported Control of a digital input supported Switching frequency * with resistive load * with inductive load to IEC 947-5-1, AC 15 * with lamp load max. 10 Hz max. 0.5 Hz 1 Hz Short-circuit protection of the output no Wiring of the actuators using a 20-pin* front connector *Requires two front connectors of the appropriate version S7-300 Module data 142 Manual, 06/2017, A5E00105505-AJ Digital modules 3.23 Digital output module SM 322; DO 16 x DC 24 V/ 0.5 A; (6ES7322-1BH01-0AA0) 3.23 Digital output module SM 322; DO 16 x DC 24 V/ 0.5 A; (6ES7322-1BH01-0AA0) Order number: "Standard module" 6ES7322-1BH01-0AA0 Order number: "SIPLUS S7-300 module" 6AG1322-1BH01-2AA0 Properties Properties of SM 322; DO 16 x DC 24 V/0.5 A: 16 outputs, electrically isolated in groups of 8 Output current 0.5 A Rated load voltage 24 V DC Suitable for solenoid valves, DC contactors and signal lamps Use of the module with high-speed counters Please note when using the module in combination with high-speed counters: Note When using a mechanical contact to switch on the 24-V power supply to SM 322; DO 16 x DC 24 V/0.5 A, its outputs will carry "1" signal for the duration of ca. 50 s, due to the circuit structure. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 143 Digital modules 3.23 Digital output module SM 322; DO 16 x DC 24 V/ 0.5 A; (6ES7322-1BH01-0AA0) Wiring and block diagram of SM 322; DO 16 x DC 24 V/ 0.5 A Channel number Status display - green Backplane bus interface S7-300 Module data 144 Manual, 06/2017, A5E00105505-AJ Digital modules 3.23 Digital output module SM 322; DO 16 x DC 24 V/ 0.5 A; (6ES7322-1BH01-0AA0) SM 322; DO 16 x DC 24 V/0.5 A - Technical specifications Table 3- 21 Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 190 g Module-specific data Supports isochronous mode no Number of outputs 16 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L+ 24 V DC Total current of outputs (per group) * horizontal mounting position to 40 C to 60 C * vertical mounting position to 40 C max. 4 A max. 3 A max. 2 A Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of Isolation test voltage 8 500 V DC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 80 mA max. 80 mA typ. 4.9 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none S7-300 Module data Manual, 06/2017, A5E00105505-AJ 145 Digital modules 3.23 Digital output module SM 322; DO 16 x DC 24 V/ 0.5 A; (6ES7322-1BH01-0AA0) Technical specifications Actuator selection data Output voltage * min. L + (- 0.8 V) "1" signal Output current * "1" signal Rated value Permitted range * "0" signal (residual current) 0.5 A 5 mA to 0.6 A Max. 0.5 mA Output delay (resistive load) * "0" to "1" transition max. 100 s * "1" to "0" transition max. 500 s Load resistance range 48 to 4 k Lamp load max. 5 W Wiring two outputs in parallel * For redundant load control Supported (only outputs of the same group) * For performance increase Not supported Control of a digital input Supported Switching frequency * with resistive load max. 100 Hz * with inductive load to IEC 947-5-1, DC 13 max. 0.5 Hz * with lamp load max. 10 Hz Internal limiting of the inductive shutdown voltage to Short-circuit protection of the output * Threshold Wiring of the actuators typ. L + (-53 V) yes, electronic typ. 1 A using a 20-pin front connector S7-300 Module data 146 Manual, 06/2017, A5E00105505-AJ Digital modules 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) Order number 6ES7322-8BH10-0AB0 Order number: "SIPLUS S7-300 module" 6AG1322-8BH10-7AB0 Properties The digital output module SM 322; DO 16 x DC24 V/0.5 A is distinguished by the following properties: 16 outputs, electrically isolated in groups of 4 channels A nominal load voltage of 24 V DC Configurable diagnostics Programmable diagnostic interrupt Redundant Wire break at "0" and "1" signal Identification Data Firmware update possible Use of the module with high-speed counters Please note when using the module in combination with high-speed counters. Note When using a mechanical contact to switch on the 24-V power supply to SM 322; DO 16 x DC 24 V/0.5 A, its outputs will carry "1" signal for the duration of ca. 50 s, due to the circuit structure. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 147 Digital modules 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) Using the module For the use of the SM 322; DO 16 x DC24V/0.5A, the following hardware and software requirements must be fulfilled: For the central use in S7-300, the module can be used with all available CPUs. For the decentral use in ET 200M, the module can be used with the following IM 153modules and compatible successor modules: - IM 153-2; as of 6ES7153-2BA02-0XB0, (PROFIBUS). - IM 153-2; as of 6ES7153-2BA82-0XB0; (PROFIBUS, OUTDOOR). - IM 153-4; as of 6ES7153-4BA0x-0XB0; (PROFINET). Requirement: STEP 7 V5.5 (HSP0217) or higher. A GSD file or a GSDML file must be used if the module is part of a distributed and controlled by a master produced by a third-party manufacturer. The corresponding file for the selected IM 153 is available for download from the Internet (http://www.siemens.com/automation/service&support). Module diagnosis and identification data (I&M) are available through STEP 7 and with SIMATIC PDM as of V6.0 + SP5 (HSP0217) or SIMATIC PDM V7.0 or higher and EDD for ET 200M "DP_IOSystem_Siemens_ET200M_Module.Device" as of V1.1.12. Compatible use of the module 6ES7322-8BH0x-0AB0 You can repalce the digital output module 6ES7322-8BH0x-0AB0 without changing your settings through a digital output module 6ES7322-8B10-0AB0. In this case, the module does not offer discrepancy failure monitoring. If a STEP 7 version before STEP 7 V5.1 SP3 is used, the replacement value behavior will only be entered through the parameter dialog from HW config and transferred to the module during system startup. In this case, all other settings must be transferred through SIMATIC PDM or in the user program through datasets to the module. These settings are not saved retentively on the digital output module 6ES7322-8BH10-0AB0 and are reset after restarting the module. Note A setting through SIMATIC PDM is only possible with the use of a 6ES7322-8BH10-0AB0 as a replacement for a 6ES7322-8BH0x-0AB0 as long as the device label (6ES7322-8BH0x-0AB0) in SIMATIC PDM was not updated with the actual device label through Device -> Load in PC/PG. Redundant use of the module A redundant use of the module is only permissible if the 6ES7322-8BH10-0AB0 is used and configured for both modules. No short-circuit monitoring occurs according to L+ in redundant use. S7-300 Module data 148 Manual, 06/2017, A5E00105505-AJ Digital modules 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) Wiring and block diagram Status displays - green Error - red Channel numbers Numbers 0 to 7 on the right side correspond to channel numbers 8 to 15 Channel status Channel fault Backplane bus interface Redundant Output Signals Two clamps are on each channel. Both connections are similar and can be used for a redundant control of an actuator. Redundant control can take place from 2 different modules without an external circuit. Both signal modules must be connected to the common reference potential M. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 149 Digital modules 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) Technical specifications Table 3- 22 Technical specifications SM 322; DO 16 x DC 24V/0.5A Technical specifications Dimensions and Weight Dimensions W x H x D (mm) 40 x 125 x 120 Weight approx. 300 g Module-specific data Supports isochronous mode No Number of outputs 16 Cable length * Unshielded Max. 600 m * Shielded Max. 1000 m Voltages, Currents, Potentials Nominal load voltage L+ * Reverse polarity protection 24 V DC Yes Total current of outputs (per group) * Horizontal mounting position to 60 C Max. 2 A * Vertical mounting position to 40 C Max. 2 A Electrical isolation * Between channels and the backplane bus Yes * between channels in groups of yes 4 Insolation tested with DC 500 V Power consumption * From the backplane bus Max. 100 mA * From load voltage L+ (without load) Max. 100 mA Power dissipation of the module Typically 6 W Status, Interrupts, Diagnostics Status LEDs Green LED per channel Interrupts * Diagnostic interrupt Diagnostic functions Programmable Programmable * Group error display Red LED (SF) * Channel error display red LED, per channel * Diagnostic information readable supported S7-300 Module data 150 Manual, 06/2017, A5E00105505-AJ Digital modules 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) Technical specifications Actuator selection data Output voltage * "1" signal Min. L + (- 0.7 V) * "0" signal 0.7 mA * RL (RL = load resistance value) max. 31 V for RL = infinite Output current * At signal "1" Nominal value Permitted range 0.5 A 5 mA up to 600 mA * "0" signal (residual current) Max. 0.7mA Output delay (with resistive load) * At "1" to "0" Max. 2.7 ms (including module cycle time) * At "1" to "0" Max. 2.7 ms (including module cycle time) Load resistor range 48 bis 4k Lamp load Max. 5 W Connecting 2 outputs in parallel * For redundant triggering of a load supported * To increase performance Not possible Control of a digital input supported Operating frequency * with resistive load Max. 100 Hz * With inductive load, to IEC 947-5-1, DC 13 Max. 2 Hz * With lamp load Max. 10 Hz Limit (internal) of the inductive circuit interruption voltage to Typical L+ (-68 V) Short-circuit of an output Yes, electronic * Response threshold Typical 1.4 A S7-300 Module data Manual, 06/2017, A5E00105505-AJ 151 Digital modules 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) Load resistances of the actuators The load resistances of the actuators must be in the range from 48 to 4 . For larger values, a suitable resistance must be switched directly on the connection clamps of the actuator (observe the maximum power loss with signal "1"). The permissible rated voltage of the actuator must be greater than 28.2 V. The lower response threshold of the actuator must be known in the operating temperature range or be determined experimentally. The output voltage of the module with signal "0" can be influenced through parallel switching of a resistance directly on the actuator connection clamps. With the selection of the resistance, the maximum power loss with signal "1" must be observed. Load resistances between 10 k and 1 M can be reported as short-circuits after L+. Unwired outputs or loads greater than 1 M are reporeted as "wire-break". 3.24.1 Parameters of digital output modules Programming For general information on programming digital modules, refer to the chapter Programming digital modules (Page 58). The table below describes the programmable parameters of SM 322; DO 16 x DC 24 V/0.5 A, including defaults. Note A setting of the module through SIMATIC PDM is not possible. Table 3- 23 Setting for the digital output module SM 322; 6ES7322-8BH10-0AB0 Parameters Value range Default setting Applicability Diagnostics * Group diagnostics Yes/no no Channel * Load voltage L+ missing Yes/no No Channel group * Discrepancy error Yes/no No Channel group Diagnostics interrupt yes/no no Module Response at CPU-STOP Substitute a value/ Keep last value Substitute a value Module Substitute value 0/1 0 Channel See also Settings from the digital output module SM 322; DO 16 x DC 24 V/0.5 A (6ES7322-8BH10-0AB0) (Page 530) S7-300 Module data 152 Manual, 06/2017, A5E00105505-AJ Digital modules 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) 3.24.2 Diagnosis of digital output modules Introduction General information in regards to the evaluation of the diagnosis messages can be found in the chapter Diagnosis of digital modules (Page 59) and the design and content of the individual bytes in the chapter Diagnosis data from the SM 322; DO 16 x DC24 V/0.5 A (6ES7322-8BH10-0AB0) (Page 590). Channel errors are signaled with the channel error display (red LED per channel) and reported in the data record 1. As soon as at least one channel error display is lit, the group error display (SF) is also lit. Module errors are signaled via the diagnostic data record 0/1 and only displayed via the the group error display (SF). Group diagnostics Through the "Group diagnositcs" setting, the message from the channel-specific fields, with the exception of "external load voltage L+", for "Setting error" and the recognition of a discrepancy error can be turned off. Load voltage L+ missing The approval of the channel diagnositcs "external load point L+" occurs in channel groups through the diagnostics setting "Missing load voltage L+". This means that if the load voltage fails, the error will be reported to all four channels of a channel group. Additionally, the module-specific message occurs in the byte 0 of the diagnostics dataset 0 / 1, "external auxiliary voltage missing". Even if the diagnostics of "Missing load voltage L+" is turned off for all channels/channel groups, the recognition within the module remains active. This means that if there is a failure of at least one load voltage, the module error will always be reported in the byte 0 of the diagnostics data set 0 / 1 "External auxiliary voltage missing". Fuse blown If a fuse is blown, it will always be reported to all four channels of a channel group. In addition to the channel message, there is always the module-specific message in the byte 3 of the diagnostics dataset 0 / 1 "Fuse defect". Even if the "Group diagnostics" setting is disabled by all channels, a defective fuse will always be reported as module error in the byte 3 of the diagnostics dataset 0 / 1 "Fuse defect". S7-300 Module data Manual, 06/2017, A5E00105505-AJ 153 Digital modules 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) Discrepancy error monitoring For project engineering with the MLFB 6ES7322-8BH10-0AB0, the SM 322 DO 16 x DC24 V / 0.5A offers a discrepancy error monitoring. The approval of the channel discrepancy error monitoring occurs in channel groups through the "Discrepancy error" diagnostics settings. With an approved discrepancy error monitoring, the module constantly checks the set and actual status of the corresponding digital outputs. With a recognized discrepancy, for example, due to a component defect on the digital module, the corresponding channel group will be turned off and the "Fuse defect" error will be reported to all affected channels in the channel group. After removal/insertion or restart of the module, the digital outputs will be reactivated and the discrepancy test runs again. A discrepancy error is exclusively reported through the "Fuse defect" error. An additional indication through the byte 3 "Fuse defect" does not occur. Thus, a differentiation between the actual fuse blown and a discrepancy error is possible. Description of the Diagnostic Evaluation You can find a detailed description of how to evaluate diagnostic information in the STEP 7 online help. 3.24.3 Firmware update via HW Config Introduction The SM 322; DO 16 x DC 24V/0.5 A can be updated to the newest firmware version depending on the available compatible functional updates. The most recent firmware versions are available from your Siemens representative or from the Internet (http://www.siemens.com/automation/service&support). Preconditions / Requirements STEP 7 V5.5 +(HSP0217) or higher With a central use of the module in a S7-300, the firmware update must occur in the CPU-operating mode STOP. If the CPU is in the operating mode RUN, it may lead to unexpected behavior and the module is only available after a network off/network on. If the module is used in a distributed IO device ET 200M with active backplane bus modules (removal and insertion allowed), the a firmware update is also possible in the RUN CPU state. With a distributed use without active backplane bus modules, the firmware update is also possible in the RUN CPU state. Please observe that during the firmware update, the distributed IO device will be turned off shortly. S7-300 Module data 154 Manual, 06/2017, A5E00105505-AJ Digital modules 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) Firmware update This is how you update the firmware of a central or distributed module: 1. Select the module SM 322; DO 16 x DC 24V/0.5 A in HW-config. 2. Select PLC > Update Firmware. 3. Use the "Browse" button to select the path to the firmware files (*.upd). 4. Click the "Run" button. - The module performs the firmware update. 5. You can find additional information in the STEP 7 Online Help. Note * During the firmware update, the OB 83 (alarm due to removing and inserting modules), the OB 85 (program execution error) and the OB 86 (error due to module rack failure) are opened. If the diagnostics alarm of the module is approved, the OB 82 (diagnostics alarm) will also be opened during the firmware update. Make sure that the OB is set correspondingly. * If the red LED (SF) on the module blinks, an error occurred during the firmware update and the update must be repeated. In this case, the bootloader version Ex.x.x is displayed in the online diagnostics. * A firmware update through HW-config is not permitted if the module is in redundant mode. Identification of the firmware version After the firmware update, you must label the firmware version on the module. 3.24.4 I&M identification data Properties I data: Information about the module, which is normally found on the module casing. I-data is write-protected. They include: Hardware release status Firmware release status Serial number M data: System-dependent information (e.g. plant designation). M data is created during configuration. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 155 Digital modules 3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0) All identification data (I&M) is stored retentively in a module and supports you with the following tasks: Error search and repair in the system Testing the system configuration Finding changes to the system hardware. The SM 322; DO 16 x DC 24V/0.5 A supports: I&M 0 (identification) I&M 1 (system identification / location identification) I&M 2 (installation date) I&M 3 ( additional information) Reading and writing the identification data with STEP 7 System-dependent information (M-data) is configured in the properties dialog of the module. You obtain information on the module (I data) from the module status dialog. The systemdependent information on the module is displayed here too. Note Identification data can only be written for modules if the CPU is in the STOP operating mode. Reading and writing the identification data with PDM Through the "Identification" flap, the identification data is evaluated and transferred to the module. Location identification is not available in PDM. Note Identification data can only be written for modules if the CPU is in the STOP operating mode. It is recommended to change at most one entry per download, if applicable, the transferring of the identification data must be activated multiple times. S7-300 Module data 156 Manual, 06/2017, A5E00105505-AJ Digital modules 3.25 Digital output module SM 322; DO 16 x DC 24 V/0.5 A High Speed; (6ES7322-1BH10-0AA0) 3.25 Digital output module SM 322; DO 16 x DC 24 V/0.5 A High Speed; (6ES7322-1BH10-0AA0) Order number 6ES7322-1BH10-0AA0 Properties Properties of SM 322; DO 16 x DC 24 V/0.5 A High Speed: 16 outputs, electrically isolated in groups of 8 Output current 0.5 A Rated load voltage 24 V DC Suitable for solenoid valves, DC contactors and signal lamps Supports isochronous mode Use of the module with high-speed counters Please note when using the module in combination with high-speed counters: Note When using a mechanical contact to switch on the 24-V power supply to SM 322; DO 16 x DC 24 V/0.5 A High Speed, its outputs will carry "1" signal for the duration of ca. 50 s, due to the circuit structure. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 157 Digital modules 3.25 Digital output module SM 322; DO 16 x DC 24 V/0.5 A High Speed; (6ES7322-1BH10-0AA0) Wiring and block diagram of SM 322; DO 16 x DC 24 V/0.5 A High Speed Channel number Status display - green Backplane bus interface S7-300 Module data 158 Manual, 06/2017, A5E00105505-AJ Digital modules 3.25 Digital output module SM 322; DO 16 x DC 24 V/0.5 A High Speed; (6ES7322-1BH10-0AA0) Technical specifications of SM 322; DO 16 x DC 24 V/0.5 A High Speed Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 200 g Module-specific data Supports isochronous mode yes Number of outputs 16 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L+ 24 V DC Total current of outputs (per group) * horizontal mounting position to 40 C to 60 C * vertical mounting position max. 4 A max. 3 A max. 2 A to 40 C Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of Isolation test voltage 8 500 V DC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 70 mA max. 110 mA typ. 5 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none S7-300 Module data Manual, 06/2017, A5E00105505-AJ 159 Digital modules 3.25 Digital output module SM 322; DO 16 x DC 24 V/0.5 A High Speed; (6ES7322-1BH10-0AA0) Technical specifications Actuator selection data Output voltage * min. L + (- 0.8 V) "1" signal Output current * "1" signal Rated value Permitted range * "0" signal (residual current) 0.5 A 5 mA to 0.6 A Max. 0.5 mA Output delay (resistive load) * "0" to "1" transition max. 100 s * "1" to "0" transition max. 200 s Internal module cycle time between the backplane bus and the output driver input * "0" to "1" transition 0.1 s to 20 s * "1" to "0" transition 0.1 s to 20 s Load resistance range 48 to 4 k Lamp load max. 5 W Wiring two outputs in parallel * For redundant load control Supported (only outputs of the same group) * For performance increase Not supported Control of a digital input Supported Switching frequency * with resistive load max. 1000 Hz * with inductive load to IEC 947-5-1, DC 13 max. 0.5 Hz * with lamp load max. 10 Hz Internal limiting of the inductive shutdown voltage to typ. L + (-53 V) Short-circuit protection of the output yes, electronic * Threshold Wiring of the actuators typ. 1 A using a 20-pin front connector S7-300 Module data 160 Manual, 06/2017, A5E00105505-AJ Digital modules 3.26 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0) 3.26 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0) Order number 6ES7322-5GH00-0AB0 Properties Performance features of the SM 322; DO 16 x UC24/48 V digital output module: 16 electrically isolated semiconductor relay outputs Electrical isolation between channels of 120 V Switching characteristics: RDS ON is typically 0.25 Ohm, and RDS OFF is typically greater than 100 GOhm Designed for load voltages up to 48 V AC or DC, no minimum load voltage Designed for output loads up to 0.5 A, no minimum load current Outputs are fully independent and support any wiring configuration Set substitution values or "Hold last values" can be programmed at the outputs for CPU STOP. The module supports diagnostics of programming errors and of external power failure Suitable for AC solenoids, actuators, motor starters, FHP motors and signal lamps Supports parameter reassignment in RUN S7-300 Module data Manual, 06/2017, A5E00105505-AJ 161 Digital modules 3.26 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0) Wiring and block diagram of SM 322; DO 16 x UC 24/48 V Channel number Status LEDs - green Backplane bus interface Technical specifications of SM 322; DO 16 x UC 24/48 V Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 260 g Module-specific data Supports parameter reassignment in RUN * Reaction of non-programmed outputs Yes Return the output value which was valid before the parameterization Supports isochronous mode no Number of outputs 16 Cable length * * unshielded shielded max. 600 m max. 1000 m S7-300 Module data 162 Manual, 06/2017, A5E00105505-AJ Digital modules 3.26 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0) Dimensions and weight Voltages, currents, electrical potentials Rated electronics supply voltage L + * Reverse polarity protection * Power failure buffering 24 V DC yes min. 5 ms Total current of outputs (per group) * horizontal mounting position up to 60 C max. 0.5 A * other mounting positions to 40 C max. 0.5 A Cumulated current of outputs (per module) * horizontal mounting position to 60 C max. 8 A * other mounting positions to 40 C max. 8 A Electrical isolation * between channels and the backplane bus yes * between channels and electronics power supply yes * between channels yes in groups of 1 Maximum potential difference * between channels and the backplane bus 170 V DC, 120 V AC * between channels and electronics power supply 170 V DC, 120 V AC * between outputs of different groups 170 V DC, 120 V AC Isolation test voltage * between channels and the backplane bus 1500 V AC * between channels and electronics power supply 1500 V AC * between outputs of different groups 1500 V AC Current consumption * from the backplane bus * from supply voltage L+ Power loss of the module max. 100 mA max. 200 mA typ. 2.8 W Status, interrupts, diagnostics Status display green LED per channel Diagnostic functions * Group error display red LED (SF) Interrupts * Diagnostic interrupt * Reading diagnostics information programmable supported S7-300 Module data Manual, 06/2017, A5E00105505-AJ 163 Digital modules 3.26 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0) Dimensions and weight Actuator selection data Output voltage * min. L+ (-0.25 V) "1" signal Output current * Rated inrush current (per group) with "1" signal * "0" signal (residual current) 0.5 A max. 1.5 A (max. 50 ms) max. 10 A Output delay (resistive load) * "0" to "1" transition * "1" to "0" transition max. 6 ms max. 3 ms External fuse for relay outputs Fuse, I2 t :1 A2 s, fast-blow fuse* Lamp load max. 2.5 W Internal parallel wiring of 2 outputs Varistor, 85 V * for redundant load control * for performance increase Control of a digital input supported not supported supported Switching frequency * with resistive load max. 10 Hz * with inductive load to IEC 947-5-1; DC 12 AC/12 max. 0.5 Hz * with lamp load max. 0.5 Hz Wiring of the actuators using a 40pin front connector * Outputs must be protected by a 250 V fast-blow fuse (recommended fuses: Wickman 194-1100 1.1 A and Littlefuse 0217-800 V 800 mA.) When mounted in a hazardous area to National Electric Code (NEC), always remove the fuse when the module is outside of the potentially explosive atmosphere, and use a suitable tool. Configuration in RUN Special considerations must be given if you use the Configuration in RUN function. SF LED is lit: Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or module), although diagnostics are no longer pending and the module is operating correctly. Solution: Only change the configuration when no diagnostics are pending for the module or Pulling and plugging the module. S7-300 Module data 164 Manual, 06/2017, A5E00105505-AJ Digital modules 3.26 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0) 3.26.1 Parameters of digital output module SM 322 DO 16 x UC24/48 V Programming The tables below show data record numbers for static and dynamic parameters. Table 3- 24 Data record 0 (static parameters): Parameters Comment Enable diagnostics Enabling an interrupt as a reaction to module failure caused by faulty parameter, hardware error, or voltage error. Table 3- 25 Data record 1 (dynamic parameters): Parameters Comment Reaction to CPU STOP Hold last value Substitute value output Substitute value Substitute value Each bit represents an output This module supports fail state/substitution value outputs when the CPU changes from RUN to STOP. Status displays Each output of this module is equipped with a green LED to indicate the relay state. In addition, a red LED (SF) indicates the diagnostics status of the module. Diagnostics, troubleshooting Diagnostics data are assigned according to the technical data listed below. The four system diagnostics data bytes can be read in the additional interrupt information as data record 0, or in the first 4 bytes of data record 1. Structure of the data record and system diagnostics for SM 322 DO 16x UC 24/48V Structure of data record 1: Table 3- 26 Structure of the data record for SM 322 DO 16 x UC 24/48 V Data record 1 byte address Available information Contents 0..3 System-specific diagnostics data 4 bytes S7-300 Module data Manual, 06/2017, A5E00105505-AJ 165 Digital modules 3.26 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0) System diagnostics for SM 322;DO 16 x UC24/48 V: Table 3- 27 System diagnostics for SM 322 DO 16 x UC 24/48 V System diagnostics byte 1: Technical data D0: Module fault yes D1: Internal fault yes D2: External fault yes D3: Channel fault no D4: External auxiliary voltage missing yes D5: Front connector missing no D6: Module not programmed yes D7: Incorrect parameters yes System diagnostics byte 2: D0..D3: Module class 1111 D4: Channel information available no D5: User information available no D6: Diagnostics interrupt from substitute no D7: Reserve System diagnostics byte 3: D0: Wrong/missing memory module no D1: Communication error no D2: RUN/STOP operating state no D3: Watchdog timeout yes D4: Internal power failure no D5: Battery 1 low no D6: Backup system failure no D7: Reserve System diagnostics byte 4: D0: Rack failure no D1: Processor failure yes D2: EPROM fault yes D3: RAM fault yes D4: DAC error no D5: Fuse blown no D6: Process interrupt lost no D7: Reserve S7-300 Module data 166 Manual, 06/2017, A5E00105505-AJ Digital modules 3.27 Digital output module SM 322; DO 16 x AC 120/230 V/1 A; (6ES7322-1FH00-0AA0) 3.27 Digital output module SM 322; DO 16 x AC 120/230 V/1 A; (6ES7322-1FH00-0AA0) Order number 6ES7322-1FH00-0AA0 Properties Properties of digital output module SM 322; DO 16 x AC120/230 V/1 A: 16 outputs, fused and electrically isolated in groups of 8 Output current 1 A Rated load voltage 120/230 VAC Suitable for AC solenoids, actuators, motor starters, FHP motors and signal lamps Wiring and block diagram of SM 322 DO 16 x AC120/230 V/1 A Channel number Status LEDs - green Error LED - red Backplane bus interface S7-300 Module data Manual, 06/2017, A5E00105505-AJ 167 Digital modules 3.27 Digital output module SM 322; DO 16 x AC 120/230 V/1 A; (6ES7322-1FH00-0AA0) SM 322; DO 16 x AC 120/230 V/1 A - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D 40 x 125 x 117 Weight ca. 275 g Module-specific data Supports isochronous mode No Number of outputs 16 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Load voltage L1 All load voltages must be connected to the same phase 120/230 VAC Total current of outputs (per group) * horizontal mounting position to 40 C to 60 C * vertical mounting position max. 4 A max. 2 A max. 2 A to 40 C Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of 8 Maximum potential difference * between Minternal and outputs 230 VAC * between outputs of different groups 500 VAC Isolation test voltage 4000 VDC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 200 mA max. 2 mA typ. 8.6 W Status, interrupts, diagnostics Status display green LED per channel Interrupts * Diagnostic interrupt Diagnostic functions * Group error display no red LED (SF) (fuse or no L1/N) S7-300 Module data 168 Manual, 06/2017, A5E00105505-AJ Digital modules 3.27 Digital output module SM 322; DO 16 x AC 120/230 V/1 A; (6ES7322-1FH00-0AA0) Technical specifications Actuator selection data Output voltage * "1" signal - At maximum current - At minimum current min. L 1 (- 1.5 V) min. L 1 (- 8.5 V) Output current * "1" signal Rated value Permitted range at 0 C to 40 C Permitted range at 0C to 60C 1A 10 mA to 1 A 10 mA to 0.5 A 20 A (two half-waves) Maximum inrush current (per group) * with "0" signal (residual current) Blocking voltage max. 2 mA max. 60 V Zero transition Size of the motor starter max. size 4 to NEMA Lamp load max. 50 W Wiring two outputs in parallel * for redundant load control supported (only outputs of the same group) * for performance increase no Control of a digital input supported Switching frequency max. 10 Hz * with resistive load * with inductive load to IEC 947-5-1, AC 15 max. 0.5 Hz * with lamp load max. 1 Hz Short-circuit protection of the output Fuse 8 A, 250 V; per group * Fuse-tripping current min. 40 A * Response time max. 300 ms Replacement fuses * Wickman * Schurter * Littlefuse 8 A fuse, fast-blowing 19 194-8 A SP001.1014 217.008 Fuse holder * Wickman Wiring of the actuators 19 653 using a 20-pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 169 Digital modules 3.28 Digital output module SM 322; DO 8 x DC 24 V/2 A; (6ES7322-1BF01-0AA0) 3.28 Digital output module SM 322; DO 8 x DC 24 V/2 A; (6ES7322-1BF01-0AA0) Order number 6ES7322-1BF01-0AA0 Properties Properties of SM 322; DO 8 x DC 24 V/2 A: 8 outputs, electrically isolated in groups of 4 Output current 2 A Rated load voltage 24 V DC Suitable for solenoid valves, DC contactors and signal lamps Use of the module with high-speed counters Please note when using the module in combination with high-speed counters: Note When using a mechanical contact to switch on the 24-V power supply to SM 322; DO 8 x DC 24 V/2 A, the module outputs will carry a "1" signal for the duration of ca. 50 s due to the circuit structure. S7-300 Module data 170 Manual, 06/2017, A5E00105505-AJ Digital modules 3.28 Digital output module SM 322; DO 8 x DC 24 V/2 A; (6ES7322-1BF01-0AA0) Wiring and block diagram of SM 322; DO 8 x DC 24 V/2 A Channel number Status display - green Backplane bus interface SM 322; DO 8 x DC 24 V/2 A - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 190 g Module-specific data Supports isochronous mode no Number of outputs 8 Cable length * unshielded * shielded max. 600 m max. 1000 m S7-300 Module data Manual, 06/2017, A5E00105505-AJ 171 Digital modules 3.28 Digital output module SM 322; DO 8 x DC 24 V/2 A; (6ES7322-1BF01-0AA0) Technical specifications Voltages, currents, electrical potentials Rated load voltage L+ 24 V DC Total current of outputs (per group) * horizontal mounting position max. 4 A to 60 C * vertical mounting position max. 4 A to 40 C Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of Isolation test voltage 4 500 V DC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 40 mA max. 60 mA typ. 6.8 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none Actuator selection data Output voltage * min. L+ (- 0.8 V) "1" signal Output current * "1" signal Rated value Permitted range * with "0" signal (residual current) 2A 5 mA to 2.4 A max. 0.5 mA Output delay (with resistance load) * "0" to "1" transition max. 100 s * "1" to "0" transition max. 500 s Load resistance range 12 to 4 k Lamp load max. 10 W Wiring two outputs in parallel * for redundant load control supported (only outputs of the same group) * for performance increase not supported Control of a digital input supported S7-300 Module data 172 Manual, 06/2017, A5E00105505-AJ Digital modules 3.28 Digital output module SM 322; DO 8 x DC 24 V/2 A; (6ES7322-1BF01-0AA0) Technical specifications Switching frequency * with resistive load max. 100 Hz * with inductive load to IEC 947-5-1, DC 13 max. 0.5 Hz * with lamp load max. 10 Hz Internal limiting of the inductive shutdown voltage to typ. L + (-48 V) Short-circuit protection of the output yes, electronic * Threshold Wiring of the actuators typ. 3 A using a 20-pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 173 Digital modules 3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) 3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) Order number: "Standard module" 6ES7322-8BF00-0AB0 Order number: "SIPLUS S7-300 module" 6AG1322-8BF00-2AB0 Properties Properties of SM 322; DO 8 x DC 24 V/0.5 A: 8 outputs, electrically isolated in groups of 8 Output current 0.5 A Rated load voltage 24 V DC Suitable for solenoid valves, DC contactors and signal lamps 2 terminals per output - Output without series diode - Output with series diode (for redundant load control) Group error display (SF) Channel-specific status and error LEDs Programmable diagnostics Programmable diagnostic interrupt Programmable substitute value output Supports parameter reassignment in RUN S7-300 Module data 174 Manual, 06/2017, A5E00105505-AJ Digital modules 3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) Wiring and block diagram of SM 322; DO 8 x DC 24 V/ 0.5 A Group error display -redChannel number (0 ... 7) Channel fault display -red- (F0 ... F7) Status display -greenBackplane bus interface Figure 3-9 Wiring and block diagram of SM 322; DO 8 x 24 V DC / 0.5 Redundant load control The output with series diode can be used for redundant load control. Redundant control without external circuitry is possible using two different signal modules. Both modules must be connected to the common reference potential M. Note It is not possible to detect external short-circuits to L+ at output with series diode. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 175 Digital modules 3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) SM 322; DO 8 x DC 24 V/0.5 A - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 210 g Module-specific data Supports parameter reassignment in RUN * Reaction of non-programmed outputs Yes Return the output value which was valid before the parameterization Supports isochronous mode no Number of outputs 8 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L+ 24 V DC Total current (per group) of outputs without series diode * horizontal mounting position to 40 C to 60 C * vertical mounting position max. 4 A max. 3 A max. 4 A to 40 C Total current of outputs (per group) with series diode * horizontal mounting position to 40 C to 60 C * vertical mounting position max. 3 A max. 2 A max. 3 A to 40 C Electrical isolation * between channels and the backplane bus yes * between channels in groups of yes 8 Isolation test voltage 500 V DC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 70 mA max. 90 mA typ. 5 W S7-300 Module data 176 Manual, 06/2017, A5E00105505-AJ Digital modules 3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) Technical specifications Status, interrupts, diagnostics Status display green LED per channel Interrupts programmable * Diagnostic interrupt Diagnostic functions * Group error display * Channel error display (F) * Reading diagnostics data programmable red LED (SF) red LED (F) per channel supported Actuator selection data Output voltage * "1" signal without series diode with series diode min. L + (- 0.8 V) min. L+ (-1.6 V) Output current * "1" signal Rated value Permitted range * "0" signal (residual current) 0.5 A 10 mA to 0.6 A1) max. 0.5 mA Output delay (resistive load) * "0" to "1" transition max. 180 s "1" to "0" transition max. 245 s Load resistance range 48 to 3 k Lamp load max. 5 W * Wiring two outputs in parallel * for redundant load control Only outputs with series diode and common reference potential * for performance increase not supported Control of a digital input supported 1 binary input to IEC 61131, Type 2; Type 1, with disabled wire-break monitoring Switching frequency * with resistive load * with inductive load to IEC 947-5-1, DC 13 * with lamp load Internal limiting of the inductive shutdown voltage to Short-circuit protection of the output * Threshold Wiring of the actuators max. 100 Hz max. 2 Hz max. 10 Hz typ. L + (-45 V) yes, electronic typ. 0.75 A to 1.5 A using a 20-pin front connector 1) 5 mA to 0.6 A, with disabled wire-break monitoring S7-300 Module data Manual, 06/2017, A5E00105505-AJ 177 Digital modules 3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) Configuration in RUN Special considerations must be given if you use the Configuration in RUN function. SF LED is lit: Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or module), although diagnostics are no longer pending and the module is operating correctly. Solution: Only change the configuration when no diagnostics are pending for the module or Pulling and plugging the module. 3.29.1 SM 322; DO 8 x DC 24 V/0.5 A - Parameters Programming The general procedure of programming digital modules is described in the chapter Programming digital modules (Page 58). SM 322; DO 8 x DC 24 V/0.5 A - Parameters The table below lists the programmable parameters of SM 322; DO 8 x DC 24 V/0.5 A, including defaults. The defaults apply if you have not set any parameters in STEP 7. Table 3- 28 Parameters of SM 322; DO 8 x DC 24 V/0.5 A Parameters Range of values Default Parameter type Scope yes/no no dynamic Module Set substitute value (SSV) SSV static Channel dynamic Channel Enable * Diagnostics interrupt Reaction to CPU STOP Hold last value (HLV) Diagnostics * Wirebreak * No load voltage L * Short-circuit to M * Short-circuit to L Set substitute value "1" yes/no no yes/no yes/no no no yes/no no yes/no no S7-300 Module data 178 Manual, 06/2017, A5E00105505-AJ Digital modules 3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) 3.29.2 SM 322; DO 8 x DC 24 V/0.5 A - Diagnostics Diagnostics messages of SM 322; DO 8 x DC 24 V/0.5 A The table provides an overview of the diagnostic messages of SM 322; DO 8 x DC 24 V/0.5 A Table 3- 29 Diagnostics messages of SM 322; DO 8 x DC 24 V/0.5 A Diagnostics message LED Scope of diagnostics programmable Wire-break* SF Channel yes Load voltage missing SF Channel yes Short-circuit to M SF Channel yes Short-circuit to L+ SF Channel yes External auxiliary voltage missing SF Module no Internal auxiliary voltage missing SF Module no Fuse blown SF Module no Watchdog time-out SF Module no EPROM fault SF Module no RAM fault SF Module no * The module detects a wire-break at a current < 1 mA. If configured accordingly, the SF LED and corresponding channel error LED light up when a wire-break is detected. Note Prerequisite for the detection of errors indicated by programmable diagnostic messages is an appropriate configuration of the digital module in STEP 7. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 179 Digital modules 3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) Causes of error and troubleshooting Table 3- 30 Diagnostic messages of SM 322; DO 8 x DC 24 V/0.5 A, causes of error and troubleshooting Diagnostics message Error detection condition ... Possible cause of error To correct or avoid error Wirebreak Only when output = "1" Wire-break between the module and actuator Connect the cable Channel not connected (open) Disable the "wire-break diagnostics" parameter for the channel in STEP 7 Load voltage missing Only when output = "1" Defective output Replace the module Short-circuit to M Only when output = "1" Overload at output Eliminate overload Short-circuit of output to M Eliminate the short-circuit Short-circuit to L+ generally Short-circuit at output to L+ of the module power supply Eliminate the short-circuit External auxiliary voltage missing generally Power supply L+ to module missing Feed supply L+ Internal auxiliary voltage missing generally Power supply L+ to module missing Feed supply L+ Fuse blown Watchdog timeout EPROM fault RAM fault Fuse blown in module Replace the module generally Fuse blown in module Replace the module generally Infrequent high electromagnetic interference Eliminate the interference Defective module Replace the module Infrequent high electromagnetic interference Eliminate interference and cycle the power supply of CPU off/on. Defective module Replace the module Infrequent high electromagnetic interference Eliminate interference and cycle the power supply of CPU off/on. Defective module Replace the module generally generally S7-300 Module data 180 Manual, 06/2017, A5E00105505-AJ Digital modules 3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) 3.29.3 SM 322; DO 8 x DC 24 V/0.5 A - Behavior Influence of the operating state and supply voltage on output values The output values of SM 322; DO 8 x DC 24V/0.5 A are determined by the CPU's operating state and the module's power supply. Table 3- 31 Influence of the CPU operating state and of the supply voltage L+ of SM 322; DO 8 24 VDC/0.5 A on output values. CPU operating state POWER ON RUN STOP POWER OFF - Power supply L+ at digital module Output value of the digital module L+ present CPU value L+ missing 0 signal L+ present Substitute value/last value (default = 0 signal) L+ missing 0 signal L+ present 0 signal L+ missing 0 signal Reaction to power failure Failure of the power supply to SM 322; DO 8 x DC 24V/0.5 A is always indicated at the module's SF LED. This information is also available on the module (entry in diagnostics data.) Triggering of diagnostics interrupts is determined by the parameter settings (see the next chapter Interrupts of SM 322; DO 8 x DC 24/0.5 A (Page 182)). See also SM 322; DO 8 x DC 24 V/0.5 A - Parameters (Page 178) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 181 Digital modules 3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0) 3.29.4 SM 322; DO 8 x DC 24 V/0.5 A - Interrupts Introduction The SM 322; DO 8 x DC 24 V/0.5 A can trigger diagnostic interrupts. For detailed information on the OBs and SFCs mentioned below, refer to the STEP 7 Online Help. Enabling interrupts There is no default interrupt setting, i.e. interrupts are disabled if parameters are not set accordingly. Program the interrupt enable parameter in STEP 7. Diagnostics interrupt Incoming error events (initial occurrence) and outgoing error events (error is cleared) are reported by means of diagnostics interrupt, if this interrupt is enabled. The CPU interrupts user program execution in order to process diagnostics interrupt OB82. You can call SFC51 or 59 in OB82 in the user program to view detailed diagnostics data output by the module. Diagnostics data remain consistent until the program exits OB82. The module acknowledges the diagnostics interrupt when the program exits OB82. See also SM 322; DO 8 x DC 24 V/0.5 A - Parameters (Page 178) S7-300 Module data 182 Manual, 06/2017, A5E00105505-AJ Digital modules 3.30 Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0) 3.30 Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0) Order number: "Standard module" 6ES7322-1CF00-0AA0 Order number: "SIPLUS S7-300 module" 6AG1322-1CF00-2AA0 Properties Properties of SM 322; DO 8 x DC 48-125 V/1.5 A: 8 outputs, with reverse polarity protection, and electrically isolated in groups of 4 Output current 1.5 A Rated load voltage 48 VDC to 125 VDC Suitable for solenoid valves, DC contactors and signal lamps Group error display (SF) Use of the module with high-speed counters Please note when using the module in combination with high-speed counters: Note When using a mechanical contact to switch on the power supply, the outputs of SM 322; DO 8 x DC 48-125 V/1.5 A will carry a "1" signal for the duration of ca. 50 s due to the circuit structure. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 183 Digital modules 3.30 Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0) Wiring and block diagrams of SM 322; DO 8 x DC 48-125 V/1.5 A Channel number Status display - green Error LED - red Backplane bus interface S7-300 Module data 184 Manual, 06/2017, A5E00105505-AJ Digital modules 3.30 Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0) Technical specifications of M 322; DO 8 x DC 48-125 V/1.5 A Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 250 g Module-specific data Supports isochronous mode no Number of outputs 8 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L+ * Reverse polarity protection 48 VDC to 125 VDC yes, by fusing1) Total current of outputs (per group) * horizontal mounting position to 40 C to 50 C max. 6 A max. 4 A max. 3 A to 60 C * vertical mounting position max. 4 A to 40 C Electrical isolation * between channels and the backplane bus * between channels in groups of yes yes 4 Maximum potential difference * between different circuits Isolation test voltage 146 VDC / 132 VAC 1500 VAC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 100 mA max. 2 mA typ. 7.2 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions * Group error display red LED (SF) 2) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 185 Digital modules 3.30 Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0) Technical specifications Actuator selection data Output voltage * min. L+ (-1.2 V) "1" signal Output current * "1" signal 1.5 A 10 mA to 1.5 A Rated value Permitted range * Permitted surge current max. 3 A for a duration of 10 ms * with "0" signal (residual current) max. 0.5 mA Output delay (resistive load) * "0" to "1" transition * "1" to "0" transition Lamp load max. 2 ms max. 15 ms max. 15 W at 48 V max. 40 W at 125 V Wiring two outputs in parallel * for redundant load control supported (only outputs of the same group) * for performance increase not supported Control of a digital input Switching frequency * with resistive load * with inductive load * with lamp load Internal limiting of the inductive shutdown voltage to Short-circuit protection of the output * Threshold Replacement fuses * Schurter * Wickman supported max. 25 Hz max. 0.5 Hz max. 10 Hz typ. M (-1V) yes, electronic3) typ. 4.4 A Fuse 6.3 A/250 V, fast-blow, 5 x 20 mm SP0001.1012 194-1630-0 Fuse holder * 653 0000 040 Wickman Wiring of the actuators using a 20-pin front connector 1) Fuses on this module are only supplementary. External surge current protection (suitable for tap circuits conforming to local regulations for electrical engineering) is required in the supply lines of the load circuit. 2) Possible errors: - no load voltage - defective fuse - output overload 3) If an overload condition is detected, the output is disabled for the duration of ca. 2.4 s. S7-300 Module data 186 Manual, 06/2017, A5E00105505-AJ Digital modules 3.31 Digital output module SM 322;DO 8 x AC 120/230 V/2 A; (6ES7322-1FF01-0AA0) 3.31 Digital output module SM 322;DO 8 x AC 120/230 V/2 A; (6ES7322-1FF01-0AA0) Order number: "Standard module" 6ES7322-1FF01-0AA0 Order number: "SIPLUS S7-300 module" 6AG1322-1FF01-2AA0 Properties Properties of SM 322; DO 8 x AC 120/230 V/2 A: 8 outputs, fused and electrically isolated in groups of 4 Output current 2 A Rated load voltage 120/230 VAC Suitable for AC solenoid valves, contactors, motor starters, FHP motors and signal lamps. Group error display (SF) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 187 Digital modules 3.31 Digital output module SM 322;DO 8 x AC 120/230 V/2 A; (6ES7322-1FF01-0AA0) Wiring and block diagram of SM 322; DO 8 x AC 120/230 V/2 A Channel number Status display - green Error LED - red Backplane bus interface Optotriac S7-300 Module data 188 Manual, 06/2017, A5E00105505-AJ Digital modules 3.31 Digital output module SM 322;DO 8 x AC 120/230 V/2 A; (6ES7322-1FF01-0AA0) SM 322; DO 8 x AC 120/230 V/2 A - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 275 g Module-specific data Supports isochronous mode no Number of outputs 8 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L1 * Maximum frequency range 120/230 VAC 47 Hz to 63 Hz Total current of outputs (per group) * horizontal mounting position to 40 C to 60 C * vertical mounting position to 40 C max. 4 A max. 2 A max. 2 A Electrical isolation * between channels and the backplane bus * between channels in groups of yes yes 4 Maximum potential difference * between Minternal and outputs 230 VAC * between outputs of different groups 500 VAC Isolation test voltage 1500 VAC Current consumption * from the backplane bus * from load voltage L1 (no-load) Power loss of the module max. 100 mA max. 2 mA typ. 8.6 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions yes * Group error display red LED (SF) 2) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 189 Digital modules 3.31 Digital output module SM 322;DO 8 x AC 120/230 V/2 A; (6ES7322-1FF01-0AA0) Technical specifications Actuator selection data Output voltage * "1" signal - At maximum current - At minimum current min. L1 (-1.5 V) min. L1 (-8.5 V) Output current * "1" signal Rated value permissible range at 0 C to 40 C permissible range at 40 C to 60 C Maximum inrush current (per group) * "0" signal (residual current) AC 2 A1) 10 mA to 2 A 10 mA to 1 A max. 20 A (max. 1 AC cycle) max. 2 mA Output delay (resistive load) * "0" to "1" transition max. 1 AC cycle * "1" to "0" transition max. 1 AC cycle Minimum load current Zero transition 10 mA max. 60 V Size of the motor starter Lamp load Wiring two outputs in parallel max. size 5 to NEMA max. 50 W * for redundant load control supported (only outputs of the same group) * for performance increase not supported Control of a digital input supported Switching frequency * with resistive load * with inductive load to IEC 947-5-1, AC 15 * with lamp load Short-circuit protection of the output max. 10 Hz max. 0.5 Hz max. 1 Hz * Fuse-tripping current Fuse, 8 A/250 V; per group min. 40 A * Response time max. 300 ms Replacement fuses * Wickman * Schurter * Littlefuse 8 A fuse/fast-blow 194-1800-0 SP001.1013 217.008 Fuse holder * 653 07 Wickman Wiring of the actuators using a 20-pin front connector 1) The load current must not be half-wave 2) Possible errors: - no load voltage - defective fuse S7-300 Module data 190 Manual, 06/2017, A5E00105505-AJ Digital modules 3.32 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0) 3.32 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0) Order number 6ES7322-5FF00-0AB0 Properties Properties of digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL: 8 outputs, electrically isolated Group error display Channelspecific status LEDs Configurable diagnostics Programmable diagnostic interrupt Programmable substitute value output Output current 2 A Rated load voltage 120/230 V AC Suitable for AC solenoid valves, contactors, motor starters, FHP motors and signal lamps Supports parameter reassignment in RUN S7-300 Module data Manual, 06/2017, A5E00105505-AJ 191 Digital modules 3.32 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0) Wiring and block diagram of SM 322; DO 8 x AC 120/230 V/2 A ISOL Group error display - red Backplane bus interface Channel number Status display - green S7-300 Module data 192 Manual, 06/2017, A5E00105505-AJ Digital modules 3.32 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0) SM 322; DO 8 x AC 120/230 V/2 A ISOL - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D 40 x 125 x 117 Weight approx. 275 g Module-specific data Supports parameter reassignment in RUN * Reaction of non-programmed outputs Yes Return the output value which was valid before the parameterization Supports isochronous mode No Number of outputs 8 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L1 120/230 V AC Total current of outputs (module) * Horizontal mounting position to 40 C to 60 C * vertical mounting position max. 8 A max. 4 A max. 4 A to 40 C Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of 1 Maximum potential difference * between Minternal and outputs 230 V AC * between outputs 500 V AC Isolation test voltage * between Minternal and outputs 1500 V AC * between outputs of different groups 2000 V AC Current consumption * from the backplane bus * from load voltage L1 (no-load) Power loss of the module max. 100 mA max. 2 mA typ. 8.6 W S7-300 Module data Manual, 06/2017, A5E00105505-AJ 193 Digital modules 3.32 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0) Technical specifications Status, interrupts, diagnostics Status display green LED per channel Interrupts * Diagnostic interrupt programmable Diagnostic functions * Group error display red LED (SF) Actuator selection data Output voltage * "1" signal - At maximum current - At minimum current min. L1 (-1.5 V) min L1 (-8.5 V) Output current * "1" signal 2A Rated value permissible range at 0 C to 40 C permissible range at 40 C to 60 C 10 mA to 2 A 10 mA to 1 A 20 A (with two half-waves) Maximum inrush current (per group) * "0" signal (residual current) max. 2 mA Zero transition max. 60 V Size of the motor starter max. size 5 to NEMA Lamp load max. 50 W Wiring two outputs in parallel * for redundant load control supported * for performance increase not supported Control of a digital input supported Switching frequency * with resistive load max. 10 Hz * with inductive load to IEC 947-5-1, AC 15 max. 0.5 Hz * with lamp load max. 1 Hz Short circuit-proof output yes, 3.15 A / 250 V fuse, fast-blow Wiring of the actuators Using a 40-pin front connector Note The outputs must be protected by a high-speed, fast-blow 3.15 A 250 V AC fuse. Hazardous areas to National Electric Code must be determined safe before you remove/replace the fuse. Removal and replacement may only be possible using a suitable tool. S7-300 Module data 194 Manual, 06/2017, A5E00105505-AJ Digital modules 3.32 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0) Configuration in RUN Special considerations must be given if you use the Configuration in RUN function. SF LED is lit: Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or module), although diagnostics are no longer pending and the module is operating correctly. Solution: Only change the configuration when no diagnostics are pending for the module or Pulling and plugging the module. 3.32.1 Parameters of SM 322; DO 8 x AC 120/230 V/2 A ISOL Parameters of SM 322; DO 8 x AC 120/230 V/2 A ISOL The table below lists the configurable parameters of SM 322; DO 8 x AC120/230 V/2 A ISOL, including defaults. The defaults apply if you have not set any parameters in STEP 7. Table 3- 32 Parameters of SM 322; DO 8 x AC 120/230 V/2 A ISOL Parameters Range of values Defaults Parameter type Scope yes/no no dynamic Module Set substitute value (SSV) SSV dynamic Channel no dynamic Channel Enable * Diagnostic interrupts Reaction to CPU STOP Hold last value (HLV) Set substitute value "1" yes/no Programming For detailed information on parameters of the digital output module, refer to the appendix Settings for the digital output modules (Page 528). See also Programming digital modules (Page 58) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 195 Digital modules 3.32 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0) 3.32.2 SM 322; DO 8 x AC 120/230 V/2 A ISOL - Diagnostics Diagnostic messages of SM 322; DO 8 x AC 120/230 V/2 A ISOL The table below provides an overview of the diagnostic messages of SM 322; DO 8 x 120/230 VAC/2 A ISOL. Table 3- 33 Diagnostic messages of SM 322; DO 8 x AC 120/230 V/2 A ISOL Diagnostics message LED Scope of diagnostics programmable Watchdog timeout SF Module no EPROM fault SF Module no RAM fault SF Module no Causes of error and troubleshooting The following table shows the diagnostic messages of SM 322; DO 8 x AC 120/230V/2 A ISOL, causes of error and troubleshooting. Table 3- 34 Diagnostic messages of SM 322; DO 8 x AC 120/230V/2 A ISOL, error causes and troubleshooting Diagnostics message Error detection Possible cause of error To correct or avoid errors Watchdog timeout Always Transient high electromagnetic interference Eliminate interference and cycle the CPU power supply off and on Defective module Replace the module Transient high electromagnetic interference Eliminate interference and cycle the CPU power supply off and on Defective module Replace the module Transient high electromagnetic interference Eliminate interference and cycle the CPU power supply off and on Defective module Replace the module EPROM fault Always RAM fault 3.32.3 Always SM 322; DO 8 x AC 120/230 V/2 A ISOL - Interrupts Introduction The SM 322; DO 8 x AC 120/230 V/2 A ISOL can trigger diagnostic interrupts. For detailed information on the OBs and SFCs mentioned below, refer to the STEP 7 Online Help. Enabling interrupts There is no default interrupt setting, i.e. interrupts are disabled if not set accordingly. Program the interrupt enable parameter in STEP 7. S7-300 Module data 196 Manual, 06/2017, A5E00105505-AJ Digital modules 3.32 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0) Diagnostic interrupt When diagnostic interrupts are enabled, incoming error events (initial occurrence) and outgoing error events (error is cleared) are reported by means of interrupt. The CPU interrupts user program execution in order to process diagnostics interrupt OB82. You can call SFC51 or 59 in OB82 in the user program to obtain detailed diagnostics data from the module. Diagnostics data remain consistent until the program exits OB82. The module acknowledges the diagnostic interrupt when the program exits OB82. Load restrictions in horizontal mounting position In horizontal mounting position, the module loads must be restricted so that two adjacent inputs or outputs do not exceed their rated load. Load restrictions in vertical mounting position In vertical mounting position, the module loads must be restricted so that four adjacent inputs or outputs do not exceed their rated load. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 197 Digital modules 3.33 Relay output module SM 322; DO 16 x Rel. AC 120/230 V; (6ES7322-1HH01-0AA0) 3.33 Relay output module SM 322; DO 16 x Rel. AC 120/230 V; (6ES7322-1HH01-0AA0) Order number 6ES7322-1HH01-0AA0 Properties The SM 322; DO 16 x Rel. 120/230 V AC is characterized by the following properties: 16 outputs, electrically isolated in groups of 8 Load voltage 24 to 120 V DC; 24 to 230 V AC Suitable for AC/DC solenoid valves, contactors, motor starters, FHP motors and signal lamps. Reaction to a shutdown of the power supply Note The internal 200-ms buffer capacitance discharges sufficient power after power off to allow the user program to set a defined relay state. S7-300 Module data 198 Manual, 06/2017, A5E00105505-AJ Digital modules 3.33 Relay output module SM 322; DO 16 x Rel. AC 120/230 V; (6ES7322-1HH01-0AA0) Wiring and block diagram of SM 322; DO 16 x Rel. 120/230 V AC Channel number Status display - green Backplane bus interface S7-300 Module data Manual, 06/2017, A5E00105505-AJ 199 Digital modules 3.33 Relay output module SM 322; DO 16 x Rel. AC 120/230 V; (6ES7322-1HH01-0AA0) Technical specifications of the SM 322; DO 16 x Rel. 120/230 V AC Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 250 g Module-specific data Supports isochronous mode no Number of outputs 16 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated power supply L+ to the relays 24 V DC Total current of outputs (per group) max. 8 A Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of 8 Maximum potential difference * Between Minternal and the power supply to relays and outputs 230 V AC * Between outputs of different groups 500 V AC Isolation test voltage * between Minternal and the power supply to relays 500 V DC * between Minternal and the power supply to relays and outputs 1500 V AC * between outputs of different groups 2000 V AC Current consumption * from the backplane bus * from power supply L+ Power loss of the module max. 100 mA max. 250 mA typ. 4.5 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none S7-300 Module data 200 Manual, 06/2017, A5E00105505-AJ Digital modules 3.33 Relay output module SM 322; DO 16 x Rel. AC 120/230 V; (6ES7322-1HH01-0AA0) Technical specifications Actuator selection data Thermal current, continuous max. 2 A Minimum load voltage / current 10 V / 10 mA Short-circuit current to IEC 947-5-1 200 A, with B10/B16 circuit breaker Switching capacity and service life of contacts * with resistive load Voltage Current No. of switching cycles (typical) 24 V DC 2.0 A 0.1 million 1.0 A 0.2 million 0.5 A 1.0 million 60 V DC 0.5 A 0.2 million 120 V DC 0.2 A 0.6 million 24 V AC 1.5 A 1.5 million 48 V AC 1.5 A 1.5 million 60 V AC 1.5 A 1.5 million 120 V AC 2.0 A 1.0 million 1.0 A 1.5 million 0.5 A 2.0 million 2.0 A 1.0 million 1.0 A 1.5 million 0.5 A 2.0 million Voltage Current No. of switching cycles (typical) 24 V DC 2.0 A 0.05 million 1.0 A 0.1 million 230 V AC * with inductive load to IEC 947-5-1 DC13/AC15 0.5 A 0.5 million DC 60 V 0.5 A 0.1 million DC 120 V 0.2 A 0.3 million 24 V AC 1.5 A 1 million 48 V AC 1.5 A 1 million AC 60 V 1.5 A 1 million AC 120 V 2.0 A 0.7 million 1.0 A 1.0 million 0.5 A 1.5 million 2.0 A 0.7 million 1.0 A 1.0 million 0.5 A 1.5 million 230 V AC An external protective circuit will increase the service life of contacts. Size of the motor starter Lamp load max. size 5 to NEMA 50 W / 230 V AC 5 W / 24 V DC Contact protection (internal) none S7-300 Module data Manual, 06/2017, A5E00105505-AJ 201 Digital modules 3.33 Relay output module SM 322; DO 16 x Rel. AC 120/230 V; (6ES7322-1HH01-0AA0) Technical specifications Wiring two outputs in parallel * for redundant load control supported (only outputs of the same group) * for performance increase not supported Control of a digital input supported Switching frequency * Mechanical max. 10 Hz * with resistive load max. 1 Hz * with inductive load to IEC 947-5-1, DC13/AC15 max. 0.5 Hz * with lamp load max. 1 Hz Wiring of the actuators using a 20-pin front connector S7-300 Module data 202 Manual, 06/2017, A5E00105505-AJ Digital modules 3.34 Relay output module SM 322; DO 8 x Rel. AC 230 V; (6ES7322-1HF01-0AA0) 3.34 Relay output module SM 322; DO 8 x Rel. AC 230 V; (6ES7322-1HF01-0AA0) Order number 6ES7322-1HF01-0AA0 Properties The SM 322; DO 8 x Rel. 230 V AC is characterized by the following properties: 8 outputs, electrically isolated in groups of 2 Rated load voltage 24 to 120 V DC, 48 V to 230 V AC Suitable for AC/DC solenoid valves, contactors, motor starters, FHP motors and signal lamps. Reaction to a shutdown of the power supply Note The following only applies to SM 322; DO 8 x Rel. 230 V AC with product version 1: The internal backup capacitor provides power for the duration of ca. 200 ms. This backup time is sufficient to briefly control the relay in the user program. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 203 Digital modules 3.34 Relay output module SM 322; DO 8 x Rel. AC 230 V; (6ES7322-1HF01-0AA0) Wiring and block diagram of SM 322; DO 8 x Rel. 230 V AC Channel number Status display - green Backplane bus interface Technical specifications of the SM 322; DO 8 x Rel. 230 V AC Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 190 g Module-specific data Supports isochronous mode no Number of outputs 8 Cable length * unshielded * shielded max. 600 m max. 1000 m S7-300 Module data 204 Manual, 06/2017, A5E00105505-AJ Digital modules 3.34 Relay output module SM 322; DO 8 x Rel. AC 230 V; (6ES7322-1HF01-0AA0) Technical specifications Voltages, currents, electrical potentials Rated power supply L+ to the relays 24 V DC Total current of outputs (per group) max. 4 A Electrical isolation * between channels and the backplane bus yes * between channels yes 2 in groups of Maximum potential difference * Between Minternal and the power supply to relays and outputs 230 V AC * Between outputs of different groups 500 V AC Isolation test voltage * between Minternal and the power supply to relays 500 V DC * between Minternal and the power supply to relays and outputs 2000 V AC * between outputs of different groups 2000 V AC Current consumption * from the backplane bus * from power supply L+ max. 40 mA max. 160 mA Power loss of the module typ. 3.2 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none Actuator selection data Thermal current, continuous max. 3 A Minimum load voltage / current Short circuit-proof to IEC 947-5-1 10 V / 5 mA 2) With circuit-breaker, characteristics B, for: cos 1.0: 600 A cos 0.5...0.7: 900 A With 8 A Diazed fuse: 1000 A S7-300 Module data Manual, 06/2017, A5E00105505-AJ 205 Digital modules 3.34 Relay output module SM 322; DO 8 x Rel. AC 230 V; (6ES7322-1HF01-0AA0) Technical specifications Switching capacity and useful life of contacts * with resistive load Voltage Current No. of switching cycles (typical) 24 V DC 2.0 A 0.7 million 1.0 A 1.6 million 0.5 A 4 million 60 V DC 0.5 A 1.6 million 120 V DC 0.2 A 1.6 million 48 V AC 2.0 A 1.6 million 60 V AC 2.0 A 1.2 million 120 V AC 2.0 A 0.5 million 2) 1.0 A 0.7 million 2) 0.5 A 1.5 million 2) 2.0 A 0.5 million 2) 1.0 A 0.7 million 2) 0.5 A 1.5 million Voltage Current No. of switching cycles (typical) 24 V DC 2.0 A 0.3 million 1.0 A 0.5 million 0.5 A 1.0 million 0.5 A 0.5 million 0.2 A 0.3 million 2) 120 V DC 1.5 A 1 million 48 V AC 1.5 A 1 million 60 V AC 2.0 A 0.2 million 120 V AC 1.0 A 0.7 million 0.7 A 1 million 0.5 A 2.0 million 2.0 A 0.3 million 2) 1.0 A 0.7 million 2) 0.5 A 2 million 2) 230 V AC * with inductive load to IEC 947-5-1 DC13/AC15 60 V DC 230 V AC Contact protection (internal) Varistor SIOV-CU4032 K275 G An external protective circuit extends the useful life of contacts. Actuator selection data [continued] Lamp load 1) Lamp load (230 V AC) 2) Energy-saving lamps/fluorescent lamps with electronic ballast2) max. 50 W Power No. of switching cycles (typical) 700 W 25000 1500 W 10000 10 x 58 W 25000 S7-300 Module data 206 Manual, 06/2017, A5E00105505-AJ Digital modules 3.34 Relay output module SM 322; DO 8 x Rel. AC 230 V; (6ES7322-1HF01-0AA0) Technical specifications Fluorescent lamps, conventionally compensated 2) 1 x 58 W 25000 Fluorescent lamps, non-compensated 10 x 58 W 25000 2) Wiring two outputs in parallel * for redundant load control supported (only outputs of the same group) * for performance increase not supported Control of a digital input supported Switching frequency * Mechanical max. 10 Hz * with resistive load max. 2 Hz * with inductive load to IEC 947-5-1, DC13/AC15 max. 0.5 Hz * with lamp load max. 2 Hz Wiring of the actuators using a 20-pin front connector 1) Product version 1 2) Product version 2 or higher S7-300 Module data Manual, 06/2017, A5E00105505-AJ 207 Digital modules 3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0) 3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0) Order number 6ES7322-5HF00-0AB0 Properties The relay output module SM 322; DO 8 x Rel. 230 V AC / 5A is characterized by the following properties: 8 outputs, electrically isolated Load voltage 24 to 120 V DC, 24 to 230 V AC Suitable for AC solenoid valves, contactors, motor starters, FHP motors and signal lamps You can protect the contacts with an RC quenching element by setting a jumper (SJ.) Group error display Channel-specific status displays Programmable diagnostic interrupt Programmable substitute value output Supports parameter reassignment in RUN Overvoltage protection of contacts You can protect the contacts against overvoltage by bridging (SJ) the module terminals 3 and 4, 7 and 8, 12 and 13 etc. (see the diagram below). S7-300 Module data 208 Manual, 06/2017, A5E00105505-AJ Digital modules 3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0) Wiring and block diagram of SM 322; DO 8 x Rel. 230 V AC / 5A Error LED - red Channel number Status display - green Backplane bus interface S7-300 Module data Manual, 06/2017, A5E00105505-AJ 209 Digital modules 3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0) Operation on safety extra-low voltage (SELV) Make allowances for the special feature outlined below when operating the 6ES7322-5HF00-0AB0 relay output module on SELV: The horizontally adjacent terminal of a terminal operated on SELV may not be operated at a rated voltage higher than 120 VUC. When operated at voltages higher than 120 VUC, the creepage distances and air gaps in the 40-pin front connector do not meet SIMATIC requirements of safe electrical separation. If one of two horizontally adjacent terminals is operated on SELV, the other terminal may not be operated at more than 120 VUC. Technical specifications of the SM 322; DO 8 x Rel. 230 V AC / 5A Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 320 g Module-specific data Supports parameter reassignment in RUN * Reaction of non-programmed outputs Yes Return the output value which was valid before the parameterization Supports isochronous mode no Number of outputs 8 Cable length * unshielded * shielded max. 600 m max. 1000 m S7-300 Module data 210 Manual, 06/2017, A5E00105505-AJ Digital modules 3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0) Technical specifications Voltages, currents, electrical potentials Rated electronics supply voltage L+ * Reverse polarity protection 24 V DC yes Total current of outputs (per group) * horizontal mounting position up to 60 max. 5 A * vertical mounting position up to 40 max. 5 A Electrical isolation * between channels and the backplane bus yes * between channels and the power supply to relays yes * between channels yes in groups of 1 Maximum potential difference * Between Minternal and the power supply to relays and outputs 250 V AC * Between outputs of different groups 500 V AC Isolation test voltage * between Minternal and the power supply to relays 500 V DC * between Minternal and the power supply to relays and outputs 1500 V AC * between outputs of different groups 2000 V AC Current consumption * from the backplane bus * from power supply L+ Power loss of the module max. 100 mA max. 160 mA typ. 3.5 W Status, interrupts, diagnostics Status display green LED per channel Interrupts * Diagnostic interrupt Diagnostic functions programmable programmable * Group error display red LED (SF) * Reading diagnostics information supported S7-300 Module data Manual, 06/2017, A5E00105505-AJ 211 Digital modules 3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0) Technical specifications Actuator selection data Thermal current, continuous max. 5 A Minimum load voltage / current 10 V /10 mA1) Residual current 11.5 mA 2) Short circuit-proof to IEC 947-5-1 With circuit-breaker, characteristics B, for: cos 1.0: 600 A cos 0.5...0.7: 900 A With 8 A Diazed fuse: 1000 A Switching capacity and useful life of contacts * with resistive load Voltage Current No. of switching cycles (typical) 24 V DC 5.0 A 0.2 million 24 V DC 2.5 A 0.4 million 24 V DC 1.0 A 0.9 million 24 V DC 0.2 A 1.7 million 24 V DC 0.1 A 2 million 120 V DC 0.2 A 1.7 million 120 V DC 0.1 A 2 million 230 V AC 5.0 A 0.2 million 230 V AC 2.5 A 0.4 million 230 V AC 1.0 A 0.9 million 230 V AC 0.2 A 1.7 million 230 V AC 0.1 A 2 million Voltage Current No. of switching cycles (typical) 24 V DC 5.0 A 0.1 million 24 V DC 2.5 A 0.25 million 24 V DC 1.0 A 0.5 million 24 V DC 0.2 A 1 million 24 V DC 0.1 A 1.2 million 120 V DC 0.1 A 1.2 million 230 V AC 5.0 A 0.1 million 230 V AC 2.5 A 0.25 million 230 V AC 1.0 A 0.5 million 230 V AC 0.2 A 1 million 230 V AC 0.1 A 1.2 million * with inductive load S7-300 Module data 212 Manual, 06/2017, A5E00105505-AJ Digital modules 3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0) Technical specifications An RC quenching element (jumper "SJ" inserted) or an external protection circuit extend the service life of contacts. Size of the motor starter max. size 5 to NEMA Lamp load (230 V AC) Energy-saving lamps/fluorescent lamps with electronic ballast3) Power No. of switching cycles (typical) 1000 W 25000 1500 W 10000 10 x 58 W 25000 Fluorescent lamps, conventionally compensated 1 x 58 W 25000 Fluorescent lamps, non-compensated 10 x 58 W 25000 Contact protection RC quenching element; 330 , 0.1 F Wiring two outputs in parallel * for redundant load control supported (only outputs with the same load voltage) * for performance increase not supported Control of a digital input supported Switching frequency * Mechanical max. 10 Hz * with resistive load max. 2 Hz * with inductive load to IEC 947-5-1, DC13/AC15 max. 0.5 Hz * with lamp load max. 2 Hz Wiring of the actuators using a 40-pin front connector 1) Without inserted jumper (SJ). 2) With AC load voltage and inserted jumper (SJ). No residual current if the jumper (SJ) is not installed. 3) The sum of all inrush currents on a ballast connected to an output must not exceed 5 A. Note The residual current of an RC quenching element connected to IEC Type 1 inputs may cause unwanted signal states. Remove the SJ jumper to rectify this fault. Configuration in RUN Special considerations must be given if you use the Configuration in RUN function. SF LED is lit: Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or module), although diagnostics are no longer pending and the module is operating correctly. Solution: Only change the configuration when no diagnostics are pending for the module or Pulling and plugging the module. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 213 Digital modules 3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0) 3.35.1 Parameters of SM 322; DO 8 x Rel. AC 230V/5A Parameters of SM 322; DO 8 x Rel. AC 230V/5A The table below provides an overview of configurable parameters and defaults for SM 322; DO 8 x Rel. AC 230V/5A. The defaults apply if you have not set any parameters in STEP 7. Table 3- 35 Parameters of SM 322; DO 8 x Rel. AC 230V/5A Parameters Range of values Defaults Parameter type Scope yes/no no Dynamic Module Set substitution value (SSV) SSV Dynamic Channel no Dynamic Channel Enable * Diagnostic interrupts Reaction to CPU STOP Hold last value (HLV) Set substitution value "1" yes/no See also Programming digital modules (Page 58) 3.35.2 SM 322; DO 8 x Rel. AC 230V/5A - Diagnostics Diagnostics messages of SM 322; DO 8 x Rel. AC 230V/5A The table below provides an overview of the diagnostic messages of SM 322; DO 8 x Rel. AC 230V/5A. Table 3- 36 Diagnostics messages of SM 322; DO 8 x Rel. AC 230V/5A Diagnostics message LED Scope of diagnostics programmable Watchdog time-out SF Module no EPROM error SF Module no RAM error SF Module no S7-300 Module data 214 Manual, 06/2017, A5E00105505-AJ Digital modules 3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0) Causes of error and troubleshooting Table 3- 37 Diagnostic messages of SM 322; DO 8 x Rel. AC230V/5A, cause of error and troubleshooting Diagnostics message Error detection Possible cause of error To correct or avoid errors Watchdog time-out generally infrequent high level of electromagnetic interference Eliminate interference and cycle the CPU power supply off and on Defective module Replace the module infrequent high level of electromagnetic interference Eliminate interference and cycle the CPU power supply off and on Defective module Replace the module transient high electromagnetic interference Eliminate interference and cycle the CPU power supply off and on Defective module Replace the module EPROM error generally RAM error 3.35.3 generally SM 322; DO 8 x Rel. AC 230V/5A - Interrupts Introduction The SM 322; DO 8 x Rel. AC 230V/5A can trigger diagnostic interrupts. For detailed information on the OBs and SFCs mentioned below, refer to the STEP 7 Online Help. Enabling interrupts There is no default interrupt setting, i.e. interrupts are disabled if not set accordingly. Program the interrupt enable parameter in STEP 7. Diagnostic interrupt Incoming error events (initial occurrence) and outgoing error events (error is cleared) are reported by means of diagnostics interrupt, if this interrupt is enabled. The CPU interrupts user program execution in order to process diagnostics interrupt OB82. You can call SFC51 or 59 in OB82 in the user program to obtain detailed diagnostics data from the module. Diagnostics data remain consistent until the program exits OB82. The module acknowledges the diagnostics interrupt when the program exits OB82. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 215 Digital modules 3.36 Relay output module SM 322; DO 8 x Rel. AC 230 V/5 A; (6ES7322-1HF10-0AA0) 3.36 Relay output module SM 322; DO 8 x Rel. AC 230 V/5 A; (6ES7322-1HF10-0AA0) Order number: "Standard module" 6ES7322-1HF10-0AA0 Order number: "SIPLUS S7-300 module" 6AG1322-1HF10-2AA0 Properties The SM 322; DO 8 x Rel. 230 V AC / 5 A is characterized by the following properties: 8 outputs, electrically isolated in groups of 1 Rated load voltage 24 to 120 V DC, 48 V to 230 V AC Suitable for AC/DC solenoid valves, contactors, motor starters, FHP motors and signal lamps. Measures to take for switching currents > 3 A Note Always use connecting cables with a cross-section of 1.5 mm2 when operating with switching currents > 3 A in order to reduce any temperature rise in the connector area of the module to a minimum. S7-300 Module data 216 Manual, 06/2017, A5E00105505-AJ Digital modules 3.36 Relay output module SM 322; DO 8 x Rel. AC 230 V/5 A; (6ES7322-1HF10-0AA0) Wiring and block diagram of SM 322; DO 8 x Rel. 230 V AC / 5 A Channel number Status displays - green Backplane bus interface Options of looping the power supply to contacts IAccumulated current 8 A at TU 30 C IAccumulated current 5 A at TU 60 C S7-300 Module data Manual, 06/2017, A5E00105505-AJ 217 Digital modules 3.36 Relay output module SM 322; DO 8 x Rel. AC 230 V/5 A; (6ES7322-1HF10-0AA0) Operation on safety extra-low voltage (SELV) Make allowances for the special feature outlined below when operating relay output module 322-1HF10 on SELV: To operate a terminal on SELV, the horizontally adjacent terminal may not be operated at a rated voltage higher than 120 VUC. The creepage distances and air gaps of the 40-pin front connector do not meet SIMATIC requirements in terms of safe electrical separation if operated with voltages above 120 VUC. If one of two horizontally adjacent terminals is operated on SELV, the other terminal may not be operated at more than 120 VUC. Technical specifications of the SM 322; DO 8 x Rel. 230 V AC / 5 A Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 120 Weight ca. 320 g Module-specific data Supports isochronous mode no Number of outputs 8 Cable length * * unshielded shielded max. 600 m max. 1000 m S7-300 Module data 218 Manual, 06/2017, A5E00105505-AJ Digital modules 3.36 Relay output module SM 322; DO 8 x Rel. AC 230 V/5 A; (6ES7322-1HF10-0AA0) Technical specifications Voltages, currents, electrical potentials Rated power supply L+ to the relays 24 V DC Total current of outputs (per group) * horizontal mounting position to 30 C to 60 C * vertical mounting position max. 8 A max. 5 A max. 5 A to 40 C Electrical isolation * between channels and the backplane bus yes * between channels yes in groups of 1 Maximum potential difference * Between Minternal and the power supply to relays and outputs 250 V AC * Between outputs of different groups 500 V AC Isolation test voltage * between Minternal and the power supply to relays 500 V DC * between Minternal and the power supply to relays and outputs 1500 V AC * between outputs of different groups 2000 V AC Current consumption * from the backplane bus * from power supply L+ Power loss of the module max. 40 mA max. 125 mA typ. 3.2 W Status, interrupts, diagnostics Status display green LED per channel Interrupt none Diagnostic functions none S7-300 Module data Manual, 06/2017, A5E00105505-AJ 219 Digital modules 3.36 Relay output module SM 322; DO 8 x Rel. AC 230 V/5 A; (6ES7322-1HF10-0AA0) Technical specifications Actuator selection data Thermal current, continuous max. 8 A Minimum load voltage / current 10 V / 5 mA Short-circuit current to IEC 947-5-1 With circuit-breaker, characteristics B, for: cos 1.0: 600 A cos 0.5...0.7: 900 A With 8 A Diazed fuse: 1000 A Switching capacity and useful life of contacts * with resistive load Voltage Current No. of switching cycles (typical) 24 V DC 8.0 A 0.1 million 4.0 A 0.3 million 2.0 A 0.7 million 0.5 A 4.0 million 60 V DC 0.5 A 4 million 120 V DC 0.2 A 1.6 million 48 V AC 8.0 A 0.1 million 2.0 A 1.6 million 8.0 A 0.1 million 2.0 A 1.2 million 8.0 A 0.1 million 4.0 A 0.3 million 2.0 A 0.5 million 1.0 A 0.7 million 0.5 A 1.5 million 8.0 A 0.1 million 4.0 A 0.3 million 2.0 A 0.5 million 1.0 A 0.7 million 0.5 A 1.5 million 60 V AC 120 V AC 230 V AC Switching capacity and useful life of contacts * with inductive load to IEC 947-5-1 DC13/AC15 S7-300 Module data 220 Manual, 06/2017, A5E00105505-AJ Digital modules 3.36 Relay output module SM 322; DO 8 x Rel. AC 230 V/5 A; (6ES7322-1HF10-0AA0) Technical specifications Voltage Current No. of switching cycles (typical) 24 V DC 2.0 A 0.3 million 60 V DC 120 V DC 48 V AC 60 V AC 120 V AC 230 V AC 1.0 A 0.5 million 0.5 A 1 million 0.5 A 0.5 million 0.3 A 1 million 0.2 A 0.5 million 3.0 A 0.5 million 1.5 A 1 million 3.0 A 0.3 million 1.5A 1 million 3.0 A 0.2 million 2.0 A 0.3 million 1.0 A 0.7 million 0.5 A 2 million 3.0 A 0.1 million 2.0 A 0.3 million 1.0 A 0.7 million 0.5 A * 2.0 million 30 million Aux. contactors Size 0 (3TH28) An external protective circuit extends the useful life of contacts. Lamp load (230 V AC) Power No. of switching cycles (typical) 1000 W 25000 1500 W 10000 Energy-saving lamps/fluorescent lamps with electronic ballast 10 x 58 W 25000 Fluorescent lamps, conventionally compensated 1 x 58 W 25000 Fluorescent lamps, non-compensated 10 x 58 W 25000 Contact protection (internal) none Wiring two outputs in parallel * For redundant load control supported * for performance increase not supported Control of a digital input supported Switching frequency * Mechanical max. 10 Hz * with resistive load max. 2 Hz * with inductive load to IEC 947-5-1, DC13/AC15 max. 0.5 Hz * with lamp load max. 2 Hz Wiring of the actuators using a 40-pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 221 Digital modules 3.37 Digital IO module SM 323; DI 16/DO 16 x DC 24 V/0.5 A; (6ES7323-1BL00-0AA0) 3.37 Digital IO module SM 323; DI 16/DO 16 x DC 24 V/0.5 A; (6ES7323-1BL00-0AA0) Order number 6ES7323-1BL00-0AA0 Properties Properties of SM 323; DI 16/DO 16 x DC 24 V/0.5 A: 16 inputs, electrically isolated in groups of 16 16 outputs, electrically isolated in groups of 8 Rated input voltage 24 V DC Rated load voltage 24 V DC Inputs suitable for switches and 2-/3-/4-wire proximity switches (BEROs) Outputs capable of driving solenoid valves, DC contactors and indicator lights Use of the module with high-speed counters Please note when using the module in combination with high-speed counters: Note When using a mechanical contact to switch on the 24-V power supply to SM 323; DI 16/DO 16 x DC 24 V/0.5 A, its outputs will carry "1" signal for the duration of ca. 50 s, due to the circuit structure. S7-300 Module data 222 Manual, 06/2017, A5E00105505-AJ Digital modules 3.37 Digital IO module SM 323; DI 16/DO 16 x DC 24 V/0.5 A; (6ES7323-1BL00-0AA0) Wiring and block diagram of SM 323; DI 16/DO 16 x DC 24 V/0.5 A Channel number Status displays - green Backplane bus interface Terminal assignment The diagram below shows the IO addressing of channels. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 223 Digital modules 3.37 Digital IO module SM 323; DI 16/DO 16 x DC 24 V/0.5 A; (6ES7323-1BL00-0AA0) SM 323; DI 16/DO 16 x DC 24 V/0.5 A - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 260 g Module-specific data Isochronous no Number of inputs 16 Number of outputs 16 Cable length * unshielded * shielded max. 600 m max. 1000 m Voltages, currents, electrical potentials Rated load voltage L+ 24 V DC Number of simultaneously controlled inputs * horizontal mounting position to 40 C to 60 C * vertical mounting position 16 8 16 to 40 C Total current of outputs (per group) * horizontal mounting position to 40 C to 60 C * vertical mounting position max. 4 A max. 3 A max. 2 A to 40 C Electrical isolation * between channels and the backplane bus yes * between channels yes Inputs in groups of Outputs in groups of 16 8 Isolation test voltage 500 V DC Current consumption max. 80 mA * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 80 mA typ. 6.5 W S7-300 Module data 224 Manual, 06/2017, A5E00105505-AJ Digital modules 3.37 Digital IO module SM 323; DI 16/DO 16 x DC 24 V/0.5 A; (6ES7323-1BL00-0AA0) Technical specifications Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none Encoder selection data Input voltage * Rated value * "1" signal * "0" signal 24 V DC 13 V to 30 V - 30 V to + 5 V Input current * "1" signal typ. 7 mA Input delay * "0" to "1" transition * "1" to "0" transition 1.2 ms to 4.8 ms 1.2 ms to 4.8 ms Input characteristics to IEC 61131, type 1 Connection of 2-wire BEROs supported * Permissible quiescent current Wiring of the signal transmitters max. 1.5 mA using a 40-pin front connector Actuator selection data Output voltage * "1" signal min. L + (- 0.8 V) Output current * "1" signal Rated value Permitted range * "0" signal (residual current) 0.5 A 5 mA to 0.6 A max. 0.5 mA Output delay (resistive load) * "0" to "1" transition Max. 100 s "1" to "0" transition Max. 500 s Load resistance range 48 to 4 k Lamp load Max. 5 W * Wiring two outputs in parallel * for redundant load control supported (only outputs of the same group) * for performance increase not supported S7-300 Module data Manual, 06/2017, A5E00105505-AJ 225 Digital modules 3.37 Digital IO module SM 323; DI 16/DO 16 x DC 24 V/0.5 A; (6ES7323-1BL00-0AA0) Technical specifications Control of a digital input supported Switching frequency * with resistive load * with inductive load to IEC 947-5-1, DC 13 * with lamp load max. 100 Hz max. 0.5 Hz max. 10 Hz Internal limiting of the inductive shutdown voltage to typ. L + (- 53 V) Short circuit-proof output yes, electronic * Threshold Wiring of the actuators typ. 1 A using a 40-pin front connector S7-300 Module data 226 Manual, 06/2017, A5E00105505-AJ Digital modules 3.38 Digital IO module SM 323; DI 8/DO 8 x DC 24 V/0.5 A; (6ES7323-1BH01-0AA0) 3.38 Digital IO module SM 323; DI 8/DO 8 x DC 24 V/0.5 A; (6ES7323-1BH01-0AA0) Order number: "Standard module" 6ES7323-1BH01-0AA0 Order number: "SIPLUS S7-300 module" 6AG1323-1BH01-2AA0 Properties Properties of SM 323; DI 8/DO 8 x DC 24 V/0.5 A: 8 inputs, electrically isolated in groups of 8 8 outputs, electrically isolated in groups of 8 Rated input voltage 24 V DC Rated load voltage 24 V DC Inputs suitable for switches and 2-/3-/4-wire proximity switches (BEROs) Outputs capable of driving solenoid valves, DC contactors and indicator lights Use of the module with high-speed counters Please note when using the module in combination with high-speed counters: Note When using a mechanical contact to switch on the 24-V power supply to SM 323; DI 8/DO 8 x DC 24 V/0.5 A, its outputs will carry "1" signal for the duration of ca. 50 s, due to the circuit structure. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 227 Digital modules 3.38 Digital IO module SM 323; DI 8/DO 8 x DC 24 V/0.5 A; (6ES7323-1BH01-0AA0) Wiring and block diagram of SM 323; DI 8/DO 8 x DC 24 V/0.5 A Channel number Status displays - green Backplane bus interface SM 323; DI 8/DO 8 x DC 24 V/0.5 A - Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 200 g Module-specific data Supports isochronous mode no Number of inputs 8 Number of outputs 8 Cable length * unshielded * shielded max. 600 m max. 1000 m S7-300 Module data 228 Manual, 06/2017, A5E00105505-AJ Digital modules 3.38 Digital IO module SM 323; DI 8/DO 8 x DC 24 V/0.5 A; (6ES7323-1BH01-0AA0) Technical specifications Voltages, currents, electrical potentials Rated load voltage L+ 24 V DC Number of simultaneously controlled inputs * horizontal mounting position to 60 C * vertical mounting position to 40 C Total current of outputs (per group) * horizontal mounting position to 60 C * vertical mounting position to 40 C Electrical isolation 8 8 max. 4 A max. 4 A * between channels and the backplane bus yes * between channels yes 8 8 Inputs in groups of Outputs in groups of Isolation test voltage 500 V DC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 40 mA max. 40 mA typ. 3.5 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none Encoder selection data Input voltage * Rated value * "1" signal * "0" signal 24 V DC 13 V to 30 V - 30 V to + 5 V Input current * "1" signal typ. 7 mA Input delay * "0" to "1" transition * "1" to "0" transition 1.2 ms to 4.8 ms 1.2 ms to 4.8 ms Input characteristics to IEC 61131, type 1 Connection of 2-wire BEROs supported max. 1.5 mA * Permissible quiescent current Wiring of the signal transmitters using a 20-pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 229 Digital modules 3.38 Digital IO module SM 323; DI 8/DO 8 x DC 24 V/0.5 A; (6ES7323-1BH01-0AA0) Technical specifications Actuator selection data Output voltage * "1" signal min. L + (- 0.8 V) Output current * "1" signal Rated value Permitted range * "0" signal (residual current) 0.5 A 5 mA to 0.6 A Max. 0.5 mA Output delay (resistive load) * "0" to "1" transition Max. 100 s "1" to "0" transition Max. 500 s Load resistance range 48 to 4 k Lamp load Max. 5 W * Wiring two outputs in parallel * for redundant load control supported (only outputs of the same group) * for performance increase not supported Control of a digital input supported Switching frequency * with resistive load * with inductive load to IEC 947-5-1, DC 13 * with lamp load Internal limiting of the inductive shutdown voltage to Short circuit-proof output * Threshold Wiring of the actuators max. 100 Hz max. 0.5 Hz max. 10 Hz typ. L + (- 53 V) yes, electronic typ. 1 A using a 20-pin front connector S7-300 Module data 230 Manual, 06/2017, A5E00105505-AJ Digital modules 3.39 Programmable digital IO module SM 327; DI 8/DO 8 x DC 24 V/0.5 A (6ES7327-1BH00-0AB0) 3.39 Programmable digital IO module SM 327; DI 8/DO 8 x DC 24 V/0.5 A (6ES7327-1BH00-0AB0) Order number 6ES7327-1BH00-0AB0 Properties Properties of SM 327; DI 8/DO 8 x DC 24 V/0.5 A: 8 digital inputs and 8 individually configurable inputs or outputs, isolated in groups of 16 Rated input voltage 24 V DC Inputs suitable for switches and 2-/3-/4-wire proximity switches (BEROs) Output current 0.5 A Rated load voltage 24 V DC Outputs capable of driving solenoid valves, DC contactors and indicator lights Dynamic change of parameters in RUN (CiR-compatible), separately at each channel. Readback of outputs. Use of the module with high-speed counters Please note when using the module in combination with high-speed counters: Note When using a mechanical contact to switch on the 24-V power supply to SM 327; DI 8/DO 8 x DC 24 V/0.5 A, its outputs will carry "1" signal for the duration of ca. 50 s, due to the circuit structure. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 231 Digital modules 3.39 Programmable digital IO module SM 327; DI 8/DO 8 x DC 24 V/0.5 A (6ES7327-1BH00-0AB0) Wiring and block diagram of SM 327; DI 8/DO 8 x DC 24 V/0.5 A, programmable Channel number Status display - green Backplane bus interface Technical specifications of SM 327; DI 8/DO 8 x DC 24 V/0.5 A, programmable Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 120 Weight ca. 200 g Module-specific data Supports isochronous mode no Number of inputs 8 digital Number of inputs/outputs 8, can be programmed separately Cable length * unshielded * shielded max. 600 m max. 1000 m S7-300 Module data 232 Manual, 06/2017, A5E00105505-AJ Digital modules 3.39 Programmable digital IO module SM 327; DI 8/DO 8 x DC 24 V/0.5 A (6ES7327-1BH00-0AB0) Technical specifications Voltages, currents, electrical potentials Rated load voltage L+ 24 V DC Number of simultaneously controlled inputs * horizontal mounting position to 60 C * vertical mounting position to 40 C 16 16 Total current of outputs (per group) * horizontal mounting position to 40 C to 60 C * vertical mounting position max. 4 A max. 3 A max. 2 A to 40 C Electrical isolation * between channels and the backplane bus yes * between channels no Isolation test voltage 500 V DC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 60 mA max. 20 mA typ. 3 W Status, interrupts, diagnostics Status display green LED per channel Interrupts none Diagnostic functions none Encoder selection data Input voltage * Rated value * "1" signal * "0" signal 24 V DC 15 V to 30 V - 30 V to + 5 V Input current * "1" signal typ. 6 mA Input delay * "0" to "1" transition * "1" to "0" transition 1.2 ms to 4.8 ms 1.2 ms to 4.8 ms Input characteristics to IEC 61131, type 1 Connection of 2-wire BEROs supported * Permissible quiescent current Wiring of the signal transmitters max. 1.5 mA using a 20pin front connector S7-300 Module data Manual, 06/2017, A5E00105505-AJ 233 Digital modules 3.39 Programmable digital IO module SM 327; DI 8/DO 8 x DC 24 V/0.5 A (6ES7327-1BH00-0AB0) Technical specifications Actuator selection data Output voltage * "1" signal min. L+ (-1.5 V) Output current * "1" signal Rated value Permitted range * "0" signal (residual current) 0.5 A 5 mA to 0.6 A Max. 0.5 mA Output delay (resistive load) * "0" to "1" transition max. 350 s "1" to "0" transition max. 500 s Load resistance range 48 to 4 k Lamp load max. 5 W * Wiring two outputs in parallel * for redundant load control supported * for performance increase not supported Control of a digital input supported Switching frequency * with resistive load * with inductive load to IEC 947-5-1, DC 13 * with lamp load Internal limiting of the inductive shutdown voltage to Short circuit-proof output * Threshold Wiring of the actuators max. 100 Hz max. 0.5 Hz max. 10 Hz typ. L + (-54 V) yes, electronic typ. 1 A using a 20pin front connector S7-300 Module data 234 Manual, 06/2017, A5E00105505-AJ Digital modules 3.39 Programmable digital IO module SM 327; DI 8/DO 8 x DC 24 V/0.5 A (6ES7327-1BH00-0AB0) 3.39.1 Parameters of SM 327; DI 8/DO 8 x 24 VDC/0.5 A Programming The general procedure of programming digital modules is described in the chapter Programming digital modules (Page 58). Parameters of SM 327; DI 8/DO 8 x DC 24 V/0.5 A, programmable The table below lists the programmable parameters of SM 327; DI 8/DO 8 x DC 24 V/0.5 A, including defaults. The defaults apply if you have not set any parameters in STEP 7. The comparison illustrates the parameters you can edit: inSTEP 7 using SFC55 "WR_PARM" using SFB53 "WRREC" (for GSD, for example). Parameters set in STEP 7 may also be transferred to the module using SFCs 56 and 57, and SFB 53 (refer to the STEP 7) Online Help). Table 3- 38 Parameters of SM 327; DI 8/DO 8 x DC 24 V/0.5 A Parameters Range of values Default Parameter type Scope Data record Programmable using ... number SFC55, PG SFB53 Digital output yes/no no dynamic Channel 1 yes yes S7-300 Module data Manual, 06/2017, A5E00105505-AJ 235 Digital modules 3.39 Programmable digital IO module SM 327; DI 8/DO 8 x DC 24 V/0.5 A (6ES7327-1BH00-0AB0) 3.39.1.1 Structure of data record 1 of SM 327; DI 8/DO 8 x DC 24 V/0.5 A Structure of data record 1 The figure below shows the structure of data record 1 of the dynamic parameters of SM 327; DI 8/DO 8 x DC 24 V/0.5 A. Figure 3-10 Structure of data record 1 of SM 327; DI 8/DO 8 x DC 24 V/0.5 A S7-300 Module data 236 Manual, 06/2017, A5E00105505-AJ Digital modules 3.39 Programmable digital IO module SM 327; DI 8/DO 8 x DC 24 V/0.5 A (6ES7327-1BH00-0AB0) Readback of outputs The readback function is a simple form of diagnostics. You can use this to determine whether the information output to the process ("1" or "0") actually arrives there. The digital outputs can be read back to the user data area: When Q11.3 is configured as an output, for example, it can be read back at I11.3. See the figure below Figure 3-11 Readback of the outputs of SM 327; DI 8/DO 8 x DC 24 V/0.5 A S7-300 Module data Manual, 06/2017, A5E00105505-AJ 237 4 Principles of analog value processing 4.1 Overview Introduction This chapter describes the basic procedure in wiring and connecting signal sensors to analog inputs and analog outputs and corresponding items to observe. The diagrams below do not show the connecting lines required to connect the electrical potentials of the analog input module and sensors. Always adhere to the general information on sensor wiring and connecting. Special wiring and connecting options are described in the corresponding module data. Installation and wiring For information on installation and wiring, refer to the S7-300, CPU 31xC, and CPU 31x Operating Instructions: Installation The operating instructions are available on the Internet (http://support.automation.siemens.com/WW/view/en/13008499). S7-300 Module data 238 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.2 Wiring and connecting transducers to analog inputs 4.2 Wiring and connecting transducers to analog inputs Transducers which can be wired and connected to analog inputs You can wire and connect the following transducers to the analog input modules, depending on the type of measurement: Voltage transducers Current transducers - As 2-wire transducer - As 4-wire transducer Resistors Thermocouples Cables for analog signals Always use shielded twisted-pair cables to wire analog signals. This reduces interference. Connect both ends of the analog cable shield to ground. Any potential difference between the cable ends may cause an equipotential current on the shield and disturbance on analog signals. Avoid this effect by means of low-impedance equipotential bonding. Ground only one end of the shielding. Electrically isolated analog input modules Electrically isolated analog input modules are not electrically interconnected at the reference point of the measuring circuit (MANA and/or M) and the M terminal of the CPU/IM153. Always use electrically isolated analog input modules if there is any risk of potential difference VISO developing between the reference point of measuring circuit (MANA and/or M-) and the M terminal of the CPU/IM153 . You can prevent the potential difference V ISO from exceeding limits by means of equipotential interconnection of terminals MANA and M of the CPU/IM153. Non-isolated analog input modules Non-isolated analog input modules require a low-impedance connection between the reference point of measuring circuit MANA and the M terminal of the CPU or interface module IM 153. Interconnect terminals MANA with M of the CPU or interface module IM 153. Any potential difference between MANA and M of the CPU or interface module IM 153 may corrupt the analog signal. Limited potential difference CMV The permissible potential difference UCM (CMV/Common Mode) may not be exceeded. A CMV fault may develop between the measurement inputs (M+ / M-) and the reference potential of measuring circuit MANA between the measuring inputs. The following diagrams show the measures to be taken when wiring transducers. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 239 Principles of analog value processing 4.2 Wiring and connecting transducers to analog inputs 4.2.1 Wiring and connecting electrically isolated transducers Electrically isolated transducers Electrically isolated transducers are not connected to local ground potential. They can be operated in electrically isolated mode. Potential differences may develop between electrically isolated sensors. These potential differences may be caused by interference, or may develop as a result of the local distribution of transducers. In environments with a high level of EMC interference, it is advisable to interconnect M- with MANA in order to prevent the permissible CMV value from being exceeded. Note For modules where VCM 2.5 V, interconnect M- and MANA (see the diagrams below). Wiring and connecting electrically isolated transducesr to an electrically isolated AI The CPU / IM 153 can be operated in grounded mode or ungrounded mode. Figure 4-1 Wiring and connecting electrically isolated transducers to electrically isolated AI S7-300 Module data 240 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.2 Wiring and connecting transducers to analog inputs Wiring and connecting electrically isolated transducers to a non-isolated AI The CPU / IM 153 can be operated in grounded mode or ungrounded mode. Figure 4-2 Wiring and connecting electrically isolated transducers to a non-isolated AI Note Do not interconnect M- with MANA when wiring and connecting 2-wire transducers and resistance transducers. An equalization current develops at the interconnection of M- with MANA and corrupts the measured value. This also applies to unused inputs which are programmed accordingly. 4.2.2 Wiring non-isolated transducers Non-isolated transducer Non-isolated transducers are interconnected with local ground potential. Always interconnect MANA with local ground when using non-isolated transducers. Local conditions or interference may cause potential differences CMV (static or dynamic) between locally distributed measuring points. If the maximum CMV value is exceeded, interconnect the measuring points by means of equipotential conductors. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 241 Principles of analog value processing 4.2 Wiring and connecting transducers to analog inputs Wiring non-isolated transducer to electrically isolated AI When connecting non-isolated transducers to electrically isolated modules, the CPU / IM 153 can be operated in grounded or ungrounded mode. Figure 4-3 Wiring non-isolated transducer to electrically isolated AI S7-300 Module data 242 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.2 Wiring and connecting transducers to analog inputs Wiring non-isolated transducer to a non-isolated AI Always operate the CPU / IM 153 in grounded mode if you connect non-isolated transducers to non-isolated modules. Figure 4-4 Wiring non-isolated transducers to a non-isolated AI Note You may not connect non-isolated 2-wire transducers/resistive transducers to non-isolated analog inputs! S7-300 Module data Manual, 06/2017, A5E00105505-AJ 243 Principles of analog value processing 4.3 Wiring and connecting voltage transducers 4.3 Wiring and connecting voltage transducers Introduction This chapter describes how to wire and connect voltage transducers and and the corresponding items to be observed. Wiring and connecting voltage transducers Figure 4-5 Wiring and connecting voltage transducers to electrically isolated AI S7-300 Module data 244 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.4 Wiring and connecting current transducers 4.4 Wiring and connecting current transducers Introduction This chapter describes the wiring and connecting of current transducers and rules to be observed. Supported current transducers As 2-wire transducer As 4-wire transducer Wiring and connecting 2-wire transducers with power supply from the module The 2-wire transducer is wired to the short circuit-proof supply voltage at the terminals of the analog input module. The 2-wire transducer converts the process variable into a current. 2-wire transducers must be electrically isolated. Figure 4-6 Wiring and connecting 2-wire transducers to electrically isolated AI S7-300 Module data Manual, 06/2017, A5E00105505-AJ 245 Principles of analog value processing 4.4 Wiring and connecting current transducers Wiring and connecting 2-wire transducers with power supply from L+ Configure the 2-wire as a 4-wire transducer in STEP 7 if it is connected to supply voltage L+. Figure 4-7 Wiring and connecting a 2-wire transducer with supply from L + to an electrically isolated AI Wiring and connecting 4-wire transducers 4-wire transducers are connected to a separately power supply. Figure 4-8 Wiring and connecting 4-wire transducers to electrically isolated AI S7-300 Module data 246 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.5 Wiring and connecting resistance thermometers and resistors 4.5 Wiring and connecting resistance thermometers and resistors Introduction This chapter describes the wiring and connecting of resistance thermometers and resistors and rules to be observed. Supported resistance transducers With 4-wire connection With 3-wire connection With 2-wire connection Wiring and connecting resistance thermometers and resistors The module provides a constant current at terminals IC+ and IC- for current measurements. The constant current is fed to the resistance for measuring its voltage potential. The constant current cables must be wired directly to the resistance thermometer/resistor. Measurements programmed for 4-or 3-wire connections compensate for line resistance and return considerably higher precision compared to 2-wire connections. Measurements with programmed 2-wire connections also record line impedance in addition to their internal resistance. 4-wire connection of a resistance thermometer The voltage generated at the resistance thermometer is measured across the M+ and Mterminals. Observe the correct polarity when wiring and connecting the devices (IC+ and M+, and IC - and M- at the resistance thermometer). Always wire and connect the IC+, M+, IC- and M- lines directly to the resistance thermometer. Figure 4-9 4-wire connection of resistance thermometers to an electrically isolated analog input S7-300 Module data Manual, 06/2017, A5E00105505-AJ 247 Principles of analog value processing 4.5 Wiring and connecting resistance thermometers and resistors 3-wire connection of a resistance thermometer (not for 6ES7331-7PF01-0AB0) When connecting 3-wire devices to modules equipped with four terminals, you should generally bridge M- and IC-. Always wire and connect the connected C+ and M+ lines directly to the resistance thermometer. The image shows the basic wiring. Please observe the notes in the description about the respective module. Figure 4-10 3-wire connection of resistance thermometers to an electrically isolated analog input 2-wire connection of a resistance thermometerError! Bookmark not defined. For 2-wire connections, insert a bridge between the M+ and IC+ and between the M- and ICterminals of the module. The line impedance is included in the measurement. Figure 4-11 2-wire connection of resistance thermometers to an electrically isolated analog input S7-300 Module data 248 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.6 Wiring and connecting thermocouples 4.6 Wiring and connecting thermocouples Introduction This chapter describes the wiring and connecting of thermocouples and corresponding rules to be observed. Supported thermocouples (depending on module) B; C; E; J; K; L; N; R; S; T; U; TXK / XKL GOST Thermocouple selection The figure below shows several thermocouples and their temperature ranges. Figure 4-12 Thermocouples and their ranges S7-300 Module data Manual, 06/2017, A5E00105505-AJ 249 Principles of analog value processing 4.6 Wiring and connecting thermocouples Thermocouple structure Thermocouples consist of a pair of thermal probes and all necessary installation and connecting parts. The thermocouple pair consists of two wires made of different metals, or of metal alloys soldered or welded together at their ends. The different thermocouple types, for example, K, J or N, are derived from different material compositions. The measuring principle of all thermocouples is the same, irrespective of their type. Measurement point Thermocouple with positive and negative thermal elements Terminal Compensating line Reference junction Supply line Thermal voltage acquisition point Figure 4-13 Fig. 4-22 Structure of thermocouples S7-300 Module data 250 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.6 Wiring and connecting thermocouples Operating principle of thermocouples Any temperature difference between the measuring point and the free ends of the thermocouple (point of connection) generates a thermoelectric voltage. The thermoelectric voltage is a function of the temperature difference between the measuring point and the free ends, and is also determined by the material composition of the thermal elements. As thermocouples always sense temperature differences, it is essential to maintain the free ends at the known temperature of a reference junction in order to be able to determine the temperature at the measuring point. The thermocouples can be extended from their point of connection to the reference junction by means of compensating lines. These compensating lines are made of the same materials as the thermocouple wires. The supply lines from the reference junction to the module are made of copper. Note Make sure of the correct polarity in order to avoid serious measuring errors. Compensation for the reference junction temperature You can compensate for the influence of temperature fluctuation at the reference junction by means of a compensating circuit. You have several options of measuring the reference junction temperature in order to obtain an absolute temperature value as a function of the temperature difference between the reference junction and the measuring point. You can use either an internal or an external compensating circuit, depending on the required location of the reference junction. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 251 Principles of analog value processing 4.6 Wiring and connecting thermocouples Options of compensating for the reference junction temperature Table 4- 1 Options of compensating for the reference junction temperature Option Explanations No compensation To record only the temperature difference between the measuring point and reference junction. Internal compensation (for wiring and connecting, see Connecting thermo- The internal compensation is based on a comparison using the internal temperature (thermocouple internal comparison) of the module. External compensation with compensation box in the feed lines of each thermocouple (the wiring and connecting is shown in the diagram Wiring and You have already measured and compensated for the reference junction temperature (thermocouple external comparison) using an interconnected compensating box in the feed lines of each thermocouple. couples with internal compensation box to electrically isolated analog inputs) connecting of thermocouples with compensation box to electrically isolated analog inputs and Wiring and connecting of thermocouples with reference junction (order no. M72166-xxx00) to electrically isolated analog inputs) Further signal processing is not required at the module. Only for SM 331; AI 8 x TC: You can measure the reference temperature using a (platinum or External compensation with resistance thermometer nickel) resistance thermometer, and compute it in the module for any thermocouple. for recording the reference junction temperature See also Wiring and connecting thermocouples with internal compensation (Page 253) Wiring and connecting thermocouples with external compensation (Page 254) Wiring and connecting transducers to analog inputs (Page 239) S7-300 Module data 252 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.6 Wiring and connecting thermocouples 4.6.1 Wiring and connecting thermocouples with internal compensation Function principle of internal compensation Internal compensation allows you to form the reference point at the terminals of the analog input module. In this case, route the compensating lines directly to the analog module. The internal temperature sensor measures the module's temperature and returns a compensation voltage. Note that internal compensation is not as accurate as external compensation. Wiring and connecting thermocouples with internal compensation Wire the thermocouples either directly to the inputs of the module, or indirectly via compensating lines. Each channel group can use any type of thermocouple supported by the analog module, independently of other channel groups. Figure 4-14 Wiring and connecting thermocouples with internal compensation to electrically isolated analog inputs S7-300 Module data Manual, 06/2017, A5E00105505-AJ 253 Principles of analog value processing 4.6 Wiring and connecting thermocouples 4.6.2 Wiring and connecting thermocouples with external compensation Function principle of external compensation with compensating box With external compensation, the temperature at the reference junction of the thermocouples is evaluated using a compensating box. The compensating box contains a bridge circuit which is calibrated to a defined reference junction temperature /calibrating temperature.) The reference junction is formed by the connecting ends of the thermocouple's equalizing conductor. The resistance of the temperature-sensitive bridge changes as a function of the difference between the actual reference temperature and calibrating temperature. This difference induces a positive or negative compensating voltage, which is added to the thermoelectrical voltage. Wiring and connecting the compensating box Terminate the compensating box at the COMP terminals of the module; the compensating box must be installed at the reference junction of the thermocouples. The compensating box be supplied with an electrically isolated voltage. The power supply module must provide adequate noise filtering, for example, by means of grounded cable shielding. The terminals for the connection of the thermocouple on the compensating box are not required and must therefore be jumpered (for example, see figure Connection of thermocouples to reference junction) Restrictions: The channel group parameters always apply to the all its channels (for example, input voltage, integrating time etc.) External compensation with connection of the compensating box to the COMP connections of the module can only be made for one thermocouple type. That is, all channels that work with external compensation must use the same type. S7-300 Module data 254 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.6 Wiring and connecting thermocouples Wiring and connecting thermocouples via compensating box If all thermocouples connected to the module's inputs share a common reference junction, compensate the circuit as follows: Figure 4-15 Wiring and connecting thermocouples to electrically isolated analog inputs via compensation box Note To compensate the analog input modules, always use compensation boxes with a reference junction temperature of 0 C. Recommended compensating box Use a compensating box with a reference junction. You must order compensating box from external companies. Contact your Siemens representative or Industry Online Support on the Internet (https://support.industry.siemens.com/cs/ww/en/). S7-300 Module data Manual, 06/2017, A5E00105505-AJ 255 Principles of analog value processing 4.6 Wiring and connecting thermocouples Connection of the reference junction If all thermocouples connected to the module's inputs share a common reference junction, compensate the circuit as follows: Figure 4-16 Connection of thermocouples to reference junction Additional information You can find additional information on the compensating box and connection to an analog module on the Internet. (https://support.industry.siemens.com/cs/ww/en/view/18272332) S7-300 Module data 256 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.7 Wiring and connecting loads/actuators to analog outputs 4.7 Wiring and connecting loads/actuators to analog outputs Wiring and connecting loads/actuators to analog outputs The analog output modules can be used as current or voltage source for loads and actuators. Cables for analog signals Always use shielded twisted-pair cables to wire analog signals. Form two twisted pairs of the QV and S+, and M and S- signals in order to reduce interference. Connect both ends of the analog cable shield to ground. Any potential difference between the cable ends may cause an equipotential current on the shield and disturbance on analog signals. Avoid this situation by grounding only one end of the shielding. Electrically isolated analog output modules Electrically isolated analog output modules do not have a galvanic interconnection between the reference point of measuring circuit MANA and the CPU's M terminal. Always use electrically isolated analog input modules if there is any risk of potential difference Viso developing between the reference point of measuring circuit MANA and the M terminal of the CPU. Use an equipotential bonding conductor to interconnect the MANA terminal and the M terminal of the CPU, in order to prevent Viso from exceeding the permitted value. Non-isolated analog output modules When using on-isolated analog output modules, always interconnect the reference point MANA of the of measuring circuit with terminal M of the CPU. Wire the MANA terminal to the M terminal of the CPU. Any potential difference between MANA and the M terminal of the CPU could otherwise corrupt the analog signal. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 257 Principles of analog value processing 4.7 Wiring and connecting loads/actuators to analog outputs 4.7.1 Wiring and connecting loads/actuators to voltage outputs Wiring and connecting loads to a voltage output The voltage outptus support the wiring and connecting of 2-wire and 4-wire loads. Certain analog output modules, however, do not support both types of wiring and connecting. Wiring 4-wire loads to the voltage output of an electrically isolated module The 4-wire load circuit returns high precision. Wiring and connecting the S- and S+ sense lines directly to the load. This allows direct measurement and correction of the load voltage. Interference or voltage dips may lead to potential differences between the sense line S- and the reference loop of analog circuit MANA. This potential difference may not exceed set limits. Any potential difference above limits has a negative impact on analog signal precision. Figure 4-17 4-wire connection of loads to the voltage output of an electrically isolated analog output module S7-300 Module data 258 Manual, 06/2017, A5E00105505-AJ Principles of analog value processing 4.7 Wiring and connecting loads/actuators to analog outputs Wiring 2-wire loads to the voltage output of non-isolated module Wire the loads to the QV terminals and to the reference point of measuring circuit MANA. Interconnect terminal S+ to QV with terminal S to MANA in the front connector. A 2-wire circuit does not provide for compensation of line impedance. Figure 4-18 2-wire connection of loads to the voltage output of a non-isolated analog module See also Wiring and connecting loads/actuators to analog outputs (Page 257) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 259 Principles of analog value processing 4.7 Wiring and connecting loads/actuators to analog outputs 4.7.2 Wiring and connecting loads/actuators to current outputs Wiring and connecting loads to a current output Wire and connect the loads to QI and to the reference point of analog circuit MANA of a current output. Wiring and connecting loads to a current output of an electrically isolated module Figure 4-19 Wiring and connecting loads to a current output of an electrically isolated analog output module Wiring and connecting loads to a current output of a non-isolated analog output module Figure 4-20 Wiring and connecting loads to a current output of a non-isolated analog output module See also Wiring and connecting loads/actuators to analog outputs (Page 257) S7-300 Module data 260 Manual, 06/2017, A5E00105505-AJ 5 Principles of analog modules Introduction This chapter describes the analog values for all measuring or output ranges supported by the analog modules. Analog value conversion The CPU always processes the analog values in binary format. Analog input modules convert the analog process signal to a digital format. Analog output modules convert digital output values to analog signals. Representation of analog values at a resolution of 16 bits The digitized analog value applies to input and output values of the same rated range. Analog values are output as fixed point numbers with two's complement. The resultant assignment: Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit values 215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 Sign The sign of the analog value is always set at bit 15: "0" + "1" - Resolution < 16 bits On analog modules with a resolution of < 16 bits, the analog value is stored left-aligned. The unused least significant bit positions are padded with zeros ("0".) Example The example below demonstrates the zero padding of unused bit positions for low resolution values. Table 5- 1 Example: Bit pattern of a 16-bit and 13-bit analog value Resolution Analog value Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 16-bit analog value 0 1 0 0 0 1 1 0 0 1 1 1 0 0 1 1 13-bit analog value 0 1 0 0 0 1 1 0 0 1 1 1 0 0 0 0 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 261 Principles of analog modules 5.1 Representation of the values for analog input channels 5.1 Representation of the values for analog input channels Measured value resolution The resolution of the analog values may differ, based on the analog module and module parameters. At resolutions < 15 bits, all bits identified by "x" are set to "0". Note This resolution does not apply to temperature values. Converted temperature values are the result of a conversion in the analog module. Table 5- 2 Supported analog value resolutions Resolution Units Analog value in bits (+ sign) dec hex high byte low byte 8 128 80H Sign 0 0 0 0 0 0 0 1xxxxxxx 9 64 40H Sign 0 0 0 0 0 0 0 01xxxxxx 10 32 20H Sign 0 0 0 0 0 0 0 001xxxxx 11 16 10H Sign 0 0 0 0 0 0 0 0001xxxx 12 8 8H Sign 0 0 0 0 0 0 0 00001xxx 13 4 4H Sign 0 0 0 0 0 0 0 000001xx 14 2 2H Sign 0 0 0 0 0 0 0 0000001x 15 1 1H Sign 0 0 0 0 0 0 0 00000001 Binary representation of input ranges Table 5- 3 Units Bipolar input ranges Measured value in % Data word Range 215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 32767 >118.515 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Overflow 32511 117.589 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 27649 >100.004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1 Overshoot range 27648 100.000 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0 1 0.003617 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0.000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -1 -0.003617 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -27648 -100.000 1 0 0 1 0 1 0 0 0 0 0 0 0 0 0 0 -27649 -100.004 1 0 0 1 0 0 1 1 1 1 1 1 1 1 1 1 -32512 -117.593 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 Undershoot range -32768 -117.596 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Underflow Rated range S7-300 Module data 262 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.1 Representation of the values for analog input channels Table 5- 4 Units Unipolar input ranges Measured value in % Data word Range 215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 32767 118.515 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Overflow 32511 117.589 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Overshoot 27649 100.004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1 range 27648 100.000 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0 range 1 0.003617 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Rated range 0 0.000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -1 -0.003617 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Undershoot -4864 -17.593 1 1 1 0 1 1 0 1 0 0 0 0 0 0 0 0 range range -32768 -17.596 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Underflow Representation of analog values in voltage measuring ranges Table 5- 5 Representation of analog values in the 1 V to 10 V voltage measuring range System Voltage measuring range dec hex 10 V 5 V 2.5 V 1 V 32767 7FFF 11.851 V 5.926 V 2.963 V 1.185 V Overflow 32512 7F00 32511 7EFF 11.759 V 5.879 V 2.940 V 1.176 V Overshoot range 27649 6C01 27648 6C00 10 V 5V 2.5 V 1V 20736 5100 7.5 V 3.75 V 1.875 V 0.75 V 1 1 361.7 V 180.8 V 90.4 V 36.17 V 0 0 0V 0V 0V 0V -1 FFFF -20736 AF00 -7.5 V -3.75 V -1.875 V -0.75 V -27648 9400 -10 V -5 V -2.5 V -1 V -27649 93FF -32512 8100 -11.759 V -5.879 V -2.940 V -1.176 V -32513 80FF -32768 8000 -11.851 V -5.926 V -2.963 V -1.185 V Rated range Undershoot range Underflow S7-300 Module data Manual, 06/2017, A5E00105505-AJ 263 Principles of analog modules 5.1 Representation of the values for analog input channels Table 5- 6 Representation of analog values in the 80 mV to 500 mV voltage measuring ranges System Voltage measuring range dec hex 500 mV 250 mV 80 mV 32767 7FFF 592.6 mV 296.3 mV 94.8 mV Overflow 32512 7F00 32511 7EFF 587.9 mV 294.0 mV 94.1 mV Overshoot range 27649 6C01 27648 6C00 500 mV 250 mV 80 mV 20736 5100 375 mV 187.5 mV 60 mV 1 1 18.08 V 9.04 V 2.89 V 0 0 0 mV 0 mV 0 mV -1 FFFF -20736 AF00 -375 mV -187.5 mV -60 mV -27648 9400 -500 mV -250 mV -80 mV -27649 93FF -32512 8100 -32513 80FF -32768 8000 Table 5- 7 Rated range Undershoot range -587.9 mV -294.0 mV -94.1 mV Underflow -592.6 mV -296.3 mV -94.8 mV Representation of analog values in the 1 V to 5 V and 0 V to 10 V voltage measuring ranges System Voltage measuring range dec hex 1 V to 5 V 0 V to 10 V 32767 7FFF 5.741 V 11.852 V Overflow 32512 7F00 32511 7EFF 5.704 V 11.759 V Overshoot range 27649 6C01 27648 6C00 5V 10 V 20736 5100 4V 7.5 V 1 1 1 V + 144.7 V 0 V + 361.7 V 0 0 1V 0V -1 FFFF -4864 ED00 -4865 ECFF -32768 8000 Rated range Undershoot range 0.296 V Negative values are not supported Underflow S7-300 Module data 264 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.1 Representation of the values for analog input channels Representation of analog values in the current measuring ranges Table 5- 8 Representation of analog values in the 3.2 mA to 20 mA current measuring ranges System dec Current measuring range hex 20 mA 10 mA 3.2 mA 32767 7FFF 23.70 mA 11.85 mA 3.79 mA Overflow 32512 7F00 32511 7EFF 23.52 mA 11.76 mA 3.76 mA Overshoot range 27649 6C01 27648 6C00 20 mA 10 mA 3.2 mA 20736 5100 15 mA 7.5 mA 2.4 mA 1 1 723.4 nA 361.7 nA 115.7 nA 0 0 0 mA 0 mA 0 mA -1 FFFF -20736 AF00 -15 mA -7.5 mA -2.4 mA -27648 9400 -20 mA -10 mA -3.2 mA -27649 93FF -32512 8100 -32513 80FF -32768 8000 Table 5- 9 Rated range Undershoot range -23.52 mA -11.76 mA -3.76 mA -23.70 mA -11.85 mA -3.79 mA Underflow Representation of analog values in the 0 mA to 20 mA and 4 mA to 20 mA current measuring ranges System Current measuring range dec hex 0 mA to 20 mA 4 mA to 20 mA 32767 7FFF 23.70 mA 22.96 mA Overflow 32512 7F00 32511 7EFF 23.52 mA 22.81 mA Overshoot range 27649 6C01 27648 6C00 20 mA 20 mA 20736 5100 15 mA 16 mA 1 1 723.4 nA 4 mA + 578.7 nA 0 0 0 mA 4 mA -1 FFFF -4864 ED00 -3.52 mA 1.185 mA -4865 ECFF -32768 8000 Rated range Undershoot range Underflow S7-300 Module data Manual, 06/2017, A5E00105505-AJ 265 Principles of analog modules 5.1 Representation of the values for analog input channels Representation of the analog values of resistive transducers Table 5- 10 Representation of the analog values of 6 k; 10 k and from 150 to 600 resistive transducers System Resistive transducer range dec hex 6k 10 k 32767 7FFF 7.111 k 11.852 k 32512 7F00 32511 7EFF 27649 6C01 27648 150 300 600 177.77 355.54 711.09 176.39 352.78 705.55 7.055 k 11.759 k 176.38 352.77 705.53 6C00 6.0 k 10 k 150 300 600 20736 5100 4.5 k 7.5 k 112.5 225 450 1 1 217.0 m 361.7 m 5.43 m 10.85 m 21.70 m 0 0 0 0 0 0 0 Overflow Overshoot range Rated range (negative values are physically impossible) Undershoot range Representation of analog values for resistance thermometers Pt x00 and Pt x00 GOST (0.003850) standard Table 5- 11 Representation of analog values for resistance thermometers PT 100, 200, 500,1000 and PT 10, 50,100, 500 GOST (0.003850) standard Pt x00 Units Standard / dec GOST in C (1 digit = 0.1C) Pt x00 Standard/ GOST in F (1 digit = 0.1 F) Units dec hex 7FFFH > 1832.0 32767 hex Pt x00 Standard/ GOST in K (1 digit = 0.1 K) Units Range dec hex 7FFFH > 1273.2 32767 7FFFH Overflow Overshoot range > 1000.0 32767 1000.0 10000 2710H 1832.0 18320 4790H 1273.2 12732 31BCH : : : : : : : : : 850.1 8501 2135H 1562.1 15621 3D05H 1123.3 11233 2BE1H 850.0 8500 2134H 1562.0 15620 3D04H 1123.2 11232 2BE0H : : : : : : : : : -200.0 -2000 F830H -328.0 -3280 F330H 73.2 732 2DCH -200.1 -2001 F82FH -328.1 -3281 F32FH 73.1 731 2DBH : : : : : : : : : -243.0 -2430 F682H -405.4 -4054 F02AH 30.2 302 12EH < - 243.0 -32768 8000H < - 405.4 -32768 8000H < 30.2 32768 8000H Rated range Undershoot range Underflow S7-300 Module data 266 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.1 Representation of the values for analog input channels Representation of the analog values of Pt x00 GOST (0.003910) standard resistance thermometers Table 5- 12 Representation of the analog values of Pt 10, 50, 100, 500 GOST (0.003910) standard resistance thermometers Pt x00 GOST Standard in C (1 digit = 0.1C) Units hex Pt x00 GOST Standard in F (1 digit = 0.1 F) Units dec dec hex Range > 1295.0 32767 7FFFH > 2363.0 32767 7FFFH Overflow 1295.0 12950 3296H 2363.0 23630 5CE4H Overshoot range : : : : : : 1100.1 11001 2AF9H 2012.1 20121 4E99H 1100.0 11000 2AF8H 2012.0 20120 4E98H : : : : : : -260.0 -2600 F5D8H -436.0 -4360 EEF8H -260.1 -2601 F5D7H -436.1 -4361 EEF7H : : : : : : -273.2 -2732 F554H -459.7 -4597 EE0BH < - 273.2 -32768 8000H < - 459.7 -32768 8000H Rated range Undershoot range Underflow Representation of analog values for Pt x00 and Pt x0 GOST (0.003850 and 0.003910) climatic resistance thermometers Table 5- 13 Representation of analog values for Pt 100, 200, 500,1000 and Pt 10, 50, 100, 500 GOST (0.003850 and 0.003910) climatic resistance thermometers Pt x00 climat- Units ic/GOST in C dec (1 digit = 0.01 C) Pt x00 climatic/GOST in F (1 digit = 0.01 F) Units hex > 155.00 32767 155.00 : Range dec hex 7FFFH > 311.00 32767 7FFFH Overflow 15500 3C8CH 311.00 31100 797CH Overshoot range : : : : : 130.01 13001 32C9H 266.01 26601 67E9H 130.00 13000 32C8H 266.00 26600 67E8H : : : : : : -120.00 -12000 D120H -184.00 -18400 B820H -120.01 -12001 D11FH -184.01 -18401 B81FH : : : : : : -145.00 -14500 C75CH -229.00 -22900 A68CH < - 145.00 -32768 8000H < - 229.00 -32768 8000H Rated range Undershoot range Underflow S7-300 Module data Manual, 06/2017, A5E00105505-AJ 267 Principles of analog modules 5.1 Representation of the values for analog input channels Representation of the analog values of Ni x00 Standard resistance thermometers Table 5- 14 Representation of the analog values of Ni100, 120, 200, 500, 1000 and LG-Ni 1000 resistance thermometers Ni x00 Units Standard dec in C (1 digit = 0.1C) Ni x00 Standard in F (1 digit = 0.1 F) Units dec hex Ni x00 standard in K (1 digit = 0.1 K) Units hex dec hex > 295.0 32767 7FFFH > 563.0 32767 7FFFH > 568.2 32767 7FFFH Overflow 295.0 2950 B86H 563.0 5630 15FEH 568.2 5682 1632H : : : : : : : : : Overshoot range 250.1 2501 9C5H 482.1 4821 12D5H 523.3 5233 1471H 250.0 2500 9C4H 482.0 4820 12D4H 523.2 5232 1470H : : : : : : : : : -60.0 -600 FDA8H -76.0 -760 FD08H 213.2 2132 854H -60.1 -601 FDA7H -76.1 -761 FD07H 213.1 2131 853H : : : : : : : : -105.0 -1050 FBE6H -157.0 -1570 F9DEH 168.2 1682 692H < -105.0 -32768 8000H < -157.0 -32768 8000H < 168.2 32768 8000H : Range Rated range Undershoot range Underflow Representation of the analog values of Ni x00 climate resistance thermometers The following table shows the analog values for the resistance thermometer Nix00 Climatic for all analog input modules. Exceptions: Analog input module AI 8x12-bit; 6ES7331-7KF02-0AB0 Analog input module AI 2x12-bit; 6ES7331-7KB02-0AB0 There is no overrange for these analog input modules. Overflow begins at 240 C and is encoded with 7FFFH. S7-300 Module data 268 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.1 Representation of the values for analog input channels Table 5- 15 Representation of the analog values of Ni 100, 120, 200, 500, 1000 and LG-Ni 1000 resistance thermometers Ni x00 climatic in C (1 digit = 0.01 C) Units Units hex Ni x00 climatic in F (1 digit = 0.01 F) dec > 295.00 295.00 Range dec hex 32767 7FFFH > 327.66 32767 7FFFH Overflow 29500 733CH 327.66 32766 7FFEH Overshoot range : : : : : : 250.01 25001 61A9H 280.01 28001 6D61H 250.00 25000 61A8H 280.00 28000 6D60H : : : : : : -60.00 -6000 E890H -76.00 -7600 E250H -60.01 -6001 E88FH -76.01 -7601 E24FH : : : : : : -105.00 -10500 D6FCH -157.00 -15700 C2ACH < - 105.00 -32768 8000H < - 157.00 -32768 8000H Rated range Undershoot range Underflow Representation of the analog values of Ni 100 GOST Standard resistance thermometers Table 5- 16 Representation of the analog values of Ni 100 GOST Standard resistance thermometers Ni 100 GOST Standard in C (1 digit = 0.1C) Units Ni 100 GOST Standard in F (1 digit = 0.1 F) Units dec hex > 212.4 32767 212.4 2124 : 180.1 Range dec hex 7FFFH > 414.3 32767 7FFFH Overflow 084CH 414.3 4143 102FH Overshoot range : : : : : 1801 0709H 356.1 3561 0DE9H 180.0 1800 0708H 356.0 3560 0DE8H : : : : : : -60.0 -600 FDA8H -76.0 -760 FD08H -60.1 -601 FDA7H -76.1 -761 FD07H : : : : : : -105.0 -1050 FBE6H -157.0 -1570 F9DEH < - 105.0 -32768 8000H < - 157.0 -32768 8000H Rated range Undershoot range Underflow S7-300 Module data Manual, 06/2017, A5E00105505-AJ 269 Principles of analog modules 5.1 Representation of the values for analog input channels Representation of the analog values of Ni 100 GOST Klima resistance thermometers Table 5- 17 Representation of the analog values of Ni 100 GOST Klima resistance thermometers Ni 100 GOST Klima in C (1 digit = 0.1C) Units dec hex Ni 100 GOST Klima in F (1 digit = 0.1 F) Units dec hex > 212.40 32767 212.40 : Range 7FFFH > 327.66 32767 7FFFH Overflow 21240 52F8H 327.66 32766 7FFEH Overshoot range : : : : : 180.01 18001 4651H 280.01 28001 6D61H 180.00 18000 4650H 280.00 28000 6D60H : : : : : : -60.00 -6000 E890H -76.00 -7600 E250H -60.01 -6001 E88FH -76.01 -7601 E24FH : : : : : : -105.00 -10500 D6FCH -157.00 -15700 C2ACH < - 105.00 -32768 8000H < - 157.00 -32768 8000H Rated range Undershoot range Underflow Representation of the analog values for Cu 10 standard resistance thermometers Table 5- 18 Representation of the analog values for Cu 10 standard resistance thermometers Cu 10 standard in C (1 digit = 0.01 C) Units Units hex Cu 10 standard in F (1 digit = 0.01 F) Units hex Cu 10 standard in K (1 digit = 0.01 K) dec dec > 312.0 32767 7FFFH > 593.6 32767 312.0 3120 C30H 593.6 : : : : 260.1 2601 A29H 260.0 2600 A28H : : -200.0 -2000 -200.1 : Range dec hex 7FFFH > 585.2 32767 7FFFH Overflow 5936 1730H 585.2 5852 16DCH : : : : : Overshoot range 500.1 5001 12D5H 533.3 5333 14D5H 500.0 5000 1389H 533.2 5332 14D4H : : : : : : : F830H -328.0 -3280 F330H 73.2 732 2DCH -2001 F82FH -328.1 -3281 F32FH 73.1 731 2DBH : : : : : : : : -240.0 -2400 F6A0H -400.0 -4000 F060H 33.2 332 14CH < - 240.0 -32768 8000H < - 400.0 -32768 8000H < 33.2 32768 8000H Rated range Undershoot range Underflow S7-300 Module data 270 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.1 Representation of the values for analog input channels Representation of analog values for Cu 10 climatic and Cu 10, 50, 100 GOST climatic resistance thermometers Table 5- 19 Representation of analog values for Cu 10 climatic and Cu 10, 50, 100 GOST climatic resistance thermometers Cu x0 climatic/in C (1 digit = 0.01 C) Units hex Cu x0 climatic in F (1 digit = 0.01 F) Units dec dec hex Range > 180.00 32767 7FFFH > 327.66 32767 7FFFH Overflow 180.00 18000 4650H 327.66 32766 7FFEH Overshoot range : : : : : : 150.01 15001 3A99H 280.01 28001 6D61AH 150.00 15000 3A98H 280.00 28000 6D60H : : : : : : -50.00 -5000 EC78H - 58.00 -5800 E958H -50.01 -5001 EC77H -58.01 -5801 E957H : : : : : : -60.00 -6000 E890H -76.00 -7600 E250H < - 60.00 -32768 8000H < - 76.00 -32768 8000H Rated range Undershoot range Underflow Representation of analog values for Cu 10, 50, 100, 500 GOST standard (0.00426) resistance thermometers Table 5- 20 Representation of analog values for Cu 10, 50, 100, 500 GOST standard (0.00426) resistance thermometers Cu x0 Units Standard in dec C (1 digit = 0.1C) Units hex Cu x0 standard in F (1 digit = 0.01 F) > 240.0 32767 240.0 : Range dec hex 7FFFH > 464.0 32767 7FFFH Overflow 2400 0960H 464.0 4640 1220H Overshoot range : : : : : 200.1 2001 07D1H 392.1 3921 0F51H 200.0 2000 07D0H 392.0 3920 0F50H : : : : : : -50.0 -500 FE0CH -58.0 -580 FDBCH -50.1 -501 FE0BH -58.1 -581 FDBBH : : : : : : -60.0 -600 FDA8H -76.0 -760 FD08H < - 60.00 -32768 8000H < - 76.0 -32768 8000H Rated range Undershoot range Underflow S7-300 Module data Manual, 06/2017, A5E00105505-AJ 271 Principles of analog modules 5.1 Representation of the values for analog input channels Representation of the analog values for Cu 10, 50, 100, 500 GOST standard (0.00428) resistance thermometers Table 5- 21 Representation of the analog values for Cu 10, 50, 100, 500 GOST standard (0.00428) resistance thermometers Cu x0 standard in C (1 digit = 0.01 C) Units hex Cu x0 standard in F (1 digit = 0.01 F) Units dec dec hex Range > 240.0 32767 7FFFH > 464.0 32767 7FFFH Overflow 240.0 2400 0960H 464.0 4640 1220H Overshoot range : : : : : : 200.1 2001 07D1H 392.1 3921 0F51H 200.0 2000 07D0H 392.0 3920 0F50H : : : : : : -200.0 -2000 F830H -328.0 -3280 F330H -200.1 -2001 F82FH -328.1 -3281 F32FH : : : : : : -240.0 -2400 F6A0H -405.4 -4054 F02AH < - 240.0 -32768 8000H < - 405.4 -32768 8000H Rated range Undershoot range Underflow Representation of analog values for KTY83/110 silicon temperature sensors Table 5- 22 Representation of analog values for KTY83/110 silicon temperature sensors KTY83/110 in Units C dec (1 digit = 0.1 C) Units hex KTY83/110 in F (1 digit = 0.1 F) Units hex KTY83/110 in K (1 digit = 0.1 K) dec > 206.3 32767 7FFFH > 403.3 206.3 : 2063 080FH : : 175.1 1751 175 1750 : -55 Range dec hex 32767 7FFFH > 479.5 32767 7FFFH Overflow 403.3 4033 0FC1H 479.5 4795 12BBH : : : : : : Overshoot range 06D7H 347.1 3471 0D8FH 448.3 4483 1183H 06D6H 347 3470 0D8EH 448.2 4482 1182H : : : : : : : : -550 FDDAH -67 -670 FD62H 218.2 2182 0886H -55.1 -551 FDD9H -67.1 -671 FD61H 218.1 2181 0885H : : : : : : : : : -64.7 -647 FD79H -84.5 -845 FCB3H 208.5 2085 08205H < -64.7 -32768 8000H < -84.5 -32768 8000H < 208.5 -32768 8000H Rated range Undershoot range Underflow S7-300 Module data 272 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.1 Representation of the values for analog input channels Representation of analog values for KTY84/130 silicon temperature sensors Table 5- 23 Representation of analog values for KTY84/130 silicon temperature sensors KTY84/130 in C (1 digit = 0.1 C) Units dec hex KTY84/130 in K (1 digit = 0.1 K) Units hex KTY84/130 in F (1 digit = 0.1 F) Units dec dec hex Range > 352.8 32767 7FFFH > 667.0 32767 7FFFH > 626.0 32767 7FFFH Overflow 352.8 3528 0DC8H 667.0 6670 1A0EH 626.0 6260 1874H : : : : : : : : : Overshoot range 300.1 3001 0BB9H 572.1 5721 1659H 573.3 5733 1665H 300 3000 0BB8H 572 5720 1658H 573.2 5732 1664H : : : : : : : : : -40 -400 FE70H -40 -400 FE70H 233.2 2332 091CH -40.1 -401 FE6FH -40.1 -401 FE6FH 233.1 2331 091BH : : : : : : : : : -47.0 -470 FE2AH -52.6 -526 FDF2H 226.2 2262 08D6H < -47.0 -32768 8000H < -52.6 -32768 8000H < 226.2 -32768 8000H Rated range Undershoot range Underflow Representation of the analog values of thermocouples type B Table 5- 24 Representation of the analog values of thermocouples type B Type B in C Units Units hex Type B in F dec > 2070.0 32767 2070.0 : Type B in K Units Range dec hex dec hex 7FFFH > 3276.6 32767 7FFFH > 2343.2 32767 7FFFH Overflow 20700 50DCH 3276.6 32766 7FFEH 2343.2 23432 5B88H : : : : : : : : Overshoot range 1820.1 18201 4719H 2786.6 27866 6CDAH 2093.3 20933 51C5H 1820.0 18200 4718H 2786.5 27865 6CD9H 2093.2 20932 51C4H : : : : : : : : : 0.0 0 0000H 32.0 320 0140H 273.2 2732 0AACH : : : : : : : : : -120.0 -1200 FB50H -184.0 -1840 F8D0H 153.2 1532 05FCH Undershoot range < -120.0 -32768 8000H < -184.0 -32768 8000H < 153.2 32768 8000H Underflow Rated range S7-300 Module data Manual, 06/2017, A5E00105505-AJ 273 Principles of analog modules 5.1 Representation of the values for analog input channels Representation of the analog values of thermocouples type C Table 5- 25 Representation of the analog values of thermocouples type C Type C in C Units hex Type C in F Units dec dec hex Range > 2500.0 32767 7FFFH > 3276.6 32767 7FFFH Overflow 2500.0 25000 61A8H 3276.6 32766 7FFEH Overshoot range : : : : : : 2315.1 23151 5A6FH 2786.6 27866 6CDAH 2315.0 23150 5A6EH 2786.5 27865 6CD9H : : : : : : 0.0 0 0000H 32.0 320 0140H -0.1 -1 FFFFH 31.9 319 013FH : : : : : : -120.0 -1200 FB50H -184.0 -1840 F8D0H < -120.0 -32768 8000H < -184.0 -32768 8000H Rated range Undershoot range Underflow Representation of the analog values of thermocouples type E Table 5- 26 Representation of the analog values of thermocouples type E Type E i n C Units hex Type E in F Units dec dec hex Type E in K > 1200.0 32767 7FFFH > 2192.0 32767 7FFFH 1200.0 12000 2EE0H 2192.0 21920 55A0H : : : : : 1000.1 10001 2711H 1832.2 18322 1000.0 10000 2710H 1832.0 18320 : : : : -270.0 -2700 F574H -454.0 < -270.0 < -2700 < F574H < -454.0 Units Range dec hex > 1473.2 32767 7FFFH Overflow 1473.2 14732 398CH : : : : Overshoot range 4792H 1273.3 12733 31BDH 4790H 1273.2 12732 31BCH : : : : : -4540 EE44H 0 0 0000H < -4540 1450.0 32767 7FFFH 1450.0 14500 : : 1200.1 1200.0 : -210.0 < -210.0 Type J in K dec hex > 2642.0 32767 7FFFH 38A4H 2642.0 26420 : : : 12001 2EE1H 2192.2 21922 12000 2EE0H 2192.0 21920 : : : -2100 F7CCH -346.0 < -2100 1723.2 32767 7FFFH Overflow 6734H 1723.2 17232 4350H : : : : Overshoot range 55A2H 1473.3 14733 398DH 55A0H 1473.2 14732 398CH : : : : : -3460 F27CH 63.2 632 0278H < -3460 1622.0 32767 1622.0 : Type K in K Units Range dec hex dec hex 7FFFH > 2951.6 32767 7FFFH > 1895.2 32767 7FFFH Overflow 16220 3F5CH 2951.6 29516 734CH 1895.2 18952 4A08H : : : : : : : : Overshoot range 1372.1 13721 3599H 2501.8 25018 61BAH 1645.3 16453 4045H 1372.0 13720 3598H 2501.6 25061 61B8H 1645.2 16452 4044H : : : : : : : : : -270.0 -2700 F574H -454.0 -4540 EE44H 0 0 0000H < -270.0 < -2700 < F574H < -454.0 < -4540 1150.0 32767 7FFFH 1150.0 11500 : : 900.1 9001 900.0 9000 : -200.0 < -200.0 Type L in K dec hex > 2102.0 32767 7FFFH 2CECH 2102.0 21020 : : : 2329H 1652.2 16522 2328H 1652.0 16520 : : : -2000 F830H -328.0 < -2000 < F830H < -328.0 Units Range dec hex > 1423.2 32767 7FFFH Overflow 521CH 1423.2 14232 3798H : : : : Overshoot range 408AH 1173.3 11733 2DD5H 4088H 1173.2 11732 2DD4H : : : : : -3280 F330H 73.2 732 02DCH < -3280 < F330H < 73.2 < 732 <02DCH Rated range Underflow Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ... ... from F380H underflow and outputs 8000H. ... from EAC0H underflow and outputs 8000H. ... from FE2CH underflow and outputs 8000H. Representation of the analog values of thermocouples type N Table 5- 30 Representation of the analog values of thermocouples type N Type N in C Units Units hex Type N in F dec > 1550.0 32767 1550.0 : Type N in K Units Range dec hex dec hex 7FFFH > 2822.0 32767 7FFFH > 1823.2 32767 7FFFH Overflow 15500 3C8CH 2822.0 28220 6E3CH 1823.2 18232 4738H : : : : : : : : Overshoot range 1300.1 13001 32C9H 2372.2 23722 5CAAH 1573.3 15733 3D75H 1300.0 13000 32C8H 2372.0 23720 5CA8H 1573.2 15732 3D74H : : : : : : : : : -270.0 -2700 F574H -454.0 -4540 EE44H 0 0 0000H < -270.0 < -2700 < F574H < -454.0 < -4540 2019.0 32767 7FFFH > 3276.6 32767 7FFFH > 2292.2 32767 7FFFH Overflow 2019.0 20190 4EDEH 3276.6 32766 7FFEH 2292.2 22922 598AH : : : : : : : : : Overshoot range 1769.1 17691 451BH 3216.4 32164 7DA4H 2042.3 20423 4FC7H 1769.0 17690 451AH 3216.2 32162 7DA2H 2042.2 20422 4FC6H : : : : : : : : : -50.0 -500 FE0CH -58.0 -580 FDBCH 223.2 2232 08B8H -50.1 -501 FE0BH -58.2 -582 FDBAH 223.1 2231 08B7H : : : : : : : : : -170.0 -1700 F95CH -274.0 -2740 F54CH 103.2 1032 0408H < -170.0 -32768 8000H < -274.0 -32768 8000H < 103.2 < 1032 8000H Rated range Undershoot range Underflow Representation of the analog values of thermocouples type T Table 5- 32 Representation of the analog values of thermocouples type T Type T in C Units dec hex Type T in F Units > 540.0 32767 7FFFH 540.0 5400 1518H : : 400.1 4001 400.0 Type T in K dec hex > 1004.0 32767 7FFFH 1004.0 10040 2738H : : : 0FA1H 752.2 7522 4000 0FA0H 752.0 : : : -270.0 -2700 F574H < -270.0 < -2700 < F574H Units Range dec hex > 813.2 32767 7FFFH Overflow 813.2 8132 1FC4H : : : : Overshoot range 1D62H 673.3 6733 1AADH 7520 1D60H 673.2 6732 1AACH : : : : : : -454.0 -4540 EE44H 3.2 32 0020H < -454.0 < -4540 850.0 32767 7FFFH > 1562.0 32767 7FFFH 850.0 8500 2134H 1562.0 15620 : : : : : 600.1 6001 1771H 1112.2 11122 600.0 6000 1770H 1112.0 11120 : : : : -200.0 -2000 F830H -328.0 < -200.0 < -2000 < F830H < -328.0 Units Range dec hex > 1123.2 32767 7FFFH Overflow 2738.0H 1123.2 11232 2BE0H : : : : Overshoot range 2B72H 873.2 8732 221CH 2B70H 873.2 8732 221CH : : : : : -3280 F330H 73.2 732 02DCH < -3280 < F330H < 73.2 < 732 <02DCH Rated range Underflow Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ... ... from F380H underflow and outputs 8000H. ... from EAC0H underflow and outputs 8000H. ... from FE2CH underflow and outputs 8000H. Representation of analog values for type TXK/XKL GOST thermocouple Table 5- 34 Type TXK/XKL Representation of analog values for type TXK/XKL GOST thermocouple Units dec hex Type TXK/XKL > 1050.0 32767 7FFFH 1050.0 8500 2904H : : 800.1 8001 800.0 Units Range dec hex > 1922.0 32767 7FFFH Overflow 1922.0 19220 4B14H Overshoot range : : : : 1F41H 1472.1 14721 3981H 8000 1F40H 1472.0 14720 3980H : : : : : : 0.0 0 0000H 32.0 320 0140H : : : : : : -200.0 -2000 F830H -328.0 -3280 F330H < -200.0 <-32768 < F8000H < -328.0 <-32768 8000H in C in F Rated range Underflow S7-300 Module data 278 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.2 Representation of analog values for analog output channels 5.2 Representation of analog values for analog output channels Binary representation of output ranges Table 5- 35 Bipolar output ranges 215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 32512 0% 0 1 1 1 1 1 1 1 x x x x x x x x Overflow 32511 117,589 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 27649 100,004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1 Overshoot range 27648 100,000 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0 1 0,003617 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0,000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -1 -0,003617 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -27648 -100,000 1 0 0 1 0 1 0 0 0 0 0 0 0 0 0 0 -27649 100,004 1 0 0 1 0 0 1 1 1 1 1 1 1 1 1 1 -32512 -117,593 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 Undershoot range -32513 0% 1 0 0 0 0 0 0 0 x x x x x x x x Underflow Table 5- 36 Units Rated range Unipolar output ranges Output value in % Data word Range 215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 32512 0% 0 1 1 1 1 1 1 1 x x x x x x x x Overflow 32511 117,589 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 27649 100,004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1 Overshoot range 27648 100,000 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0 1 0,003617 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0,000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -1 0,000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 x x x x x x x x -32512 -32513 0% Rated range limited to the low limit of the rated range, 0 V or 0 mA Underflow S7-300 Module data Manual, 06/2017, A5E00105505-AJ 279 Principles of analog modules 5.2 Representation of analog values for analog output channels Representation of analog values in the voltage output ranges Table 5- 37 Representation of analog values in the 10 V output range System 118,5149 % 117,589 % Voltage output range dec hex 10 V 32767 7FFF 0.00 V Overflow, off power 32512 7F00 32511 7EFF 11.76 V Overshoot range 27649 6C01 100 % 27648 6C00 10 V 75 % 20736 5100 7.5 V 0,003617 % 1 1 361.7 V 0% 0 0 0V -1 FFFF -361.7 V -75 % -20736 AF00 -7.5 V -100 % -27648 9400 -10 V -27649 93FF -32512 8100 -32513 80FF -32768 8000 -117,593 % -118,519 % Table 5- 38 Rated range Undershoot range -11.76 V Underflow, at zero voltage and current 0.00 V Representation of analog values in the 0 V to 10 V and 1 V to 5 V output ranges System Voltage output range dec hex 0 V to 10 V 1 V to 5 V 32767 7FFF 0.00 V 0.00 V Overflow, off power 32512 7F00 32511 7EFF 11.76 V 5.70 V Overshoot range 27649 6C01 100 % 27648 6C00 10 V 5V 75 % 20736 5100 7.5 V 3.75 V 0,003617 % 1 1 361.7 V 1 V +144.7 V 0% 0 0 0V 1V -1 FFFF -6912 E500 -6913 E4FF -32512 8100 -32513 80FF -32768 8000 118,5149 % 117,589 % -25 % -117,593 % -118,519 % Rated range Undershoot range 0V Not supported. Output value limited to 0 V. 0.00 V 0.00 V Underflow, at zero voltage and current S7-300 Module data 280 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.2 Representation of analog values for analog output channels Representation of analog values in the current output ranges Table 5- 39 Representation of analog values in the 20 mA output range System Current output range dec 118,5149 % 117,589 % hex 20 mA 32767 7FFF 0.00 mA Overflow, off power 32512 7F00 32511 7EFF 23.52 mA Overshoot range 27649 6C01 100 % 27648 6C00 20 mA 75 % 20736 5100 15 mA 0,003617 % 1 1 723.4 nA 0% 0 0 0 mA -1 FFFF -723.4 nA -75 % -20736 AF00 -15 mA -100 % -27648 9400 -20 mA -27649 93FF -32512 8100 -32513 80FF -32768 8000 -117,593 % -118,519 % Table 5- 40 Rated range Undershoot range -23.52 mA Underflow, at zero voltage and current 0.00 mA Representation of analog values in the 0 mA to 20 mA and 4 mA to 20 mA output ranges System Current output range dec hex 0 mA to 20 mA 4 mA to 20 mA 32767 7FFF 0.00 mA 0.00 mA Overflow, off power 32512 7F00 32511 7EFF 23.52 mA 22.81 mA Overshoot range 27649 6C01 100 % 27648 6C00 20 mA 20 mA 75 % 20736 5100 15 mA 16 mA 0,003617 % 1 1 723.4 nA 4 mA + 578.7 nA 0% 0 0 0 mA 4 mA -1 FFFF -6912 E500 -6913 E4FF -32512 8100 -32513 80FF -32768 8000 118,5149 % 117,589 % -25 % -117,593 % -118,519 % Rated range Undershoot range 0 mA Not supported. Output value limited to 0 mA. 0.00 mA 0.00 mA Underflow, at zero voltage and current S7-300 Module data Manual, 06/2017, A5E00105505-AJ 281 Principles of analog modules 5.3 Setting the measuring method and ranges of analog input channels 5.3 Setting the measuring method and ranges of analog input channels Two procedures There are two methods of setting the measuring method and ranges of analog input channels at analog modules: using a measuring range module and STEP 7 hardwiring of the analog input channel and STEP 7 The method to use for the various analog modules is module-specific and is described in detail in the special module chapters. This section describes how to set up the type and range of measurement using measuring range modules. Setting the measurement type and ranges using measuring range modules The analog modules are supplied with corresponding measuring range modules as required. You may have to change the position of the measuring range module to suit the measurement type and range. Note Note that the measuring range modules are installed on the side of the analog input module. Always check whether the measuring range modules needs to be set up for a different measurement type and range before you install the analog input module. Optional settings of the measuring range modules Optional settings of the measuring range modules: "A", "B", "C" and "D". For detailed information on settings to be made for a specific measurement type and range, refer to the special module chapter. The settings for the different measurement types and ranges are also printed onto the analog module. S7-300 Module data 282 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.3 Setting the measuring method and ranges of analog input channels Changing the positioning of measuring range modules To insert the measuring range module into a different slot: 1. Remove the measuring range module from the slot of the analog input module by lifting it out with a screwdriver. Figure 5-1 Removing the measuring range module from a slot of the analog input module 2. Insert the measuring range module into the required slot (1) of the analog input module. The indicator of the selected measuring range must be in line with the marker on the module (2). Figure 5-2 Inserting the measuring range module into the analog input module S7-300 Module data Manual, 06/2017, A5E00105505-AJ 283 Principles of analog modules 5.3 Setting the measuring method and ranges of analog input channels Proceed likewise with any other measuring range modules. You can now install the module. CAUTION Incorrect settings of the measuring range modules may lead to the destruction of the module. Always make sure that the measuring range module is in the correct position before you connect a sensor to the module. S7-300 Module data 284 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.4 Response of the analog modules 5.4 Response of the analog modules This chapter This chapter describes: the dependency of analog input and output values on CPU operating states and on the supply voltage of the analog module the reaction of analog modules, based on the actual analog value within the relevant range of values the influence of the operational limits of analog modules on analog IO values, as illustrated by an example 5.4.1 Influence of the power supply and operating state Introduction This chapter describes: the dependency of analog IO values on CPU operating states, and on the supply voltage of the analog module the reaction of analog modules, based on the actual analog value within the relevant range of values the influence of the operational limits of analog modules on analog IO values, as illustrated by an example S7-300 Module data Manual, 06/2017, A5E00105505-AJ 285 Principles of analog modules 5.4 Response of the analog modules Influence of the supply voltage and operating state on the modules The IO values of analog modules are determined by the CPU operating state and the module's supply voltage. Table 5- 41 Dependencies of the analog IO values on the CPU's operating State and on the L+ supply voltage CPU operating state Supply voltage L+ at the analog module Input value of the analog input module POWER ON L+ present Measured value CPU values 7FFFH, until the first conversion after POWER ON is completed, or when the module has been programmed. Until the first conversion... RUN L+ missing POWER ON POWER OFF STOP - L+ present Overflow value Output value of the analog output module * after POWER ON, the module outputs a 0 mA or 0 V signal. * after programming is successfully completed, it outputs the previous value. 0 mA / 0 V Measured value Substitution value / last value 7FFFH, until the first conversion after POWER ON is completed, or when the module has been programmed. (default: 0 mA / 0 V) L+ missing Overflow value 0 mA / 0 V L+ present - 0 mA / 0 V L+ missing - 0 mA / 0 V Reaction to power failure Power failure at analog modules is always indicated by their relevant SF LED. This information is also available on the module (in diagnostics buffer data.) Diagnostics interrupt triggering is based on parameter settings. See also Programming analog modules (Page 294) S7-300 Module data 286 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.4 Response of the analog modules 5.4.2 Influence of the range of analog values influence of errors on analog modules with diagnostics functions Errors may lead to an entry in the diagnostics buffer and trigger a diagnostics interrupt at analog modules with diagnostics function and corresponding parameter settings. Influence of the range of values on the analog input module The reaction of analog modules is determined by the actual input values within the range of values. Table 5- 42 Reaction of analog input modules as a function of the actual analog value within the range of values Measured value within Input value SF LED Diagnostics Interrupt Rated range Measured value - - - Overshoot/undershoot range Measured value - - - Overflow 7FFFH lit1 Entry is made1 Diagnostics interrupt1) Underflow 8000H lit1 Entry is made1 Diagnostics interrupt1) beyond programmed limit Measured value - - Process interrupt1) 1), only supported by modules with diagnostics function, and depending on parameter settings Influence of the range of values on the analog output module The reaction of analog modules is determined by the actual output values within the value range. Table 5- 43 Reaction of analog output modules as a function of the actual analog value within the range of values Output value within Output value SF LED Diagnostics Interrupt Rated range CPU value - - - Overshoot/undershoot range CPU value - - - Overflow 0 signal - - - Underflow 0 signal - - - S7-300 Module data Manual, 06/2017, A5E00105505-AJ 287 Principles of analog modules 5.4 Response of the analog modules 5.4.3 Influence of operational limits and basic error limits Operational limit The operational limit represents the total measuring/output error of an analog module within the permissible temperature range, based on the module's rating. Basic error limit The basic error limit represents the total measuring/output error at 25 C, based on the module's rating. Note The percentile values of operational and basic error limits in the module's technical data always refer to the highest possible input and output value within the nominal range of the module. Example of the determination of the output error of a module An analog output module SM 332; AO 4 x 12 Bit is being used for voltage output. An output range of "0 to 10 V" is set. The module is operating at an ambient temperature of 30 C, i.e. the operational limit applies. The technical data of the module state: Operational limit for voltage output: 0,5 % Hence, an output error of 0.05 V (0.5 % of 10 V) across the nominal range of the module must be expected. At an actual voltage of 1 V, for example, the module will then output a value in the range from 0.95 V to 1.05 V. The relative error is 5 % in this case. For the example, the figure below shows how the relative error decreases as the output value approaches the end of the 10-V range. Figure 5-3 Example of the relative error of an analog output module S7-300 Module data 288 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.5 Conversion and cycle times of analog modules 5.5 Conversion and cycle times of analog modules Conversion time of analog input channels The conversion time is the total of the basic conversion time plus additional processing times of the module for: Resistance measurement Wirebreak monitoring The basic conversion time depends directly on the conversion method of the analog input channel (integrating method, actual value conversion.) The integration time of integrating conversions has a direct influence on conversion times. The integration time depends on the interference frequency suppression you set in STEP 7. For information on basic conversion times and additional processing times of the various analog modules, refer to the technical data of the relevant module. Cycle time of analog input channels Analog-to-digital conversion, and the transfer of digitized measured values to memory and/or to the backplane bus, are carried out sequentially, i.e. the analog input channels are converted in successive order. The cycle time, i.e. the time expiring until an analog input value is converted again, represents the accumulated conversion time of all activated analog input channels of the analog input module. The figure below provides an overview of the cycle time elements for an n-channel analog module. Figure 5-4 Cycle time of an analog input or output module Conversion and cycle times for analog input channels in channel groups Make allowances for the accumulated channel conversion time when the analog input channels are joined to form channel groups. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 289 Principles of analog modules 5.5 Conversion and cycle times of analog modules Example Two analog input channels of the SM 331; AI 2 x 12 Bit analog input module form a channel group. You must therefore grade the cycle time in steps of 2. Setting smoothing of analog values Certain analog input modules allow you to set smoothing of analog values in STEP 7. Using smoothing Smoothed analog values provide a reliable analog signal for further processing. It is useful to smooth the analog values with slow variations of measured values, for example, when measuring temperature. Smoothing principle The measured values are smoothed by digital filtering. Smoothing is accomplished by the module calculating mean values, derived from a defined number of converted (digitized) analog values. The user configures up to four grades of smoothing (none, low, average, high). The grade determines the number of analog signals used for averaging. A higher smoothing provides a more reliable analog value, and prolongs the time it takes to apply a smoothed analog signal following a step response (see the example below.) S7-300 Module data 290 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.5 Conversion and cycle times of analog modules Examples The figures below show the number of cycles a module requires to apply a close to 100% smoothed analog value after a step response, based on the smoothing function settings. The figure applies to all signal changes at the analog input. Low smoothing grade Medium smoothing grade High smoothing grade Figure 5-5 Example of impact of smoothing on the jump response with the AI 8 x 14 bit S7-300 Module data Manual, 06/2017, A5E00105505-AJ 291 Principles of analog modules 5.5 Conversion and cycle times of analog modules Low smoothing grade Medium smoothing grade High smoothing grade Figure 5-6 Example of impact of smoothing on the step response with the AI 6 x TC Further information on smoothing For information showing whether a specific module supports smoothing functions, and special features to observe, refer to the chapter dealing with the analog input module. Conversion time of the analog output channels The conversion time of the analog output channels includes the transfer of digitized output values from internal memory, and their digital-to-analog conversion. Cycle time of analog output channels Analog output channels are converted sequentially, i.e. successively. The cycle time, i.e. the time expiring until an analog output value is converted again, is equivalent to the accumulated conversion times of all activated analog output channels. Refer to the figure Cycle time of an analog IO channel. Tip You should disable all unused analog channels in STEP 7 in order to reduce cycle times. S7-300 Module data 292 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.6 Settling and response times of analog output channels 5.6 Settling and response times of analog output channels Settling time The settling time (t2 to t3), i.e. the time expiring until a converted value has gained a specified level at an analog output, is load-dependent. We therefore distinguish between resistive, capacitive and inductive load. For information on settling times as a function of load at the various analog output modules, refer to the technical data of the relevant module. Response time The worst case response time (t1 to t3), i.e. the time expiring between the input of digital output values to internal memory, and the signal settling time at the analog output, may be equivalent to the total of cycle time plus settling time. The worst case scenario is given, when the analog channel has been converted immediately before a new output value is transferred, and is not converted again until all other channels have been converted (cycle time.) Overview of the settling time and response time of analog output modules tA Response time tC tC = Cycle time, equivalent to n x conversion time (n = active channels) tS Settling time t1 new digital output value is set t2 Output value is applied and converted t3 specified output value is reached S7-300 Module data Manual, 06/2017, A5E00105505-AJ 293 Principles of analog modules 5.7 Programming analog modules 5.7 Programming analog modules Introduction The properties of analog modules may differ. The module properties can be programmed. Programming tools You program analog modules in STEP 7. Always program the module while the CPU is in STOP mode. After you defined all parameters, download these from your PG to the CPU. The CPU transfers the parameters to the relevant analog modules at the STOP RUN transition. Also, position the measuring range modules of the module as required. Static and dynamic parameters Parameters are organized by static and dynamic properties. Set the static parameters while the CPU is in STOP, as described earlier. You can also modify dynamic parameters in the active user program using SFCs. However, the parameters set in STEP 7 will be applied again after a RUN STOP, STOP RUN transition of the CPU. Parameters configurable using CPU operating state static PG (STEP 7 HW CONFIG) STOP dynamic PG (STEP 7 HW CONFIG) STOP SFC 55 in the user program RUN See also Programmable parameters (Page 348) 5.7.1 Parameters of analog input modules Parameters of analog input modules For information on parameters supported by specific analog modules, refer to the chapter dealing with the relevant module. The defaults apply if you have not set any parameters in STEP 7. S7-300 Module data 294 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.8 Diagnostics of analog modules 5.8 Diagnostics of analog modules Programmable and non-programmable diagnostic messages We distinguish between programmable and non-programmable diagnostic messages. You only obtain programmable diagnostic messages if you have enabled diagnostics at the relevant parameters. Program these functions in the "Diagnostics" parameter block in STEP 7. The the analog module always provides non-programmable diagnostic messages, irrespective of the enable state of diagnostic functions. Reactions to a diagnostic message in STEP 7 Actions initiated by diagnostic messages: The diagnostic message is written to the diagnostics buffer of the analog module, and is then passed to the CPU. The error LED on the analog module is lit. When "Enable Diagnostics Interrupt" is set in STEP 7, the system triggers a diagnostic interrupt and calls OB82. Reading diagnostic messages You can read detailed diagnostic messages in the user program using SFCs. Viewing the cause of error You can view the cause of the error in the module diagnostics data in STEP 7 (refer to the STEP 7 Online Help.) Diagnostic message included in the measured value of analog input modules All analog input modules return the measured value 7FFFH as a reaction to errors, irrespective of parameter settings. This measured value indicates either overflow, error, or a disabled channel. Diagnostic message using the SF LED Diagnostics-capable analog modules indicate errors by means of their SF LED (group error LED). The SF LED lights up when the analog module has generated a diagnostic message. It goes dark after all error states are cleared. See also Programming analog modules (Page 294) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 295 Principles of analog modules 5.8 Diagnostics of analog modules 5.8.1 Diagnostics messages of analog input modules Overview of the diagnostics messages of analog input modules The table below provides an overview of the diagnostics messages of analog input modules. Table 5- 44 Diagnostics messages of analog input modules Diagnostics message LED Scope of diagnostics programmable External load voltage missing SF Module no Configuration / programming error SF Channel yes Common-mode error SF Channel yes Wirebreak SF Channel yes Underflow SF Channel yes Overflow SF Channel yes 5.8.2 Diagnostic messages of analog output modules Overview of the diagnostic messages of analog output modules The table below provides an overview of the diagnostic messages of analog output modules. Table 5- 45 Diagnostic messages of analog output modules Diagnostic message LED Scope of diagnostics programmable External load voltage missing SF Module no Configuration / programming error SF Channel yes Short-circuit to M* SF Channel yes Wire-break* SF Channel yes * Not with the SM 332, AO 4 x 16 bit, isochrone Note The detection of errors which are indicated in programmable diagnostic messages requires appropriate configuration of the analog module in STEP 7. S7-300 Module data 296 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.8 Diagnostics of analog modules 5.8.3 Causes of error and troubleshooting at analog input modules Overview of the causes of error and troubleshooting at analog input modules Table 5- 46 Diagnostics messages of analog input modules, causes of error and troubleshooting Diagnostics message Possible cause of error To correct or avoid errors External load voltage miss- Load voltage L+ of module missing ing Connect supply L+ Configuration / programming error Faulty parameters transferred to module Check the measuring range module Common-mode error Potential difference CMV between inputs M- Connect M- with MANA and the reference potential of measuring circuit (MANA out of limits) Wirebreak Resistance of transducer circuit too high Use a different type of sensor, or modify the wiring, for example, using a larger conductor cross-section. Open circuit between module and sensor Connect the cable Channel not connected (open) Disable the channel group ("measuring method" parameter) Program the module Wire the channel Underflow Input value below undershoot range; possible cause of error: wrong measuring range setting Overflow 5.8.4 program a different measuring range polarity reversal of the sensor wiring in the measuring ranges 4 to 20 mA and 1 to 5 V Check the connections Input value exceeds overshoot range program a different measuring range Causes of error and troubleshooting at analog output modules Overview of the causes of error and troubleshooting routines at analog output modules Table 5- 47 Diagnostics messages of analog output modules, causes of error and troubleshooting Diagnostics message Possible cause of error To correct or avoid errors External load voltage miss- Load voltage L+ of module missing ing Connect supply L+ Configuration / programming error Faulty parameters transferred to module Assign new module parameters Short-circuit to M Overload at output Eliminate overload Short-circuit at output QV to MANA Eliminate the short-circuit Actuator impedance too high Use a different type of actuator, or modify the wiring using cables with a larger conductor cross-section Wire-break between the module and actuator Connect the cable Channel not used (open) Disable the channel group ("output type" parameter) Wirebreak S7-300 Module data Manual, 06/2017, A5E00105505-AJ 297 Principles of analog modules 5.9 Interrupts of analog modules 5.9 Interrupts of analog modules Introduction This section describes the interrupt response of analog modules. Always distinguish between the following interrupts: Diagnostic interrupt Hardware interrupt Note that certain analog modules do not support interrupts, or are only partially capable of "handling" the interrupts described below. For information on modules which support interrupt functionality, refer to their technical data. Description of the STEP 7 blocks For detailed information on the OBs and SFCs mentioned below, refer to the STEP 7 Online Help. Enabling interrupts There are no default interrupt settings, that is, interrupts are disabled if not set accordingly. Program the interrupt enable parameter in STEP 7. Diagnostic interrupt Incoming error events (initial occurrence) and outgoing error events (error is cleared) are reported by means of diagnostic interrupt, if this interrupt is enabled. The CPU interrupts user program execution in order to process diagnostic interrupt OB82. You can call SFC51 or 59 in OB82 in the user program to view details of diagnostics data output by the module. Diagnostics data remain consistent until the program exits OB82. The program acknowledges the diagnostic interrupt at the module when it exits OB82. Hardware interrupt with "high or low limit exceeded" trigger Define a working range by setting a high and low limit. If the process signal (for example, the temperature) overshoots this working range, the module triggers a hardware interrupt, provided the interrupt is enabled. The CPU interrupts user program execution in order to execute hardware interrupt OB40. In the user program of OB 40, you can define the reaction of the automation system to the violation of limits. S7-300 Module data 298 Manual, 06/2017, A5E00105505-AJ Principles of analog modules 5.9 Interrupts of analog modules The program acknowledges the diagnostic interrupt at the module when it exits OB40. Note Note: the system does not generate a hardware interrupt if your limit setting exceeds the overshoot or undershoot range. Structure of the start information variable OB40_POINT_ADDR of OB 40 The channel at which a specific limit is exceeded is logged to the OB40_POINT_ADDR variable in the start information of OB40. The diagram below shows the bit assignment of DWORD 8 in local data. Figure 5-7 Start information of OB40: which limits event has triggered a hardware interrupt Hardware interrupt triggered by "End of cycle reached" You can synchronize a process with the cycle of the analog input module by programming a hardware interrupt trigger at the end of the cycle. One cycle comprises the conversion of the measured values of all active channels of the analog input module. The module processes the channels in successive order. After all measured values were successfully converted, the module outputs an interrupt to the CPU in order to report new measured values at its channels. You can always use this interrupt to download the actual converted analog values. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 299 6 Analog modules Introduction This chapter describes: 1. Analog module selection and commissioning sequence 2. Overview of essential module properties 3. Modules which are available (properties, connection and block diagrams, technical data and additional information on the module): a) for analog input modules b) for analog output modules c) for analog IO modules STEP 7 blocks for analog functions You can use FC105 "SCALE" (scale values) and FC106 "UNSCALE" (unscale values) blocks to read and output analog values in STEP 7. Those FCs are available in the STEP 7 standard library, in the "TI-S7-Converting Blocks" subfolder. Description of STEP 7 blocks for analog functions For information on FCs 105 and 106, refer to the STEP 7 Online Help. Further information You should be familiar with the structure of the parameter sets (data records 0, 1 and 128) in system data before you edit module parameters in the STEP 7 user program. You should be familiar with the structure of diagnostics data (data records 0, 1) in system data before you edit any diagnostics data of the module in the STEP 7 user program. See also Principles of programming signal modules in the user program (Page 522) Evaluating diagnostic data of signal modules in the user program (Page 583) S7-300 Module data 300 Manual, 06/2017, A5E00105505-AJ Analog modules 6.1 Analog module selection and commissioning sequence 6.1 Analog module selection and commissioning sequence Introduction The table below contains the steps required to successfully complete commissioning of analog modules. You do not strictly have to adhere to this suggested sequence, that is, you can complete other tasks such as installing or commissioning other modules, or program the module at an earlier or later time. Analog module selection and commissioning sequence 1. Selecting the module 2. For certain analog input modules: Set the measuring type and range using the measuring range module 3. Installing the module in the SIMATIC S7 system 4. Assigning module parameters 5. Connect the measuring transducers or loads to the module 6. Commission the configuration 7. Analyze the configuration if commissioning failed More information on installation and commissioning See the "Installation" and "Commissioning" chapter in the Installation Manual for your automation system: S7-300 Automation System, Installation or S7-400 Automation System, Installation or Distributed I/O Device ET 200M The documentation is available on the Internet (http://support.automation.siemens.com/WW/view/en). S7-300 Module data Manual, 06/2017, A5E00105505-AJ 301 Analog modules 6.2 Module overview 6.2 Module overview Introduction The tables below summarize the essential properties of the analog modules. This overview supports you in selecting a module to suit your requirements. 6.2.1 Analog input modules Overview of properties The table below shows essential properties of the analog input modules Table 6- 1 Analog input modules Properties Module SM 331; AI 8 x 16 Bit SM 331; AI 8 x 16 Bit SM 331; AI 8 x 14 Bit High Speed SM 331; AI 8 x 13 Bit SM 331; AI 8 x 12 Bit (-7NF00-) (-7NF10-) (-7HF0x-) (-1KF02-) (-7KF02-) Number of inputs 8 inputs in 4 channel groups 8 inputs in 4 chan- 8 inputs in 4 chan- 8 inputs in 8 chan- 8 inputs in 4 channel groups nel groups nel groups nel groups Resolution programmable for each channel group: programmable for each channel group: * 15 bits+sign Measurement type programmable for each channel group: * 15 bits+sign programmable for each channel group: programmable for each channel group: * 13 bits+sign programmable for each channel group: * Voltage * Voltage * Voltage * Current * Current * Current programmable for each channel group: * 12 bits+sign programmable for each channel group: * 9 bits+sign * 12 bits+sign * 14 bits+sign programmable per programmable for channel: each channel group: * Voltage * Voltage * Current * Resistance * Temperature * Current * Resistance * Temperature Measuring range selection any, per channel group any, per channel group any, per channel group any, per channel any, per channel group Supports isochronous mode no no yes no yes Programmable diagnostics yes yes yes no no Diagnostic interrupt programmable programmable programmable no programmable S7-300 Module data 302 Manual, 06/2017, A5E00105505-AJ Analog modules 6.2 Module overview Properties Module Limit value monitoring programmable for 8 channels programmable for 2 channels no programmable for 2 channels Hardware interrupt programmable when limit exceeded programmable programmable no Programmable Hardware interrupt no at end of cycle yes no No no Potential ratios programmable for 2 channels electrically isolated electrically isolated electrically isolated electrically isolated electrically isolated from: from: from: from: from: * The backplane bus interface * The backplane bus interface * * The backplane bus interface * The backplane bus interface * the CPU * The load voltage (not for 2DMU) The load voltage (not for 2DMU) maximum potential 50 V DC difference between inputs (ICM) 60 V DC 11 V DC 2.0 V DC DC 2.3 V Special features - - Motor protection with PTC and - - silicone temperature sensors Z sign 2-DMU = 2-wire transducer Table 6- 2 Analog input modules (continued) Properties Module SM 331; AI 2 x 12 Bit SM 331; AI 6 x TC SM 331; AI 8 x TC SM 331; AI 8 x RTD SM 331; AI 8 x 0/4...20 mA HART (-7KB02-) (-7PE10-) (-7PF11-) (-7PF01-) (-7TF00-)* Number of inputs 2 inputs in 1 chan- 6 inputs in 1 chan- 8 inputs in 4 chan- 8 inputs in 4 chan- 8 inputs in 1 channel group nel group nel groups nel groups nel group Resolution programmable for each channel group: * 9 bits+sign * 12 bits+sign * 14 bits+sign Measurement type programmable for each channel group: Programmable for each channel group: * 15 bits+sign Programmable for each channel group: * Voltage * Voltage * Current * Temperature * Resistance * Temperature Programmable for each channel group: * 15 bits+sign programmable for each channel group: * Temperature Programmable for each channel group: * 15 bits+sign programmable for each channel group: * Resistance * Temperature programmable for each channel group: 15 bits+sign Programmable for each channel group: * Current S7-300 Module data Manual, 06/2017, A5E00105505-AJ 303 Analog modules 6.2 Module overview Properties Module Measuring range selection any, per channel group any, per channel group any, per channel group any, per channel group any, per channel group Supports isochronous mode Yes No Yes Yes Yes Programmable diagnostics No Yes No No no Diagnostic interrupt programmable Programmable Programmable Programmable Programmable Limit value monitoring programmable for 1 channel Programmable for 6 channels programmable for 8 channels programmable for 8 channels programmable for 8 channels Hardware interrupt Programmable when limit exceeded Programmable Programmable Programmable programmable Hardware interrupt no at end of cycle No Programmable Programmable No Potential ratios electrically isolated electrically isolated electrically isolated electrically isolated electrically isolated from: from: from: from: from: * the CPU * The load voltage (not for 2DMU) * the CPU * of the CPU * the CPU * the CPU * The load voltage (not for 2DMU) maximum potential DC 2.3 V difference between inputs (ICM) 250 V AC - - - Special features Calibration - - - - Z sign 2-DMU = 2-wire transducer * This module is described in the Distributed I/O Device ET 200M HART Analog Modules manual. You can find the manual on the Internet (http://support.automation.siemens.com/WW/view/en/22063748). S7-300 Module data 304 Manual, 06/2017, A5E00105505-AJ Analog modules 6.2 Module overview 6.2.2 Analog output modules Overview of properties The table below shows the analog output modules based on their essential properties Table 6- 3 Analog output modules: Overview of properties Properties Modules SM 332; AO 8 x 12 Bit SM 332; AO 4 x 16 Bit SM 332; AO 4 x 12 Bit SM 332; AO 2 x 12 Bit SM 332; AO 8 x 0/4...20mA HART (-5HF00-) (-7ND02-) (-5HD01-) (-5HB01-) (-8TF00-) * Number of outputs 8 output channels 4 outputs in 4 channel groups 4 output channels 2 output channels 8 output channels Resolution 12 bits 16 bits 12 bits 12 bits 15 bits (0 mA to 20mA) 15 bits +sign (4 mA to 20mA) Output type per channel: per channel: per channel: per channel: per channel: * Voltage * Voltage * Voltage * Voltage * Voltage * Current * Current * Current * Current * Current Supports isochronous mode no yes no no no Programmable diagnostics yes yes yes yes yes Diagnostic interrupt programmable programmable programmable programmable programmable Substitute value output no programmable programmable programmable programmable Potential ratios electrical isolation between: electrical isolation between: electrically isolated from: electrically isolated from: electrically isolated from: Special features * the backplane bus connection * * load voltage * - backplane bus * interface and channel * channels * output and L+, M * CPU and L+, M - - the backplane bus interface load voltage * the back* plane bus interface * load voltage - - * the backplane bus interface load voltage +sign = plus sign * This module is described in the Distributed I/O Device ET 200M HART Analog Modules manual. You can find the manual on the Internet (http://support.automation.siemens.com/WW/view/en/22063748). S7-300 Module data Manual, 06/2017, A5E00105505-AJ 305 Analog modules 6.2 Module overview 6.2.3 Analog I/O modules Overview of properties The table below shows the analog IO modules based on their essential properties Table 6- 4 Analog IO modules: Overview of properties Properties Modules SM 334; AI 4/AO 2 x 8/8 Bit SM 334; AI 4/AO 2 x 12 Bit (-0CE01-) (-0KE00-) 4 inputs in 1 channel group 4 inputs in 2 channel groups Number of outputs 2 outputs in 1 channel group 2 outputs in 1 channel group Resolution 8 bits 12 bits + sign Measurement type programmable for each channel group: programmable for each channel group: Number of inputs Output type * Voltage * Voltage * Current * Resistance * Temperature per channel: * Voltage * Current per channel: * Voltage Supports isochronous mode no no Programmable diagnostics no no Diagnostic interrupt no no Limit value monitoring no no Hardware interrupt when limit is exceeded no no Hardware interrupt at end of cycle no no Substitute value output no no * connected to potential of the backplane bus interface electrically isolated to: * backplane bus interface electrically isolated to load voltage * load voltage Not programmable, measurement and output type defined by hardwiring - Potential ratios * Special features S7-300 Module data 306 Manual, 06/2017, A5E00105505-AJ Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) Order number 6ES7331-7NF00-0AB0 Properties 8 inputs in 4 channel groups Programmable measurement type at each channel group - Voltage - Current Programmable resolution for each channel group (15 bits + sign) Any measuring range per channel group Programmable diagnostics and diagnostic interrupt Programmable limit value monitoring for 2 channels Programmable hardware interrupt when limit is exceeded High-speed update of measured values Electrically isolated to the CPU Supports parameter reassignment in RUN Resolution The resolution of measured values is independent of the selected integration time. Diagnostics For information on diagnostic messages at the "group diagnostics" parameter, refer to the table Diagnostic messages of analog input modules. Hardware interrupts Hardware interrupts for channel groups 0 and 1 can be programmed in STEP 7. However, set a hardware interrupt only for the first channel of a channel group, that is, either at channel 0, or at channel 2 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 307 Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) High-speed update of measured values A high-speed update of measured values at two channels of a channel group is three times compared to the activation of several channel groups. Example: When channels 0 and 1 are active with 2.5 ms filtering, both channels return new measured values to the PLC at intervals of 10 ms. (with other settings, the refresh rate is equivalent to the filter setting.) High-speed update of measured values is only possible if both channels of channel group 0 and 1 are active, that is, the "measuring type" parameter is set. However, only one of the two channel groups 0 or 1 may be active (not concurrently active.) Terminal assignment The diagrams below show various wiring options S7-300 Module data 308 Manual, 06/2017, A5E00105505-AJ Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) Wiring: Voltage and current measurement Wire the voltage inputs of the channel voltage in parallel using the corresponding shunt resistor when measuring current. Bridge the channel input terminals with the adjacent connector terminals. Example: You configure channel 0 for current measurement by bridging terminals 22 and 2, and terminals 23 to 3. At the channel configured for current measurements, connect the shunt resistor to the adjacent channel terminals in order to achieve the specified precision. Voltage measurement Backplane bus interface Electrical isolation Analog-to-Digital Converter (ADC) Equipotential bonding Figure 6-1 Wiring and block diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 309 Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) Wiring: 2-wire and 4-wire transducers Backplane bus interface Electrical isolation Analog-to-Digital Converter (ADC) Channel 0 for 4-wire transducer Channel 7 for 2-wire transducer (with external supply) Equipotential bonding Figure 6-2 Wiring and block diagram S7-300 Module data 310 Manual, 06/2017, A5E00105505-AJ Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 272 g Module-specific data Supports parameter reassignment in RUN Yes Response of non-configured inputs Return the process value which was valid before configuration Supports isochronous mode no Number of inputs 8 Cable length * shielded max. 200 m Voltages, currents, electrical potentials Electrical isolation * between channels and the backplane bus yes Maximum potential difference * between inputs (CMV) Isolation test voltage 35 V AC / 50 V DC, 500 V DC Current consumption * from the backplane bus Power loss of the module max. 130 mA typ. 0.6 W Generation of analog values Measuring principle Integrating Integration/conversion time/resolution (per channel) * programmable yes * Integration time in ms 10 16.7 20 100 * Basic conversion time for each group with more than one active channel 35 55 65 305 * Channel conversion time for each group, only with active channel group 0 or 1 10 16.7 20 100 10 16.7 20 100 60 50 10 220 260 1220 Channel integration time (1/f1) in ms * Resolution (including overshoot range) 15 bits + sign * Interference frequency suppression at interference frequency f1 in Hz 100 Basic execution time of the module in ms (all channels enabled) 140 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 311 Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) Technical specifications Interference frequency suppression and error limits Interference frequency suppression at f = n (f1 1%), (f1 = interference frequency); n= 1, 2, ... * * Common mode interference (CMV < 50 V) > 100 dB Series mode interference (peak value of interference < rated > 90 dB input range) Crosstalk between inputs > 100 dB Operational limit (across entire temperature range, relative to measurement range end value in the selected input range) CMV = 0 / CMV = 50 V * Voltage input * Current input 0.1% / 0.7% 0.3% / 0.9% Basic error limit (operational limit at 25 C, relative to measurement range end value in the selected input range) * * Voltage input Current input 0.05% 0.05% Temperature error (relative to input range) 0.005%/K Linearity error (relative to input range) 0.03% Repeat accuracy (in transient state at 25 C, relative to input range) 0.025% Status, interrupts, diagnostics Interrupts * * Limit interrupt programmable Diagnostic interrupt programmable Diagnostic functions * Group error display * Reading diagnostic information Channels 0 and 2 programmable red LED (SF) supported Encoder selection data Input ranges (rated values) / input impedance * * Voltage 5V / 2 M 1 V to 5 V / 2 M 10 V / 2 M Current 0 mA to 20 mA / 250 20 mA / 250 4 mA to 20 mA / 250 Maximum voltage at voltage input (destruction limit) max. 50 V, continuous Maximum current at current input (destruction limit) max. 32 mA Wiring of the signal transmitters using a 40pin front connector * for voltage measurement * for current measurement - as 2-wire transducer - as 4-wire transducer supported possible, with separate transducer supply supported S7-300 Module data 312 Manual, 06/2017, A5E00105505-AJ Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) Parameter reassignment in RUN If you reassign parameters in RUN, the following special characteristic applies. SF LED is lit: If a diagnostics was pending prior to reconfiguration, the SF LEDs (on CPU, IM or module) may be lit even though diagnostics are no longer pending and the module is operating correctly. Solution: Only assign new parameters if no diagnostics is pending, or unplug module and plug it in again. 6.3.1 Measurement types and ranges Introduction The measurement type and range is configured at the "measuring range" parameter in STEP 7. The default setting of the module is "voltage" measurement with " 10V" range. You can use these default settings without having to program the SM 331; AI 8 x 16 Bit in STEP 7. Measurement types and ranges Table 6- 5 Measurement types and ranges Selected type of measurement Measuring range Voltage V: 5V 1 V to 5 V 10 V Current 0 mA to 20 mA 20 mA 4 mA to 20 mA S7-300 Module data Manual, 06/2017, A5E00105505-AJ 313 Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) 6.3.2 Programmable parameters Introduction For information on programming analog modules, refer to the chapter Programming analog modules (Page 294). Parameters Table 6- 6 Overview of the parameters of SM 331; AI 8 x 16 Bit Parameters Range of values Default Parameter type Scope yes/no no dynamic Module yes/no no - dynamic Channel yes/no no static yes/no no Channel group disabled V dynamic Channel group Enable * * Diagnostic interrupt Hardware interrupt when limit exceeded Hardware interrupt trigger * * May be restricted by the measuring range. from 32511 to - 32512 High limit from - 32512 to 32511 Low limit Diagnostics * * Group diagnostics with line continuity check Measurement * Measurement type Voltage V: 4DMU current (4-wire transducer) * Measuring range See the table Measurement types and ranges 10 V * Noise suppression 100 Hz; 60 Hz; 50 Hz; 10 Hz 50 Hz Channel groups The channels of SM 331; AI 8 x 16 Bit are arranged in four groups of two channels. You can assign parameters only to one channel group. S7-300 Module data 314 Manual, 06/2017, A5E00105505-AJ Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) The table below shows the relevant configuration of channel groups. The channel group number is required to program SFC parameters in the user program. Table 6- 7 Assignment of SM 331; AI 8 x 16 Bit channels to channel groups Channels ... ... form one channel group each Channel 0 Channel group 0 Channel 1 Channel 2 Channel group 1 Channel 3 Channel 4 Channel group 2 Channel 5 Channel 6 Channel group 3 Channel 7 See also Diagnostics messages of analog input modules (Page 296) 6.3.3 Additional information on SM 331; AI 8 x 16 Bit Unused channels Set the "disabled" value at the "measuring type" parameter for unused channels. This setting reduces module cycle times. As certain programmed inputs may remain unused due to the channel group configuration, make allowances for the special features of those inputs outlined below in order to be able to use the diagnostic functions at these used channels: Measuring range 1 V to 5 V: wire the used input and unused input of the same channel group in parallel. Current measurement, 4 mA to 20 mA: wire the used input and unused input of the same channel group in series. Connect a shunt resistor to each programmed and unused channel. Other measuring ranges:Short-circuit the plus and minus inputs of the channel. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 315 Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) Line continuity check The line continuity check is available for the 1 V to 5 V and 4 mA to 20 mA ranges. Rule for both measuring ranges: When the line continuity check is enabled, the module logs the wire-break to diagnostics data when the current drops below 3.6 mA (0.9 V.) The module also triggers a diagnostic interrupt if this function is enabled in the program. A wire break can only be signaled by means of the lit SF LED and the diagnostic bytes must be evaluated in the user program if diagnostic interrupts are disabled. When line continuity check is disabled and diagnostic interrupts are enabled, the module triggers a diagnostic interrupt when underflow is detected. Special features in programming high and low limits The programmable limits (hardware interrupt triggers) of SM 331; AI 8 x 16 Bit differ from the range of value shown in the Overview of parameters of SM 331; AI 8 x 16 Bit. table. Reason: The calculation methods deployed in the module software to evaluate the process variables do not allow the reporting of values up to 32511 in certain situations. The process value triggering a hardware interrupt at underflow or overflow limits is based on the calibration factors of the relevant channel, and may vary between the low limits shown in the table below and the value 32511 (7EFFH). You may not define any limits which exceed the minimum limits specified in the table below. Table 6- 8 Minimum high and low limits of SM 331; AI 8 x 16 Bit Measuring range Minimum high limit Minimum low limit 10 V 11.368 V 31430 7AC6H -11.369 V -31433 8537H 5V 5.684 V 31430 7AC6H -5.684 V -31430 853AH 1 V to 5 V 5.684 V 32376 7E78H 0.296 V -4864 ED00H 0 mA to 20 mA 22.737 mA 31432 7AC8H -3.519 mA -4864 ED00H 4 mA to 20 mA 22.737 mA 32378 7E7AH 1.185 mA -4864 ED00H 20 mA 22.737 mA 31432 7AC8H -22.737 mA -31432 8538H S7-300 Module data 316 Manual, 06/2017, A5E00105505-AJ Analog modules 6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0) Measuring errors as a result of CMV SM 331; AI 8 x 16 Bit is capable of taking measurements, irrespective of the presence of any CMV in the AC or DC range. With AC CMV values of a multiple of filter frequency settings, noise is suppressed as a result of ADC integration time and common mode suppression at the input amplifiers. With AC CMV < 35 VRMS, the noise suppression of > 100 dB results in negligible measurement errors. The influence of DC CMV can only be reduced to minimum using the noise suppression function of the input amplifier unit. A certain degradation of measuring accuracy in proportion to CMV must be expected. The worst case error is generated at 50 VDC between one channel and the remaining seven channels. The calculated worst case error is 0.7% at 0 C to 60 C, while the measured error usually lies at 0.1% at 25 C. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 317 Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) Order number 6ES7331-7NF10-0AB0 Properties 8 inputs in 4 channel groups Programmable measurement type at each channel group - Voltage - Current Programmable resolution for each channel group (15 bits + sign) Any measuring range selection per channel group Programmable diagnostics and diagnostic interrupt Programmable limit value monitoring for 8 channels Programmable hardware interrupt when limit is exceeded Programmable hardware interrupt at end of cycle High-speed update of measured values at up to 4 channels Electrical isolation to the CPU Supports parameter reassignment in RUN Diagnostics For information on diagnostic messages at the "group diagnostics" parameter, refer to the table Diagnostic messages of analog input modules. Terminal assignment The diagrams below show various wiring options S7-300 Module data 318 Manual, 06/2017, A5E00105505-AJ Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) Wiring: Voltage and current measurement Connection possible at both sides to channels 0 to 7 Connection for voltage measurement Equipotential bonding Figure 6-3 Wiring and block diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 319 Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) Wiring: 2-wire and 4-wire transducer Connection possible at both sides to channels 0 to 7 2-wire transducer 4-wire transducer Equipotential bonding Figure 6-4 Wiring and block diagram Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 272 g Module-specific data Supports parameter reassignment in RUN Yes Response of non-programmed inputs Return the process value which was valid before configuration Supports isochronous mode no Number of inputs 8 Cable length * shielded max. 200 m S7-300 Module data 320 Manual, 06/2017, A5E00105505-AJ Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) Technical specifications Voltages, currents, electrical potentials Rated electronics supply voltage L + * Reverse polarity protection 24 V DC yes Electrical isolation * between channels and the backplane bus * between channels and electronics power supply yes yes * between channels in groups of yes Isolation test voltage 500 V AC 2 Current consumption * * from the backplane bus from supply voltage L+ Power loss of the module max. 100 mA max. 200 mA typ. 3.0 W Generation of analog values Measuring principle Integrating Integration/conversion time/resolution (per channel) * programmable * Basic conversion time in ms (8-channel mode) * Basic conversion time in ms (4-channel mode) * Resolution, including sign * Interference frequency suppression at frequency f1 in Hz yes 95/83/72/23 101) 4) 16 bits All2)/50/60/400 Measured value smoothing None / low/ average/ high Basic execution time of the module, in ms (8-channel-mode) 190/166/144//46 Basic execution time of the module, in ms (4-channel-mode) 101) Interference frequency suppression, error limits Interference frequency suppression at F = n x (f1 1%)(f1 = interference frequency, n = 1, 2, ...) * Common mode interference (VCM < AC 60 V) * Series mode interference (peak value of disturbance < rated input range) Crosstalk between inputs > 100 dB > 90 dB 3) > 100 dB Operational limit (across entire temperature range, relative to the measurement range end value in the selected input range) * Input voltage * Input current 0.1% 0.1% Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected input range) * Voltage input * Current input 0.05% 0.05% Temperature error (relative to input range) 0.005%/K Linearity error (relative to input range) 0.01% Repeat accuracy (in settled state at 25 C, relative to measurement range end value in the input range) 0.01% S7-300 Module data Manual, 06/2017, A5E00105505-AJ 321 Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) Technical specifications Status, interrupts, diagnostics Interrupts * Hardware interrupt when limit value is exceeded * Hardware interrupt at end of cycle * Diagnostic interrupt Diagnostic functions * Group error display * Reading diagnostic information Programmable channels 0 to 7 programmable programmable programmable red LED (SF) supported Encoder selection data Input range (rated values) / input impedance * Voltage 5 V / 2 M 1 V to 5 V / 2 M 10 V / 2 M * Current 0 mA to 20 mA / 250 4 mA to 20 mA / 250 20 mA / 250 Maximum voltage at voltage input (destruction limit) 35 V continuous; 75 V for max. duration of 1 s (duty factor 1:20) Maximum current at current input (destruction limit) 40 mA Wiring of the signal transmitters using a 40pin front connector for voltage measurement * * for current measurement as 2-wire transducer supported possible, with separate transducer supply supported as 4-wire transducer 1) Interference frequency for 4-channel mode is "All" 2) Interference frequencies 50/60/400 Hz are designated as "All" The series mode rejection in 8-channel mode is reduced as follows: 50 Hz > 70 db 60 Hz > 70 db 400 Hz > 80 dB 50/60/400 Hz > 90 dB 3) In 4-channel mode, the converted value settles to 100% within 80 ms. The value determined in this process is returned at intervals of max. 10 ms. 4) S7-300 Module data 322 Manual, 06/2017, A5E00105505-AJ Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) Reassigning parameters in RUN If you reassign parameters in RUN, the following special characteristic applies. SF LED is lit: If a diagnostics was pending prior to reconfiguration, the SF LEDs (on CPU, IM or module) may be lit even though diagnostics is no longer pending and the module is operating correctly. Solution: Only assign new parameters if no diagnostics is pending, or unplug module and plug it in again. 6.4.1 Measurement types and measuring ranges Introduction The measurement type and range is configured at the "measuring type" parameter in STEP 7. Table 6- 9 Measurement types and ranges Selected type of measurement Output range Voltage V: 5 V, from 1 V to 5 V, 10 V Current (4-wire transducer) 0 mA to 20 mA 4 mA to 20 mA 20 mA 4DMU Channel groups The channels of SM 331; AI 8 x 16 bits are arranged in four groups of two channels. You always assign parameters to a group. The interrupt limits form the exception. The table below shows the relevant configuration of channel groups. The channel group number is required to program SFC parameters in the user program. Table 6- 10 Assignment of SM 331; AI 8 x 16 Bit channels to channel groups Channels ... ...form one channel group each Channel 0 Channel group 0 Channel 1 Channel 2 Channel group 1 Channel 3 Channel 4 Channel group 2 Channel 5 Channel 6 Channel group 3 Channel 7 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 323 Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) 6.4.2 Programmable parameters Introduction For information on programming analog modules, refer to the chapter Programming analog modules (Page 294). Parameter Table 6- 11 Overview of parameters of SM 331; AI 8 x 16 Bit Parameters Enable * * * Range of values Defaults Parameter type Scope no dynamic Module no no dynamic dynamic 32511 to -32512 -32512 to 32511 - dynamic dynamic Channel Channel yes/no yes/no no no static Channel Channel yes no dynamic Module Channel group dynamic Channel group dynamic Channel group Process interrupt when limit value yes/no is exceeded yes/no Process interrupt at end of cycle yes/no Diagnostics interrupt Process interrupt trigger * High limit * Low limit Diagnostics * Group diagnostics * Line continuity check Measurement * Module operating mode * Noise suppression * * Smoothing Measurement type disabled Voltage Current (4-wire transducer) * 8 channels * 4 channels 50 Hz 60 Hz 400 Hz 50/60/400 Hz * none * weak * medium * strong * Measuring range: * 5V * 1 V to 5 V * 10 V * 0 mA to 20 mA * 4 mA to 20 mA * 20 mA 50/60/400 Hz none 10 V 4 mA to 20 mA See also Diagnostics messages of analog input modules (Page 296) Programming analog modules (Page 294) S7-300 Module data 324 Manual, 06/2017, A5E00105505-AJ Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) 6.4.3 Additional information for SM 331; AI 8 x 16 Bit Modes of operation Operating modes of SM 331; AI 8 x 16 Bit: 8-channel mode 4-channel mode 8-channel operating mode In this mode, the module changes between the two channels of each group. Since the module contains four analog/digital converters (ADC), all four ADCs convert simultaneously for channels 0, 2, 4 and 6. After converting the channels with the even numbers, all ADCs simultaneously convert for the channels with the odd numbers 1, 3, 5 and 7 (see the figure below). Figure 6-5 8-channel mode cycle time S7-300 Module data Manual, 06/2017, A5E00105505-AJ 325 Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) Cycle time of module in 8-channel mode The channel conversion time is based on the programmed noise suppression. The channel conversion time is 76 ms, including communication time, at a set interference frequency of 50 Hz. The channel conversion time is 65 ms when you set an interference frequency of 60 Hz. You can reduce channel conversion times to 16 ms by setting an interference frequency of 400 Hz. When you set 50, 60 and 400 Hz , the channel conversion time amounts to 88 ms. The module then has to switch to a different channel of the group by means of the OptoMOS relay. Opto-MOS relays require 7 ms for switching and settling. The following table shows this relationship. Table 6- 12 Cycle times in 8-channel mode Interference frequency (Hz) Channel cycle time (ms) Module cycle time (all channels) 50 83 166 60 72 144 400 23 46 50/60/400 95 190 4-channel operating mode In this mode, the module does not change between the channels of the groups. The four ADCs of the module simultaneously convert the channels 0, 2, 4 and 6. Figure 6-6 4-channel mode cycle time Module cycle time The converted value settles to 100% within 80 ms and is updated every 10 ms when 4channel mode is set. The channel and module cycle times are always identical, because the module does not change between the channels of a group: 10 ms. Channel conversion time = channel cycle time = module cycle time = 10 ms S7-300 Module data 326 Manual, 06/2017, A5E00105505-AJ Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) Unused channels Set the "disabled" value at the "measuring method" parameter for unused channels. This setting reduces module cycle times. As certain programmed inputs may remain unused due to the channel group configuration in 8-channel mode, make allowances for the special features of these inputs outlined below to activate the diagnostics functions at the channels being used: Measuring range 1 V to 5 V: wire the used input and unused input of the same channel group in parallel. Current measurement, 4 to 20 mA: Connect unused input in series to the input of the same channel group. A shunt resistor must be connected for each programmed and unused channel. Other measuring ranges: Short-circuit the plus and minus inputs of the channel. Line continuity check The wire break test is available for the voltage measuring range 1 to 5 V and the current measuring range 4 to 20 mA. When there is a configured measuring range of 1 to 5 V or 4 to 20 mA and the wire break test is activated, the analog input module reports a wire break in the diagnostics when underflow (-32768) is reached. The module also triggers a diagnostic interrupt if this function is enabled in the program. A wire break can only be signaled by means of the lit SF LED and the diagnostic bytes must be evaluated in the user program if diagnostic interrupts are disabled. Under the following circumstances, wire-break detection can take up to 2 s: If a wire break occurs during voltage measurement. If a wire break occurs on the front-connector jumpers from shunt (250 ) to the inputs during current measurement. The measured value can go through the entire valid value range during the wire break detection. When there are configured measuring ranges 10 V, 5 V, 1 to 5 V or 4 to 20 mA, the wire break test is not activated and a diagnostic interrupt is enabled, the module triggers a diagnostic interrupt when the underflow is reached. The module detect the underflow when the input signal is below 0.296 V or 1.185 mA. Overflow, underflow and hardware interrupt limits The limits in diagnostics response to overflow and underflow in certain measuring ranges differ compared to the listed ranges starting at the chapterAnalog value representation for analog input channels of the manual. In certain situations the numerical methods of the module software used to evaluate the process variables do not return values up to 32511. Do not set any hardware interrupt limits higher than the lowest possible overflow or underflow response limits. End of cycle interrupt starting at the chapter Analog value representation for analog input channels. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 327 Analog modules 6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0) End of cycle interrupt You can synchronize a process with the conversion cycle of the module by enabling the end of cycle interrupt. The interrupt is set when enabled channels have been converted. The table below shows the contents of the 4 bytes of additional OB40 information during process or end of cycle interrupts. Content of the 4 bytes of additional information 27 26 25 24 23 Special analog flags High limit exceeded at channel 7 6 Low limit exceeded at channel 7 6 22 5 4 3 2 5 4 3 2 21 20 Byte 1 0 0 1 0 1 2 bits per channel to identify the range End of cycle event X 2 Free bit 3 Operation of the module on the ET 200M Distributed IO devices Operation of SM 331; AI 8 x 16 Bit on ET 200M requires one of the following IM 153 x: IM 153-1; as of 6ES7153-1AA03-0XB0, E 01 IM 153-2; as of 6ES7153-2AA02-0XB0; E 05 IM 153-2; as of 6ES7153-2AB01-0XB0; E 04 Programming restrictions when operating SM 331; AI 8 x 16 Bit on PROFIBUS masters which only support DPV0 Certain parameters are not supported when operating an electrically isolated SM 331; AI 8 16 Bit analog input module on an ET200M PROFIBUS slave system in combination with a PROFIBUS master which is not an S7 master. Non-S7 masters do not support hardware interrupts. All parameters associated with these functions are disabled for this reason. This includes hardware interrupt enable, hardware restrictions and end the enabling of cycle interrupts. All other parameters are allowed. S7-300 Module data 328 Manual, 06/2017, A5E00105505-AJ Analog modules 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) Order number 6ES7331-7HF00-0AB0 or 6ES7331-7HF01-0AB0 Properties 8 inputs in 4 channel groups Measurement type programmable for each channel group: - Voltage - Current Programmable resolution for each group (13 bits + sign) Any measuring range per channel group Programmable diagnostics and diagnostic interrupt Programmable limit value monitoring for 2 channels Programmable hardware interrupt when limit is exceeded High-speed update of measured values Supports isochronous mode Electrical isolation from the CPU Electrically isolated from load voltage (not for 2-wire transducers) Diagnostics For information on diagnostics messages at the "group diagnostics" parameter, refer to chapter Diagnostic messages of analog input modules (Page 296). Hardware interrupts Hardware interrupts for channel groups 0 and 1 can be programmed in STEP 7. However, set a hardware interrupt only for the first channel of a channel group, that is, either at channel 0, or at channel 2 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 329 Analog modules 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) Terminal assignment The diagrams below show the various wiring options. Wiring: Voltage measurement Figure 6-7 Block diagram and wiring diagram Measuring range module settings Measuring range Measuring range module setting 1V A 5V B 10V B (Default) 1 V to 5V B S7-300 Module data 330 Manual, 06/2017, A5E00105505-AJ Analog modules 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) Wiring: 2-wire and 4-wire transducers for current measurement Figure 6-8 Block diagram and wiring diagram Measuring range module settings Measuring range Measuring range module setting 2-wire transducer 4 mA to 20mA 4-wire transducer 20mA 0 mA to 20mA D C 4 mA to 20mA S7-300 Module data Manual, 06/2017, A5E00105505-AJ 331 Analog modules 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 230 g Module-specific data Supports isochronous mode yes Number of inputs 8 Cable length * shielded max. 200 m Voltages, currents, electrical potentials Rated electronics supply voltage L + * Reverse polarity protection 24 V DC yes Transducer power supply * Supply current * short circuit-proof max. 30 mA (per channel) yes Electrical isolation * between channels and the backplane bus * between channels * between channels and electronics power supply yes no yes Maximum potential difference * * between inputs and MANA (CMV) - at signal = 0 V - not for 2-wire transducers between inputs (CMV) 11 V DC / 8 V AC 11 V DC / 8 V AC Isolation test voltage * Channels to backplane bus and load voltage L + 500 V DC Current consumption * from the backplane bus * from load voltage L + (without 2-wire transducer) Power loss of the module max. 100 mA max. 50 mA typ. 1.5 W S7-300 Module data 332 Manual, 06/2017, A5E00105505-AJ Analog modules 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) Technical specifications Generation of analog values Measuring principle Actual value conversion Integration/conversion time/resolution (per channel) * programmable yes * Basic conversion time per channel 52 s * Resolution (including overshoot range) 14 bits * Interference frequency suppression at interference frequency f1 in Hz none 400 60 50 * Basic execution time of the module (independent of the number of enabled channels) 0.42 ms 2.5 ms 16.7 ms 20 ms Interference frequency suppression, error limits Interference frequency suppression at f = n (f1 1 %), (f1 = interference frequency) n=1.2... * Common mode interference (CMV < 11 Vpp) * Series-mode interference (peak value < rated input range) Crosstalk between inputs > 80 dB > 40 dB > 65 dB Operational limit (across entire temperature range, relative to measurement range end value in the selected input range) * * Voltage input Current input 1V 0.3 % 5V 0.4 % 10 V 0.3 % 1 V to 5 V 0.4 % 20 mA 0.3 % 0 mA to 20 mA 0.3 % 4 mA to 20 mA 0.3 % Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected input range) * * Voltage input Current input 1V 0.2 % 5V 0.25 % 10 V 0.2 % 1 V to 5 V 0.25 % 20 mA 0.2 % 0 mA to 20 mA 0.2 % 4 mA to 20 mA 0.2 % Temperature error (relative to input range) 0.004 %/K Linearity error (relative to input range) 0.03 % Repeat accuracy (in settled state at 25 C, relative to input range) 0.1 % S7-300 Module data Manual, 06/2017, A5E00105505-AJ 333 Analog modules 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) Technical specifications Status, interrupts, diagnostics Interrupts * Hardware interrupt * Diagnostic interrupt programmable programmable Diagnostic functions * Group error display * Reading diagnostics information red LED (SF) supported Encoder selection data Input ranges (rated values) / input impedance * * Voltage Current Maximum voltage at voltage input (destruction limit) 1V 10 M 5V 100 k 10 V 100 k 1 V to 5 V 100 k 20 mA 50 0 mA to 20 mA 50 4 mA to 20 mA 50 max. 20 V continuous; 75 V for the duration of max. 1 s (duty factor 1:20) Maximum current at current input (destruction limit) 40 mA Wiring of the signal transmitters using a 20-pin front connector for voltage measurement supported * for current measurement as 2-wire transducer supported * as 4-wire transducer * Load of the 2-wire transducer at L+ = DC 24 V Characteristics linearization 6.5.1 supported max. 820 none Measurement types and measuring ranges Introduction The analog input module has measuring range modules. The measurement type and range is configured at the "measuring range" parameter in STEP 7. The default setting of the module STEP 7 is "voltage" measurement with " 10V" range. You can use those default settings without having to program the SM 331; AI 8 x 14 Bit High Speed in STEP 7. S7-300 Module data 334 Manual, 06/2017, A5E00105505-AJ Analog modules 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) Measuring range modules You may have to change the position of the measuring range module to suit the measurement type and range. See table Setting measuring methods and ranges of analog input channels. The settings are also printed on the module. Mark the position of the measuring range module on the front door (see figure). Measurement types and measuring ranges Table 6- 13 Measurement types and ranges Selected type of measurement Measuring range (type of sensor) Measuring range module settings V: Voltage 1V A 5V B 1 V to 5 V 10 V 4DMU: Current (4-wire transducer) 0 mA to 20 mA C 4 mA to 20 mA 20 mA 2DMU: Current (2-wire transducer) 4 mA to 20 mA D Channel groups The channels of SM 331; AI 8 x 14 Bit High Speed are arranged in four groups of two channels. You can assign parameters only to one channel group. SM 331; AI 8 x 14 bits High Speed is equipped with one measuring range module per channel group. The table below shows the relevant configuration of channel groups. The channel group number is required to program SFC parameters in the user program. Table 6- 14 Assignment of SM 331; AI 8 x 14 bits High Speed channels to channel groups Channels ... ... form one channel group each Channel 0 Channel group 0 Channel 1 Channel 2 Channel group 1 Channel 3 Channel 4 Channel group 2 Channel 5 Channel 6 Channel group 3 Channel 7 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 335 Analog modules 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) 6.5.2 Programmable parameters Introduction For information on programming analog modules, refer to the chapter Programming analog modules (Page 294). Parameter Table 6- 15 Overview of parameters for SM 331; AI 8 x 14 Bit High Speed Parameters Range of values Default Parameter type Scope yes/no no dynamic Module yes/no no Fast Mode (can only be set if the yes/no 331-7HF01 is included for isochronous operation in the DP slave properties) no static Module - dynamic Channel yes/no no static Channel group disabled V dynamic Channel or channel group Enable * * Diagnostics interrupt Process interrupt when limit exceeded Process interrupt trigger * * High limit Low limit May be restricted by the measuring range. from 32511 to - 32512 from - 32512 to 32511 Diagnostics * Group diagnostics Measurement * Measurement type Voltage V 4DMU current (4-wire transducer) 2DMU current (2-wire transducer) * Measuring range See the table Measurement types and * Noise suppression none; 400 Hz; 60 Hz; 50 Hz ranges 10 V 50 Hz S7-300 Module data 336 Manual, 06/2017, A5E00105505-AJ Analog modules 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) 6.5.3 Isochronous mode Properties Reproducible reaction times (i.e. of the same length) are achieved in a SIMATIC system by means of a constant DP bus cycle, and synchronization of the single cyclic processes outlined below: Independent user program cycle. The length of the cycle time may vary due to non-cyclic program branching. Independent and variable DP cycle on the PROFIBUS subnet Cyclic operation of the backplane bus of the DP slave. Cyclic signal preparation and conversion at the electronic modules of the DP slave. The constant DP cycle runs in synchronism and at the same length. The CPU run levels (OB61 to OB64) and isochronous IO are synchronized with this cycle. I/O data are therefore transferred at defined and constant intervals (isochronous mode.) Requirements The DP master and slave must support isochronous mode. You require STEP 7 V5.2 or higher. Mode of operation: Isochronous mode Table 6- 16 Conditions of isochronous mode: Standard Mode Filtering and processing time TWE between reading actual values and writing these to the transfer buffer(the value defined for TWE applies, irrespective of the enable status of diagnostics) max. 625 s including an input delay time of 10 s TDPmin 3.5 ms Diagnostics interrupt max. 4 x TDP Fast Mode (only possible with 6ES7331-7HF01-0AB0) Filter and processing time TWE between reading actual value and writing the results to the transfer buffer (diagnosis not selectable) max. 625 s including an input delay time of 10 s TDPmin 1 ms Note You can accelerate the cycle of your DP system by setting "Fast Mode." However, this is at the expense of diagnostics: Diagnostics functions will be disabled in this operating mode. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 337 Analog modules 6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0) The minimum Ti value of 875 s which you can set in HW Config is derived from the defined TWE value plus calculation and transfer times required by the IM 153. The specified TDPmin value is determined by the size of the DP slave/IM 153 configuration: Of the diverse installed modules, the slowest always determines the time TDPmin. Note When operated in "isochronous" mode, the modules automatically sets "Integration time: none/interference frequency", irrespective of parameter settings in STEP 7. none / interference frequency". "Process interrupt" functionality is not available in "isochronous" mode. Calculation of filter and processing times The same time conditions always apply, regardless of the number of configured channels. The time relative to the clock signal for reading a specific channel is calculated according to the formula: TWE_CH = (channel number +1) x 52 s + tv; tv = 119 to 209 s Figure 6-9 Calculation of filter and processing times Definition of isochronous mode The module starts with the analog-to-digital conversion of channel 7, and saves the result internally. Next, it converts channels 6...0 sequentially at intervals of 52 ms and in the same way. After an additional internal processing time, it outputs the result of all converted channels to the backplane bus interface where it can be fetched by the CPU. Further information You can find additional information on isochronous mode in the online help for STEP 7, and in the operating instructions Distributed I/O System ET 200M (http://support.automation.siemens.com/WW/view/en/1142798). S7-300 Module data 338 Manual, 06/2017, A5E00105505-AJ Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) 6.5.4 Additional information on SM 331; AI 8 x 14 Bit High Speed, isochrone Unused channels You should wire unused channels as shown in the following table. This optimizes interference immunity of the analog input module. Measuring range M+/ M- M_ana Voltage short-circuit connect with M- Current / 4-wire transducer leave open connect with M- Current / 2-wire transducer leave open connect with M As certain programmed inputs may remain unused due to the channel group configuration, make allowances for the special features of these inputs outlined below in order to be able to use the diagnostics functions at these used channels: Measuring range 1 V to 5 V: wire the used input and unused input of the same channel group in parallel. Current measurement, 2-wire transducer: There are two options of wiring the channel circuit. a) Open unused inputs; channel group diagnostics disabled. If you were to enable diagnostics, the analog module would trigger a single diagnostic interrupt, and light up its SF LED. b) Loading the unused input using a 1.5 k to 3.3 k resistor. This allows you to enable diagnostics for this channel group. Current measurement 4 mA to 20 mA, 4-wire transducer: wire the used input and unused input of the same channel group in series. Line continuity check for the 4 mA to 20 mA measuring range If you configured a measuring range of 4 mA to 20 mA, and enabled the line continuity check, the analog input module logs a wire-break event to diagnostics data when the current drops below 1.185 mA. The module also triggers a diagnostics interrupt if this function is enabled in the program. A wire break can only be signaled by means of the lit SF LED and the diagnostic bytes must be evaluated in the user program if diagnostics interrupts are disabled. If you configured a measuring range of 4 mA to 20 mA, disabled the line continuity check, and enabled diagnostic interrupts, the module triggers a diagnostic interrupt when the underflow value is reached. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 339 Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Order number 6ES7331-1KF02-0AB0 Properties 8 inputs in 8 channel groups Programmable resolution for each group (12 bits + sign) Measurement type programmable for each channel group: - Voltage - Current - Resistance - Temperature Any measuring range per channel Motor protection / temperature monitoring with PTC in accordance with IEC 60034-11-2 type A Temperatures recorded via KTY83/110, KTY84/130 silicon temperature sensors Terminal assignment The diagrams below show various wiring options. These examples apply to all channels (channel 0 to 7). Note When connecting voltage and current transducers, make sure that the maximum permitted common-mode voltage CMV of 2 V is not exceeded between the inputs. Prevent measuring errors by interconnecting the corresponding M- terminals. S7-300 Module data 340 Manual, 06/2017, A5E00105505-AJ Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Wiring: Voltage measurement Voltage measurement: ( 5V, 10V, 1 ... 5V, 0...10V) Voltage measurement ( 50 mV, 500 mV, 1 V) (note the input resistance defined in the technical data) Equipotential bonding Internal supply + 5 V from backplane bus Logic and backplane bus interface Electrical isolation Multiplexer Analog to Digital Converter (ADC) Current source Figure 6-10 Block diagram and terminal diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 341 Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Wiring: 2-wire and 4-wire transducers for current measurement 4-wire transducer (0/4 mA to 20 mA or 20 mA) 2-wire transducer (4 mA to 20 mA) Equipotential bonding Internal supply + 5 V from backplane bus Logic and backplane bus interface Electrical isolation Multiplexer Analog to Digital Converter (ADC) Current source Figure 6-11 Block diagram and wiring diagram S7-300 Module data 342 Manual, 06/2017, A5E00105505-AJ Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Wiring: Resistance measurement with 2-, 3- and 4-wire connection The following connection possibilities also apply to silicon temperature sensors and PTCs. 2-wire connection. Insert a bridge between M and S (no line resistance compensation). 3-wire connection 4-wire connection. The fourth line may not be wired (remains unused) 4-wire connection. The fourth line is routed to the terminal strip in the cabinet but is not wired. Internal supply + 5 V from backplane bus Logic and backplane bus interface Electrical isolation Multiplexer Analog to Digital Converter (ADC) Current source Figure 6-12 Block diagram and terminal diagram Note It is not necessary to interconnect the M- terminals when measuring using resistors, resistance thermometers, PTCs, or silicon temperature sensors. However, interconnection of the M- terminals may enhance interference immunity. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 343 Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 250 g Module-specific data Supports isochronous mode no Number of inputs 8 * with resistive transducers 8 Cable length * shielded max. 200 m max. 50 m at 50 mV Voltages, currents, electrical potentials Constant current for resistive transducers * Resistance thermometer and resistance measurements 0 to 600 0.83 mA (pulsed) * Resistance measurement 0 to 6 k, PTC, silicon temperature sensors 0.25 mA (pulsed) Electrical isolation * between channels and the backplane bus * between channels yes no Maximum potential difference * between inputs (CMV) Isolation test voltage 2.0 V DC 500 V DC Current consumption * from the backplane bus Power loss of the module max. 90 mA typ. 0.4 W Generation of analog values Measuring principle Integrating Integration/conversion time/resolution (per channel) yes * programmable * Interference frequency suppression at interference frequency 50 f1 in Hz 60 * Integration time in ms 60 50 * Basic conversion time, including the integration time in ms 66 55 Additional conversion time for resistance measurements in ms 66 55 13 bits 13 bits * Resolution in bits (including overshoot range) S7-300 Module data 344 Manual, 06/2017, A5E00105505-AJ Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Technical specifications Interference frequency suppression, error limits Interference frequency suppression at f = n (f1 1 %), (f1 = interference frequency) n=1.2 * Common mode interference (VCM < 2 V) * Seriesmode interference (peak value < rated input range) Crosstalk between inputs > 86 dB > 40 dB > 50 dB Operational limit (across entire temperature range, relative to the measurement range end value in the selected input range) * Voltage input 5V 0.6 % 10 V 0.5 % 1 V to 5 V 0 V to 10 V 50 mV 500 mV 1 V * Current input 20 mA 0.5 % 0 mA to 20 mA 4 mA to 20 mA * * Resistor/PTC Resistance thermometer/silicon temperature sensors 0 k to 6 k 0.5 % 0 to 600 0.5 % PTC 0.5 % Pt 100 1.2 K Ni 100 Standard Pt 100 1K Ni 100 Klima Ni 1000, 1K LG-Ni 1000 Standard Ni 1000 1K LG-Ni 1000 Klima KTY83/110 3.5 K KTY84/130 4.5 K S7-300 Module data Manual, 06/2017, A5E00105505-AJ 345 Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Technical specifications Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected input range) * Voltage input 5V 0.4 % 10 V 1 V to 5 V 0 V to 10 V 0.3 % 50 mV 500 mV 1V * Current input 20 mA 0.3 % 0 to 20 mA 4 mA to 20 mA * * Resistor/PTC 0 k to 6 k 0.3 % 0 to 600 0.3 % PTC 0.3 % Resistance thermometer/silicon temperature sensors Pt 100 1K Ni 100 Standard Pt 100 0.8 K Ni 100 Klima Ni 1000 0.8 K LG-Ni 1000 Standard Ni 1000 0.8 K LG-Ni 1000 Klima KTY83/110 2K KTY84/130 2.7 K Temperature error (relative to input range) 0.006 %/K / 0.006 K/K Linearity error (relative to input range) 0.1 % / 0.1 K Repeat accuracy (in transient state at 25 C, relative to input range) 0.1 % / 0.1 K Status, interrupts, diagnostics Interrupts none Diagnostic functions none S7-300 Module data 346 Manual, 06/2017, A5E00105505-AJ Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Technical specifications Encoder selection data Input ranges (rated values) / input impedance * Voltage 50 mV 100 k 500 mV 1V 5V 10 V 1 V to 5 V 0 V to 10 V * Current 20 mA 100 0 mA to 20 mA 4 mA to 20 mA * Resistor/PTC 0 k to 6 k 100 M 0 to 600 PTC * Resistance thermometer/silicon temperature sensors Pt 100 100 M Ni 100 Ni 1000 LG-Ni 1000 Standard / Klima KTY83/110 KTY84/130 Maximum voltage at voltage input U+ (destruction limit) max. 30 V, continuous Maximum voltage at voltage inputs M+, M-, S- (destruction limit) max. 12 V continuous; 30 V for a duration of max. 1 s Maximum current at current input I+ (destruction limit) 40 mA Wiring of the signal transmitters using a 40pin front connector * for voltage measurement * for current measurement - as 2-wire transducer - as 4-wire transducer supported supported, with external supply supported * for resistance measurement with 2-wire connection supported with 3-wire connection supported with 4-wire connection supported Characteristics linearization programmable * for resistance thermometers Pt 100 Standard / Klima Ni 100 Standard / Klima Ni 1000 Standard / Klima LG-Ni 1000 Standard / Klima * Technical unit of temperature measurement Degrees Centigrade, degrees Fahrenheit, Kelvin S7-300 Module data Manual, 06/2017, A5E00105505-AJ 347 Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) 6.6.1 Measurement types and measuring ranges Introduction The measurement type and range is configured at the "measuring type" parameter in STEP 7. Selected type of measurement Measuring range Voltage 50 mV V: 500 mV 1V 5V 1 V to 5 V 0 V to 10 V 10 V Current I 0 mA to 20 mA 4 mA to 20 mA 20 mA resistance (4-wire connection) R-4L 6 k 600 PTC Thermal resistance Pt 100 Klima / Standard RTD-4L (linear, 4-wire connection) Ni 100 Klima / Standard (temperature measurement) Ni 1000 Klima / Standard Silicon temperature sensors LG-Ni 1000 Klima / Standard KTY83/110 KTY84/130 6.6.2 Programmable parameters Introduction You will find a description of the general procedure for assigning parameters to analog modules in section Programming analog modules (Page 294). S7-300 Module data 348 Manual, 06/2017, A5E00105505-AJ Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Parameter Table 6- 17 Overview of the parameters of SM 331; AI 8 x 13 Bit Parameters Range of values Default disabled V Parameter type Scope dynamic Channel Measurement * Measurement type Voltage V Current I Resistance R, PTC Thermal resistance RTD, silicon temperature sensors * Measuring range Voltage 10 V 50 mV; 500 mV; 1 V; 1 V to 5 V 5 V; 0 V to 10 V; 10 V Current 20 mA 0 mA to 20 mA; 4 mA to 20 mA; 20 mA Resistance 600 0 to 600 ; 0 k to 6 k; PTC Thermoelectric resistance (linear) Pt 100 Klima / Standard Pt 100 Standard Ni 100 Klima / Standard Ni 1000 Klima / Standard LG-Ni 1000 Klima / Standard KTY83/110 KTY84/130 * Temperature coefficient Pt 100 0,003850 0.003850 // C (IST-90) Ni 100 / Ni 1000 0.006180 // C LG-Ni 1000 0.005000 // C * * Interference frequency suppression 50 Hz; 60 Hz Temperature unit Degrees Centigrade, degrees Fahrenheit, Kelvin* 50 Hz Module degrees Centigrade * only Pt 100 Standard, Ni 100 Standard, Ni 1000 Standard, LG-Ni 1000 Standard S7-300 Module data Manual, 06/2017, A5E00105505-AJ 349 Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) 6.6.3 Additional information on SM 331; AI 8 x 13 Bit Using the module The spare parts of the SM 331-1KF02 are compatible with the SM 331-1KF01 and are configured with HSP 2067. HSP 2067 can be installed for STEP7 V5.4, SP5 and higher and is included for STEP7 V5.4, SP6 and higher. Unused channels Set the "disabled" value at the "measurement type" parameter for unused channels. This setting reduces module cycle times. Interconnect the M- terminals of unused channels. Using PTC resistors PTCs are suitable for monitoring the temperature of or providing thermal protection for complex drives and transformer windings. The module has no analog values when PTC resistances are used. Status information on fixed temperature ranges are displyed instead of analog values. When setting the parameters, select measurement type R "Resistance" and measuring range "PTC". Connect the PTC (see "Terminal diagram for resistance measurement"). Use PTC resistors that comply with IEC 60034-11-2 (previously, PTC thermistors that complied with DIN/VDE 0660, Part 302). Sensor data for the PTC resistor: S7-300 Module data 350 Manual, 06/2017, A5E00105505-AJ Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Property Switching points Technical specifications Comment Response to rising temperature < 550 Normal range: Bit 0 = "0", bit 2 = "0" (in the PII) 550 to 1650 Advance warning range: Bit 0 = "0", bit 2 = "1" (in the PII) > 1650 Actuating range: Bit 0 = "1", bit 2 = "0" (in the PII) Response to falling temperature > 750 Actuating range: Bit 0 = "1", bit 2 = "0" (in the PII) 750 to 540 Advance warning range: Bit 0 = "0", bit 2 = "1" (in the PII) < 540 Normal range: Bit 0 = "0", bit 2 = "0" (in the PII) (RRT-5) C Max. 550 (RRT+5) C Min. 1,330 (RRT+15) C Min. 4,000 Measurement voltage Max. 7.5 V RRT = Rated response temperature Voltage at PTC Assignment in the process image input (PII) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 351 Analog modules 6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0) Notes on programming Note Only bits 0 and 2 in the process image input are relevant for evaluation. You can use bits 0 and 2 to monitor the temperature of a motor, for example. Bits 0 and 2 in the process image input cannot be saved. When assigning parameters, make sure that the motor, for example, starts up in a controlled manner (by means of an acknowledgment). Bits 0 and 2 can never be set at the same time; they are set one after the other. Using silicon temperature sensors Silicon temperature sensors are commonly used to detect temperatures in motors. When assigning the parameters, select measurement type "thermoresistor" and measuring range "KTY83/110" or "KTY84/130". Connect the temperature sensor (see "Terminal diagram for resistance measurement"). Use temperature sensors which comply with the Product Specifications published by Philips Semiconductors. KTY83 series (KTY83/110) KTY84 series (KTY84/130) Also take note of the accuracy of the temperature sensors. The temperature is specified in 0.1 degrees C, 0.1 degrees K, and/or 0.1 degrees F, see section Representation of the values for analog input channels (Page 262). S7-300 Module data 352 Manual, 06/2017, A5E00105505-AJ Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) 6.7.1 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Order number 6ES7331-7KF02-0AB0 Properties 8 inputs in 4 channel groups Programmable measurement type at each channel group - Voltage - Current - Resistance - Temperature Programmable resolution at each channel group (9/12/14 bits + sign) Any measuring range selection per channel group Programmable diagnostics and diagnostic interrupt Programmable limit value monitoring for 2 channels Programmable hardware interrupt when limit is exceeded Electrically isolated to CPU and load voltage (not for 2-wire transducers) Resolution The resolution of measured values is directly dependent of the selected integration time. In other words, the longer the integration time for an analog input channel, the higher the resolution of a measured value. Diagnostics For information on diagnostics messages at the "group diagnostics" parameter, refer to chapter Diagnostic messages of analog input modules. Hardware interrupts Hardware interrupts for channel groups 0 and 1 can be programmed in STEP 7. However, set a hardware interrupt only for the first channel of a channel group, that is, either at channel 0, or at channel 2 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 353 Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Terminal assignment The diagrams below show various wiring options The input impedance depends on the setting of the measuring range module, see table Measurement types and ranges. Wiring: Voltage measurement Figure 6-13 Block diagram and wiring diagram Measuring range module settings Measuring range Measuring range module setting 80 mV A 250 mV 500 mV 1,000 mV 2.5 V B 5V 1 V to 5 V 10 V S7-300 Module data 354 Manual, 06/2017, A5E00105505-AJ Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Wiring: 2-wire and 4-wire transducers for current measurement Figure 6-14 Block diagram and wiring diagram Note The interconnection between MANA and M- (terminals 11, 13, 15, 17, 19) is not required when using grounded 4-wire transducers with non-isolated supply. Measuring range module settings Measuring range 4 mA to 20 mA 2-wire transducer 4-wire transducer 3.2 mA 10 mA 0 mA to 20 mA 4 mA to 20 mA 20 mA Measuring range module setting D C CAUTION Measuring range module in "Current" position Any voltage measurement will destroy the measuring range module if "current" measuring mode is set. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 355 Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Wiring: 2-, 3- and 4-wire connection of resistance transducers or thermoresistors 4-wire connection 3-wire connection, no compensation for line resistors 2-wire connection, no compensation for line resistors Figure 6-15 Block diagram and wiring diagram Measuring range module settings Measuring range Measuring range module setting A 150 300 600 Thermoresistor (linear, 4-wire connection) (temperature measurement) RTD-4L Pt 100 Klima Ni 100 Klima Pt 100 Standard Ni 100 Standard A Note * "Resistance measurement" is only available at one channel per group. The "2nd" channel of the group is used accordingly for current measuring mode (IC). The "1st" channel of the group returns the measured value. The "2nd" channel of the group is assigned the default overflow value "7FFFH." * There is no compensation of the line resistance with a 2 and 3-wire connection. S7-300 Module data 356 Manual, 06/2017, A5E00105505-AJ Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Wiring: Thermocouples with external compensation Insert a bridge between Comp+ and MANA when using the internal compensation. Figure 6-16 Block diagram and wiring diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 357 Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Measuring range module settings Measuring range Measuring range module setting Thermocouple TC-I Type N [NiCrSi-NiSi] (internal comparison) (thermal voltage measurement) Type E [NiCr-CuNi] Linearization is ignored Thermocouple TC-E (external comparison) (thermovoltage measurement) A Type J [Fe-CuNi] Type K [NiCr-Ni] Type L [Fe-CuNi] Linearization is ignored Thermocouple (linear, internal comparison) (temperature measurement) TC-IL Thermocouple (linear, external comparison) (temperature measurement) TC-EL Type N [NiCrSi-NiSi] A Type E [NiCr-CuNi] Type J [Fe-CuNi] Type K [NiCr-Ni] Type L [Fe-CuNi] Note * An interconnection of M- and MANA is prohibited when using grounded thermocouples. In this case, you must ensure that low-resistance equipotential bonding is in place so that the permitted common-mode voltage is not exceeded. * Interconnect M- and MANA when using non-grounded thermocouples S7-300 Module data 358 Manual, 06/2017, A5E00105505-AJ Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight approx. 250 g Module-specific data Supports isochronous mode No Number of inputs 8 * with resistive transducers Cable length * shielded 4 max. 200 m max. 50 m at 80 mV and with thermocouples Voltages, currents, electrical potentials Rated electronics supply voltage L + * Reverse polarity protection 24 V DC Yes Transducer power supply * Supply current * short circuit-proof Constant current for resistive transducers max. 60 mA (per channel) Yes typ. 1.67 mA (pulsed) Electrical isolation * between channels and the backplane bus * between channels and electronics power supply - Yes Yes Not for 2-wire transducers Maximum potential difference * between inputs and MANA (VCM) - * at signal = 0 V between inputs (VCM) Isolation test voltage typ. 2.5 V DC (> 2.3 V DC) typ. 2.5 V DC (> 2.3 V DC) 500 V DC Current consumption * from the backplane bus * from load voltage L+ Power loss of the module max. 50 mA max. 30 mA (without 2-wire transducer) typ. 1 W Generation of analog values Measuring principle Integrating Integration/conversion time/resolution (per channel) * programmable Yes * Integration time in ms 2.5 162/3 20 100 * Basic conversion time, including the integration time in ms 3 17 22 102 Additional conversion time for resistance measurement, in ms or 1 1 1 1 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 359 Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Technical specifications additional conversion time for wire-break monitoring in ms 10 10 10 10 16 16 16 16 or additional conversion time for resistance measurements and wire-break monitoring in ms * Resolution in bits (including overrange) 9 bits 12 bits 12 bits 14 bits * Interference frequency suppression at interference frequency f1 in Hz 400 60 50 10 * Basic execution time of the module in ms (all channels enabled) 24 136 176 816 Measured value smoothing none Interference frequency suppression, error limits Interference frequency suppression at F = n (f1 1 %), (f1 = interference frequency) > 70 dB * Common mode interference (VCM < 2.5 V) * Seriesmode interference (peak interference value < rated > 40 dB input range) Crosstalk between inputs > 50 dB Operational limit (across entire temperature range, relative to the measurement range end value in the selected input range) 80 mV 1% * Voltage input 250 mV to 1,000 mV 0.6 % 2.5 V to 10 V 0.8 % 3.2 mA to 20 mA 0.7 % * Current input * Resistance 150 ; 300; 600 0. 7 % * Thermocouple Types E, N, J, K, L 1. 1 % * Resistance thermometer Pt 100/Ni 100 0. 7 % Pt 100 Klima 0. 8 % Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected input range) 80 mV 0.7 % * Voltage input 250 mV to 1,000 mV 0.4 % 2.5 V to 10 V 0.6 % 3.2 mA to 20 mA 0.5 % * Current input * Resistance 150 ; 300 ; 600 0.5 % * Thermocouple Types E, N, J, K, L 0.7 % * Resistance thermometer Pt 100/Ni 100 0.5 % Pt 100 Klima 0.005%/K 0.05 % 0.05 % 0.6 % Temperature error (relative to input range) Linearity error (relative to input range) Repeat accuracy (in settled state at 25 C, relative to input range) Temperature error of internal compensation 1% S7-300 Module data 360 Manual, 06/2017, A5E00105505-AJ Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Technical specifications Status, interrupts, diagnostics Interrupts * Limit interrupt * Diagnostic interrupt Diagnostic functions * Group error display * Reading diagnostics information programmable Channels 0 and 2 programmable programmable red LED (SF) supported Encoder selection data Input ranges (rated values) / input impedance Thermocouples 80 mV 250 mV 500 mV 1,000 mV 2.5 V 5V 1 V to 5 V 10 V 3.2 mA 10 mA 20 mA 0 mA to 20 mA 4 mA to 20 mA 150 300 600 Types E, N, J, K, L 10 M 10 M 10 M 10 M 100 k 100 k 100 k 100 k 25 25 25 25 25 10 M 10 M 10 M 10 M Resistance thermometer Pt 100, Ni 100 10 M * Voltage * Current * Resistance * * Maximum voltage at voltage input (destruction limit) Maximum current at current input (destruction limit) Wiring of the signal transmitters * for voltage measurement * for current measurement as 2-wire transducer as 4-wire transducer * For thermoresistor/resistance measurement with 2-wire connection with 3-wire connection with 4-wire connection * Load of the 2-wire transducer Characteristics linearization * for thermocouples * for resistance thermometers max. 20 V, continuous 75 V for the duration of max. 1 s (duty factor 1:20) 40 mA using a 20-pin front connector supported supported supported Supported, cable resistances are not compensated Supported, cable resistances are not compensated Supported, cable resistances are compensated max. 820 programmable Types E, N, J, K, L Pt 100 (Standard and Klima range) Ni 100 (Standard and Klima range) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 361 Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Technical specifications Temperature compensation programmable supported * Internal temperature compensation * External temperature compensation with compensating box supported * Compensation for 0 C reference junction temperature supported * Technical unit of temperature measurement degrees Centigrade See also Diagnostics messages of analog input modules (Page 296) 6.7.2 Measurement types and ranges Introduction Module SM 331; AI 8 x 12 Bit has measuring range modules The measurement type and range is configured at the "measuring range" parameter in STEP 7. The default setting of the module is "voltage" measurement with " 10V" range. You can use these default settings without having to program the SM 331; AI 8 x 12 Bit in STEP 7. Measuring range modules You may have to change the position of the measuring range modules to suit the measurement type and range (see the chapter Setting the measuring types and ranges of analog input channels). The necessary settings are also available on the module's imprint. Mark the position of the measuring range module on the front door (see figure). S7-300 Module data 362 Manual, 06/2017, A5E00105505-AJ Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Measurement types and ranges Table 6- 18 Measurement types and ranges Selected type of measurement Measuring range (type of sensor) Measuring range module settings Voltage V 80 mV A 250 mV 500 mV 1000 mV 2.5 V B 5V 1 V to 5 V 10 V Thermocouple TC-I Type N [NiCrSi-NiSi] (internal comparison) (thermal voltage measurement) Type J [Fe-CuNi] Linearization is ignored Thermocouple TC-E A Type E [NiCr-CuNi] Type K [NiCr-Ni] Type L [Fe-CuNi] (external comparison) (thermovoltage measurement) Linearization is ignored Thermocouple (linear, internal comparison) (temperature measurement) TC-IL Thermocouple (linear, external comparison) (temperature measurement) TC-EL Current (2-wire transducer) Type N [NiCrSi-NiSi] A Type E [NiCr-CuNi] Type J [Fe-CuNi] Type K [NiCr-Ni] Type L [Fe-CuNi] 4 mA to 20 mA D 3.2 mA C 2DMU Current (4-wire transducer) 4DMU 10 mA 0 mA to 20 mA 4 mA to 20 mA 20 mA Resistance (4-wire connection) R-4L 150 A 300 600 Thermoresistor (linear, 4-wire connection) (temperature measurement) RTD-4L Pt 100 Klima A Ni 100 Klima Pt 100 Standard Ni 100 Standard S7-300 Module data Manual, 06/2017, A5E00105505-AJ 363 Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Channel groups The channels of SM 331; AI 8 x 12 Bit are arranged in four groups of two channels. You can assign parameters only to one channel group. SM 331; AI 8 x 12 Bit is equipped with one measuring range module per channel group. The table below shows the relevant configuration of channel groups. The channel group number is required to program SFC parameters in the user program. Table 6- 19 Assignment of SM 331; AI 8x12 bit channels to channel groups Channels ... ...form one channel group each Channel 0 Channel group 0 Channel 1 Channel 2 Channel group 1 Channel 3 Channel 4 Channel group 2 Channel 5 Channel 6 Channel group 3 Channel 7 See also Programming analog modules (Page 294) Diagnostics messages of analog input modules (Page 296) 6.7.3 Programmable parameters Introduction For information on programming analog modules, refer to the chapter Programming analog modules (Page 294). S7-300 Module data 364 Manual, 06/2017, A5E00105505-AJ Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) Parameters Table 6- 20 Overview of the parameters for SM 331; AI 8 x 12 Bit Parameters Range of values Default Parameter type Scope yes/no no dynamic Module yes/no no - dynamic Channel yes/no no static yes/no no Channel group disabled V dynamic Channel or channel group Enable * * Diagnostics interrupt Process interrupt when limit exceeded Process interrupt trigger * High limit * Low limit May be restricted by the measuring range from 32511 to - 32512 from - 32512 to 32511 Diagnostics * Group diagnostics * with line continuity check Measurement * Measurement type Voltage V 4DMU current (4-wire transducer) 2DMU current (2-wire transducer) R-4L resistance (4-wire connection) RTD-4L thermoresistor (linear, 4-wire connection) TC-I thermocouple (internal comparison) TC-E thermocouple (external comparison) TC-IL thermocouple (internal comparison) TC-EL thermocouple (linear, external comparison) * Measuring range See the table Measurement types and rang- 10 V * Noise suppression 400 Hz; 60 Hz; 50 Hz; 10 Hz 50 Hz es S7-300 Module data Manual, 06/2017, A5E00105505-AJ 365 Analog modules 6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0) 6.7.4 Additional information on SM 331; AI 8 x 12 Bit Unused channels As certain programmed inputs may remain unused due to the channel group configuration, make allowances for the special features of these inputs outlined below in order to be able to use the diagnostics functions at these used channels: Voltage measurement (except 1 V to 5V) and for thermocouples: Short-circuit unused channels and connect these with MANA. This optimizes interference immunity of the analog input module. Set the "disabled" value at the "measurement type" parameter for unused channels. This setting reduces module cycle times. Also short-circuit the COMP input if this is not used. Measuring range 1 V to 5 V: wire the used and unused inputs of the same channel group in parallel. Current measurement, 2-wire transducer: There are two options of wiring the channel circuit. a) Open unused input; channel group diagnostics disabled. If you were to enable diagnostics, the analog module would trigger a single diagnostic interrupt, and light up its SF LED. b) Loading the unused input using a 1.5 k to 3.3 k resistor. This allows you to enable diagnostics for this channel group. Current measurement 4 mA to 20 mA, 4-wire transducer: wire the unused inputs of the same channel group in series. All channels deactivated If you disable all input channels of the module and enable diagnostics at the parameters of SM 331; AI 8 x 12 Bit, the module does not report "external auxiliary voltage missing." Line continuity check for the 4 mA to 20 mA measuring range If you configured a measuring range of 4 mA to 20 mA, and enabled the line continuity check, the analog input module logs a wire-break event to diagnostics data when the current drops below 3.6 mA. The module also triggers a diagnostics interrupt if this function is enabled in the program. A wire break can only be signaled by means of the lit SF LED and the diagnostic bytes must be evaluated in the user program if diagnostics interrupts are disabled. If you configured a measuring range of 4 mA to 20 mA, disabled the line continuity check, and enabled diagnostic interrupts, the module triggers a diagnostic interrupt when the underflow value is reached. Line continuity check The line continuity check is designed only for temperature measurements (thermocouples and thermoresistors.) See also Representation of the values for analog input channels (Page 262) S7-300 Module data 366 Manual, 06/2017, A5E00105505-AJ Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) 6.8.1 Analog input module SM 331; AI 2 x 12-bit; (6ES7331-7KB02-0AB0) Order number: "Standard module" 6ES7331-7KB02-0AB0 Order number: "SIPLUS S7-300 module" 6AG1331-7KB02-2AB0 Properties Two inputs in one channel group Programmable measurement type for each channel group - Voltage - Current - Resistance - Temperature Programmable resolution at each channel group (9/12/14 bits + sign) Any measuring range selection per channel group Programmable diagnostics and diagnostic interrupt Programmable limit value monitoring for one channel Programmable hardware interrupt when limit is exceeded Electrically isolated from the CPU and load voltage (not for 2DMU) Resolution The measured value resolution is directly proportional to the selected integration time, that is, the measured value resolution increases in proportion to length of the integration time at the analog input channel. Diagnostics For information on diagnostics messages at the "group diagnostics" parameter, refer to chapter Diagnostic messages of analog input modules. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 367 Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) Hardware interrupts Hardware interrupts for channel groups can be programmed in STEP 7. However, set a hardware interrupt only for the first channel of a channel group, that is channel 0. Terminal assignment The diagrams below show various wiring options The input impedance depends on programmed measuring range. Wiring: Voltage measurement Figure 6-17 Wiring and block diagram Measuring range module settings Measuring range Measuring range module setting 80 mV A 250 mV 500 mV 1,000 mV 2.5 V B 5V 1 V to 5 V 10 V S7-300 Module data 368 Manual, 06/2017, A5E00105505-AJ Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) Wiring: Thermocouple with external compensation Insert a bridge between Comp+ and MANA when using the internal compensation. Figure 6-18 Wiring and block diagram Measuring range module settings Measuring range Measuring range module setting TC-I: Thermocouple Type N [NiCrSi-NiSi] (internal comparison) (thermal voltage measurement) Type E [NiCr-CuNi] TC-E: Thermocouples Type K [NiCr-Ni] A Type J [Fe-CuNi] (external comparison) (thermovoltage measurement) Type L [Fe-CuNi] TC-IL: Thermocouples (linear, internal comparison) (temperature measurement) Type N [NiCrSi-NiSi] A Type E [NiCr-CuNi] Type J [Fe-CuNi] Type K [NiCr-Ni] Type L [Fe-CuNi] TC-EL: Thermocouples Type N [NiCrSi-NiSi] (linear, external comparison) (temperature measurement) Type E [NiCr-CuNi] A Type J [Fe-CuNi] Type K [NiCr-Ni] Type L [Fe-CuNi] S7-300 Module data Manual, 06/2017, A5E00105505-AJ 369 Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) Wiring: 2-, 3- and 4-wire connection of resistance transducers or thermoresistors 4-wire connection 3-wire connection, no compensation for line resistors 2-wire connection, no compensation for line resistors Figure 6-19 Wiring and block diagram Measuring range module settings Measuring range 150 300 600 RTD-4L: Thermal resistance (linear, 4-wire connection) (temperature measurement) Measuring range module setting A Pt 100 Klima Ni 100 Klima Pt 100 Standard Ni 100 Standard A Note "Resistance measurement" is only available at one channel per group. The "2nd" channel of the group is used accordingly for current measuring mode (IC). The "1st" returns the measured value. The "2nd" channel of the group is assigned the default overflow value "7FFFH." S7-300 Module data 370 Manual, 06/2017, A5E00105505-AJ Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) Wiring: 2-wire and 4-wire transducers for current measurement Figure 6-20 Wiring and block diagram Measuring range module settings Measuring range Measuring range module setting 2-wire transducer 4 mA to 20 mA D 4-wire transducer 3.2 mA C 10 mA 0 mA to 20 mA 4 mA to 20 mA 20 mA CAUTION Measuring range module in "Current" position If "current" measuring mode is set, any voltage measurement will destroy the measuring range module. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 371 Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight approx. 250 g Module-specific data Supports isochronous mode No Number of inputs 2 * with resistive transducers Cable length * shielded 1 max. 200 m max. 50 m at 80 mV and with thermocouples Voltages, currents, electrical potentials Rated electronics supply voltage L + * Reverse polarity protection 24 V DC Yes Transducer power supply * Supply current * short circuit-proof Constant current for resistive transducers max. 60 mA (per channel) Yes typ. 1.67 mA (pulsed) Electrical isolation * between channels and the backplane bus * between channels and electronics power supply - Yes Yes Not for 2-wire transducers Maximum potential difference * between inputs and MANA (VCM) - * at signal = 0 V between inputs (VCM) Isolation test voltage typ. 2.5 V DC (> 2.3 V DC) typ. 2.5 V DC (> 2.3 V DC) 500 V DC Current consumption * from the backplane bus * from load voltage L+ Power loss of the module max. 50 mA max. 30 mA (without 2-wire transducer) typ. 1 W S7-300 Module data 372 Manual, 06/2017, A5E00105505-AJ Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) Technical specifications Generation of analog values Measuring principle Integrating Integration/conversion time/resolution (per channel) * programmable Yes * Integration time in ms 2.5 162/3 20 100 * Basic conversion time, including the integration time in ms 3 17 22 102 Additional conversion time for resistance measurement, in ms or 1 1 1 1 additional conversion time for wire-break monitoring in ms 10 10 10 10 16 16 16 16 or additional conversion time for resistance measurements and wire-break monitoring in ms * Resolution in bits (including overshoot range) 9 bits 12 bits 12 bits 14 bits * Interference frequency suppression at interference frequency f1 in Hz 400 60 50 10 * Basic execution time of the module in ms (all channels enabled) 6 34 44 204 Measured value smoothing none Interference frequency suppression, error limits Interference frequency suppression at f = n (f1 1%), (f1 = interference frequency) n=1.2... * Common mode interference (VCM < 2.5 V) * Seriesmode interference (peak interference value < rated input range) Crosstalk between inputs > 70 dB > 40 dB > 50 dB Operational limit (across entire temperature range, relative to the measurement range end value of the selected input range) * Voltage input 80 mV 1% 250 mV to 1,000 mV 0.6 % 2.5 V to 10 V 0.8 % 0.7 % * Current input 3.2 mA to 20 mA * Resistance 150 ; 300 ; 600 0. 7 % * Thermocouple Types E, N, J, K, L 1. 1 % * Resistance thermometer Pt 100/Ni 100 0. 7 % Pt 100 Klima 0. 8 % S7-300 Module data Manual, 06/2017, A5E00105505-AJ 373 Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) Technical specifications Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected input range) * Voltage input 80 mV 0.6 % 250 mV to 1,000 mV 0.4 % 2.5 V to 10 V 0.6 % 0.5 % * Current input 3.2 mA to 20 mA * Resistance 150 ; 300 ; 600 0.5 % * Thermocouple Types E, N, J, K, L 0.7 % * Resistance thermometer Pt 100/Ni 100 0.5 % Pt 100 Klima 0.6 % Temperature error (relative to input range) 0.005%/K Linearity error (relative to input range) 0.05 % Repeat accuracy (in settled state at 25C, relative to input range) 0.05 % Temperature error of internal compensation 1% Status, interrupts, diagnostics Interrupts * Limit interrupt * Diagnostic interrupt Diagnostic functions * Group error display * Reading diagnostics information programmable Channels 0 programmable programmable red LED (SF) supported Encoder selection data Input ranges (rated values) / input impedance * Voltage 80 mV 10 M 250 mV 10 M 500 mV 10 M 1,000 mV 10 M 2.5 V 100 k 5V 100 k 1 V to 5 V 100 k 10 V 100 k 3.2 mA 25 10 mA 25 20 mA 25 0 mA to 20 mA 25 4 mA to 20 mA 25 Resistance 150 10 M 300 10 600 10 * Thermocouples Types E, N, J, K, L 10 * Resistance thermometer Pt 100, Ni 100 10 * * Current S7-300 Module data 374 Manual, 06/2017, A5E00105505-AJ Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) Technical specifications Maximum voltage at voltage input (destruction limit) max. 20 V continuous; 75 V for the duration of max. 1 s (duty factor 1:20) Maximum current at current input (destruction limit) 40 mA Wiring of the signal transmitters using a 20-pin front connector * for voltage measurement supported * for current measurement as 2-ire transducer as 4-wire transducer supported supported * For thermoresistor/resistance measurement With 2-wire connection With 3-wire connection With 4-wire connection Supported, cable resistances are not compensated Supported, cable resistances are not compensated Supported, cable resistances are compensated * Load of the 2-wire transducer max. 820 Characteristics linearization * for thermocouples * for resistance thermometers Temperature compensation programmable Types E, N, J, K, L Pt 100 (Standard and Klima range) Ni 100 (Standard and Klima range) programmable * Internal temperature compensation supported * External temperature compensation with compensating box supported supported * Compensation for 0 C reference junction temperature degrees Centigrade * Technical unit of temperature measurement See also Causes of error and troubleshooting at analog input modules (Page 297) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 375 Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) 6.8.2 Measurement types and measuring ranges Introduction SM 331; AI 2 x 12 Bit is equipped with a measuring range module. The measurement type and range is configured at the "measuring range" parameter in STEP 7. You can use the default "voltage" measurement type and " 10 V range without having to program the SM 331; AI 2 x 12 Bit in STEP 7. Measuring range module Change the position of the measuring range module to set the measurement type and range (see the chapter Setting the measurement types and ranges of analog input channels ). The necessary settings are also available on the module's imprint. Mark the position of the measuring range module on the front door (see figure). Table 6- 21 Measurement types and ranges Selected type of measurement Measuring range (type of sensor) Measuring range module settings V: Voltage 80 mV A 250 mV 500 mV 1000 mV 2.5 V B 5V 1 V to 5 V 10 V TC-I: Thermocouple Type N [NiCrSi-NiSi] (internal comparison) (thermal voltage measurement) Type E [NiCr-CuNi] TC-E: Thermocouples Type K [NiCr-Ni] (external comparison) (thermal voltage measurement) A Type J [Fe-CuNi] Type L [Fe-CuNi] 2DMU: Current (2-wire transducer) 4 mA to 20 mA D 4DMU: Current (4-wire transducer) 3.2 mA C 10 mA 0 mA to 20 mA 4 mA to 20 mA 20 mA R-4L: Resistance 150 (4-wire connection) 300 A 600 S7-300 Module data 376 Manual, 06/2017, A5E00105505-AJ Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) Selected type of measurement Measuring range (type of sensor) TC-IL: Thermocouples (linear, internal compar- Type N [NiCrSi-NiSi] ison) Type E [NiCr-CuNi] (temperature measurement) Type J [Fe-CuNi] Measuring range module settings A Type K [NiCr-Ni] Type L [Fe-CuNi] TC-EL: Thermocouples Type N [NiCrSi-NiSi] (linear, external comparison) (temperature measurement) Type E [NiCr-CuNi] A Type J [Fe-CuNi] Type K [NiCr-Ni] Type L [Fe-CuNi] RTD-4L: Thermal resistance Pt 100 Klima (linear, 4-wire connection) (temperature measurement) Ni 100 Klima A Pt 100 Standard Ni 100 Standard Channel groups The two channels of SM 331; AI 2 x 12 Bit form a channel group. You can assign parameters only to one channel group. SM 331; AI 2 x 12 Bit is equipped with a measuring range module for channel group 0. Line continuity check The line continuity check is designed only for temperature measurements (thermocouples and thermoresistors.) Special features of the line continuity check for the 4 mA to 20 mA measuring range If you configured a measuring range of 4 mA to 20 mA, and enabled the line continuity check, the analog input module logs a wire-break event to diagnostics data when the current drops below 3.6 mA. The module also triggers a diagnostics interrupt if this function is enabled in the program. A wire break can only be signaled by means of the lit SF LED and the diagnostic bytes must be evaluated in the user program if diagnostics interrupts are disabled. If you configured a measuring range of 4 mA to 20 mA, disabled the line continuity check, and enabled diagnostic interrupts, the module triggers a diagnostic interrupt when the underflow value is reached. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 377 Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) 6.8.3 Programmable parameters Introduction For general information on programming analog modules, refer to the chapter Programming analog modules (Page 294). Parameters Table 6- 22 Overview of the parameters of SM 331; AI 2 x 12 Bit Parameters Range of values Default Parameter type Scope yes/no no dynamic Module yes/no no 32511 to -32512 - dynamic Channel yes/no no static yes/no no Channel group disabled V dynamic Channel or channel group Enable * * Diagnostics interrupt Process interrupt when limit exceeded Process interrupt trigger * High limit * Low limit from - 32512 to 32511 Diagnostics * * Group diagnostics with line continuity check Measurement * Measurement type Voltage V 4DMU current (4-wire transducer) 2DMU current (2-wire transducer) R-4L resistance (4-wire connection) RTD-4L thermoresistor (linear, 4-wire connection) TC-I thermocouple (internal comparison) TC-E thermocouple (external comparison) TC-IL thermocouple (internal comparison) TC-EL thermocouple (linear, external comparison) * Measuring range Refer to the chapter Measuring methods and ranges (Page 376) for the adjustable measuring ranges of the input channels 10 V * Noise suppression 400 Hz; 60 Hz; 50 Hz; 10 Hz 50 Hz See also Diagnostics messages of analog input modules (Page 296) S7-300 Module data 378 Manual, 06/2017, A5E00105505-AJ Analog modules 6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0) 6.8.4 Additional information on SM 331; AI 2 x 12 Bit Unused channels Short-circuit unused channels and connect these with MANA. This optimizes interference immunity of the analog input module. Set the "disabled" value at the "measurement type" parameter for unused channels. This setting reduces module cycle times. Also short-circuit the COMP input if this is not used. As certain programmed inputs may remain unused due to the channel group configuration, make allowances for the special features of these inputs outlined below in order to be able to use the diagnostics functions at these used channels: Measuring range 1 V to 5 V: wire the used input and unused input of the same channel group in parallel. Current measurement, 2-wire transducer: There are two options of setting up the channel circuit: a) Open unused input; channel group diagnostics disabled. The analog module would trigger a single diagnostics interrupt and set its SF LED if diagnostics is enabled. b) Terminating the unused input using a 1.5 k to 3.3 k resistor. This allows you to enable diagnostics for this channel group. Current measurement 4 mA to 20 mA, 4-wire transducer: wire the used input and unused input of the same channel group in series. Line continuity check The line continuity check is designed only for temperature measurements (thermocouples and thermoresistors.) Special features of the line continuity check for the 4 mA to 20 mA measuring range If you configured a measuring range of 4 mA to 20 mA, and enabled the line continuity check, the analog input module logs a wire-break event to diagnostics data when the current drops below 3.6 mA. The module also triggers a diagnostics interrupt if this function is enabled in the program. A wire break can only be signaled by means of the lit SF LED and the diagnostic bytes must be evaluated in the user program if diagnostics interrupts are disabled. If you configured a measuring range of 4 mA to 20 mA, disabled the line continuity check and enabled diagnostic interrupts, the module triggers a diagnostic interrupt when the underflow value is reached. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 379 Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) 6.9.1 Analog input module SM 331; AI 8 x RTD (6ES7331-7PF01-0AB0) Order number 6ES7331-7PF01-0AB0 Properties 8 inputs in 4 channel groups Measurement type programmable for each channel group - Resistor - Temperature Programmable resolution for each channel group (15 bits + sign) Measuring range selection for each channel group Configurable diagnostics and diagnostic interrupt Limit monitoring adjustable for 8 channels Hardware interrupt can be set for violation of the limit Fast measurement update for 4 channels Hardware interrupt can be set for end of scan cycle Potential-free from the CPU Supports the Configuration in RUN function Resolution The resolution of measured values is independent of the selected integration time. Diagnostics You can find the diagnostic messages grouped under the "Group diagnostics" parameter in the section Diagnostic messages of the analog input modules. Hardware interrupts You can set hardware interrupts in STEP 7 for channel groups 0 and 1. However, set a hardware interrupt only for the first channel of a channel group, that is, either at channel 0, or at channel 2. S7-300 Module data 380 Manual, 06/2017, A5E00105505-AJ Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Pin assignment The figures below show the various connection options. These connection examples apply to all channels (channels 0 to 7). CAUTION Wiring Incorrect wiring of the 3-wire connection can result in unpredictable operation of the module and dangerous conditions in the plant. Wiring: 2, 3 and 4-wire connection for resistance and thermal resistance measurement Connection possible at both sides to channels 0 to 7 4-wire connection 3-wire connection 2-wire connection Digital-analog converter Backplane bus interface Analog-to-digital converter (ADC) Figure 6-21 Wiring and block diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 381 Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Figure 6-22 Unused channel Note - Always use channel n (in this case channel 0) for measurement - Short-circuit unused channels (in this case channel 1) or connect them in order to avoid diagnostic results with a resistance of the rated range (eg.100 ohms at Pt 100) CAUTION Wiring Incorrect wiring of the 3-wire connection can result in unpredictable operation of the module and dangerous conditions in the plant. Wiring: 3-wire connection With a 3-wire connection to the SM 331; AI 8 x RTD, you need to set a jumper between M+ and IC+. Always ensure that the connected IC and M cables are directly to the resistance thermometer. Wiring: 2-wire connection With a 2-wire connection to the SM 331; AI 8 x RTD, you need to set a jumper between M+ and IC+ as well as M- and IC- . There is no compensation of the line resistance with a 2-wire connection. The line resistances are also measured! S7-300 Module data 382 Manual, 06/2017, A5E00105505-AJ Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight approx. 272 g Module-specific data Configuration in RUN possible Yes Behavior of the non-configured inputs Provides the last valid process value before the parameter assignment Supports isochronous operation No Number of inputs 8 Cable length * Shielded max. 200 m Voltages, currents, potentials Supply voltage of the electronics L+ * Reverse polarity protection Constant measurement current for resistance-type transmitter 24 V DC Yes max. 5 mA (pulsed) Electrical isolation * Between channels and backplane bus * between channels and electronics power supply Yes Yes * Between the channels In groups of Yes Insulation tested with 500 V DC 2 Current consumption * From backplane bus * from supply voltage L+ Power loss of the module max. 100 mA max. 240 mA typ. 4.6 W Analog value formation Measuring principle Integrating Mode 8-channel mode (hardware filter) Integration/conversion time/resolution (per channel) * Configurable * Basic conversion time in ms * Additional conversion time for resistance measurement in ms * Additional conversion time for wire break monitoring in ms * Resolution (including overrange) * Interference voltage suppression at interference frequency f1 in Hz Yes 80 100* 0 16-bit (including sign) 400 / 60 / 50 Smoothing of the measured values None/Weak/Medium/Strong Conversion time (per channel) 100 ms Basic execution time of the module (all channels enabled) 200 ms S7-300 Module data Manual, 06/2017, A5E00105505-AJ 383 Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Technical specifications Mode 8-channel mode (software filter) Integration/conversion time/resolution (per channel) * Configurable * Basic conversion time in ms * Additional conversion time for resistance measurement in ms * Additional conversion time for wire break monitoring in ms * Resolution (including overrange) * Interference voltage suppression at interference frequency f1 in Hz Yes 8 / 25 / 30 25/ 43/ 48* 0 16-bit (including sign) 400 / 60 / 50 Smoothing of the measured values None/Weak/Medium/Strong Conversion time (per channel) 25/ 43/ 48 ms Basic execution time of the module (all channels enabled) 50/ 86/ 96 ms Mode 4-channel mode (hardware filter) Integration/conversion time/resolution (per channel) * Configurable * Basic conversion time in ms * Additional conversion time for resistance measurement in ms * Additional conversion time for wire break monitoring in ms * Resolution (including overrange) * Interference voltage suppression at interference frequency f1 in Hz Yes 3.3**** 100* 100** 16-bit (including sign) 400 / 60 / 50 Smoothing of the measured values None/Weak/Medium/Strong Basic execution time of the module (all channels enabled) 10 ms Interference suppression, error limits Interference voltage suppression for f = n x (f1 1 %), (f1 = interference frequency), n = 1, 2, etc. * Common mode interference (UCM < 60 V AC) * Series-mode interference (peak value of the interference < rated value of the input range) Crosstalk between inputs > 100 dB > 90 dB > 100 dB Operational limit (within the entire temperature range, relative to the measuring range end value of the selected input range) * Resistance thermometer - - * Pt 50, Pt 100, Pt 200, Pt 500, Pt 1000, Ni 100, Ni 120, Ni 200, 1.0 C Ni 500, Ni 1000, LG-Ni 1000, Cu 50, Cu 100, 2.0 C Pt 10, Cu 10 0.1 % Resistor Basic error limit (operational limit at 25 C, in relation to measuring range full-scale value of the input range) * Resistance thermometer - - * Pt 50, Pt 100, Pt 200, Pt 500, Pt 1000, Ni 100, Ni 120, Ni 200, 0.5 C Ni 500, Ni 1000, LG-Ni 1000, Cu 50, Cu 100, 1.0 C Pt 10, Cu 10 0.05 % Resistor S7-300 Module data 384 Manual, 06/2017, A5E00105505-AJ Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Technical specifications Temperature error (in relation to input range) * * Resistance thermometer Resistor 0.015 C/K 0.005 %/K Linearity error (referenced to input range) * Resistance thermometer * Resistor Repeat accuracy (in steady state at 25 C, referenced to input range) * Resistance thermometer * Resistor 0.2 C 0.02 % 0.2 C 0.01 % Status, interrupts, diagnostics Interrupts * * Hardware interrupt Diagnostics interrupt Diagnostics function * Group error display * Diagnostic information can be read Configurable (channels 0-7) Configurable Configurable Red LED (group error) possible Encoder selection data Input range (rated values) input resistance * Resistance thermometer * Resistor Pt 10, Pt 50, Pt 100, Pt 200, Pt 500, Pt 1000, Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000, LG-Ni 1000, Cu 10, Cu 50, Cu 100 (standard and climatic) 150, 300, 600 Permissible input voltage at voltage input (destruction limit) 35 V DC continuous 75 V DC for max. 1 s (duty cycle 1 : 20) Wiring of the signal transmitters with 40-pin front connector * for resistance measurement with 2-wire connection possible with 3-wire connection possible*** with 4-wire connection possible Characteristic linearization * Resistance thermometer * Technical unit for temperature measurement Pt 10, Pt 50, Pt 100, Pt 200, Pt 500, Pt 1000, Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000, LG-Ni 1000, Cu 10, Cu 50, Cu 100 (standard and climatic) Degrees Celsius / degrees Fahrenheit * The resistance test for compensation of the line resistances with a 3-wire connection is performed every 5 minutes. ** Wire break monitoring in 4-channel mode (hardware filter) is performed every 3 seconds. *** The maximum line resistance with 3-wire encoder measurements for the RTD elements PT 10 and Cu 10 is 10 . For all other RTD elements, the maximum power resistance for 3-wire encoder measurements is 20 . **** In 4-channel mode, the converted value settles to 100% within 80 ms. The value determined in this process is switched typically every 3.3 ms (max. 10 ms). S7-300 Module data Manual, 06/2017, A5E00105505-AJ 385 Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Configuration in RUN Special considerations must be given if you use the Configuration in RUN function. SF LED is lit: Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or module), although diagnostics are no longer pending and the module is operating correctly. Solution: Only change the configuration when no diagnostics are pending for the module or Pulling and plugging the module. S7-300 Module data 386 Manual, 06/2017, A5E00105505-AJ Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) 6.9.2 Measurement types and measuring ranges Introduction The measurement type and range is configured at the "measurement type" parameter in STEP 7. Table 6- 23 Measurement types and ranges Selected type of measurement Measuring range Resistance: 150 (3-/4-wire connection) 300 600 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 387 Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Selected type of measurement Measuring range RTD resistance and linearization: Pt 100 Klima (3-/4-wire connection) Pt 200 Klima Pt 500 Klima Pt 1000 Klima Ni 100 Klima Ni 120 Klima Ni 200 Klima Ni 500 Klima Ni 1000 Klima* LG-Ni 1000 Klima Cu 10 Klima Pt 100 Standard Pt 200 Standard Pt 500 Standard Pt 1000 Standard Ni 100 Standard Ni 120 Standard Ni 200 Standard Ni 500 Standard Ni 1000 Standard* LG-Ni 1000 Standard Cu 10 Standard Pt 10 GOST Klima Pt 10 GOST Standard Pt 50 GOST Klima Pt 50 GOST Standard Pt 100 GOST Klima Pt 100 GOST Standard Pt 500 GOST Klima Pt 500 GOST Standard Cu 10 GOST Klima Cu 10 GOST Standard Cu 50 GOST Klima Cu 50 GOST Standard Cu 100 GOST Klima Cu 100 GOST Standard Ni 100 GOST Klima Ni 100 GOST Standard * LG-Ni 1000 with temperature coefficient 0.00618 or 0.00672 S7-300 Module data 388 Manual, 06/2017, A5E00105505-AJ Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Channel groups The channels of SM 331; AI 8 x RTD are arranged in four groups of two channels. You can assign parameters only to one channel group. The table below shows the relevant configuration of channel groups. The channel group number is required to program SFC parameters in the user program. Table 6- 24 Assignment of SM 331; AI 8 x RTD channels to channel groups Channels ... ... form one channel group each Channel 0 Channel group 0 Channel 1 Channel 2 Channel group 1 Channel 3 Channel 4 Channel group 2 Channel 5 Channel 6 Channel group 3 Channel 7 6.9.3 Programmable parameters Introduction For general information on programming analog modules, refer to the chapter Programming analog modules (Page 294). The table below provides an overview of programmable parameters and of their defaults: Parameters Table 6- 25 Overview of SM 331; AI 8 x RTD parameters Parameters Range of values Default yes/no no yes/no no yes/no no 32511 to -32512 32767 Parameter type Scope dynamic Module dynamic Channel static Channel group Enable * Diagnostics interrupt * Process interrupt when limit exceeded * Process interrupt at end of cycle Process interrupt trigger * High limit * Low limit from - 32512 to 32511 -32768 Diagnostics * Group diagnostics * with line continuity check yes/no no yes/no no S7-300 Module data Manual, 06/2017, A5E00105505-AJ 389 Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Parameters Range of values Default disabled R-4L resistance (4-wire connection) R-3L resistance (3-wire connection) RTD-4L thermoresistor (linear, 4-wire connection) RTD-3L thermoresistor (linear, 3-wire connection) RTD-4L Parameter type Scope dynamic Channel group dynamic Module dynamic Module dynamic Channel group dynamic Channel group Channel group Measurement * Measurement type * Measuring range See chapter Measurement types and measuring ranges (Page 387) Pt 100 Klima 0.003850 (IPTS-68) * Temperature unit * Mode of operation degrees Centigrade 8-channel mode, hardware filter * Temperature coefficient for temperature measurement with thermoresistor (RTD) Degrees Centigrade; degrees Fahrenheit 8-channel mode (hardware filter) 8-channel mode (software filter) 4-channel mode (hardware filter) Platinum (Pt) 0.003850 // C (IPTS-68) 0.003916 // C 0.003902 // C 0.003920 // C 0.003850 // C (ITS-90) 0.003910 // C Nickel (Ni) 0.006170 // C 0.006180 // C 0.006720 // C 0.005000 // C (LG Ni 1000) Copper (Cu) 0.004260 // C 0.004270 // C 0.004280 // C 50/60/400 Hz; 400 Hz; 60 Hz; 50 Hz * Noise suppression* 0,003850 50/60/400 Hz none none dynamic weak medium strong * 50/60/400 Hz only programmable for 8-channel mode (hardware filter) and 4-channel mode (hardware filter); 50 Hz, 60 Hz or 400 Hz only programmable for 8-channel mode (software filter) * Smoothing See also Diagnostics messages of analog input modules (Page 296) S7-300 Module data 390 Manual, 06/2017, A5E00105505-AJ Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) 6.9.4 Additional information on SM 331; AI 8 x RTD Modes of operation Operating modes of SM 331; AI 8 x RTD: 8-channel mode (hardware filter) 8-channel mode (software filter) 4-channel mode (hardware filter) The operating mode influences the module cycle time. 8-channel mode (hardware filter) In this mode, the module changes between the two channels of each group. The four ADCs of the module simultaneously convert channels 0, 2, 4 and 6. The ADCs first convert the channels with even numbers, and then the channels with the odd numbers 1, 3, 5 and 7 (see the figure below.) Figure 6-23 8-channel mode cycle time (hardware filter) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 391 Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Cycle time of module in 8-channel mode The channel conversion time, including module communication time, is 84 ms. The module must change to the second channel of the group using OptoMOS relays when conversion is completed. Opto-MOS relays require 12 ms for switching and settling. Each channel requires a time of 97 ms, i.e. the total cycle time equals 194 ms. Cycle time = (tK + tU) x 2 Cycle time = (84 ms + 16 ms) x 2 Cycle time = 200 ms tC: Conversion time for one channel tC: Channel changeover time within the channel group 8-channel mode (software filter) Analog-to-digital conversion in this mode is identical to the conversion in 8-channel mode (hardware filter). The four ADCs of the module simultaneously convert channels 0, 2, 4 and 6. The ADCs first convert the channels with even numbers, and then the channels with the odd numbers 1, 3, 5 and 7 (see the figure below.) Figure 6-24 8-channel mode cycle time (software filter) S7-300 Module data 392 Manual, 06/2017, A5E00105505-AJ Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Cycle time of module in 8-channel mode (software filter) The channel conversion time is based on the programmed interference frequency. The channel conversion time is 32 ms, including communication time, when you set an interference frequency of 50 Hz. The channel conversion time is 27 ms when you set an interference frequency of 60 Hz. You can reduce channel conversion times to 9 ms by setting an interference frequency of 400 Hz. As in "hardware filter, 8channel" mode, the module has to toggle to the second channel of the group within a changeover time of 16 ms using the Opto-MOS relays. The table below shows this correlation. Table 6- 26 Cycle times in "8-channel mode (software filter)" Interference frequency Channel cycle time* Module cycle time (all channels) 50 Hz 48 ms 96 ms 60 Hz 43 ms 86 ms 400 Hz 25 ms 50 ms * Channel cycle time = channel conversion time + 12 ms channel changeover time within the group 4-channel mode (hardware filter) In this mode, the module does not change between the channels of the groups. The four ADCs of the module simultaneously convert the channels 0, 2, 4 and 6. Figure 6-25 4-channel mode cycle time (hardware filter) Cycle time of the module in 4-channel mode (hardware filter) The converted value settles to 100% within 80 ms and is updated at intervals of 10 ms when 4-channel mode is set. The channel and module cycle times are always identical, as the module does not change between the channels of a group: 10 ms. Channel conversion time = channel cycle time = module cycle time = 10 ms S7-300 Module data Manual, 06/2017, A5E00105505-AJ 393 Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Cycle time extension due to wire-break monitoring The wire-break monitoring software function of the module is available in all operating modes. The cycle time of the module is doubled in 8-channel mode (hardware or software filter), irrespective of the number of channels at which wire-break monitoring is enabled. In 4-channel mode (hardware filter), the module interrupts processing of input data for the duration of 100 ms and performs a line continuity check. That is, each line continuity check extends the module cycle time by 100 ms. Unused channels In order to avoid incorrect measurements, an unused channel from an active group of channels must be configured. Connect a resistor of the nominal range to the unused channel in order to suppress diagnostics errors. Set the "disabled" value at the "measurement type" parameter for unused channels. This setting reduces module cycle times. Short-circuit to M or L The module does not suffer any damage if you short-circuit an input channel to M or L.. The channel continues to output valid data and does not report a diagnostics event. End of cycle interrupt You can synchronize a process with the conversion cycle of the module by enabling the end of cycle interrupt. The interrupt is set when all active channels have been converted. The table below shows the contents of the 4 bytes of additional OB40 information during process or end of cycle interrupts. Content of the 4 bytes with additional information 27 Special 2 bits per channel to identify the range analog flags High limit exceeded at channel 7 Low limit exceeded at channel End of cycle event Free bit 7 26 25 24 23 22 21 20 Byte 6 5 4 3 2 1 0 0 6 5 4 3 2 1 0 1 X 2 3 Programming restrictions when operating SM 331; AI 8 x RTD with PROFIBUS masters which only support DPV0. Certain parameters are not allowed when operating the SM 331; AI 8 x RTD analog input module on an ET 200M PROFIBUS slave system and the PROFIBUS master is not an S7 master.. Non-S7 masters do not support process interrupts. All parameters associated with these functions are disabled for this reason. This includes process interrupt enable, hardware restrictions and end the enabling of cycle interrupts. All other parameters are allowed. S7-300 Module data 394 Manual, 06/2017, A5E00105505-AJ Analog modules 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Operating the module on the ET 200M Distributed IO device Operation of SM 331; AI 8 x RTD on ET 200M requires one of the following IM 153 x: IM 153-1; as of 6ES7153-1AA03-0XB0, V 01 IM 153-2; as of 6ES7153-2AA02-0XB0, V 05 IM 153-2; as of 6ES7153-2BA00-0XA0; V 01 IM 153-2; as of 6ES7153-2AA01-0XB0, V 04 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 395 Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Order number 6ES7331-7PF11-0AB0 Properties 8 inputs in 4 channel groups Programmable measurement type at each channel group - Temperature Programmable resolution at each channel group (15 bits + sign) Any measuring range selection per channel group Programmable diagnostics and diagnostic interrupt Programmable limit value monitoring for 8 channels Programmable hardware interrupt when limit is exceeded High-speed update of measured values at up to 4 channels Programmable hardware interrupt at end of cycle Electrically isolated from the CPU Supports parameter reassignment in RUN Resolution The resolution of measured values is independent of the selected integration time. Diagnostics For information on diagnostics messages at the "group diagnostics" parameter, refer to chapter Diagnostic messages of analog input modules (Page 296). Hardware interrupts Hardware interrupts for channel groups 0 and 1 can be programmed in STEP 7. However, set a hardware interrupt only for the first channel of a channel group, that is, either at channel 0, or at channel 2 Terminal assignment The diagrams below show various wiring options. These examples apply to all channels (channel 0 to 7). S7-300 Module data 396 Manual, 06/2017, A5E00105505-AJ Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Wiring: Thermocouple via reference junction All 8 inputs are available as measurement channels if thermocouples are wired via reference junctions which are regulated to 0 C or 50 C. Thermocouple via reference junction Reference junction regulated to 0 C or 50 C for example, compensation box (per channel) or thermostat Analog-to-Digital Converter (ADC) Backplane bus interface External cold spot comparison Figure 6-26 Wiring and block diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 397 Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Wiring: Thermocouple with external compensation With this type of compensation, the temperature of the terminals at the reference junction is established using a resistance thermometer Pt100 with a temperature range of -25 C to 85 C (see terminals 35 to 38). Thermocouple with external temperature compensation Backplane bus interface Analog-to-Digital Converter (ADC) External cold spot comparison Figure 6-27 Wiring and block diagram S7-300 Module data 398 Manual, 06/2017, A5E00105505-AJ Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Wiring: Thermocouple with internal compensation With this kind of compensation, the module registers the temperature at the reference junction in the connector. Thermocouple with equalizing conductor up to front connector Backplane bus interface Analog-to-Digital Converter (ADC) External cold spot comparison Figure 6-28 Wiring and block diagram Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x117 Weight approx. 272 g Module-specific data Supports parameter reassignment in RUN Yes Response of non-programmed inputs Return the process value which was valid before configuration Supports isochronous mode No Cable length * shielded max. 100 m S7-300 Module data Manual, 06/2017, A5E00105505-AJ 399 Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Technical specifications Voltages, currents, electrical potentials Rated electronics supply voltage L + * Reverse polarity protection Constant measuring current for resistance-type transmitters 24 V DC Yes typ. 0.7 mA Electrical isolation * between channels and the backplane bus * between channels and electronics power supply * between channels in groups of Isolation test voltage Yes Yes Yes 2 500 V DC Current consumption * from the backplane bus * from supply voltage L+ Power loss of the module max. 100 mA max. 240 mA typ. 3.0 W Generation of analog values Measuring principle Integrating Operating mode 8-channel mode (hardware filter) Integration/conversion time/resolution (per channel) * programmable * Basic conversion time in ms * additional conversion time for wire-break monitoring in ms * Resolution (including overshoot range) * Interference frequency suppression at interference frequency f1 in Hz Yes 95 4 16 bits (including sign) 400/60/50 Measured value smoothing none/weak/medium/strong Basic execution time of the module (all channels enabled) 196 ms ****** Operating mode 8-channel mode (software filter) Integration/conversion time/resolution (per channel) * programmable * Basic conversion time in ms * additional conversion time for wire-break monitoring in ms * Resolution (including overshoot range) * Interference frequency suppression at interference frequency f1 in Hz Yes 23/72/83 4 16 bits (including sign) 400/60/50 Measured value smoothing none/weak/medium/strong Basic execution time of the module (all channels enabled) 46/144/166 ms ****** Measuring principle Integrating S7-300 Module data 400 Manual, 06/2017, A5E00105505-AJ Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Technical specifications Operating mode 4-channel mode (hardware filter) Integration/conversion time/resolution (per channel) Yes * programmable * Basic conversion time in ms 3.3 ms ***** * additional conversion time for wire-break monitoring in ms 93 * * Resolution (including overshoot range) 16 bits (including sign) * Interference frequency suppression at interference frequen- 400/60/50 cy f1 in Hz Measured value smoothing none/weak/medium/strong Basic execution time of the module (all channels enabled) 10 ms ****** Interference frequency suppression, error limits Interference frequency suppression at f = n (f1 1%), (f1 = interference frequency) n = 1.2, etc. * Common mode interference (VCM < 60 V AC) * Series-mode interference (peak interference value < rated input range) Crosstalk between inputs > 100 dB > 90 dB ** > 100 dB Operational limit (across temperature range, relative to the measurement range end value of the input range) (0 to 60 C) Note: This limit does not cover the temperature-error comparison points. * Thermocouple Type T Type U Type E Type J Type L Type K Type N Type R Type S Type B **** Type C -200 C to +400 C 0.7 C -230 C to -200 C 1.5 C -150 C to +600 C 0.9 C -200 C to -150 C 1.2 C -200 C to +1000 C 1.2 C -230 C to -200 C 1.5 C -150 C to +1200 C 1.4 C -210 C to -150 C 1.7 C -150 C to +900 C 1.5 C -200 C to -150 C 1.8 C -150 C to +1372 C 2.1 C -220 C to -150 C 2.9 C -150 C to +1300 C 2.2 C -220 C to -150 C 3.0 C +100 C to +1769 C 1.5 C -50 C to +100 C 1.8 C +100 C to +1769 C 1.7 C -50 C to +100 C 2.0 C +800 C to +1820 C 2.3 C +200 C +800 C 2.5 C +100 C to +2315 C 2.3 C 0 C +100 C 2.5 C S7-300 Module data Manual, 06/2017, A5E00105505-AJ 401 Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Technical specifications Txk/xk(L) -150 C to +800 C 1.0 C -200 C -150 C 1.5 C Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected input range) * Thermocouple Type T Type U Type E Type J Type L Type K Type N Type R Type S Type B **** Type C Txk/xk(L) -200 C to +400 C 0.5 C -230 C to -200 C 1.0 C -150 C to +600 C 0.5 C -200 C to -150 C 1.0 C -200 C to +1000 C 0.5 C -230 C to -200 C 1.0 C -150 C to +1200 C 0.5 C -210 C to -150 C 1.0 C -150 C to +900 C 0.5 C -200 C to -150 C 1.0 C -150 C to +1372 C 0.5 C -220 C to -150 C 1.0 C -150 C to +1300 C 0.5 C -200 C to -150 C 1.0 C +100 C to +1769 C 0.5 C -50 C to +100 C 0.5 C +100 C to +1769 C 0.5 C -50 C to +100 C 1.0 C +800 C to +1820 C 1.0 C +200 C to +800 C 2.0 C +100 C to +2315 C 0.5 C 0 C +100 C 1.0 C -150 C to +800 C 0.5 C -200 C -150 C 1.0 C Temperature error (relative to input range) 0.005%/K Linearity error (relative to input range) 0.02% Repeat accuracy (in settled state at 25 C, relative to input range)*** 0.01% Status, interrupts, diagnostics Interrupts * * Hardware interrupt programmable Diagnostic interrupt programmable Diagnostic functions * Group error display * Reading diagnostics information (channels 0 to 7) programmable red LED (SF) supported S7-300 Module data 402 Manual, 06/2017, A5E00105505-AJ Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Technical specifications Encoder selection data Input ranges (rated values) / input impedance * Thermocouples Types B, C, N, E, R, S, J, L, T, K, U, TxK/xK (L)/ > 10 megaohms Maximum voltage at voltage input (destruction limit) 20 V DC continuous; 75 V DC for the duration of max. 1 s (duty factor 1:20) Characteristics linearization programmable Temperature compensation programmable * Internal temperature compensation * External temperature compensation with Pt 100 (0.003850) * Compensation for 0 C reference junction temperature * Compensation for 50 C reference junction temperature * Technical unit of temperature measurement Wiring of the signal transmitters supported supported supported supported Degrees Centigrade / degrees Fahrenheit using a 40-pin front connector ** Wire-break monitoring in 4-channel mode (hardware filter) at intervals of three seconds. ** In 8-channel software mode (software filter), series-mode rejection is reduced as follows: * 50 Hz > 70 dB * 60 Hz > 70 dB * 400 Hz > 80 dB *** The operational limit comprises only the basic error of the analog input at Ta = 25 C and the total temperature error. The total error must include the compensation error of the cold reference junction. Internal compensation of the reference junction = max. 1.5 C External compensation of the reference junction = accuracy of the used external RTD 0.1 C. External compensation of the reference junction at which the reference junction is maintained at 0 C or 50 C = accuracy of the temperature control of the reference junction. **** Due to its small slope of approx. 0 C to 40 C, a lack of compensation for the reference junction temperature only has a slight effect with thermocouple type B. With missing compensation and set measuring type "Compensation to 0 C", the deviation with thermocouple type B at measuring temperatures between: * 700 C and 1820 C is < 0.5 C * 500 C and 700 C is < 0.7 C. If the reference junction temperature is approximately that of the module temperature, "internal compensation" should be set. As a result, the error for the temperature range from 500 C to 1820 C is reduced to < 0.5 C. ***** In 4-channel mode, the converted value settles to 100 % within 80 ms. The value determined in this process is set at intervals of 3.3 ms (max. 10 ms). ****** If internal or external reference junction compensation is configured, the measured values of all channels are not updated for about 1 s in each minute. ### S7-300 Module data Manual, 06/2017, A5E00105505-AJ 403 Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Parameter reassignment in RUN If you reassign parameters in RUN, the following special characteristic applies. SF LED is lit: If a diagnostics was pending prior to reconfiguration, the SF LEDs (on CPU, IM or module) may be lit even though diagnostics is no longer pending and the module is operating correctly. Solution: Only assign new parameters if no diagnostics is pending, or unplug module and plug it in again. 6.10.1 Measurement types and measuring ranges Introduction The measurement type and range are configured at the "measuring range" parameter in STEP 7. Table 6- 27 Measurement types and ranges Selected type of measurement Measuring range TC-L00C: (thermocouple, linear, 0 C reference temperature) Type B TC-L50C: (thermocouple, linear, 50 C reference temperature) Type E TC-IL: (thermocouple, linear, internal comparator) TC-EL: (thermocouple, linear, external comparison) Type C Type J Type K Type L Type N Type R Type S Type T Type U Type Txk / xk (L) S7-300 Module data 404 Manual, 06/2017, A5E00105505-AJ Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Channel groups The channels of SM 331; AI 8 x TC are arranged in four groups of two channels. You can assign parameters only to one channel group. The table below shows the relevant configuration of channel groups. The channel group number is required to program SFC parameters in the user program. Table 6- 28 Assignment of SM 331; AI 8 x TC channels to channel groups Channels ... ... form one channel group each Channel 0 Channel group 0 Channel 1 Channel 2 Channel group 1 Channel 3 Channel 4 Channel group 2 Channel 5 Channel 6 Channel group 3 Channel 7 6.10.2 Adjustable parameters Introduction For general information on programming analog modules, refer to the chapter Programming analog modules (Page 294). Parameters Table 6- 29 Parameters of SM 331; AI 8 x TC Parameters Range of values Default yes/no no no Parameter type Scope dynamic Module dynamic Channel Enable * Diagnostics interrupt * Process interrupt when limit exceeded yes/no * Process interrupt at end of cycle yes/no no 32511 to -32512 32767 Process interrupt trigger * High limit * Low limit from - 32512 to 32511 -32768 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 405 Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Parameters Range of values Default Parameter type Scope yes/no no static yes/no no Channel group disabled TC-IL dynamic Channel group Diagnostics * * Group diagnostics with line continuity check Measurement * Measurement type TC-IL thermocouple (linear, internal comparison) TC-EL thermocouple (linear, external comparison) TC-L00C thermocouple (linear, ref. temp. 0 C) TC-L50C thermocouple (linear, ref. temp. 50 C) See table Measurement types and measuring ranges (Page 404) Type K * Measuring range * Reaction to open thermocouple Overflow; underflow * Temperature unit Degrees Centigrade; degrees Fahrenheit degrees Centigrade dynamic Module * Mode of operation 8-channel mode (hardware filter) 8 channels, dynamic hardware filter Module 8-channel mode (software filter) Overflow 4-channel mode (hardware filter) * Noise suppression* 50/60/400 Hz; 400 Hz; 60 Hz; 50 Hz; 50/60/400 Hz dynamic Channel group * Smoothing none none dynamic Channel group weak medium strong * 50/60/400 Hz only programmable for 8-channel mode (hardware filter) and 4-channel mode (hardware filter); 50 Hz, 60 Hz or 400 Hz only programmable for 8-channel mode (software filter) See also Diagnostics messages of analog input modules (Page 296) S7-300 Module data 406 Manual, 06/2017, A5E00105505-AJ Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) 6.10.3 Additional information on SM 331; AI 8 x TC Modes of operation Operating modes of SM 331; AI 8 x TC: 8-channel mode (hardware filter) 8-channel mode (software filter) 4-channel mode (hardware filter) The operating mode influences the module cycle time. 8-channel mode (hardware filter) In this mode, the module changes between the two channels of each group. The four ADCs of the module simultaneously convert channels 0, 2, 4 and 6. The ADCs first convert the channels with even numbers, and then the channels with the odd numbers 1, 3, 5 and 7 (see the figure below.) Figure 6-29 8-channel mode cycle time (hardware filter) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 407 Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Cycle time of the module in 8-channel mode (hardware filter) The channel conversion time, including module communication time, is 91 ms. The module must change to the second channel of the group using OptoMOS relays when conversion is completed. Opto-MOS relays require 7 ms for switching and settling. Each channel requires a time of 98 ms, i.e. the total cycle time equals 196 ms. Cycle time = (tK + tU) x 2 Cycle time = (91 ms + 7 ms) x 2 Cycle time = 196 ms tC: Conversion time for one channel tC: Time for changing over to the other channel in a channel group 8-channel mode (software filter) Analog-to-digital conversion in this mode is similar to conversion in 8-channel mode (hardware filter). The four ADCs of the module simultaneously convert channels 0, 2, 4 and 6. The ADCs first convert the channels with even numbers, and then the channels with the odd numbers 1, 3, 5 and 7 (see the figure below.) Figure 6-30 8-channel mode cycle time (software filter) S7-300 Module data 408 Manual, 06/2017, A5E00105505-AJ Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Cycle time of module in 8-channel mode (software filter) However, the channel conversion time is oriented on the programmed noise suppression. The channel conversion time is 76 ms, including communication time, when you set an interference frequency of 50 Hz. The channel conversion time is 65 ms when you set an interference frequency of 60 Hz. You can reduce channel conversion times to 16 ms by setting an interference frequency of 400 Hz. As in "hardware filter, 8channel" mode, the module has to change to the second channel of the group within a changeover time of 7 ms using the Opto-MOS relays. The table below shows this correlation. Table 6- 30 Cycle times in 8-channel mode (software filter) Programmed noise suppression Channel cycle time* Module cycle time (all channels) 50 Hz 83 ms 166 ms 60 Hz 72 ms 144 ms 400 Hz 23 ms 46 ms * Channel cycle time = channel conversion time +7 ms channel changeover time within the group 4-channel mode (hardware filter) In this mode, the module does not change between the channels of the groups. The four ADCs of the module simultaneously convert the channels 0, 2, 4 and 6. Figure 6-31 4-channel mode cycle time (hardware filter) Cycle time of the module in 4-channel mode (hardware filter) The converted value settles to 100 % within 80 ms and is updated every 10 ms when 4channel mode is set. The channel and module cycle times are always identical, as the module does not change between the channels of a group: 10 ms. Channel conversion time = channel cycle time = module cycle time = 10 ms S7-300 Module data Manual, 06/2017, A5E00105505-AJ 409 Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Cycle time extension due to wire-break monitoring The wire-break monitoring software function of the module is available in all operating modes. The 8-channel mode (hardware or software filter modes) extends module cycle times by 4 ms, irrespective of the number of channels at which wire-break monitoring is enabled. In 4-channel mode (hardware filter), the module interrupts processing of input data for the duration of 170 ms and performs a line continuity check. That is, each line continuity check extends the module cycle time by 93 ms. Unused channels Set the "disabled" value at the "measurement type" parameter for unused channels. This setting reduces module cycle times. You must short-circuit all unused channels of an active group, that is, you short-circuit the positive and negative inputs of these channels. Effect of this measure: Measurement errors at the channels used of a group are avoided Diagnostic messages from the unused channel in a group are suppressed Short-circuit to M or L The module does not suffer any damage if you short-circuit an input channel to M or L.. The channel continues to output valid data and does not report a diagnostics event. Special features of channel groups with respect to hardware interrupts upon limit violation You can set the high and low limits triggering hardware interrupts separately for each channel in STEP 7. End of cycle interrupt You can synchronize a process with the conversion cycle of the module by enabling the end of cycle interrupt. The interrupt is set when all active channels have been converted. Table 6- 31 The table below shows the contents of the 4 bytes of additional OB40 information during process or end of cycle interrupts. Content of the 4 bytes with additional information 27 26 25 24 23 22 21 20 Byte Special analog flags High limit exceeded at channel 7 6 5 4 3 2 1 0 0 Low limit exceeded at channel 7 6 5 4 3 2 1 0 1 2 bits per channel to identify the range End of cycle event Free byte X 2 3 S7-300 Module data 410 Manual, 06/2017, A5E00105505-AJ Analog modules 6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0) Programming restrictions when operating SM 331; AI 8 x TC with PROFIBUS masters which only support DPV0. When operating the SM 331; AI 8 xTC analog input module on an ET 200M PROFIBUS slave system and the PROFIBUS master is not an S7 master, certain parameters are not permitted. Non-S7 masters do not support hardware interrupts. All parameters associated with these functions are disabled for this reason. This includes hardware interrupt enable, hardware restrictions and end of cycle interrupt enable. All other parameters are allowed. Operating the module on the ET 200M Distributed IO device Operation of SM 331; AI 8 x TC on ET 200M requires one of the following IM 153 x: IM 153-1; as of 6ES7153-1AA03-0XB0, E 01 IM 153-2; as of 6ES7153-2AA02-0XB0, E 05 IM 153-2; as of 6ES7153-2AB01-0XB0, E 04 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 411 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Order number 6ES7331-7PE10-0AB0 Properties The SM 331; AI 6 x TC isolated analog input module has the following properties: 6 inputs in one group Electrical isolation 250 VAC between channels Support for user calibration via SIMATIC PDM Compensation via internal or external cold spot comparison, or via remote access by means of a separate thermoresistor module. Measurement type can be set for each channel - Voltage - Temperature Resolution of 15 bits + sign Any measuring range for each channel Programmable diagnostics and diagnostic interrupt Limit value monitoring can be set for 6 channels Programmable hardware interrupt when limit is exceeded Electrically isolated from the CPU Resolution The maximum resolution of the measured value (15 bits + sign or 0.1 K) is independent of the programmed integration time. Diagnostics For information on diagnostics messages at the "group diagnostics" parameter, refer to chapter Diagnostic messages of analog input modules (Page 296). Hardware interrupts Hardware interrupts can be set in STEP 7 for all channels. S7-300 Module data 412 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Terminal assignment The figures below show various connection possibilities. These examples apply to all channels (channels 0 to 5). Wiring: Thermocouple with internal compensation With this kind of compensation, the module detects the temperature at the reference junction of the connector. Thermocouple with compensating line (extension) to front connector Backplane bus interface Analog digital converter (ADC) External cold spot comparison (ADC and current source) Figure 6-32 Internal compensation S7-300 Module data Manual, 06/2017, A5E00105505-AJ 413 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Wiring: Thermocouple with external compensation With this type of compensation, the temperature of the terminals at the reference junction is established using a Pt 100 Klima resistance thermometer with a temperature range of -145 C to +155 C (see terminals 35, 36, 39, and 40). Thermocouple with terminal for external temperature compensation via copper wire at front connector Backplane bus interface Analog digital converter (ADC) External cold spot comparison (ADC and current source) Figure 6-33 External compensation If no Pt 100 resistance thermometer is available, the reference junction can be read using a thermoresistor module. The measured temperature values are then transferred to module AI 6 x TC via data record 2 (for details on the structure of data record 2, see the figure "Structure of data record 2 for TC"). S7-300 Module data 414 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Wiring: Thermocouple via reference junction With this kind of compensation, the temperature of the terminals at the reference junction is regulated at 0 C or 50 C. Thermocouple via reference-junction terminal with copper wire at front connector Backplane bus interface Analog digital converter (ADC) External cold spot comparison (ADC and current source) Reference junction regulated at 0 C or 50 C, for example, via compensation box (for each channel) or a thermostat Figure 6-34 Reference junction S7-300 Module data Manual, 06/2017, A5E00105505-AJ 415 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Wiring: Voltage input Applied input voltage Backplane bus interface Analog digital converter (ADC) External cold spot comparison (ADC and current source) Figure 6-35 Voltage input Technical specifications Technical specifications Dimensions and weight Dimensions (W x H x D) (mm) 40 x 125 x 120 Weight approx. 272 g Module-specific data Supports isochronous mode No Cable length * shielded Max. 200 m Max. 80 m in voltage ranges 80 mV and where thermocouples are used. S7-300 Module data 416 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Technical specifications Voltages, currents, electrical potentials Rated electronics supply voltage L + * Reverse polarity protection Constant measuring current for resistance-type transmitters 24 VDC Yes Typ. 0.9 mA Electrical isolation * between channels and the backplane bus * between channels and electronics power supply * between channels In groups of Yes Yes Yes 1 Maximum potential difference * between channels (UCM) * Between the channels and Minternal (Viso) Isolation test voltage 250 VAC 250 VAC 2,500 VDC Current consumption * from the backplane bus * from supply voltage L+ Power loss of the module max. 100 mA max. 150 mA Typ. 2.2 W Generation of analog values Measuring principle * Integration/conversion time/resolution (per channel) Integrating Yes programmable * Integration time in ms(1) 10/16.67/20/100 * Basic conversion time in ms(2) 30/50/60/300 * Additional conversion time for wire-break monitoring 65 ms * Resolution (including overshoot range) 15 bits + sign * Interference frequency suppression at interference frequency f1 in Hz 400/60/50/10 Measured value smoothing none/weak/medium/strong S7-300 Module data Manual, 06/2017, A5E00105505-AJ 417 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Technical specifications Interference frequency suppression, error limits Interference frequency suppression at f = n x (f1 1%), (f1 = interference frequency) n = 1.2, etc. * Common mode interference (CMV < 250 VAC) * Series-mode interference (peak interference value < rated input range) Crosstalk between inputs > 130 dB(3) > 90 dB > 130 dB(3) Operational limit (across entire temperature range, relative to measurement range end value in the selected input range, 060 C). Note: This limit does not cover the temperature-error comparison points. Voltage input * 25 mV * 50 mV * 80 mV * 250 mV * 500 mV * 1V 0.12% 0.08% 0.06% 0.05% 0.05% 0.05% Thermocouple(4) (5) Type T Type U Type E Type J Type L Type K Type N Type R Type S Type B(5) Type C Type TxK/XK(L) -200 C to +400 C 0.6 C -230 C to -200 C 1.6 C -150 C to +600 C 0.9 C -200 C to -150 C 1.2 C -200 C to +1000 C 0.5 C -230 C to -200 C 1.3 C -150 C to +1200 C 0.5 C -210 C to -150 C 1.2 C -150 C to +900 C 0.9 C -200 C to -150 C 1.7 C -150 C to +1372 C 0.8 C -220 C to -150 C 1.6 C -150 C to +1300 C 1.1 C -220 C to -150 C 1.9 C +100 C to +1769 C 1.2 C -50 C to +100 C 2.2 C +100 C to +1769 C 1.2 C -50 C to +100 C 1.9 C +700 C to +1820 C 1.7 C +500 C to +700 C 1.9 C +200 C to +500 C 4.4 C +100 C to +2315 C 2.3 C 0 C +100 C 2.5 C -150 C +800 C 1.0 C -200 C -150 C 1.5 C S7-300 Module data 418 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Technical specifications Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected input range) Voltage input * 25 mV * 50 mV * 80 mV * 250 mV * 500 mV * 1V 0.04% 0.03% 0.03% 0.02% 0.02% 0.02% Thermocouple(5) Type T Type U Type E Type J Type L Type K Type N Type R Type S Type B(5) Type C Type TxK/XK(L) -150 C to +400 C 0.4 C -230 C to -150 C 1.0 C -150 C to +600 C 0.4 C -200 C to -150 C 1.0 C -100 C to +1000 C 0.2 C -230 C to -100 C 1.0 C -150 C to +1200 C 0.2 C -210 C to -150 C 0.5 C -50 C to +900 C 0.4 C -200 C to -50 C 1.0 C -100 C to +1372 C 0.3 C -220 C to -100 C 1.0 C -150 C to +1300 C 0.5 C -220 C to -150 C 1.2 C +200 C to +1769 C 0.8 C -50 C to +200 C 1.5 C +100 C to +1769 C 0.8 C -50 C to +100 C 1.5 C +700 C to +1820 C 1.0 C +500 C to +700 C 1.3 C +200 C to +500 C 3.0 C +100 C to +2315 C 0.5 C 0 C to +100 C 1.0 C -150 C to +800 C 0.5 C -200 C to -150 C 1.0 C The accuracy of the temperature measurement with internal compensation (terminal temperature) is derived from: (4) (6) * Error for the analog input of the type of thermocouple used * Measuring accuracy for the temperature of the internal reference junction 1.5 K S7-300 Module data Manual, 06/2017, A5E00105505-AJ 419 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Technical specifications The accuracy of the temperature measurement with external compensation by means of thermoresistors connected locally or via remote access by means of an external thermoresistor module is derived from: (4) The accuracy of the temperature measurement with compensation of the external reference junction, which is maintained at 0 C/50 C, is derived from: (4) * Error for the analog input of the type of thermocouple used * Measuring accuracy for the type of thermoresistor used for compensation purposes * Error for the compensation input (local connection) 0.5 K * Error for the thermoresistor module (remote connection) * Error for the analog input of the type of thermocouple used * Measuring accuracy for the temperature of the reference junction Temperature error (relative to input range) Voltage input * 25 mV * 50 mV * 80 mV * 250 mV * 500 mV * 1V 0.0023%/K 0.0015%/K 0.0010%/K 0.0010 %/K 0.0010 %/K 0.0010%/K Thermocouple (at integration time of 100 ms) Type T 0.0060 K/K Type U 0.0175 K/K Type E 0.0086 K/K Type J 0.0086 K/K Type L 0.0175 K/K Type K 0.0143 K/K Type N 0.0175 K/K Type R 0.0115 K/K Type S 0.0115 K/K Type B 0.0200 K/K Type C 0.0515 K/K Type TxK/XK(L) 0.0143 K/K Linearity error (relative to input range) 0.05% Repeat accuracy (in settled state at 25 C, relative to input range) 0.05% S7-300 Module data 420 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Technical specifications Status, interrupts, diagnostics Interrupts * Hardware interrupt Programmable (channels 0 to 5) * Diagnostic interrupt programmable Diagnostic functions programmable * Group error display * Reading diagnostics information red LED (SF) Supported Sensor selection data Input ranges (rated values) / input impedance * Thermocouple * Voltage Type B, C, N, E, R, S, J, L, T, K, U, TxK/XK (L) 10 M 25 mV 50 mV 80 mV 250 mV 500 mV 1V 10 M 10 M 10 M 10 M 10 M Maximum input voltage for voltage input (destruction limit) 35 VDC continuous; 75 VDC for the duration of max. 1 s (duty factor 1:20) Characteristics linearization programmable Temperature compensation programmable * Internal temperature compensation * External temperature compensation with Pt 100 * Compensation for 0 C reference junction temperature * Compensation for 50 C reference junction temperature * Technical unit of temperature measurement Supported Supported Supported Supported Degrees Centigrade/Degrees Fahrenheit/Kelvin S7-300 Module data Manual, 06/2017, A5E00105505-AJ 421 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Technical specifications Wiring of the signal sensors using a 40-pin front connector 1. The integration time of the module at 400 Hz suppression is displayed in HW Config as 2.5 ms. To achieve the required resolution of 15 bits (plus sign), an integration time of 10 ms is needed. 2. If wire-break monitoring is active, the module cycle is performed within the basic conversion time + 65 ms. and the reaction time to a change in the step input is no longer than twice the module-cycle time. If wire-break monitoring is inactive, in the best-case scenario the module-cycle time is exactly the same as the integration time. However, this time interval cannot be guaranteed due to the time needed to process the input channels. If wire-break monitoring is inactive, the reaction time to a change in the step input is no longer than four times the integration time. 3. Common mode interference suppression and crosstalk between inputs are executed at > 130 dB, if 10 Hz, 50 Hz, or 60 Hz has been selected as the interference frequency. If 400 Hz has been selected as the interference frequency, common mode interference suppression and crosstalk between inputs are implemented at > 110 dB 4. The operational limit comprises only the basic error of the analog input at Ta = 25 C and the total temperature error. The total error must include the compensation error of the cold reference junction. Internal compensation of the reference junction = max. 1.5 C External compensation of the reference junction = accuracy of the external thermoresistor used 0.1 C. External compensation of the reference junction, which maintains the reference junction at 0 C or 50 C = accuracy of temperature control for the reference junction. 5. An integration time of 100 ms is recommended for thermocouple measurements. Integration times set lower than this will result in a higher repeat-accuracy error for the temperature measurements. 6. With thermocouple type B, a missing compensation of the reference junction temperature has no significant effect owing to its slight increase from approx. 0 C to 40 C. With missing compensation and set measuring type "Compensation to 0 C", the deviation with thermocouple type B at measuring temperatures between: - 700 C and 1820 C is < 0.5 C - 500 C and 700 C is < 0.7 C. If the reference junction temperature is approximately that of the module temperature, "internal compensation" should be set. As a result, the error for the temperature range from 500 C to 1820 C is reduced to < 0.5 C. S7-300 Module data 422 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) 6.11.1 Measurement types and measuring ranges Measurement types and measuring ranges The measurement type and measuring range is configured at the "measuring range" parameter in STEP 7. Selected measurement type Measuring range Voltage 25 mV 50 mV 80 mV 250 mV 500 mV 1V TC-L00C: (thermocouple, linear, 0 C reference temperature) Type B TC-L50C: (thermocouple, linear, 50 C reference temperature) Type E TC-IL: (thermocouple, linear, internal comparison) TC-EL: (thermocouple, linear, external comparison) Type C Type J Type K Type L Type N Type R Type S Type T Type U Type TxK/XK(L) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 423 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) 6.11.2 Programmable parameters Adjustable parameters For general information on programming analog modules, refer to the section titled Programming analog modules (Page 294). Parameters Range of values Default Type of parameter Scope Yes/no No Static Channel Yes/no No Yes/no No Yes/no No Dynamic Module Yes/no Yes Diagnostics * * Group diagnostics With wirebreak monitoring Enable * Diagnostic interrupt * Hardware interrupt when limit exceeded * Auto-calibration * Temperature unit Degrees Celsius; degrees Fahrenheit; Kelvin degrees Celsius Dynamic Module * Interference frequency suppression 400 Hz; 60 Hz; 50 Hz; 10 Hz 50 Hz Dynamic Module disabled TC-IL: Dynamic Channel Measurement * Measurement type TC-IL thermocouple (linear, internal comparison) TC-EL thermocouple (linear, external comparison) TC-L00C thermocouple (linear, 0 C reference temperature) TC-L50C thermocouple (linear, 50 C reference temperature) * Measuring range See chapter Measurement types and Type K measuring ranges (Page 423) * Response to open thermocouple Overflow; underflow Overflow Dynamic Channel * Smoothing None None Dynamic Channel Local thermoresistor Dynamic Channel Low Average High * External reference junction Local thermoresistor S7-300 Module data 424 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Parameters * Temperature coefficient Range of values Default Type of parameter Scope 0.003850 (IPTS-68) 0.003850 (ITS-90) 0.003916 0.003902 0.003920 0.003910 (GOST) 0.003850 (IPTS-68) Dynamic Module Dynamic Channel Hardware-interrupt trigger * High limit 32511 to -32512 32767 * Low limit From - 32512 to 32511 -32768 6.11.3 Additional information relating to SM 331; AI 6 x TC Using the module The following hardware and software requirements must be met to use the SM 331; AI 6 x TC isolated S7-300 analog input module: If the module is to be used centrally in S7-300, all CPUs must have firmware version 2.6 or higher (with the exception of 6ES7318-2AJ00-0AB0). If the module is to be used on a distributed basis in ET 200M, the following IM 153 modules are suitable: 6ES7153-1AA03-0XB0, product version 12 or higher 6ES7153-2BA02-0XB0 6ES7153-2BA82-0XB0 6ES7153-4BA00-0XB0 6ES7153-4AA01-0XB0 A GSD file must be used if the module is part of a distributed installation and controlled by a master produced by a third-party manufacturer with DPV1 support (operation with DPV0 is not supported). The GSD file for the selected IM 153 is available for download from the Internet (http://www.siemens.com/automation/service&support). STEP 7 V5.4 SP4 (HSP0158) or higher For user calibration: SIMATIC PDM V6.0 + SP3 + HF2 (HSP0158) or PDM V6.0 + SP4 or higher and EDD for ET 200M "DP_IOSystem_Siemens_ET200M_Module.Device" V1.1.10 or higher. Unused channels Set the "disabled" value at the "measurement type" parameter for unused channels. Unused channels should also be short-circuited at the connection plug. Effect of this measure: You prevent measurement errors at the unused channels. You suppress diagnostic messages from the unused channels. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 425 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Short-circuit to M or L The module does not suffer any damage if you short-circuit an input channel to M or L. The channel continues to output valid data and does not report a diagnostics event. Special features of channel groups with respect to hardware interrupts when limit is exceeded You can set the high and low limits triggering hardware interrupts separately for each channel in STEP 7. Hardware interrupt The table below shows the contents of the 4 bytes of additional OB40 information during a hardware interrupt. Content of the 4 bytes with additional information Special 2 bits per channel to identify the range analog flags High limit exceeded at channel Low limit undershot at channel 27 26 25 24 23 22 21 20 Byte 5 4 3 2 1 0 0 5 4 3 2 1 0 1 Free byte 2 Free byte 3 Startup characteristics and compensation time monitoring (watchdog) for external cold spot compensation via remote thermoresistor When the module starts up, all inputs report an overflow (32767). Once a compensation value has been received via data record 2, the module starts to read the TC inputs and to output correct data. If the module does not receive any data from data record 2 within 5 minutes of startup, a reference channel fault is reported in the standard channel diagnostics data. If enabled, a diagnostic interrupt is sent. The module features time monitoring (watchdog) set to 5 minutes, which is reset when a new compensation value is received via data record 2. If the module does not receive any data from data record 2 within the 5 minute interval set for the time-monitoring function in normal operation, a reference channel fault is reported in the standard channel diagnostics data. If enabled, a diagnostic interrupt is sent. Internal calibration while the process is running The module can compensate most of the internal temperature-drift errors. Internal calibration while the process is running is always executed after startup, when parameters are reassigned, and when the power is switched on/off. Once the relevant parameters have been activated, internal calibration while the process is running is also performed if the ambient temperature at the module changes by 5 degrees Celsius. Enabling calibration while the process is running interrupts the module I/O cycle until calibration is complete. The duration of the interruption depends on the programmed interference frequency; see the table below for information about this relationship. S7-300 Module data 426 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Duration of interruption caused by calibration while the process is running Interference frequency Duration of interruption 10 Hz 600 ms 50 Hz 120 ms 60 Hz 100 ms 400 Hz (100 Hz) 60 ms Calibration while the process is running should be activated to ensure measuring accuracy over a long period of time. Some applications do not permit an interruption of the I/O cycle. In such cases, you can disable the parameter for calibration while the process is running, although this will result in less accurate measurements over time. The parameter for calibration is activated as standard while the process is running. Compensation of the reference junction If the measuring point is exposed to a different temperature than the free ends of the thermocouple (connection point), a voltage known as the thermoelectric voltage arises between the free ends. The level of the thermoelectric voltage depends on the difference between the temperature at the measuring point and that at the free ends, as well as on the type of materials combined in the thermocouple. Because a thermocouple always detects any temperature difference, the free ends at the reference junction must be maintained at a certain temperature to determine the temperature at the measuring point. External compensation of the reference junction via remote thermoresistor The reference-junction temperature can also be measured via an external module and transferred to the AI 6 x TC isolated module by means of SFC 58 in data record 2 (DR2). The permitted reference temperature corresponds to the Pt100 climatic temperature range for platinum thermoresistors. -145.0 C tref +155.0 C -229.0 F < tref <+311.0 F +128.2 K < tref <+327.6 K The Kelvin measurement is only limited to 327.6 if the reference temperature is output in technical units. If the reference temperature is reported in standard units, the Kelvin measurement limit is 428.2 K. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 427 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) If a reference value above the permitted temperature limit is received in DR2, it will cause a reference channel fault, which is displayed in the standard channel diagnostic data. If enabled, a diagnostic interrupt is sent. Note If an analog input module such as AI 8 x thermoresistor is used to measure the referencejunction temperature, the thermoresistor module parameters for the output structure and the measuring accuracy must be represented by bytes 0 and 1 in data record 2. This is shown in the figure "Structure of data record 2 for SM 331; AI 6 x TC". If the external thermoresistor module does not provide correct information about data structure and scaling, it will lead to inaccurate measurements being output by the isolated SM 331; AI 6 x TC module. S7-300 Module data 428 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Structure of data record 2 for SM 331; AI 6 x TC Figure 6-36 Structure of data record 2 for SM 331; AI 6 x TC S7-300 Module data Manual, 06/2017, A5E00105505-AJ 429 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Compensation of the thermocouple via an external Pt100 element with external thermoresistor module Because of the flexible structure of data record 2, you can use a separate external Pt100 element for each channel. In addition, the channels can also be grouped together by means of the user application in such a way that they all use the same external Pt100. This simply requires the same temperature value to be specified in DR2 for all the channels which use the same reference temperature. Note Reference-junction compensation also results in an error in the temperature measured by the isolated AI 6 x TC module. For this reason, great care must be taken when detecting the reference junction. To keep this error to an absolute minimum, the reference-junction temperature must remain as constant as possible. Example: Transfer of a temperature value as a cold-spot temperature for channels 0 to 5, from a thermoresistor module to AI 6 x TC: Input address of AI 6 x TC: 238 (module address) Input address of the thermoresistor: 128 (channel address) Occupied memory: M 20.0: Request bit for SFC "WR_REC" M 20.1: Busy bit for SFC "WR_REC" MW 22: Return value for SFC "WR_REC" MW 0 to MW 12: Memory for data transfer (see table below). UN UN SPB M M END 20.0 20.1 // Check the request: new cold spot temperature // Check whether WR_REC is busy // Skip, if no transfer is required ist U M 20.1 //Check whether WR_REC is busy SPB WRT //Create the memory for data transfer L B#16#01 // Transfer the temperature in hundredthsl // of a degree (Pt100 climatic)) T MB 0 L B#16#02 // Transer the temperature in Kelvin T MB 1 L PEW 128 // Read out the input address of the used channel of // the thermoresistor module T MW 2 // for channel 0 of AI 6 x TC T MW 4 // for channel 1 of AI 6 x TC T MW 6 // for channel 2 of AI 6 x TC T MW 8 // for channel 3 of AI 6 x TC T MW 10 // for channel 4 of AI 6 x TC S7-300 Module data 430 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) T MW 12 // Transfer the cold-spot temperature to AI 6 x TC CALL "WR_REC" REQ :=M20.0 // Request bit for data transfer :=B#16#54 :=W#16#EE // Input address of AI 6 x TC :=B#16#2 // Data record number must be set to 2 WRT: IOID LADDR RECNUM RECORD :=P#M 0.0 Byte 14 RET_VAL BUSY :=MW22 :=M20.1 U SPB END: // for channel 5 ofAI 6 x TC M END CLR = 20.1 M // Indicator for the memory for data // transfer, 14 bytes long // Return value for SFC "WR_REC" // Busy bit of SFC "WR_REC" // check whether WR_REC is busy 20.0 // Reset request for cold-spot // temperature NOP 0 This is just an example. The logic and memory allocation must be adapted to the structure of the particular PLC program used. The return value of SFC "WR_REC" (MW 22) can be evaluated in accordance with the structure of the PLC program used. Additional information is available in the manual titled System Software for S7-300/400 System and Standard Functions (http://support.automation.siemens.com/WW/view/en/1214574). 6.11.4 Firmware update via HW Config for analog input module SM 331; AI 6 x TC Introduction Depending on the available comaptible function updates, the module AL 6 x TC can be updated to the newest firmware version. The most recent firmware versions are available from your Siemens representative or from the Internet (http://www.siemens.com/automation/service&support). Requirements STEP 7 V 5.4 SP4 (HSP0158) or higher For central use of the module Al 6 x TC in a S7-300, the firmware update must occur in the CPU-operating mode STOP. If the CPU is in the RUN operating mode, it may result in unexpected behavior and the module will first be available again after a network off/network on. If the module Al 6 x TC is set in a distributed IO device ET 200M, a firmware update is also possible in the CPU-operating mode RUN. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 431 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Firmware update This is how you update the firmware of a central or distributed module with the IM 153: 1. Select the module Al 6 x TC in HW Config. 2. Select the "SPS" > "Update Firmware" menu command. 3. Use the "Browse" button to select the path to the firmware files (*.upd). 4. Click the "Execute" button. - The module performs the firmware update. For additional information, refer to the STEP 7 online help. Note * During the firmware update, the OB 83 (alarm due to removing and inserting modules), the OB 85 (program execution error) and the OB 86 (error due to module rack failure) are opened. If the diagnostics alarm of the module is approved, the OB 82 will also be opened during the firmware update. Make sure that the OB is set correspondingly. * If the red LED (SF) on the module blinks, an error occurred during the firmware update and the update must be repeated. In this case, the bootloader version Ex.x.x is displayed in the online diagnostics. * A firmware update through HW-config is not permitted if the Al 6 x TC module is in redundant mode. Identification of the firmware After the firmware update, you must label the firmware version on the module. S7-300 Module data 432 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) 6.11.5 I&M data for identifying the analog input module SM 331; AI 6 x TC Properties I data: Information about the module, which is normally found on the module casing. I-data is write-protected. They include: Hardware release status Firmware release status Serial number M data: System-dependent information (e.g. plant designation). M data is created during configuration. All identification data (I&M-data) is retentively saved in a module and supports you with the following tasks: Error search and repair in the system Testing the system configuration Finding changes to the system hardware Reading and writing the identification data with STEP 7 System-dependent information is configured in the properties dialog field of the module. You obtain information on the module (I data) from the module status dialog. The systemdependent information on the module is displayed here too. Note I&M data can only be written if the CPU is in the STOP operating mode. The Al 6 x TC supports only I&M0 and I&M1 data. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 433 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) 6.11.6 Calibration of analog input module SM 331; AI 6 x TC Introduction The SM 331 is calibrated at the factory and complies with the specified accuracy values. As a rule, there is no need to recalibrate the module. With certain systems, it may be advisable or even a requirement laid down in standards (as required by particular institutions in the food and beverage or pharmaceutical industries) to recalibrate the module once it has been integrated into the system, for example, at specific time intervals. Particularly in systems where sensors detect and/or process relatively low voltages and/or currents, it may be advisable to perform recalibration when the module is in the system including all connected cables. This approach compensates any influence by cables and/or temperature. If you carry out a calibration procedure, new calibration values are detected and saved retentively on the module. This means that the calibration values determined for the module at the factory prior to delivery are not lost when users perform their own calibration work. You can revert to these original calibration values at any time. Note The calibration values from each channel are saved retentively on the module for a specific measuring range, which means they only apply to the measuring range in which the user calibration work was performed. If the parameters of a channel which has active user-calibration values are reassigned to change the measuring range, the calibration values saved at the factory for this channel and this measuring range are used from this point on. However, the user-calibration values still remain in the memory; they are not overwritten until the user calibrates the channel again. But if the original measuring range is reset for this channel without the user performing the calibration procedure again, the user-calibration values which have already been established become effective once more. Requirements The calibration function can only be used in a distributed installation and in conjunction with the SIMATIC PDM ("Process Device Manager"). The following requirements must be met to use the module calibration functions: SIMATIC PDM V6.0 + SP3 or higher + HF2 in conjunction with HSP158, or SIMATIC PDM V6.0 + SP4 or higher, and the EDD for the ET 200M, "DP_IOSystem_Siemens_ET200M_Module.Device", Version V1.1.10 or higher User calibration is not permitted if the AI 6 x TC module is running in redundant mode. S7-300 Module data 434 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Launching the calibration function The following diagrams show the sequence of a user calibration in SIMATIC PDM V6.0 + SP5. More recent versions of SIMATIC PDM can deviate from the content of these diagrams. The module calibration function is launched in the SIMATIC PDM via for the selected module. Figure 6-37 Calibration function Once the calibration function has been launched, the calibration start screen appears. Each time a new channel is selected, the module reads the following general data and calibration values: General data: Measuring range: Currently programmed measuring range for the selected channel Date: Date and time when the displayed calibration values were determined Calibration: Indicates whether the currently active calibration values are factory-set or user values S7-300 Module data Manual, 06/2017, A5E00105505-AJ 435 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Calibration values: Offset: Currently active offset for the analog digital converter Gain: Currently active gain for the analog digital converter CJ Offset: Currently active temperature offset for the internal reference-temperature sensor (only relevant for TC-IL thermocouples) TC Gain: Currently active gain for recording the temperature (only relevant for TC-IL, TC-EL, TC-L00C, and TC-L50C thermocouples) Slot address of the module Current system ID (HID) Selection of the channel to be calibrated Cancels the calibration function Resets the calibration values of the selected channel to the factory settings Starts user calibration for the selected channel Current calibration values Figure 6-38 User-calibration values S7-300 Module data 436 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Options Now you can: Start user calibration for the selected channel -> "User calibration" button Reset the calibration values set at the factory for the selected channel -> "Reset to factory setting" button Cancel the calibration function -> "Cancel" button Note If you reset the currently active channel to its factory settings, the original calibration values saved on the module when it was delivered become valid again. Any usercalibration values which may exist for this channel are then lost. You cannot restore these user-calibration values. User calibration User calibration is started for the selected channel by pressing the "User calibration" button. A 24 V load voltage must be applied at the module for calibration. The user calibration function re-establishes the calibration values required by the selected channel in accordance with the measuring range which has been programmed for that channel. Calibration can be executed in the CPU's RUN or STOP operating modes. Please note that in the CPU's RUN operating mode, the module does not return any correct analog values to the process for the duration of the calibration. Note While user calibration is ongoing, none of the module channels can handle new process values. * All analog input values of the module are set to 0x7FFF ("invalid analog value") until calibration is complete. * All channels indicate this status by means of a corresponding channel-diagnostic function using the second type of diagnosis (see Section 1.7, "Diagnostics of the analog input module SM 331; AI 6 x TC isolated"). The previously selected channel is calibrated using the calibration display which is output. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 437 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Calibration consists of several different steps, during which the individual calibration values are determined. If a fault occurs during calibration or if new parameters are assigned to the module, the calibration of the relevant channel is canceled and the most recently active calibration values for the channel become effective once more. All of the calibration values recorded up to this point are lost. The module can now handle the current process values once again. Calibration can be canceled at any time once it has been started. Following cancelation, the previously active calibration values take effect again and the calibration values recorded up to this point are lost. The module can now handle the current process values once again. S7-300 Module data 438 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) You must provide a voltage and/or temperature during user calibration. You do this by using the appropriate external wiring and an external voltage/temperature transmitter. As shown in the figure "User-calibration status", the "Instructions" field indicates the numbers of the pins where the calibration stimulus can be applied. The first pin number corresponds to the positive terminal, the second to the negative terminal. The accuracy of the calibration depends on the accuracy of the voltage/temperature supplied. To ensure that the module maintains the specified measuring accuracy following user calibration, the voltage/temperature provided must demonstrate an accuracy at least twice that defined for the module. Inaccurate voltages or temperatures will result in an incorrect calibration. Here you will find instructions on how to carry out the currently active calibration step Here you will find information relating to the currently active calibration step Here you will find information relating to the current status of the calibration procedure Cancels the calibration function completely Cancels the currently active calibration and returns to the calibration start screen Skips the currently active calibration step Confirms the currently active calibration step and proceeds to the next step Figure 6-39 User-calibration status S7-300 Module data Manual, 06/2017, A5E00105505-AJ 439 Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) Status Several different calibration steps are required to calibrate a channel, depending on the measurement type which has been set. The "Status" field indicates whether the last calibration step was completed with or without a fault. If a fault occurs while a calibration step is being executed, the fault is indicated here and the calibration for that channel is canceled. All calibration values recorded up to that point are deleted. The calibration values which were active before the user-calibration function was launched take effect once more. Comment The following entries are displayed in the "Comment" field: The number of calibration steps completed thus far The number of calibration steps which still need to be carried out for the channel to be fully calibrated The calibration value currently being determined by the module Instructions The "Instructions" field indicates which actions the user has to personally carry out for the currently active calibration step. Perform the actions indicated here and confirm by pressing the "Continue" button. The module now executes the actions required for the currently active calibration step. If this step is processed without a fault, the function proceeds to the next calibration step. If you want to avoid recording existing calibration values again during user calibration, confirm the currently active calibration step by pressing the "Skip this step" button (rather than "Continue"). In this case, the factory-set calibration value is used for the calibration step which has been skipped (see "Comment" field). S7-300 Module data 440 Manual, 06/2017, A5E00105505-AJ Analog modules 6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0) In the last calibration step, the values determined during the course of calibration are displayed. New calibration values Cancels the calibration function completely Cancels the currently active calibration and returns to the calibration start screen Confirms the determined calibration values, saves the values, and returns to the calibration start screen Figure 6-40 User-calibration values You can now adopt these calibration values as the new values for this channel by pressing the "Continue" button. The calibration values are saved retentively and the channel calibration is complete. If you do not want to use the displayed calibration values, you can either return to the start screen and start a new calibration procedure by pressing the "Restart" button, or exit calibration altogether by pressing the "Cancel" button. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 441 Analog modules 6.12 Analog output module SM 332; AO 8 x 12 bit; (6ES7332-5HF00-0AB0) 6.12 Analog output module SM 332; AO 8 x 12 bit; (6ES7332-5HF00-0AB0) Order number 6ES7332-5HF00-0AB0 Order number: "SIPLUS S7-300 module" 6AG1332-5HF00-2AB0 Properties 8 outputs in one group The output can be selected by individual channel - Voltage output - Current output Resolution 12 bits Programmable diagnostics and diagnostic interrupt Programmable diagnostic interrupt Electrically isolated from the backplane bus interface and load voltage Supports parameter reassignment in RUN Diagnostics For information on diagnostics messages at the "group diagnostics" parameter, refer to chapter Diagnostic messages of analog output modules (Page 296). Terminal assignment The diagrams below show various wiring options. These examples apply to all channels (channel 0 to 7). Note When you switch the rated load voltage (L+) off and on, the outputs can return incorrect voltage/current values for the duration of about 500 ms. S7-300 Module data 442 Manual, 06/2017, A5E00105505-AJ Analog modules 6.12 Analog output module SM 332; AO 8 x 12 bit; (6ES7332-5HF00-0AB0) Wiring: 2 and 4-wire connection for voltage output The following image depicts: 2-wire connection, no compensation for line impedance and 4-wire connection with compensation for line impedance DAC Internal supply Equipotential bonding Functional ground Backplane bus interface Electrical isolation Figure 6-41 Wiring and block diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 443 Analog modules 6.12 Analog output module SM 332; AO 8 x 12 bit; (6ES7332-5HF00-0AB0) Wiring: Current output DAC Internal supply Equipotential bonding Functional ground Backplane bus interface Electrical isolation Figure 6-42 Wiring and block diagram S7-300 Module data 444 Manual, 06/2017, A5E00105505-AJ Analog modules 6.12 Analog output module SM 332; AO 8 x 12 bit; (6ES7332-5HF00-0AB0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 272 g Module-specific data Supports parameter reassignment in RUN Yes Reaction of non-programmed outputs Return the output value which was valid before the parameterization Supports isochronous mode no Number of inputs 8 Cable length * shielded max. 200 m Voltages, currents, electrical potentials Rated load voltage L+ * Reverse polarity protection * Electrical isolation * between channels and the backplane bus * between channels and electronics power supply * between channels * between channels and load voltage L+ 24 V DC yes yes yes no yes Maximum potential difference * between S- and MANA (CMV) Isolation test voltage 3 V DC 500 V DC Current consumption * from the backplane bus * From supply voltage L+ Power loss of the module max. 100 mA max. 340 mA typ. 6.0 W Generation of analog values Resolution, including sign * 10 V; 20 mA; 4 mA to 20 mA; 1 V to 5 V 11 bits + sign * 0 V to 10 V; 0 mA to 20 mA; * Conversion time (per channel) 12 Bit max. 0.8 ms Transient recovery time * with resistive load * with capacitive load * with inductive load 0.2 ms 3.3 ms 0.5 ms (1 mH) 3.3 ms (10 mH) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 445 Analog modules 6.12 Analog output module SM 332; AO 8 x 12 bit; (6ES7332-5HF00-0AB0) Technical specifications Interference frequency suppression, error limits * Crosstalk between outputs > 40 dB Operational limit (across entire temperature range, relative to measurement range end value in the selected output range) * Voltage output * Current output 0.5 % 0.6 % Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected output range) * Output voltage * Output current * Temperature error (relative to output range) * Linearity error (relative to output range) * Repeat accuracy (in transient state at 25 C, relative to output range) * Output ripple; bandwidth 0 kHz to 50 kHz (relative to output range) 0.4 % 0.5 % 0.002 %/K + 0.05 % 0.05 % 0.05 % Status, interrupts, diagnostics Interrupts * Diagnostic interrupt Diagnostic functions * * Group error display Reading diagnostics information programmable programmable red LED (SF) supported Actuator selection data Output ranges (rated values) * Voltage 10 V 0 V to 10 V 1 V to 5 V * Current 20 mA 0 mA to 20 mA 4 mA to 20 mA Load impedance (in the rated output range) * For voltage outputs - * Capacitive load For current outputs - at CMV < 1 V - with inductive load Min. 1 k Max. 1 F max. 500 max. 600 max. 10 mH Voltage output * Short-circuit protection * Short-circuit current yes max. 25 mA S7-300 Module data 446 Manual, 06/2017, A5E00105505-AJ Analog modules 6.12 Analog output module SM 332; AO 8 x 12 bit; (6ES7332-5HF00-0AB0) Technical specifications Current output * noload voltage max. 18 V * Destruction limit against external voltages/currents * Voltage at outputs to MANA max. 18 V continuous; 75 V for a duration of max. 1 s * Current (duty factor 1:20) max. 50 mA d.c. Wiring of the actuators * for voltage output 4-wire connection * for current output 2-wire connection using a 40-pin front connector supported supported Configuration in RUN Special considerations must be given if you use the Configuration in RUN function. SF LED is lit: Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or module), although diagnostics are no longer pending and the module is operating correctly. Solution: Only change the configuration when no diagnostics are pending for the module or Pulling and plugging the module. 6.12.1 SM 332; AO 8 x 12 Bit - Output ranges Introduction You can configure the outputs for operation as voltage or current outputs, or disable them. You program the outputs at the "output type" parameter in STEP 7. Output type "Voltage" and output range " 10 V" are set by default at the module. You can always use this combination of output type and range without having to program the SM 332; AO 8 x 12 Bit in STEP 7. Table 6- 32 Output ranges Selected type of output Output range Voltage 1 V to 5 V 0 V to 10 V 10 V Current 0 mA to 20 mA 4 mA to 20 mA 20 mA See also Representation of analog values for analog output channels (Page 279) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 447 Analog modules 6.12 Analog output module SM 332; AO 8 x 12 bit; (6ES7332-5HF00-0AB0) 6.12.2 Programmable parameters Introduction For general information on programming analog modules, refer to the chapter Programming analog modules (Page 294). The table below provides an overview of configurable parameters, including defaults: Table 6- 33 Overview of the parameters of SM 332; AO 8 x 12 Bit Parameter Range of values Default Parameter type Scope Enable * Diagnostic interrupt yes/no no dynamic Module Yes/no No static Channel disabled V dynamic Channel Voltage 10 V dynamic Channel Diagnostics * Group diagnostics Output * Output type Current See chapter output ranges (Page 447) * Output range Reaction to CPU STOP ASS HLV Outputs zero current/voltage ASS Hold last value Assigning parameters to channels The parameters can be set separately at each output channel of SM 332; AO 8 x 12 Bit. You can assign separate parameters to each output channel. Assign the parameters you set at the SFCs in the user program to the channel groups. Each output channel of SM 332; AO 8 x 12 Bit is thus assigned to a channel group, i.e. output channel 0 > channel group 0, for example. Note The output may carry invalid interim values if you modify output ranges while SM 332; AO 8 x 12 bit is in RUN. See also Diagnostic messages of analog output modules (Page 296) S7-300 Module data 448 Manual, 06/2017, A5E00105505-AJ Analog modules 6.12 Analog output module SM 332; AO 8 x 12 bit; (6ES7332-5HF00-0AB0) 6.12.3 Additional information on SM 332; AO 8 x 12 Bit Unused channels To take unused output channels of SM 332; AO 8 x 12 Bit off power, set the "disabled" argument at the "output type" parameter. Disabled channels do not have to be wired. Line continuity check SM 332; AO 8 x 12 Bit only performs a line continuity check at the current outputs. In output ranges 0 mA to 20 mA and 20 mA, a "reliable" wire-break check is not possible for output values of 200 A. Short-circuit test SM 332; AO 8 x 12 Bit only performs a short-circuit test at the voltage outputs. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 449 Analog modules 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) Order number 6ES7332-7ND02-0AB0 Order number: "SIPLUS S7-300 module" 6AG1332-7ND02-4AB0 Properties 4 outputs in 4 channel groups The output channels can be programmed as - Voltage output - Current output Resolution 16 bits Supports isochronous mode Supports parameter reassignment in RUN Programmable diagnostics and diagnostic interrupt Electrical isolation between: - backplane bus interface and analog output channel - analog output channels - analog output and L+, M - Backplane bus circuit and L+, M Supports parameter reassignment in RUN Diagnostics For information on diagnostic messages at the "group diagnostics" parameter, refer to chapter Diagnostic messages of analog output modules (Page 296). Terminal assignment The diagrams below show various wiring options. Note When you switch the rated load voltage (L+) off and on, the output may carry invalid interim values for the duration of ca. 10 ms. S7-300 Module data 450 Manual, 06/2017, A5E00105505-AJ Analog modules 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) Wiring: 4-wire connection Backplane bus interface Electrical isolation Equipotential bonding Functional ground Figure 6-43 Wiring and block diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 451 Analog modules 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) Wiring: Current output Backplane bus interface Electrical isolation Equipotential bonding Functional earthing Figure 6-44 Wiring and block diagram S7-300 Module data 452 Manual, 06/2017, A5E00105505-AJ Analog modules 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 220 g Module-specific data Supports parameter reassignment in RUN * Reaction of non-programmed outputs yes return the output value which was valid before the parameterization Supports isochronous mode yes Number of outputs 4 Cable length max. 200 m * shielded Voltages, currents and potentials Rated load voltage L+ * Reverse polarity protection 24 V DC yes Electrical isolation * between channels and the backplane bus * between channels and electronics power supply * between channels yes yes yes Maximum potential difference * between outputs (ECM) * between MANA and Minternal (VISO) Isolation test voltage 200 V DC / 120 V AC 200 V DC / 120 V AC 1500 V DC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 120 mA max. 290 mA typ. 3 W Generation of analog values Resolution (including sign) * 10 V * 0 V to 10 V * 1 V to 5 V * 20 mA * 0 mA to 20 mA * 4 mA to 20 mA 16 bits 15 bits 14 bits 16 bits 15 bits 15 bits Conversion time (per channel) * in standard mode * in isochronous mode <200 s 640 s S7-300 Module data Manual, 06/2017, A5E00105505-AJ 453 Analog modules 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) Technical specifications Basic execution time of the module (independent of the number of enabled channels) * in standard mode * in isochronous mode <800 s 750 s Transient recovery time * with resistive load * with capacitive load * with inductive load 0.2 ms 3.3 ms 0.5 ms (1 mH) / 3.3 ms (10 mH) Interference suppression, error limits Crosstalk between outputs > 100 dB Operational limit (across entire temperature range, relative to measurement range end value in the selected output range) * Voltage output * Current output 0.12% 0.18% Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected output range) * Voltage output 10 V 0 V to 10 V 1 V to 5 V 0.02% 0.02% 0.04% * Current output 20 mA 0 mA to 20 mA 4 mA to 20 mA 0.02% 0.02% 0.04% Temperature error (relative to output range) * Voltage output * Current output 0.0025%/K 0.004%/K Linearity error (relative to output range) 0.004% Repeat accuracy (in transient state at 25, relative to output range) 0.002 % Output ripple; range 0 Hz to 50 kHz (relative to output range) 0.05 % Status, interrupts, diagnostics Interrupts * Diagnostic interrupt Diagnostic functions * Group error display * Reading diagnostic information Set substitute values programmable programmable red LED (SF) supported yes, programmable S7-300 Module data 454 Manual, 06/2017, A5E00105505-AJ Analog modules 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) Technical specifications Actuator selection data Output ranges (rated values) * 10 V Voltage 0 V to 10 V 1 V to 5 V * 20 mA Current 0 mA to 20 mA 4 mA to 20 mA Load impedance (in the rated range of the output) * For voltage outputs - * Capacitive load For current outputs - inductive load Min. 1 k Max. 1 F max. 500 max. 1 mH Voltage output * Short-circuit protection * Short-circuit current yes max. 40 mA Current output * max. 18 V noload voltage Destruction limit against external voltages/currents * * Voltage at outputs to MANA Current for voltage output - * 4-wire connection (measuring lead) for current output - 75 V for the duration of max. 1 s (duty factor 1:20) 20) max. 50 mA d.c. Wiring of the actuators * max. 15 V, continuous using a 20-pin front connector supported supported 2-wire connection Configuration in RUN Special considerations must be given if you use the Configuration in RUN function. SF LED is lit: Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or module), although diagnostics are no longer pending and the module is operating correctly. Solution: Only change the configuration when no diagnostics are pending for the module or Pulling and plugging the module. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 455 Analog modules 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) 6.13.1 SM 332; AO 4 x 16 Bit - Output ranges Introduction You can configure the outputs for operation as voltage or current outputs, or disable these. You program the outputs at the "output type" parameter in STEP 7. The output type "Voltage" and output range " 10 V" are set by default at the module. You can always use this combination of output type and range without having to program the SM 332; AO 4 x 16 Bit in STEP 7. Output ranges You program the output ranges for voltage and current outputs in STEP 7. Table 6- 34 Output ranges SM 332; AO 4 x 16 Bit Selected type of output Output range Voltage 1 V to 5 V 0 V to 10 V 10 V Current 0 mA to 20 mA 4 mA to 20 mA 20 mA S7-300 Module data 456 Manual, 06/2017, A5E00105505-AJ Analog modules 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) 6.13.2 Programmable parameters Introduction For general information on programming analog modules, refer to the chapter Programming analog modules (Page 294). The table below provides overview of programmable parameters and of their defaults. Table 6- 35 Overview of the parameters of SM 332; AO 4 x 16 Bit Parameters Range of values Default Parameter type Scope Enable * yes/no no dynamic Module yes/no no static Channel disabled V dynamic Channel Output type Voltage 10 V Output range See chapter Output ranges for SM 332; AO 4 x 16 Bit (Page 456) dynamic Channel Diagnostic interrupt Diagnostics * Group diagnostics Output * * Current Reaction to CPU STOP ASS HLV Outputs zero current/voltage ASS Hold last value Assigning parameters to channels The parameters can be set separately at each output channel of SM 332; AO 4 x 16 Bit. You can assign separate parameters to each output channel. Assign the parameters you set at the SFCs in the user program to the channel groups. Each output channel of SM 332; AO 4 x 16 Bit is thus assigned to a channel group, i.e. output channel 0 > channel group 0, for example. Note The output may carry invalid interim values if you modify output ranges while SM 332; AO 4 x 16 bit is in RUN. See also Diagnostic messages of analog output modules (Page 296) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 457 Analog modules 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) 6.13.3 Isochronous mode Properties Reproducible reaction times (i.e. of the same length) are achieved in a SIMATIC system by means of a constant DP bus cycle, and synchronization of the single cyclic processes outlined below: Independent user program cycle. The length of the cycle time may vary due to non-cyclic program branching. Independent and variable DP cycle on the PROFIBUS subnet Cyclic operation of the backplane bus of the DP slave. Cyclic signal preparation and conversion at the electronic modules of the DP slave. The constant DP cycle runs in synchronism and at the same length. The CPU run levels (OB61 to OB64) and isochronous IO are synchronized with this cycle. I/O data are therefore transferred at defined and constant intervals (isochronous mode.) Maximum flutter: 50 s. Requirements The DP master and slave must support isochronous mode. You require STEP 7 V5.2 or higher. Mode of operation: Isochronous mode Conditions of isochronous mode: Processing and activation time TWA between reading the output value to the transfer buffer and loading it into the D/A converter for output 750 s TDPmin 1100 s Diagnostic interrupt max. 4 x TDP S7-300 Module data 458 Manual, 06/2017, A5E00105505-AJ Analog modules 6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0) Calculation of filter and processing times The same time conditions always apply, regardless of the number of configured channels. Figure 6-45 Calculation of the processing time and refresh time of the output Definition of isochronous mode During the time TO - TWA, the module reads the output data and saves the data internally. The internal processing time for each channel is used to write the results into the individual D/A converters. Further information You can find additional information on isochronous mode in the online help for STEP 7, and in the operating instructions Distributed I/O System ET 200M. (http://support.automation.siemens.com/WW/view/en/1142798) 6.13.4 Additional information on SM 332; AO 4 x 16 Bit Unused channels To take unused output channels of SM 332; AO 4 x 16 Bit off power, set the "disabled" argument at the "output type" parameter, and leave the terminal open. Substitute values You can configure the SM 332; AO 4 x 16 Bit for CPU STOP mode as follows: Outputs off power, hold last value or set substitute values. The set substitute values must lie within the output range. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 459 Analog modules 6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0) 6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0) Order number 6ES7332-5HD01-0AB0 Order number: "SIPLUS S7-300 module" 6AG1332-5HD01-7AB0 Properties 4 outputs in one group The output can be selected by individual channel - Voltage output - Current output Resolution 12 bits Programmable diagnostics and diagnostic interrupt Electrically isolated to backplane bus interface and load voltage Supports parameter reassignment in RUN Diagnostics For information on diagnostic messages at the "group diagnostics" parameter, refer to chapter Diagnostic messages of analog output modules (Page 296). Terminal assignment The diagrams below show various wiring options. Note When you switch the rated load voltage (L+) off and on, the outputs can return incorrect voltage/current values for the duration of about 500 ms. S7-300 Module data 460 Manual, 06/2017, A5E00105505-AJ Analog modules 6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0) Wiring: 2 and 4-wire connection for voltage output The following Fig. represents the 2-wire connection with no compensation for line resistors and the 4-wire connection with compensation for line resistors. 2-wire connection, no compensation for line resistors 4-wire connection, with compensation for line resistors Equipotential bonding Functional earthing Internal supply Electrical isolation Backplane bus interface Analog-to-Digital Converter (ADC) Figure 6-46 Wiring and block diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 461 Analog modules 6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0) Wiring: Current output Equipotential bonding Functional earthing Internal supply Electrical isolation Backplane bus interface Analog-to-Digital Converter (ADC) Figure 6-47 Wiring and block diagram S7-300 Module data 462 Manual, 06/2017, A5E00105505-AJ Analog modules 6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 220 g Module-specific data Supports parameter reassignment in RUN yes Reaction of non-programmed outputs Return the output value which was valid before the parameterization Supports isochronous mode no Number of outputs 4 Cable length * shielded max. 200 m Voltages, currents, electrical potentials Rated load voltage L+ * Reverse polarity protection 24 V DC Yes Electrical isolation * between channels and the backplane bus * between channels and electronics power supply * between channels * between channels and load voltage L+ Yes Yes no Yes Maximum potential difference * between S- and MANA (CMV) Isolation test voltage 3 V DC 500 V DC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 60 mA max. 240 mA typ. 3 W Generation of analog values Resolution (including overshoot range) * 10 V; 20 mA; * 4 mA to 20 mA; 1 V to 5 V * 0 V to 10 V; 0 mA to 20 mA Conversion time (per channel) 11 bits + sign 12 bits max. 0.8 ms Transient recovery time * with resistive load * with capacitive load * with inductive load 0.2 ms 3.3 ms 0.5 ms (1 mH) 3.3 ms (10 mH) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 463 Analog modules 6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0) Technical specifications Interference frequency suppression, error limits Crosstalk between outputs > 40 dB Operational limit (across entire temperature range, relative to measurement range end value in the selected output range) * Voltage output * Current output 0.5 % 0.6 % Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected output range) * Voltage output * Current output 0.4 % 0.5 % Temperature error (relative to output range) 0.002 %/K Linearity error (relative to output range) 0.05 % Repeat accuracy (in settled state at 25 C, relative to output range) 0.05 % Output ripple; range 0 Hz to 50 kHz (relative to output range) 0.05 % Status, interrupts, diagnostics Interrupts * Diagnostic interrupt Diagnostic functions * * Group fault display Reading diagnostic information Setting substitute values Programmable programmable Red LED (SF) Supported Yes, programmable Actuator selection data Output ranges (rated values) * Voltage 10 V 0 V to 10 V 1 V to 5 V * Current 20 mA 0 mA to 20 mA 4 mA to 20 mA Load impedance (in the rated range of the output) * For voltage outputs - * Capacitive load For current outputs - at CMV < 1 V - inductive load Min. 1 k Max. 1 F max. 500 max. 600 max. 10 mH Voltage output * Short-circuit protection * Short-circuit current Yes max. 25 mA Current output * noload voltage max. 18 V S7-300 Module data 464 Manual, 06/2017, A5E00105505-AJ Analog modules 6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0) Technical specifications Destruction limit against external voltages/currents * Voltage at outputs to MANA max. 18 V continuous; 75 V for the duration of max. 1 s (duty factor 1:20) * Current max. 50 mA d.c. using a 20-pin front connector Wiring of the actuators * for voltage output - * 4-wire connection (measuring lead) for current output - supported supported 2-wire connection Parameter reassignment in RUN If you reassign parameters in RUN, the following special characteristic applies. SF LED is lit: If a diagnostics was pending prior to reconfiguration, the SF LEDs (on CPU, IM or module) may be lit even though diagnostics is no longer pending and the module is operating correctly. Solution: Only assign new parameters if no diagnostics is pending, or unplug module and plug it in again. 6.14.1 Output ranges of SM 332; AO 4 x 12 Bit Introduction You can configure the outputs for operation as voltage or current outputs, or disable them. You program the outputs at the "output type" parameter in STEP 7. The output type "Voltage" and output range " 10 V" are set by default at the module. You can always use this combination of output type and range without having to program the SM 332; AO 4 x 12 Bit in STEP 7. Output ranges Program the voltage and current output ranges in STEP 7. Table 6- 36 Output ranges of SM 332; AO 4 x 12 Bit Selected type of output Output range Voltage 1 V to 5 V 0 V to 10 V 10 V Current 0 mA to 20 mA 4 mA to 20 mA 20 mA S7-300 Module data Manual, 06/2017, A5E00105505-AJ 465 Analog modules 6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0) 6.14.2 Programmable parameters Introduction For general information on programming analog modules, refer to the chapter Programming analog modules (Page 294). The table below provides overview of programmable parameters and of their defaults. Table 6- 37 Overview of the parameters of SM 332; AO 4 x 12 Bit Parameters Range of values Default Parameter type Scope Enable * Diagnostic interrupt yes/no no dynamic Module yes/no no static Channel disabled V dynamic Channel Voltage 10 V dynamic Channel Diagnostics * Group diagnostics Output * Output type Current See table of Output ranges for SM 332; * Output range AO 4 x 12 Bit Reaction to CPU STOP ASS Outputs zero current/voltage HLV Hold last value SSV Set substitute value ASS Assigning parameters to channels The parameters can be set separately at each output channel of SM 332; AO 4 x 12 Bit. You can assign separate parameters to each output channel. Assign the parameters you set at the SFCs in the user program to the channel groups. Each output channel of SM 332; AO 4 x 12 Bit is thus assigned to a channel group, i.e. output channel 0 > channel group 0, for example. Note The output may carry incorrect interim values if you modify output ranges while SM 332; AO 4 x 12 Bit is in RUN. See also Diagnostic messages of analog output modules (Page 296) S7-300 Module data 466 Manual, 06/2017, A5E00105505-AJ Analog modules 6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0) 6.14.3 Additional information on SM 332; AO 4 x 12 Bit Unused channels To take unused output channels of SM 332; AO 4 x 12 Bit off power, set the "disabled" argument at the "output type" parameter. Disabled channels do not have to be wired. Line continuity check SM 332; AO 4 x 12 Bit only performs a line continuity check at the current outputs. In output ranges 0 mA to 20mA and 20 mA, a "reliable" wire-break check is not possible for output values of-20s to 200 A. Short-circuit test SM 332; AO 4 x 12 Bit only performs a short-circuit test at the voltage outputs. Substitute values You can configure the SM 332; AO 4 x 12 Bit for CPU STOP mode as follows: Outputs off power, hold last value or set substitute values. The set substitute values must lie within the output range. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 467 Analog modules 6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0) 6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0) Order number: "Standard module" 6ES7332-5HB01-0AB0 Order number: "SIPLUS S7-300 module" 6AG1332-5HB01-2AB0 Properties 2 outputs in one group The outputs can be set separately as - voltage output - current output Resolution 12 bits Programmable diagnostics and diagnostic interrupt Electrically isolated to backplane bus interface and load voltage Supports parameter reassignment in RUN Diagnostics For information on diagnostic messages at the "group diagnostics" parameter, refer to chapter Diagnostic messages of analog output modules (Page 296). Terminal assignment The diagrams below show various wiring options. Note When you switch the rated load voltage (L+) off and on, the outputs can return incorrect voltage/current values for the duration of about 500 ms. S7-300 Module data 468 Manual, 06/2017, A5E00105505-AJ Analog modules 6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0) Wiring: 2 and 4-wire connection for voltage output 2-wire connection: no compensation for line impedance 4-wire connection: with compensation for line impedance Equipotential bonding Functional earthing Internal supply Electrical isolation Backplane bus interface Analog-to-Digital Converter (ADC) Figure 6-48 Wiring and block diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 469 Analog modules 6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0) Wiring for current output Equipotential bonding Functional earthing Internal supply Electrical isolation Backplane bus interface Digital analog converter (DAC) Figure 6-49 Wiring and block diagram S7-300 Module data 470 Manual, 06/2017, A5E00105505-AJ Analog modules 6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight Approximately 220 g Module-specific data Supports parameter reassignment in RUN Yes Reaction of non-programmed outputs Return the output value which was valid before the parameterization Supports isochronous mode no Number of outputs 2 Cable length * shielded max. 200 m Voltages, currents, electrical potentials Rated load voltage L+ * Reverse polarity protection 24 V DC Yes Electrical isolation * between channels and the backplane bus * between channels and electronics power supply * between channels * between channels and load voltage L+ Yes Yes no Yes Maximum potential difference * between S- and MANA (CMV) Isolation test voltage 3 V DC 500 V DC Current consumption * from the backplane bus * from load voltage L+ (no-load) Power loss of the module max. 60 mA max. 135 mA typ. 3 W Generation of analog values Resolution (including overshoot range) * 10 V; 20 mA; * 4 mA to 20 mA; 1 V to 5 V * 0 V to 10 V; 0 mA to 20 mA Conversion time (per channel) 11 bits + sign 12 bits max. 0.8 ms Transient recovery time * with resistive load * with capacitive load * with inductive load 0.2 ms 3.3 ms 0.5 ms (1 mH) 3.3 ms (10 mH) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 471 Analog modules 6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0) Technical specifications Interference frequency suppression, error limits Crosstalk between outputs > 40 dB Operational limit (across entire temperature range, relative to measurement range end value in the selected output range) * Voltage output * Current output 0.5 % 0.6 % Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected output range) * Voltage output * Current output 0.4 % 0.5 % Temperature error (relative to output range) 0.002 %/K Linearity error (relative to output range) 0.05 % Repeat accuracy (in settled state at 25 C, relative to output range) 0.05 % Output ripple; range 0 Hz to 50 kHz (relative to output range) 0.05 % Status, interrupts, diagnostics Interrupts * Diagnostic interrupt Diagnostic functions * Group error display * Reading diagnostic information Setting substitute values programmable programmable red LED (SF) supported Yes, programmable Actuator selection data Output ranges (rated values) * Voltage 10 V 0 V to 10 V 1 V to 5 V * Current 20 mA 0 mA to 20 mA 4 mA to 20 mA Load impedance (in the rated range of the output) * For voltage outputs - * capacitive load For current outputs - at CMV < 1 V - inductive load min. 1 k max. 1 F max. 500 max. 600 max. 10 mH Voltage output * Short-circuit protection * Short-circuit current Yes max. 25 mA Current output * noload voltage max. 18 V S7-300 Module data 472 Manual, 06/2017, A5E00105505-AJ Analog modules 6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0) Technical specifications Destruction limit against external voltages/currents * Voltage at outputs to MANA max. 18 V continuous; 75 V for the duration of max. 1 s (duty factor 1:20) * Current max. 50 mA DC * Wiring of the actuators using a 20-pin front connector * for voltage output * supported - 2-wire connection - 4-wire connection (measuring line) for current output - supported supported 2-wire connection Reassigning parameters in RUN If you reassign parameters in RUN, the following special characteristic applies. SF LED is lit: If a diagnostics was pending prior to reconfiguration, the SF LEDs (on CPU, IM or module) may be lit even though diagnostics is no longer pending and the module is operating correctly. Solution: Only assign new parameters if no diagnostics is pending, or unplug module and plug it in again. 6.15.1 Output ranges of SM 332; AO 2 x 12 Bit Introduction You can configure the outputs for operation as voltage or current outputs, or disable them. You program the outputs at the "output type" parameter in STEP 7. Output type "Voltage" and output range " 10 V" are set by default at the module. You can always use this combination of output type and range without having to program the SM 332; AO 2 x 12 Bit in STEP 7. Output ranges Program the voltage and current output ranges in STEP 7. Table 6- 38 Output ranges of SM 332; AO 2 x 12 Bit Selected type of output Output range Voltage 1 V to 5 V 0 V to 10 V 10 V Current 0 mA to 20 mA 4 mA to 20 mA 20 mA S7-300 Module data Manual, 06/2017, A5E00105505-AJ 473 Analog modules 6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0) 6.15.2 Programmable parameters Introduction For general information on programming analog modules, refer to the chapter Programming analog modules (Page 294). The table below provides an overview of configurable parameters, including defaults: Table 6- 39 Overview of the parameters of SM 332; AO 2 x 12 Bit Parameter Range of values Default Parameter type Scope Enable * Diagnostic interrupt Yes/no No Dynamic Module Yes/no No Static Channel disabled V dynamic Channel Voltage 10 V dynamic Channel Diagnostics * Group diagnostics Edition * * Output type Output range Current See chapter Output ranges for SM 332; AO 2 x 12 Bit (Page 473) Reaction to CPU STOP ASS HLV SSV Outputs zero current/voltage ASS Hold last value Set substitute value Assigning parameters to channels The parameters can be set separately at each output channel of SM 332; AO 2 x 12 Bit. You can assign separate parameters to each output channel. Assign the parameters you set at the SFCs in the user program to the channel groups. Each output channel of SM 332; AO 2 x 12 Bit is thus assigned to a channel group, i.e. output channel 0 > channel group 0, for example. Note The output may carry invalid interim values if you modify output ranges while SM 332; AO 2 x 12 bit is in RUN. See also Diagnostic messages of analog output modules (Page 296) S7-300 Module data 474 Manual, 06/2017, A5E00105505-AJ Analog modules 6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0) 6.15.3 Additional information on SM 332; AO 2 x 12 Bit Unused channels To take unused output channels of SM 332; AO 2 x 12 Bit off power, set the "disabled" argument at the "output type" parameter. Disabled channels do not have to be wired. Line continuity check SM 332; AO 2 x 12 Bit only performs a line continuity check at the current outputs. In output ranges 0 mA to 20mA and 20 mA, a "reliable" wire-break check is not possible for output values of-20s to 200 A. Short-circuit test SM 332; AO 2 x 12 Bit only performs a short-circuit test at the voltage outputs. Substitute values You can configure the SM 332; AO 2 x 12 Bit for CPU STOP mode as follows: Outputs off power, hold last value or set substitute values. The set substitute values must lie within the output range. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 475 Analog modules 6.16 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) 6.16 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) Order number 6ES7334-0CE01-0AA0 Properties 4 inputs in one group and 2 outputs in one group Resolution 8 bits Programmable measurement type at each channel group - Voltage - Current Not programmable, measurement and output type defined by hardwiring Connected to potential of the backplane bus interface Electrically isolated to load voltage Terminal assignment The diagrams below show various wiring options. Note Note when wiring the SM 334: * analog ground MANA(terminal 15 or 18) is interconnected with chassis ground M of the CPU or interface module IM. Use a cable with a conductor cross-section of at least 1 mm2. The module will shut down if the ground connection between MANA and M is missing. Inputs are read with 7FFFH, and outputs return a value of 0. The module may be destroyed if operated without ground over a longer period of time. * the supply voltage for the CPU and/or the interface module (IM) may not be connected with reversed polarity. Reverse polarity will inevitably lead to the destruction of the module, because MANA develops an impermissible high potential (+24 V.) S7-300 Module data 476 Manual, 06/2017, A5E00105505-AJ Analog modules 6.16 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) Wiring: Voltage measurement and current output Internal supply Analog-to-Digital Converter (ADC) Inputs: Voltage measurement Outputs: Voltage output Digital-to-Analog Converter (DAC) Backplane bus interface Equipotential bonding Functional earthing Figure 6-50 Wiring and block diagrams S7-300 Module data Manual, 06/2017, A5E00105505-AJ 477 Analog modules 6.16 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) Wiring: 4-wire transducers for current measurement and voltage output Internal supply Analog-to-Digital Converter (ADC) Inputs: Current measurement with 4-wire transducer Outputs: Voltage output Digital-to-Analog Converter (DAC) Backplane bus interface Equipotential bonding Functional earthing Figure 6-51 Wiring and block diagrams S7-300 Module data 478 Manual, 06/2017, A5E00105505-AJ Analog modules 6.16 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight ca. 285 g Module-specific data Supports isochronous mode no Number of inputs 4 Number of outputs 2 Cable length * shielded max. 200 m Voltages, currents, electrical potentials Rated supply voltage of the rated electronics and load voltage L+ 24 VDC Electrical isolation * between channels and the backplane bus * between channels and electronics power supply between channels no yes no Maximum potential difference * between inputs and MANA (CMV) * between inputs (CMV) Isolation test voltage 1 VDC 1 VDC 500 VDC Current consumption * from the backplane bus * from supply and load voltage L+ (no load) Power loss of the module max. 55 mA max. 110 mA typ. 3 W Generation of analog input values Measuring principle * Resolution (including overshoot range) Actual value conversion 8 bits Integration/conversion time (per channel) * programmable * Integration time in s no <500 Basic execution time of inputs max. 5 ms Time constant of the input filter 0.8 ms S7-300 Module data Manual, 06/2017, A5E00105505-AJ 479 Analog modules 6.16 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) Technical specifications Generation of analog output values * Resolution (including overshoot range) 8 bits Conversion time (per channel) * programmable * Conversion time in s Basic execution time of outputs no <500 max. 5 ms Transient recovery time * with resistive load * with capacitive load * with inductive load 0.3 ms 3.0 ms 0.3 ms Interference frequency suppression, error limits for inputs Interference frequency suppression at F = n (f1 1 %) (f1 = interference frequency) * Common mode interference (Vpp < 1 V) Crosstalk between outputs > 60 dB > 50 dB Operational limit (across entire temperature range, relative to measurement range end value in the selected input range) * Voltage input * Current input 0,9 % 0,8 % Basic error limit (operational limit at 25 C, relative to measurement range end value of the selected input range) * Voltage input * Current input 0,7 % 0,6 % Temperature error (relative to input range) 0.005 %/K Linearity error (relative to input range) 0,05 % Repeat accuracy (in transient state at 25 C, relative to input range) 0,05 % Output ripple; range 0 Hz to 50 kHz (relative to output range) 0,05 % Interference frequency suppression, error limits of outputs Crosstalk between outputs > 40 dB Operational limit (across entire temperature range, relative to measurement range end value in the selected output range) * Voltage output * Current output 0,6 % 1,0 % Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected output range) * Voltage output * Current output 0,5 % 0,5 % Temperature error (relative to output range) 0.02 %/K Linearity error (relative to output range) 0,05 % Repeat accuracy (in transient state at 25 C, relative to output range) 0,05 % Output ripple (bandwidth relative to output range) 0,05 % Status, interrupts, diagnostics Interrupts none Diagnostic functions none S7-300 Module data 480 Manual, 06/2017, A5E00105505-AJ Analog modules 6.16 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) Technical specifications Sensor selection data Input ranges (rated values) / input impedance * Voltage * Current 0 V to 10 V/100 k 0 mA to 20 mA/50 Maximum voltage at voltage input (destruction limit) max. 20 V continuous; 75 V for max. duration of 1 s (duty factor 1:20) Maximum current at current input (destruction limit) 40 mA Wiring of the signal sensors using a 20-pin front connector * for voltage measurement supported * for current measurement as 2-wire transducer as 4-wire transducer supported with external supply Actuator selection data Output ranges (rated values) * Voltage * Current 0 V to 10 V 0 mA to 20 mA Load impedance (in the rated output range) * For voltage outputs - * capacitive load For current outputs - inductive load min. 5 k max. 1 F max. 300 max. 1 mH Voltage output * Short-circuit protection * Short-circuit current yes max. 11 mA Current output * noload voltage max. 15 V Destruction limit against external voltages/currents * Voltage at outputs to MANA * Current Wiring of the actuators * for voltage output 2-wire connection 4-wire connection (measuring line) max. 15 V, continuous max. 50 mA d.c. using a 20-pin front connector supported not supported S7-300 Module data Manual, 06/2017, A5E00105505-AJ 481 Analog modules 6.16 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) 6.16.1 SM 334; AI 4/AO 2 x 8/8 Bit - Function principle Introduction SM 334; AI 4/AO 2 x 8/8 bit is a non-isolated analog IO module. SM 334; AI 4/AO 2 x 8/8 Bit is not programmable. Addressing The I/O of the module are addressed beginning at the module start address. The address of a channel is derived from the module start address and an address offset. Input addresses Valid input addresses: Channel Address 0 Module start address 1 Module start address + 2 bytes address offset 2 Module start address + 4 bytes address offset 3 Module start address + 6 bytes address offset Output addresses Valid output addresses: Channel 6.16.2 Address 0 Module start address 1 Module start address + 2 bytes address offset Measurement and output type of SM 334; AI 4/AO 2 x 8/8 bit Introduction SM 334; AI 4/AO 2 x 8/8 Bit is not programmable. Defining the measurement and output type Set the measurement type (voltage, current) by hardwiring the input channel. Set the output type (voltage, current) by hardwiring the output channel. See also Representation of the values for analog input channels (Page 262) Representation of analog values for analog output channels (Page 279) S7-300 Module data 482 Manual, 06/2017, A5E00105505-AJ Analog modules 6.16 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) 6.16.3 Measurement and output ranges of SM 334; AI 4/ AO 2 x 8/8 bit Measuring ranges SM 334; AI 4/AO 2 x 8/8 Bit provides the 0 V to 10 V and 0 mA to 20 mA measuring ranges. By contrast to the other analog modules, the SM 334 has a lower resolution and no negative measuring ranges. Make allowances for this feature when reading the measured value tables Analog value representation in the 1 V to 10 V measuring ranges and Analog value representation in the 0 mA to 20 mA and 4 mA to 20 mA measuring ranges. Output ranges SM 334; AI 4/AO 2 x 8/8 Bit provides the 0 V to 10 V and 0 mA to 20 mA output ranges. Compared to the other analog modules, the SM 334 has a lower resolution, and its analog outputs do not have any overshoot ranges. Make allowances for this feature when reading the tables Analog value representation in the 0 V to 10 V and 1 V to 5 V output ranges and Analog value representation in the 0 mA to 20 mA and 4 mA to 20 mA output ranges. 6.16.4 Additional information on SM 334; AI 4/AO2 x 8/8 Bit Unused channels Always short-circuit unused input channels, and connect these to MANA. This optimizes interference immunity of the analog input module. Leave unused output channels open. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 483 Analog modules 6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) 6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) Order number: "Standard module" 6ES7334-0KE00-0AB0 Order number: "SIPLUS S7-300 module" 6AG1334-0KE00-2AB0 Properties 4 inputs in 2 groups and 2 outputs in one group Resolution of 12 bits + sign Programmable measurement type at each channel group: - Voltage (not adjustable for channel 0 and channel 1) - Resistance - Temperature Electrically isolated to the backplane bus interface Electrically isolated to load voltage Terminal assignment The diagrams below show various wiring options. Note When you switch the rated load voltage supply on/off, the output may assume invalid interim values below the rated load voltage. S7-300 Module data 484 Manual, 06/2017, A5E00105505-AJ Analog modules 6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) Wiring: Resistance measurement, voltage measurement and voltage output Figure 6-52 Wiring and block diagram S7-300 Module data Manual, 06/2017, A5E00105505-AJ 485 Analog modules 6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) Wiring: Resistance measurement and voltage output Figure 6-53 Wiring and block diagram Technical specifications Technical specifications Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 117 Weight approx. 200 g Module-specific data Supports isochronous mode No Number of inputs 4 * with resistive transducers 4 Number of outputs 2 Shielded cable length max. 100 m S7-300 Module data 486 Manual, 06/2017, A5E00105505-AJ Analog modules 6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) Technical specifications Voltages, currents, electrical potentials Supply voltage of the rated electronics and load voltage L+ * Reverse polarity protection 24 V DC Yes Constant measuring current for resistive transducers (pulsed) * For PT 100 * at 10 k typ. 490 A; from product version 06: 1.5 mA typ. 105 A Electrical isolation * between channels and the backplane bus * between channels and electronics power supply between channels Yes Yes No Maximum potential difference * between inputs and MANA (VCM) * between inputs (VCM) Isolation test voltage 1V 1V 500 V DC Current consumption * from the backplane bus * from supply and load voltage L+ (no load) Power loss of the module max. 60 mA max. 80 mA typ. 2 W Generation of analog input values Measuring principle Integrating Integration/conversion time (per channel) * programmable Yes * Integration time in ms 162/3 20 * Basic conversion time, including the integration time in ms 72 85 * Additional conversion time for resistance measurements in ms 72 85 * Resolution in bits (including overshoot range) 12 bits 12 bits * Interference frequency suppression at interference frequency f1 in Hz 60 50 Measured value smoothing programmable, in 2 stages Time constant of the input filter 0.9 ms Basic execution time of the module (all channels enabled) 350 ms Generation of analog output values Resolution (including overshoot range) 12 bits Conversion time (per channel) 500 s Transient recovery time * with resistive load * with capacitive load 0.8 ms 0.8 ms S7-300 Module data Manual, 06/2017, A5E00105505-AJ 487 Analog modules 6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) Technical specifications Interference frequency suppression, error limits for inputs Interference frequency suppression at F = n (f1 1 %) (f1 = interference frequency) * Common mode interference (Vpp < 1 V) * Seriesmode interference (peak interference value < rated input range) Crosstalk between inputs > 38 dB > 36 dB > 88 dB Operational limit (across entire temperature range, relative to the measurement range end value in the selected input range) * Voltage input 0 V to 10 V 0.7 % * Resistance input 10 k 3.5 % * Temperature input Pt 100 1% Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected input range) * Voltage input 0 V to 10 V 0.5 % * Resistance input 10 k 2.8 % * Temperature input Pt 100 0.8 % Temperature error (relative to input range) 0.01 %/K Linearity error (relative to input range) 0.05 % Repeat accuracy (in settled state at 25 C, relative to input range) 0.05 % Interference frequency suppression, error limits of outputs Crosstalk between outputs > 88 dB Operational limit (across entire temperature range, relative to measurement range end value in the selected output range) * Voltage output 1.0 % Basic error limit (operational limit at 25 C, relative to the measurement range end value in the selected output range) * Voltage output 0.85 % Temperature error (relative to output range) 0.01 %/K Linearity error (relative to output range) 0.01 % Repeat accuracy (in transient state at 25 C, relative to output range) 0.01 % Output ripple; range 0 Hz to 50 kHz (relative to output range) 0.1 % Status, interrupts, diagnostics Interrupts none Diagnostic function none Encoder selection data Input ranges (rated values) / input impedance * Voltage 0 V to 10 V 100 k * Resistance 10 k 10 M * Temperature Pt 100 10 M Maximum voltage at voltage input (destruction limit) max. 20 V continuous; 75 V for max. duration of 1 s (duty factor 1:20) S7-300 Module data 488 Manual, 06/2017, A5E00105505-AJ Analog modules 6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) Technical specifications Wiring of the signal transmitters * for voltage measurement supported * for resistance measurement with 2-wire connection with 3-wire connection with 4-wire connection supported supported supported Characteristics linearization * for resistance thermometers Technical unit of data formats programmable Pt 100 (Climatic range) degrees Centigrade Actuator selection data Output range (rated value) * Voltage 0 V to 10 V Load impedance (in the rated output range) * For voltage outputs - capacitive load min. 2.5 k * max. 1.0 F Voltage output * Short-circuit protection * Short-circuit current Yes max. 30 mA Destruction limit against external voltages/currents * Voltage at outputs to MANA Wiring of the actuators * for voltage output 2-wire connection 4-wire connection (measuring line) max. 15 V, continuous using a 20-pin front connector supported not supported * the error limits specified for the outputs are only valid when there is a high-ohm connection. In the entire load resistance range, an additional error of <0.9 % can result. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 489 Analog modules 6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) 6.17.1 Programmable parameters Introduction For general information on programming analog modules, refer to the chapter Programming analog modules (Page 294). The table below provides an overview of configurable parameters, including defaults: Table 6- 40 Summary of parameters SM 334; AI 4/AO 2 x 12 Bit Parameters Range of values Default Parameter type Scope Input Measurement * Measurement type disabled RTD-4L V Voltage R-4L Resistance (4-wire connection) RTD-4L Thermal resistance dynamic Channel dynamic Channel (linear, 4-wire connection) * Measuring range 0 V to 10 V Pt 100 Klima 10000 Pt 100 Klima Output * Output type disabled 0 V to 10 V * V Voltage 0 V to 10 V Output range 6.17.2 Measurement types and ranges Introduction You can configure the outputs for operation as voltage or current outputs, or disable these. You can wire the outputs as voltage outputs, or disable these. Program the outputs at the "measurement type" AND output type" parameters in STEP 7. Input defaults The "thermoelectric resistance (linear, 4-wire connection)" measurement type and "Pt 100 Klima" measuring range are set by default at the module. You can use these default settings without having to program the SM 334; AI 4/AO 2 x12 Bit in STEP 7. S7-300 Module data 490 Manual, 06/2017, A5E00105505-AJ Analog modules 6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) Options of wiring the input channels You can wire the input channels of SM 334; AI 4/AO 2 x 12 Bit in the following combinations: Channel Wiring versions Channels 0 and 1 * * Channels 2 and 3 * 2 x temperature or 2 x resistance 2 x voltage, * 2 x resistance, * 2 x temperature, * 1 x temperature and 1 x voltage, or * 1 x resistance and 1 x voltage Note Wiring both a temperature sensor and a resistor to channels 0 and 1 or 2 and 3 is not allowed. Reason: Common current source for both channels. Measuring ranges Program the measuring ranges in STEP 7. Table 6- 41 Measurement types and ranges Selected type of measurement Measuring range V: Voltage 0 V to 10 V R-4L: resistance (4-wire connection) 10 k RTD-4L: Thermoresistor (linear, 4-wire connection) Pt 100 Klima (temperature measurement) Output ranges of SM 334; AI 4/ AO 2 x 12 bit The "voltage" output type and "0 V to 10 V" output range are set by default at the module. You can always use this combination of the output type and range without having to program the SM 334; AO 4 x 2 Bit in STEP 7. Table 6- 42 Output ranges Selected type of output Output range Voltage 0 V to 10 V See also Representation of analog values for analog output channels (Page 279) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 491 Analog modules 6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0) 6.17.3 Additional information on SM 334; AI 4/ AO 2 x 12 bit Unused channels Set the "disabled" value at the "measurement type" parameter for unused input channels. This setting reduces module cycle times. Always short-circuit unused input channels, and connect these to MANA. This optimizes interference immunity of the analog input module. To take the unused output channels of SM 334; AI 4/AO 2 x 12 Bit off power, always set "disabled" argument at the "output type" parameter, and leave the connection open. S7-300 Module data 492 Manual, 06/2017, A5E00105505-AJ 7 Other signal modules Signal modules This chapter describes the technical data and properties of the S7-300 signal modules. 7.1 Module overview Introduction The table below summarizes the essential features of the signal modules described in this chapter. This overview supports you in selecting a module to suit your requirements. Table 7- 1 Special signal modules: Overview of properties Properties Simulator module SM 374; IN/OUT 16 Number of inputs/outputs * Suitable for... max. 16 inputs or outputs Simulation of: Dummy module DM 370 Position decoder module SM 338; POS-INPUT 1 slot reserved for nonprogrammable module * 3 inputs for absolute encoders (SSI) * 2 digital inputs for freezing encoder values Dummy for: * 16 inputs or * Interface modules * 16 outputs or * * 8 inputs and 8 outputs non-programmable signal modules * modules which occupy 2 slots Position detection using up to three absolute encoders (SSI) Encoder types: Absolute encoder (SSI), message frame length 13 bits, 21 bits or 25 bits Data formats: Gray code or binary code Isochronous mode supported no no yes Programmable diagnostics no no no Diagnostics interrupt no no programmable Special features Function adjustable with screwdriver the mechanical structure and addressing of the overall configuration remains unchanged when DM 370 is replaced with a different module. SM 338 does not support absolute encoders with a monoflop time > 64 s S7-300 Module data Manual, 06/2017, A5E00105505-AJ 493 Other signal modules 7.2 Simulator module SM 374; IN/OUT 16; (6ES7374-2XH01-0AA0) 7.2 Simulator module SM 374; IN/OUT 16; (6ES7374-2XH01-0AA0) Order number 6ES7374-2XH01-0AA0 Properties Properties of simulator module SM 374; IN/OUT 16: Simulation of: - 16 inputs or - 16 outputs or - 8 inputs and 8 outputs (each with the same start addresses!) Status displays for the simulation of inputs and outputs Function adjustable with screwdriver Note Do not operate the function selection switch in RUN! Configuration in STEP 7 The simulator module SM 374; IN/OUT 16 is not included in the STEP 7 module catalog. STEP 7 therefore does not recognize the SM 374 order number. "Simulate" the simulator module function required for your configuration as follows: To use the SM 374 with 16 inputs, define the order number of a digital input module with 16 inputs in STEP 7, for example: 6ES7321-1BH02-0AA0 To use the SM 374 with 16 outputs, define the order number of a digital output module with 16 outputs in STEP 7, for example: 6ES7322-1BH01-0AA0 To use the SM 374 with 8 inputs and 8 outputs, define the order number of a digital input/output module with 8 inputs and 8 outputs in STEP 7, for example: 6ES7323-1BH00-0AA0 S7-300 Module data 494 Manual, 06/2017, A5E00105505-AJ Other signal modules 7.2 Simulator module SM 374; IN/OUT 16; (6ES7374-2XH01-0AA0) Module view (without front panel door) Input status selector switch Function selector switch Channel number Status displays - green Technical data of SM 374; IN/OUT 16 Technical data Dimensions and weight Dimensions W x H x D (mm) Weight Module-specific data Optional simulation of 40 x 125 x 110 approx. 190 g 16 inputs 16 outputs 8 inputs and 8 outputs Voltages, currents, electrical potentials Current consumption from the backplane bus Power loss of the module max. 80 mA typ. 0.35 W Status, interrupts, diagnostics Status display Interrupts yes, green LED for each channel no Diagnostics functions no S7-300 Module data Manual, 06/2017, A5E00105505-AJ 495 Other signal modules 7.3 Dummy module DM 370; (6ES7370-0AA01-0AA0) 7.3 Dummy module DM 370; (6ES7370-0AA01-0AA0) Order number 6ES7 370-0AA01-0AA0 Properties The dummy module DM 370 reserves a slot for a non-configured module. It can be used as dummy module for: Interface modules (without reservation of address space) Non-configured signal modules (with reservation of address space) Modules which occupy 2 slots (with reservation of address space) When replacing the dummy module with another S7-300 module, the mechanical assembly and address assignment/addressing of the entire configuration remain unchanged. Configuration in STEP 7 Configure the DM 370 dummy module in STEP 7 only if you module for a programmed signal module. If the module reserves the slot for an interface module, you can discard module configuration in STEP 7. Modules which occupy 2 slots Install two dummy modules for modules which occupy 2 slots. You only reserve the address space using the dummy module in slot "x", rather than the dummy module in slot "x + 1". For details of the procedure, see the table below. The rack can receive up to 8 modules (SM/FM/CP.) When using two dummy modules to reserve a slot for a module of 80 mm width, you may still install 7 further modules (SM/FM/CP) because the dummy module only uses the address space for one module. S7-300 Module data 496 Manual, 06/2017, A5E00105505-AJ Other signal modules 7.3 Dummy module DM 370; (6ES7370-0AA01-0AA0) Module view Front view Rear view Address selector switch S7-300 Module data Manual, 06/2017, A5E00105505-AJ 497 Other signal modules 7.3 Dummy module DM 370; (6ES7370-0AA01-0AA0) Switch settings for addressing The table below shows how to set the switch on the rear panel of the module, according to the module type. Table 7- 2 Meaning of the switch settings of dummy module DM 370 Switch setting Meaning Use The dummy module reserves one slot. * Without active backplane bus: For configurations where a single slot is physically reserved, with electrical connection to the S7-300 bus. * With active backplane bus: no The module will not be configured, and does not use any address space. The dummy module reserves one slot. The module must be configured and occupies 1 byte in the input address space (system default: not in the process image.) For configurations where an addressed slot is reserved. Technical data of DM 370 Technical data Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 120 Weight approx. 180 g Voltages, currents, electrical potentials Current consumption from the backplane bus approx. 5 mA Power loss typ. 0.03 W S7-300 Module data 498 Manual, 06/2017, A5E00105505-AJ Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) Order number 6ES7 338-4BC01-0AB0 Properties Properties of position decoder module SM 338; POS-INPUT: 3 inputs for the connection of up to three absolute value encoders (SSI), and 2 digital inputs to freeze encoder values Allows direct reaction to encoder values in motion systems Processing of encoder values recorded by SM 338 in the user program Supports isochronous mode Selectable encoder value acquisition mode: - cyclic - isochronous Rated input voltage 24 VDC Nonisolated to the CPU Fast Mode selectable; with faster transducer action and compressed feedback interface. The Fast Mode is available from firmware version V2.0.0 in SM 338; POS-INPUT and can be selected from STEP 7 V5.3+SP2. Supported encoder types Encoder types supported by SM 338; POS-INPUT: Absolute value encoder (SSI), frame length 13 bit Absolute value encoder (SSI), frame length 21 bit Absolute value encoder (SSI), frame length 25 bit Supported data formats SM 338; POS-INPUT supports gray code and binary code. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 499 Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) Firmware update To extend functions and for troubleshooting, it is possible with the help of STEP 7 HWConfig to load firmware updates in the operating system memory of the SM 338; POSINPUT. Note When you boot the firmware update, the old firmware is deleted. If the firmware update is interrupted or terminated for some reason, thereafter the SM 338; POS-INPUT ceases to function properly. Reboot the firmware update and wait until this has completed successfully. Note The firmware update is only possible in remote operation if the header assembly (slave circuit) employed supports the system services required for this. 7.4.1 Isochronous mode Note For basic information on isochronous mode, refer to the SIMATIC; isochronous mode function manual. Hardware requirements To operate SM 338 in isochronous mode, you need: a CPU which supports isochronous mode a DP master which supports the constant bus cycle a slave interface (IM 153-x) which supports isochronous mode Properties SM 338 operates in non-isochronous or isochronous mode, depending on system parameters. In isochronous mode, data are exchanged between the DP master and SM 338 in synchronism to the PROFIBUS DP cycle. In isochronous mode, all 16 bytes of the feedback interface are consistent. If synchronism is lost due to disturbance or failure/delay of Global Control (GC), the SM 338 resumes isochronous mode at the next cycle without error reaction. If synchronism is lost, the feedback interface is not updated. S7-300 Module data 500 Manual, 06/2017, A5E00105505-AJ Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) 7.4.2 Wiring and block diagrams Wiring and block diagrams Error LED - red Connection to CPU ground Twisted-pair cables Wiring rules Important rules to observe wiring the module: Ground of the encoder supply is connected to CPU ground potential. Thus, establish a low impedance connection between pin 2 of SM 338 (M) and CPU ground. Always use shielded twisted-pair cable to wire encoder signals (pins 3 to 14.) Connect both ends of the shielding. Use the shield connection element to terminate the shielding on SM 338 (order number 6ES7390-5AA00-0AA0). Connect an external power supply if the maximum output current (900 mA) of the encoder supply is exceeded. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 501 Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) 7.4.3 Functions of SM 338; POS-INPUT; encoder value acquisition 7.4.3.1 Encoder value acquisition The absolute value encoder transfers its values in frames to the SM 338. The SM 338 initiates the frame transfer. In non-isochronous mode, the encoder values are acquired cyclically. In isochronous mode, the encoder values are acquired in synchronism with the PROFIBUS DP cycle at each Ti. Cyclic encoder value acquisition The SM 338 always initiates a frame transfer at the end of the programmed monoflop time. Asynchronously to these cyclic frames, the SM 338 processes the acquired encoder values cyclically, based on its refresh rate (refer to the chapter "Technical data of SM 338; POSINPUT (Page 512)"). Thus, cyclic acquisition returns encoder values of different ages. The difference between the min./max. age represents the jitter (refer to the chapter "Technical data of SM 338; POSINPUT (Page 512)".) Isochronous encoder value acquisition Isochronous encoder values acquisition is automatically set when the DP master system operates with active constant bus cycle, and the DP slave is in synchronism with the DP cycle. SM 338 initiates a frame transfer in each PROFIBUS DP cycle, at the time Ti. The SM 338 processes the transferred encoder values in synchronism with the PROFIBUS DP cycle. 7.4.3.2 Gray code/binary code converter When Gray code is set, the Gray code value returned by the absolute value encoder is converted into binary code. When binary code is set, the values returned by the encoder remain unchanged. Note When you set Gray code, the SM 338 always converts the entire encoder value (13, 21, 25 bits). As a result, any leading special bits will influence the encoder value, and the appended bits may be corrupted. S7-300 Module data 502 Manual, 06/2017, A5E00105505-AJ Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) 7.4.3.3 Transferred encoder value and scaling The transferred encoder value contains the encoder position of the absolute value encoder. In addition to the encoder position, the encoder transfers additional bits located before and after the encoder position, depending on the encoder used. The SM 338 determines the encoder position based on the following settings: Scaling, places (0..12), or scaling, steps / revolution Scaling, places Scaling determines the position of the encoder value at the feedback interface. "Places" = 1, 2....12 indicates that appended irrelevant bits in the encoder value are shifted out, and the encoder value is right-aligned in the address area (see the example below.) "Places" = 0 determines that appended bits are retained and available for evaluation. This may be useful when the absolute value encoder used transfers information in the appended bits (see manufacturer specifications) which you want to evaluate. Refer also to chapter "Gray code/binary code converter (Page 502)". Steps per revolution parameter Up to 13 bits are available for the steps per revolution parameter. The resultant number of steps per revolution is displayed automatically according to the "Places" setting. Example of encoder value scaling You are using a single-turn encoder with 29 steps = 512 steps per revolution (resolution/360.) Your configuration in STEP 7: Absolute encoder: 13 bits Scaling: 4 places Steps per revolution: 512 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 503 Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) 7.4.3.4 Freeze function The freeze function "freezes" the actual encoder values of SM 338. The freeze function is coupled to the digital inputs DI 0 and DI 1 of SM 338. The freeze function is triggered by a signal transition (positive edge) a DI 0 or DI 1. Bit 31 = 1 (output address) identifies a frozen encoder value. You can freeze one, two or three encoder values using one digital input. Enable the freeze function by setting the corresponding parameters in STEP 7 . To allows their event-triggered evaluation, the encoder values are retained until the freeze function is terminated. Terminating the freeze function The freeze function must be terminated separately at each encoder input. You acknowledge the function in the user program by using STEP 7 operation T PAB to set bit 0, 1 or 2 to "xyz" according to the channel (Program example: refer to chapter "AUTOHOTSPOT"). The acknowledgement resets bit 31 of the corresponding encoder value, and initiates a refresh of the encoder values. You can freeze the encoder values again after you cleared the ACK bit at the output address of the module. In isochronous mode, the acknowledgement is processed at the time To. From this point on, you can freeze the encoder values again by setting the digital inputs. Note The Freeze function is acknowledged automatically when you assign new parameters with different arguments to the relevant channel (refer to chapter "AUTOHOTSPOT"). If the parameter are identical the Freeze function remains unaffected. S7-300 Module data 504 Manual, 06/2017, A5E00105505-AJ Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) 7.4.4 Parametrization SM 338 POS-INPUT You parameterize the SM 338; POS-INPUT in STEP 7. Always parameterize the module while the CPU is in STOP mode. After you completed the parameter assignment, download the parameters from the PG to the CPU. At its next STOP RUN transition, the CPU transfers the parameters to the SM 338. New parameters can not be assigned by the user program. Parameters of SM 338; POS-INPUT The table below provides an overview of configurable parameters and defaults for the SM 338. The defaults apply if you have not set any parameters in STEP 7 (default setting bold). Table 7- 3 Parameters of SM 338; POS-INPUT Parameters Range of values Enable * Fast-Mode Note Enable parameter. yes / no Enable Applies to all 3 channels. Enable parameter. yes / no Applies to all 3 channels. Absolute value encoder (SSI) none; 13 bits; 21 bits; 25 bits none: The encoder input is switched off. Code type 1) Gray; Binary Code returned by the encoder. 125 kHz; 250 kHz; 500 kHz; 1 MHz Data transfer rate of the SSI position detection. Observe the relationship between cable lengths and the transmission rate (refer to chapter "Technical data of SM 338; POS-INPUT (Page 512)") * Diagnostic interrupt 1) Baud rate 1.3) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 505 Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) Parameters Range of values Note Monoflop time 1),2),3) 16 s; 32 s; 48 s; 64 s The monoflop time represents the minimum interval between two SSI frames. The configured monoflop time must be greater than the monoflop time of the absolute value encoder. Scaling 0 to 12 * Places * Steps per revolution 4 Enabling the Freeze function Scaling right-aligns the encoder value in the address space; irrelevant places are discarded. 2 to 8192 off; 0; 1 Definition of the digital input that initiates freezing of the encoder value at the positive edge. 1 Refer to the technical specifications of the absolute value encoder 2 The monoflop time represents the interval between two SSI frames. The configured monoflop time must be greater than the monoflop time of the absolute value encoder (see the technical data of the manufacturer). The time 2 x (1 / transmission rate) is added to the value set in HW Config. A transmission rate of 125 kHz and configured monoflop time of 16 s sets an effective monoflop time of 32 s. 3 Restriction of the monoflop time of the absolute value encoder: (1 / transmission rate) < monoflop time of the absolute value encoder < 64 s + 2 x (1 / transmission rate) 4 to powers of two Note Please note that in asynchronous mode, the transmission rate and monoflop time affect the accuracy and update quality of the encoder values. In isochronous mode, the transmission rate and monoflop time have an influence on the accuracy of the freeze function. S7-300 Module data 506 Manual, 06/2017, A5E00105505-AJ Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) 7.4.5 Addressing SM 338 POS-INPUT Data areas for encoder values The SM 338 inputs and outputs are addressed beginning at the module start address. The input and output address is determined in your configuration of SM 338 in STEP 7. Input addresses Table 7- 4 SM 338; POS-INPUT: Input addresses Encoder input Input address (derived from configuration) + address offset 0 "Module start address" 1 "Module start address" + 4 byte address offset 2 "Module start address" +8 byte address offset Structure of double data word in Standard Mode Double data word structure of the encoder inputs: Structure of double data word in Fast Mode Double data word structure of the encoder inputs: In the double data word from channel 0, the status of digital input I0 is reported to bit 27 (digital input status) and the double data word from channel 1 is reported to digital input I1. In the double data word from channel 2, the bit is always = 0. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 507 Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) Output address in Standard Mode no output data are supported in Fast Mode. Reading data areas You can read the data areas in your user program using the STEP 7 operation L PED "xyz." Example of access to encoder values and use of the freeze function You want to read and evaluate the values at the encoder inputs. The module start address is 256. STL Explanation L PED 256 // Read encoder value in the address area for encoder input 0 T MD 100 // Save encoder value to memory double word A M 100.7 // Freeze state for subsequent acknowledgement = M 99.0 // Determine and save L PED 230 // Read encoder value in the address area for encoder input 1 T MD 104 // Save encoder value to memory double word A M 104.7 // Freeze state for subsequent acknowledgement = M 99.1 // Determine and save L PED 264 // Read encoder value in the address area for encoder input 2 T MD 108 // Save encoder value to memory double word A M 108.7 // Freeze state for subsequent acknowledgement = M 99.2 // determine and save L MB 99 // Load freeze state and T POB 256 // acknowledge (SM 338: output address 256) You can then process the encoder values from the bit memory address areas MD 100, MD 104 and MD 108. The encoder value is set in bits 0 to 30 of the memory double word. S7-300 Module data 508 Manual, 06/2017, A5E00105505-AJ Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) 7.4.6 Diagnostics of SM 338; POS-INPUT Introduction The SM 338 provides diagnostics messages, i.e. it always provides all diagnostics messages without user intervention. Reactions to a diagnostic message in STEP 7 Actions initiated by diagnostic messages: The diagnostic message is entered in the diagnosis of the module and forwarded to the CPU. The SF LED on the module is lit. If you have set "Enable Diagnostic Interrupt" in STEP 7, the system triggers a diagnostic interrupt and calls OB 82. Reading diagnostic messages You can read detailed diagnostic messages using SFCs in the user program (refer to section Diagnostics data of SM 338; POS-INPUT (Page 596)). You can view the cause of the error in the module diagnostics data in STEP 7 (refer to the STEP 7 Online Help.) Diagnostic message using the SF LED The SM 338 indicates errors at its SF LED (group error LED.) The SF LED lights up when the SM 338 generates a diagnostic message. It goes dark after all error states are cleared. The SF LED also lights up to indicate external errors (short-circuit at the encoder supply), regardless of the CPU operating state (at POWER ON.) The SF LED lights up temporarily at startup, during the self test of SM 338. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 509 Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) Diagnostic messages of SM338; POS-INPUT The table below provides an overview of the diagnostic messages of SM 338; POS-INPUT. Table 7- 5 Diagnostic messages of SM 338; POS INPUT Diagnostic message LED Scope of diagnostics Module error SF Module Internal error SF Module External error SF Module Channel error SF Module External auxiliary voltage missing SF Module Module not programmed SF Module Incorrect parameters SF Module Channel information available SF Module Watchdog time-out SF Module Channel error SF Channel (encoder input) Configuration / programming error SF Channel (encoder input) External channel error (encoder error) SF Channel (encoder input) Causes of error and troubleshooting Table 7- 6 Diagnostic messages of SM 338, causes of error and troubleshooting Diagnostic message Possible cause of error Module error Any, the module has detected an error. To correct or avoid error Internal error Module has detected an error within the automation system. External error Module has detected an error outside of the automation system. Channel error Indicates that only specific channels are faulty. External auxiliary voltage missing Supply voltage L+ of the module is missing Feed supply L+ Module not programmed Module requires information whether it should operate with default system parameters or user parameters. Message present after power on, until the CPU has completed the transfer of parameters; configure the module as required. Incorrect parameters One parameter, or the combination of parameters, is not plausible Program the module Channel information available Channel error; module can provide additional channel information. Watchdog time-out Infrequent high electromagnetic interference Channel error Any, the module has detected an error at the encoder input. Configuration / programming error Illegal parameter transferred to module Program the module External channel error (encoder error) Wire-break at encoder cable, encoder cable not connected, or encoder defective. Check connected encoder Eliminate interference S7-300 Module data 510 Manual, 06/2017, A5E00105505-AJ Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) 7.4.7 SM 338; POS INPUT - Interrupts Introduction This chapter describes the interrupt reaction of SM 338; POS-INPUT. The SM 338 can trigger diagnostic interrupts. For detailed information on the OBs and SFCs mentioned below, refer to the STEP 7 Online Help. Enabling interrupts There is no default interrupt setting, i.e. interrupts are disabled if not set accordingly. You configure the interrupt enable parameter in STEP 7 (refer to chapter "Parametrization SM 338 POS-INPUT (Page 505)"). Diagnostic interrupt If you have enabled diagnostic interrupts, the incoming error events (initial occurrence of the error) and outgoing error events (message after troubleshooting) are reported by means of interrupts. The CPU interrupts user program execution, and executes diagnostic interrupt OB82. You can call SFC 51 or 59 in OB82 in the user program to view detailed diagnostic data output by the module. Diagnostics data remain consistent until the program exits OB 82. The module acknowledges the diagnostic interrupt when the program exits OB82. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 511 Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) 7.4.8 Technical data of SM 338; POS-INPUT Technical data of SM 338; POS-INPUT Technical data Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 120 Weight Approx. 235 g Voltages, currents, electrical potentials Rated load voltage L+ * * Range Reverse polarity protection Electrical isolation 24 VDC 20.4 ... 28.8 V No No, only to shield Maximum potential difference * Between the input (M terminal) and CPU grounding busbar 1 VDC Encoder supply * Output voltage * Output current L+ -0.8 V Max. 900 mA, short circuit-proof Current consumption * from the backplane bus * from load voltage L+ (no load) Power loss of the module Max. 160 mA max. 10 mA Typ. 3 W Encoder inputs POS-INPUT 0 to 2 Position detection Absolute Difference signals for SSI data and SSI clock To RS422 standard Data transfer rate and cable (twisted-pair and shielded) length of absolute value encoders SSI frame transfer rate * 125 kHz * 250 kHz * 500 kHz * 1 MHz Monoflop time2 * 125 kHz max. 320 m * 250 kHz max. 160 m * 500 kHz max. 60 m * 1 MHz max. 20 m 13 bits 21 bits 25 bits 112 s 176 s 208 s 56 s 88 s 104 s 28 s 44 s 52 s 14 s 22 s 26 s 16 s, 32 s, 48 s, 64 s S7-300 Module data 512 Manual, 06/2017, A5E00105505-AJ Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) Technical data Digital inputs DI 0, DI 1 Electrical isolation No, only to shield Input voltage 0 signal -3 V ... 5 V Input current 0 signal 2 mA (standby current) 1 signal 11 V ... 30.2 V 1 signal 9 mA (typ.) Input delay 0 > 1: max. 300 s 1 > 0: Max. 300 s Maximum repetition rate 1 kHz Connection of a two-wire BEROS, type 2 Supported Shielded cable length 600 m Unshielded cable length 32 m Status, interrupts, diagnostics Interrupts * Diagnostics interrupt programmable Status display for digital inputs LED (green) Group error LED (red) Inaccuracy of the encoder value Free-running transducer capture (Standard Mode) * maximum age 1 * minimum age 1 * Jitter Refresh rate (2 x frame transfer rate) + monoflop time + 580 s Frame transfer rate + 130 s Frame transfer rate + monoflop time + 450 s Frame evaluation at intervals of 450 s Free-running transducer capture (Fast Mode) * maximum age 1 * minimum age * Jitter 1 (2 x frame transfer rate) + monoflop time + 400 s Frame transfer rate + 100 s Frame transfer rate + monoflop time + 360 s Refresh rate Frame evaluation at intervals of 360 s Isochronous encoder value acquisition * Encoder value at time Ti of the current PROFIBUS DP cycle Age Inaccuracy of the frozen encoder value (Freeze) Cyclic encoder value acquisition (Standard Mode) * maximum age 1 * minimum age * Jitter 1 (2 x frame transfer rate) + monoflop time + 580 s Frame transfer rate + 130 s Frame transfer rate + monoflop time + 450 s Isochronous encoder value acquisition * Jitter Max. (frame transfer rate n + programmed Monoflop time n) =0, 1, 2, (channel) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 513 Other signal modules 7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0) Technical data Isochronous times for the module In Standard Mode In Fast Mode TCI 850 s TCO 620 s ToiMin 90 s TDPMin 1620 s TCI 700 s TCO 0 s ToiMin 0 s TDPMin 900 s 1 Age of the encoder values determined by the transfer process and the processing 2 Restriction of the monoflop time of the absolute value encoder: (1 / transmission rate) < monoflop of the absolute value encoder < 64 s + 2 x (1 / transmission rate) S7-300 Module data 514 Manual, 06/2017, A5E00105505-AJ 8 Interface modules Interface modules This chapter described the technical data and properties of the S7-300 interface modules. 8.1 Module overview Introduction The table below summarizes the essential features of the interface modules described in this chapter. This overview supports you in selecting a module to suit your requirements. Table 8- 1 Interface modules: Overview of properties Properties Interface module IM 360 Interface module IM 361 Interface module IM 365 Suitable for installation * in S7-300 racks 0 * 1 to 3 Data transfer * from IM 360 to IM 361 via connecting cable 386 * * from IM 360 to IM 361, or from IM 361 to IM 361, via connecting cable 386 from IM 365 to IM 365 via connecting cable 386 Distance between... * max. 10 m * max. 10 m * 1 m, permanently connected Special features --- * Preassembled module pair * Rack 1 supports only signal modules * IM 365 does not route the communication bus to rack 1 --- * 0 and 1 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 515 Interface modules 8.2 Interface module IM 360; (6ES7360-3AA01-0AA0) 8.2 Interface module IM 360; (6ES7360-3AA01-0AA0) Order number 6ES7360-3AA01-0AA0 Properties Special features of interface module IM 360: Interface for rack 0 of the S7-300 Data transfer from IM 360 to IM 361 via connecting cable 368 Maximum distance between IM 360 and IM 361 is 10 m Status and error LEDs Interface module IM 360 is equipped with the following status and error LEDs. Display element Meaning Explanations SF Group error The LED lights up if * the connecting cable is missing. * IM 361 is switched off. Front view The figure below shows the front view of interface module IM 360 S7-300 Module data 516 Manual, 06/2017, A5E00105505-AJ Interface modules 8.2 Interface module IM 360; (6ES7360-3AA01-0AA0) Technical data The overview below shows the technical data of interface module IM 360. Technical data Dimensions and weight Dimensions W x H x D (mm) 40 x 125 x 120 Weight approx. 250 g Module-specific data Cable length * Maximum length to next IM 10 m Current consumption * from the backplane bus 350 mA Power loss typ. 2 W Status and error LEDs yes S7-300 Module data Manual, 06/2017, A5E00105505-AJ 517 Interface modules 8.3 Interface module IM 361; (6ES7361-3CA01-0AA0) 8.3 Interface module IM 361; (6ES7361-3CA01-0AA0) Order number 6ES7361-3CA01-0AA0 Properties Special features of interface module IM 361: 24 VDC power supply Interface for racks 1 to 3 of the S7-300 Current output via the S7-300 backplane bus: max. 0.8 A Data transfer from IM 360 to IM 361, or from IM 361 to IM 361 via connecting cable 368 Maximum distance between IM 360 and IM 361 is 10 m Maximum distance between IM 361 and IM 361 is 10 m Status and error LEDs Interface module IM 361 is equipped with the following status and error LEDs. Display element Meaning Explanations SF Group error The LED lights up if 5 VDC 5 VDC supply for the S7-300 backplane bus * the connecting cable is missing * the IM 361 connected in series is switched off * the CPU is in POWER OFF state - S7-300 Module data 518 Manual, 06/2017, A5E00105505-AJ Interface modules 8.3 Interface module IM 361; (6ES7361-3CA01-0AA0) Front view The figure below shows the front view of interface module IM 361 Front view Technical data The overview below shows the technical data of interface module IM 361. Technical data Dimensions and weight Dimensions W x H x D (mm) 80 x 125 x 120 Weight 505 g Module-specific data Cable length Maximum length to next IM 10 m Current consumption from 24 VDC 0.5 A Power loss typ. 5 W Current sinking at backplane bus 0.8 A Status and error LEDs yes See also Spare parts and accessories for S7-300 modules (Page 616) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 519 Interface modules 8.4 Interface module IM 365; (6ES7365-0BA01-0AA0) 8.4 Interface module IM 365; (6ES7365-0BA01-0AA0) Order number: "Standard module" 6ES7365-0BA01-0AA0 Order number: "SIPLUS S7-300 module" 6AG1365-0BA01-2AA0 Properties Special features of interface module IM 365: Preassembled pair of modules for rack 0 and rack 1 Total power supply of 1.2 A, of which up to 0.8 A may be used per rack. Connecting cable with a length of 1 m already permanently connected IM 365 does not route the communication bus to rack 1, i.e. you cannot install FMs with communication bus function in rack 1. S7-300 Module data 520 Manual, 06/2017, A5E00105505-AJ Interface modules 8.4 Interface module IM 365; (6ES7365-0BA01-0AA0) Front view The figure below shows the front view of interface module IM 365 In rack 1 In rack 0 Technical specifications The overview below shows the technical data of interface module IM 365. Technical data Dimensions and weight Dimensions W x H x D (mm) per module 40 x 125 x 120 Total weight 580 g Module-specific data Cable length Maximum length to next IM 1m Current consumption from the backplane bus 100 mA Power loss typ. 0.5 W Current sinking max. 1.2 A per module 0.8 A Status and error LEDs no S7-300 Module data Manual, 06/2017, A5E00105505-AJ 521 Parameter sets of signal modules A.1 A Principles of programming signal modules in the user program Parameter assignment in the user program You have programmed the modules in STEP 7. In the user program, you can use a SFC: to assign new parameters to the module, and transfer the parameters from the CPU to the addressed signal module Parameters are stored in data records The signal module parameters are written to data records 0 and 1; for certain analog input modules, these are also written to data record 128. Editable parameters You can edit the parameters of data record 1, and then transfer these to the signal module using SFC55. The CPU parameters are not changed by this action! You cannot modify any parameters of data record 0 in the user program. SFCs for programming SFCs available for programming signal modules in the user program: Table A- 1 SFCs for programming signal modules SFC no. Identifier Application 55 WR_PARM Transfer the programmable parameters (data record 1 and 28) to the addressed signal module. 56 WR_DPARM Transfer the parameters (data record 0, 1 or 128) from the CPU to the addressed signal module. 57 PARM_MOD Transfer all parameters (data record 0, 1 and 128) from the CPU to the addressed signal module. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 522 Parameter sets of signal modules A.1 Principles of programming signal modules in the user program Description of the parameters The next chapters describe all modifiable parameters of the various module classes. For information on signal module parameters, refer to: the STEP 7 Online Help to this Reference Manual The chapters dealing with the various signal modules also show you the corresponding configurable parameters. Further references For detailed information on programming signal modules in the user program and on corresponding SFCs, refer to the STEP 7 manuals. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 523 Parameter sets of signal modules A.2 Parameters of digital IO modules A.2 Parameters of digital IO modules Parameter The table below lists the parameters you can set for digital input modules. Note For details on parameters of programmable digital IO modules, see the chapter dealing with the relevant module. The comparison illustrates the parameters you can edit: in STEP 7 using SFC55 "WR_PARM" using SFB53 "WRREC" (for GSD, for example). Parameters set in STEP 7 may also be transferred to the module using SFCs 56 and 57, and SFB53 (refer to the STEP 7) Online Help). Table A- 2 Parameters of digital IO modules Parameters Input delay Data record number Programmable, using ... ... SFC55, SFB53 ... PG 0 no yes Diagnostics of missing encoder supply no yes Wire-break diagnostics no yes Hardware interrupt enable yes yes Diagnostics interrupt enable 1 yes yes Hardware interrupt at positive edge yes yes Hardware interrupt at negative edge yes yes Note To enable diagnostics interrupts in the user program at data record 1, you first need to enable diagnostics at data record 0 in STEP 7. S7-300 Module data 524 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.2 Parameters of digital IO modules Structure of data record 1 The figure below shows the structure of data record 1 for the parameters of digital input modules. You enable a parameter by setting a logical "1" at the corresponding bit. Figure A-1 Data record 1 for parameters of digital input modules See also Diagnostics of digital modules (Page 59) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 525 Parameter sets of signal modules A.3 Parameters of the digital input module SM 321; DI 16 x DC 24/125 V A.3 Parameters of the digital input module SM 321; DI 16 x DC 24/125 V Parameters The table below lists the parameters you can set for digital input modules. Note For details on parameters of programmable digital IO modules, see the chapter dealing with the relevant module. The comparison illustrates the parameters you can edit: in STEP 7 using SFC55 "WR_PARM" using SFB53 "WRREC" (for GSD, for example). Parameters set in STEP 7 may also be transferred to the module using SFCs 56 and 57, and SFB53 (refer to the STEP 7) Online Help). Table A- 3 Parameters of the digital input module SM 321; DI 16 x DC 24/125 V Parameters Data record number Programmable, using ... ... SFC55, SFB53 ... PG 0 No Yes No Yes Yes Yes Diagnostic interrupt enable Yes Yes Hardware interrupt at positive edge Yes Yes Hardware interrupt at negative edge Yes Yes Input delay Wire-break diagnostics Hardware interrupt enable 1 Note To enable diagnostic interrupts in the user program at data record 1, you first need to enable diagnostics at data record 0 in STEP 7. Structure of data record 1 The figure below shows the structure of data record 1 for the parameters of digital input modules. You enable a parameter by setting a logical "1" at the corresponding bit. S7-300 Module data 526 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.3 Parameters of the digital input module SM 321; DI 16 x DC 24/125 V Figure A-2 Data record 1 for parameters of digital input modules S7-300 Module data Manual, 06/2017, A5E00105505-AJ 527 Parameter sets of signal modules A.4 Parameters of digital output modules A.4 Parameters of digital output modules Parameter The table below contains all parameters you can set for digital output modules. Note For details on the parameters of programmable digital IO modules, see the chapter dealing with the relevant module. The comparison illustrates the parameters you can edit: in STEP 7 using SFC55 "WR_PARM" using SFB53 "WRREC" (for GSD, for example). Parameters set in STEP 7 may also be transferred to the module using SFCs 56 and 57, and SFB 53 (refer to the STEP 7) Online Help). Table A- 4 Parameters of digital output modules Parameter Data record number Diagnostics of missing load voltage L+ 0 Programmable, using ... ... SFC55, SFB53 ... PG no yes Wire-break diagnostics No Yes Diagnostics of short-circuit to M No Yes No Yes Yes Yes Reaction to CPU STOP Yes Yes Set substitute value "1" Yes Yes Diagnosis of short-circuit to L+ Diagnostics interrupt enable 1 Note To enable diagnostic interrupts in the user program at data record 1, you first need to enable diagnostics at data record 0 in STEP 7. S7-300 Module data 528 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.4 Parameters of digital output modules Structure of data record 1 The figure below shows the structure of data record 1 for the parameters of digital output modules. You enable a parameter by setting a logic "1" at the corresponding bit of byte 0. Figure A-3 Data record 1 for parameters of digital output modules Note The "hold last valid value" and "set substitute value" parameters should only be enabled at byte 0 as an alternative. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 529 Parameter sets of signal modules A.5 Settings from the digital output module SM 322; DO 16 x DC 24 V/0.5 A (6ES7322-8BH10-0AB0) A.5 Settings from the digital output module SM 322; DO 16 x DC 24 V/0.5 A (6ES7322-8BH10-0AB0) Parameter The table below contains all parameters you can set for digital output modules. The comparison illustrates the parameters you can edit: inSTEP 7 using SFC55 "WR_PARM" using SFB53 "WRREC" (for GSD, for example). Parameters set in STEP 7 can also be transferred to the module using SFC 56 and SFC 57 (refer to the STEP 7 Online Help). Table A- 5 Digital output module SM 322; 6ES7322-8HB10-0AB0 Parameter Diagnostics: Group diagnostics Data record number Programmable, using ... ... SFC55, SFB53 ... PG 1 Yes Yes Diagnostics: Load voltage L+ missing Diagnostics: Discrepancy error Diagnostics interrupt enable Behavior at CPU/master STOP Substitute a value S7-300 Module data 530 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.5 Settings from the digital output module SM 322; DO 16 x DC 24 V/0.5 A (6ES7322-8BH10-0AB0) Structure of data record 1 The figure below shows the structure of data record 1 for the parameters of digital output modules. You enable a parameter by setting a logic "1" at the corresponding bit of byte 0. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 531 Parameter sets of signal modules A.5 Settings from the digital output module SM 322; DO 16 x DC 24 V/0.5 A (6ES7322-8BH10-0AB0) Figure A-4 Structure of data record 1 Note The "hold last valid value" and "set substitute value" parameters should only be enabled at byte 0 as an alternative. S7-300 Module data 532 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.5 Settings from the digital output module SM 322; DO 16 x DC 24 V/0.5 A (6ES7322-8BH10-0AB0) See also Parameters of digital output modules (Page 152) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 533 Parameter sets of signal modules A.6 Parameters of analog input modules A.6 Parameters of analog input modules Parameter The table below lists all parameters you can set for analog input modules. The comparison illustrates the parameters you can edit: in STEP 7 using SFC55 "WR_PARM" Parameters set in STEP 7 can also be transferred to the module using SFC56 and SFC57 (refer to the STEP 7 manuals). Table A- 6 Parameters of analog input modules Parameters Data record number Diagnostics: Group diagnostics ... SFC55 ... PG No Yes Diagnostics: with wirebreak monitoring no yes Temperature unit no yes Temperature coefficient no yes Smoothing no yes Diagnostic interrupt enable 0 Programmable, using ... yes yes Hardware interrupt when limit exceeded 1 yes yes End of cycle interrupt enable yes yes Interference frequency suppression yes yes Measurement type yes yes Measuring range yes yes High limit yes yes Low limit yes yes Note To enable diagnostic interrupts in the user program at data record 1, you first need to enable diagnostics at data record 0 in STEP 7. S7-300 Module data 534 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.6 Parameters of analog input modules Structure of data record 1 The figure below shows the structure of data record 1 of the parameters for an analog input module with 8 channels in 4 groups (e.g. AI 8 x 12 bits). The structure of a module whose channels are not grouped together is documented in the relevant module description. You enable a parameter by setting a logic "1" at the corresponding bit of byte 0. Figure A-5 Data record 1 for the parameters of analog input modules S7-300 Module data Manual, 06/2017, A5E00105505-AJ 535 Parameter sets of signal modules A.6 Parameters of analog input modules Note The representation of limits matches the analog value representation (see chapter 4.) Observe range limits when setting the limit values. Interference frequency suppression The table below contains the coding at byte 1 of data record 1 for the various frequencies (see the previous figure.) Make allowances for the resultant integration time at each channel! Table A- 7 Interference frequency suppression codes of analog input modules Interference frequency suppression Integration time Code 400 Hz 2.5 ms 2#00 60 Hz 16.7 ms 2#01 50 Hz 20 ms 2#10 10 Hz 100 ms 2#11 Measurement types and measuring ranges The table below shows all measurement types and measuring ranges of the analog input module, including their codes. Enter these codes at bytes 2 to 5 in data record 1 (refer to the previous figure.) Note You may have to reposition a measuring range module of the analog input module to suit the measuring range. Table A- 8 Measuring range codes of analog input modules Measurement type Code Measuring range Code disabled 2#0000 disabled 2#0000 Voltage 2#0001 80 mV 2#0001 250 mV 2#0010 500 mV 2#0011 1V 2#0100 2.5 V 2#0101 5V 2#0110 1 V to 5 V 0 V to 10 V 2#0111 2#1000 10 V 2#1001 25 mV 2#1010 50 mV 2#1011 S7-300 Module data 536 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.6 Parameters of analog input modules Measurement type Code Measuring range Code 4-wire transducer 2#0010 3.2 mA 2#0000 10 mA 2#0001 0 to 20 mA 2#0010 4 to 20 mA 2#0011 20 mA 2#0100 5 mA 2#0101 2-wire transducer 2#0011 4 to 20 mA 2#0011 Resistance (4-wire connection) 2#0100 150 2#0010 300 2#0100 600 10 k 2#0110 2#1001 52 to 148 2#0001 250 2#0011 400 2#0101 700 2#0111 Pt 100 Klima 2#0000 Ni 100 Klima 2#0001 Pt 100 Standard range 2#0010 Pt 200 Standard range 2#0011 Pt 500 Standard range 2#0100 Pt 1000 Standard range 2#0101 Ni 1000 standard range 2#0110 Pt 200 Klima 2#0111 Pt 500 Klima 2#1000 Pt 1000 Klima 2#1001 Ni 1000 Klima 2#1001 Resistance 4-wire connec- 2#0110 tion; 100 compensation Thermal resistance + linearization 4-wire connection 2#1000 Thermocouples with internal comparator 2#1010 Thermocouples with external comparison 2#1011 Thermocouples + linearization internal comparison 2#1101 Thermocouples + linearization external comparison 2#1110 Ni 100 standard range 2#1011 Type B [PtRh - PtRh] 2#0000 Type N [NiCrSi-NiSi] 2#0001 Type E [NiCr-CuNi] 2#0010 Type R [PtRh -Pt] 2#0011 Type S [PtRh -Pt] 2#0100 Type J [Fe - CuNi IEC] 2#0101 Type L [Fe-CuNi] 2#0110 Type T [Cu - CuNi] 2#0111 Type K [NiCr-Ni] 2#1000 Type U [Cu -Cu Ni] 2#1001 See also Analog modules (Page 300) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 537 Parameter sets of signal modules A.7 Parameters of analog input module SM 331; AI 8 x RTD A.7 Parameters of analog input module SM 331; AI 8 x RTD Parameters The table below shows all parameters you can set at analog input module SM 331; AI 8 x RTD. The comparison illustrates the parameters you can edit: in STEP 7 using SFC55 "WR_PARM" Parameters set in STEP 7 can also be transferred to the module using SFC56 and SFC57 (refer to the STEP 7 manuals). Table A- 9 Parameters of SM 331; AI 8 x RTD Parameters Data record number Diagnostics: Group diagnostics 0 Programmable, using ... ... SFC55 ... PG no yes no yes yes yes Hardware interrupt when limit exceeded yes yes End of cycle interrupt enable yes yes yes yes yes yes Measuring range yes yes Operating mode yes yes Temperature coefficient yes yes Interference frequency suppression yes yes Smoothing yes yes High limit yes yes Low limit yes yes Diagnostics: with wirebreak monitoring Diagnostic interrupt enable 1 Temperature unit Measurement type 128 Note To enable diagnostic interrupts in the user program at data record 1, you first need to enable diagnostics at data record 0 in STEP 7. S7-300 Module data 538 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.7 Parameters of analog input module SM 331; AI 8 x RTD Structure of data record 1 The diagram below shows the structure of data record 1 of SM 331; AI 8 x RTD. You enable a parameter by setting a logical "1" at the corresponding bit. Figure A-6 Data record 1 for the parameters of SM 331; AI 8 RTD S7-300 Module data Manual, 06/2017, A5E00105505-AJ 539 Parameter sets of signal modules A.7 Parameters of analog input module SM 331; AI 8 x RTD Structure of data record 128 The diagram below shows the structure of data record 128 of SM 331; AI 8 x RTD. Figure A-7 Data record 128 of SM 331; AI 8 x RTD S7-300 Module data 540 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.7 Parameters of analog input module SM 331; AI 8 x RTD Figure A-8 Data record 128 of SM 331; AI 8 x RTD (continued) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 541 Parameter sets of signal modules A.7 Parameters of analog input module SM 331; AI 8 x RTD Figure A-9 Data record 128 of SM 331; AI 8 x RTD (continued) S7-300 Module data 542 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.7 Parameters of analog input module SM 331; AI 8 x RTD Figure A-10 Data record 128 of SM 331; AI 8 x RTD (continued) Note The representation of limits matches the analog value representation. Observe range limits when setting the limit values. Modes of operation of SM 331; AI 8 x RTD The table below contains the coding at byte 0 of data record 128 for the various modes of operation (see the previous figure.) Table A- 10 Operating mode coding of SM 331; AI 8 x RTD Operating mode Code 8 channels, hardware filter 2#00000000 8 channels, software filter 2#00000001 4 channels, hardware filter 2#00000010 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 543 Parameter sets of signal modules A.7 Parameters of analog input module SM 331; AI 8 x RTD Interference frequency suppression at SM 331; AI 8 x RTD The table below contains the frequency codes to be entered at byte 1 of data record 128 (see the previous figure.) The 50 Hz, 60 Hz and 400 Hz only apply to 8channel software filter mode. The 50 Hz, 60 Hz and 400 Hz settings only apply to 4- and 8-channel hardware filter mode. Table A- 11 Interference suppression coding of SM 331; AI 8 x RTD Interference frequency suppression Code 400 Hz 2#00 60 Hz 2#01 50 Hz 2#10 50/60/400 Hz 2#11 Measurement types and measuring ranges of SM 331; AI 8 x RTD The table below shows all measurement types and measuring ranges of the module, including their codes. Enter these codes at the corresponding bytes of data record 128 (see the figure Data record 1 for the parameters of analog input modules). Table A- 12 Measuring range codes of SM 331; AI 8 x RTD Measurement type Code disabled Resistance (4-wire connection) Resistance (3-wire connection) Measuring range Code 2#0000 disabled 2#0000 2#0100 150 2#0010 300 2#0100 600 2#0110 150 2#0010 300 2#0100 600 2#0110 2#0101 S7-300 Module data 544 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.7 Parameters of analog input module SM 331; AI 8 x RTD Measurement type Code Measuring range Code Thermal resistance + linearization 4-wire connection 2#1000 Pt 100 Climatic Ni 100 Climatic Pt 100 Standard Ni 100 Standard Pt 500 Standard Pt 1000 Standard Ni 1000 Standard Pt 200 Climatic Pt 500 Climatic Pt 1000 Climatic Ni 1000 Climatic Pt 200 Standard Ni 120 Standard Ni 120 Climatic Cu 10 Climatic Cu 10 Standard Ni 200 Standard Ni 200 Climatic Ni 500 Standard Ni 500 Climatic Pt 10 GOST Climatic Pt 10 GOST Standard Pt 50 GOST Climatic Pt 50 GOST Climatic Pt 100 GOST Climatic Pt 100 GOST Standard Pt 500 GOST Climatic Pt 500 GOST Standard Cu 10 GOST Climatic Cu 10 GOST Standard Cu 50 GOST Climatic Cu 50 GOST Standard Cu 100 GOST Climatic Cu 100 GOST Standard Ni 100 GOST Climatic Ni 100 GOST Standard 2#00000000 2#00000001 2#00000010 2#00000011 2#00000100 2#00000101 2#00000110 2#00000111 2#00001000 2#00001001 2#00001010 2#00001011 2#00001100 2#00001101 2#00001110 2#00001111 2#00010000 2#00010001 2#00010010 2#00010011 2#00010100 2#00010101 2#00010110 2#00010111 2#00011000 2#00011001 2#00011010 2#00011011 2#00011100 2#00011101 2#00011110 2#00011111 2#00100000 2#00100001 2#00100010 2#00100011 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 545 Parameter sets of signal modules A.7 Parameters of analog input module SM 331; AI 8 x RTD Measurement type Code Measuring range Code Thermal resistance + linearization 3-wire connection 2#1001 Pt 100 climatic Ni 100 climatic Pt 100 standard Ni 100 standard Pt 500 standard Pt 1000 standard Ni 1000 standard Pt 200 climatic Pt 500 climatic Pt 1000 climatic Ni 1000 climatic Pt 200 standard Ni 120 standard Ni 120 climatic Cu 10 climatic Cu 10 standard Ni 200 standard Ni 200 climatic Ni 500 standard Ni 500 climatic Pt 10 GOST climatic Pt 10 GOST standard Pt 50 GOST climatic Pt 50 GOST standard Pt 100 GOST climatic Pt 100 GOST standard Pt 500 GOST climatic Pt 500 GOST standard Cu 10 GOST climatic Cu 10 GOST standard Cu 50 GOST climatic Cu 50 GOST standard Cu 100 GOST climatic Cu 100 GOST standard Ni 100 GOST climatic Ni 100 GOST standard 2#00000000 2#00000001 2#00000010 2#00000011 2#00000100 2#00000101 2#00000110 2#00000111 2#00001000 2#00001001 2#00001010 2#00001011 2#00001100 2#00001101 2#00001110 2#00001111 2#00010000 2#00010001 2#00010010 2#00010011 2#00010100 2#00010101 2#00010110 2#00010111 2#00011000 2#00011001 2#00011010 2#00011011 2#00011100 2#00011101 2#00011110 2#00011111 2#00100000 2#00100001 2#00100010 2#00100011 S7-300 Module data 546 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.8 Parameters of SM 331; AI 8 TC Temperature coefficient of SM 331; AI 8 x RTD The table below contains the temperature coefficient codes to be entered at the corresponding byte of data record 128 (refer to the previous figure.) Table A- 13 Temperature coefficient codes of SM 331; AI 8 x RTD Temperature coefficient Code Pt 0.003850 //C (IPTS-68) 2#0000 Pt 0,003916 //C 2#0001 Pt 0.003902 //C 2#0010 Pt 0.003920 //C 2#0011 Pt 0.003850 //C (ITS-90) 2#0100 Pt 0.003910 //C 2#0101 Pt 0.006170 //C 2#0111 Ni 0.006180 //C 2#1000 Ni 0.006720 //C 2#1001 0.005000 // C (LG Ni 1000) 2#1010 Cu 0.004260 //C 2#1011 Cu 0.004270 //C 2#1100 Cu 0.004280 //C 2#1101 Smoothing function at SM 331; AI 8 x RTD The table below lists all smoothing codes to be entered at the corresponding byte of data record 128 (refer to the previous figure.) Table A- 14 Smoothing codes at SM 331; AI 8 x RTD Smoothing Code None 2#00 Low 2#01 Average 2#10 High 2#11 See also Analog modules (Page 300) Parameters of analog input modules (Page 534) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 547 Parameter sets of signal modules A.8 Parameters of SM 331; AI 8 TC A.8 Parameters of SM 331; AI 8 TC Parameter The table below shows all parameters you can set at analog input module SM 331; AI 8 x TC. The comparison illustrates the parameters you can edit: in STEP 7 using SFC55 "WR_PARM" Parameters set in STEP 7 can also be transferred to the module using SFC56 and SFC57 (refer to the STEP 7 manuals). Table A- 15 Parameters of SM 331; AI 8 TC Parameters Data record number Diagnostics: Group diagnostics 0 Programmable, using ... ... SFC 55 ... PG no yes no yes yes yes Hardware interrupt when limit exceeded yes yes End of cycle interrupt enable yes yes yes yes yes yes Measuring range yes yes Operating mode yes yes Response to open thermocouple yes yes Interference frequency suppression yes yes Smoothing yes yes High limit yes yes Low limit yes yes Diagnostics: with wirebreak monitoring Diagnostic interrupt enable 1 Temperature unit Measurement type 128 Note To enable diagnostic interrupts in the user program at data record 1, you first need to enable diagnostics at data record 0 in STEP 7. S7-300 Module data 548 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.8 Parameters of SM 331; AI 8 TC Structure of data record 1 The figure below shows the structure of data record 1 of SM 331; AI 8 x TC. You enable a parameter by setting a logical "1" at the corresponding bit. Figure A-11 Data record 1 for the parameters of SM 331; AI 8 x TC S7-300 Module data Manual, 06/2017, A5E00105505-AJ 549 Parameter sets of signal modules A.8 Parameters of SM 331; AI 8 TC Structure of data record 128 The figure below shows the structure of data record 128 of SM 331; AI 8 x TC. Figure A-12 Fig. A-10 Data record 128 of SM 331; AI 8 x TC (continued) S7-300 Module data 550 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.8 Parameters of SM 331; AI 8 TC Figure A-13 Data record 128 of SM 331; AI 8 TC (continued) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 551 Parameter sets of signal modules A.8 Parameters of SM 331; AI 8 TC Figure A-14 Data record 128 of SM 331; AI 8 TC (continued) S7-300 Module data 552 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.8 Parameters of SM 331; AI 8 TC Figure A-15 Data record 128 of SM 331; AI 8 x TC (continued) Note The representation of limits matches the analog value representation. Observe range limits when setting the limit values. Modes of operation of SM 331; AI 8 x TC The table below contains the coding at byte 0 of data record 128 for the various modes of operation (see the previous figure.) Table A- 16 Operating mode codes of SM 331; AI 8 x TC Operating mode Code 8 channels, hardware filter 2#00000000 8 channels, software filter 2#00000001 4 channels, hardware filter 2#00000010 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 553 Parameter sets of signal modules A.8 Parameters of SM 331; AI 8 TC Interference frequency suppression at SM 331; AI 8 x TC The table below contains the frequency codes to be entered at byte 1 of data record 128 (see the previous figure.) The 400 Hz, 60 Hz and 50 Hz settings only apply to 8channel software filter mode. The 50 Hz, 60 Hz and 400 Hz settings only apply to 4- and 8-channel hardware filter mode. Table A- 17 Interference frequency suppression codes of SM 331; AI 8 x TC Interference frequency suppression Code 400 Hz 2#00 60 Hz 2#01 50 Hz 2#10 50/60/400 Hz 2#11 Measurement types and measuring ranges of SM 331; AI 8 x TC The table below shows all measurement types and measuring ranges of the module, including their codes. Enter these codes at the corresponding bytes of data record 128 (see the figure Data record 1 for the parameters of analog input modules). Table A- 18 Measuring range codes of SM 331; AI 8 x TC Measurement type Code Measuring range Code disabled 2#0000 disabled 2#0000 TC-L00C: (thermocouple, linear, 0 C reference temperature) 2#1010 B N E R S J L T K U 2#0000 2#0001 2#0010 2#0011 2#0100 2#0101 2#0110 2#0111 2#1000 2#1001 C 2#1010 TC-L50C: (thermocouple, linear, 50 C reference temperature) 2#1011 TXK/XK(L) 2#1011 B N E R S J L T K U 2#0000 2#0001 2#0010 2#0011 2#0100 2#0101 2#0110 2#0111 2#1000 2#1001 C 2#1010 TXK/XK(L) 2#1011 S7-300 Module data 554 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.8 Parameters of SM 331; AI 8 TC Measurement type Code Measuring range Code TC-IL: (thermocouple, linear, internal comparison) 2#1101 B N E R S J L T K U 2#0000 2#0001 2#0010 2#0011 2#0100 2#0101 2#0110 2#0111 2#1000 2#1001 C 2#1010 TC-EL: (thermocouple, linear, external comparison) 2#1110 TXK/XK(L) 2#1011 B N E R S J L T K U 2#0000 2#0001 2#0010 2#0011 2#0100 2#0101 2#0110 2#0111 2#1000 2#1001 C 2#1010 TXK/XK(L) 2#1011 Reaction to open thermocouple of the SM 331; AI 8 x TC The table below lists the codes for the reaction to an open thermocouple to enter at the corresponding byte of data record 128 (refer the previous figure.) Table A- 19 Codes of the reaction to open thermocouple of SM 331; AI 8 x TC Response to open thermocouple Code Overflow 2#0 Underflow 2#1 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 555 Parameter sets of signal modules A.8 Parameters of SM 331; AI 8 TC Smoothing of SM 331; AI 8 x TC The table below lists all smoothing codes to be entered at the corresponding byte of data record 128 (refer to the previous figure.) Table A- 20 Smoothing codes at SM 331; AI 8 x TC Smoothing Code None 2#00 Low 2#01 Average 2#10 High 2#11 See also Analog modules (Page 300) Parameters of analog input modules (Page 534) S7-300 Module data 556 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.9 Parameters of analog input module SM 331; AI 8 x 13 Bit A.9 Parameters of analog input module SM 331; AI 8 x 13 Bit Structure of data record 1 The figure below shows the structure of data record 1 for the parameters of the analog input module. You enable a parameter by setting a logical "1" at the corresponding bit in the bytes. Figure A-16 Data record 1 for the parameters of analog input modules S7-300 Module data Manual, 06/2017, A5E00105505-AJ 557 Parameter sets of signal modules A.9 Parameters of analog input module SM 331; AI 8 x 13 Bit Temperature measurement The table below lists the temperature measurement codes to be enterd at byte 0 of data record 1 (see the previous figure.) Table A- 21 Temperature measurement codes of the analog input module Temperature unit for linearization Code degrees Celsius 2#0000 0000 Degrees Fahrenheit 2#0000 1000 Kelvin 2#0001 0000 Interference frequency suppression The table below contains the frequency codes to be entered at byte 1 of data record 1 (see the previous figure.) Make allowances for the resultant integration time at each module! Table A- 22 Interference frequency suppression codes of the analog input module Interference frequency suppression Integration time Code 60 Hz 50 ms 2#01 50 Hz 60 ms 2#10 Measurement types and measuring ranges The table below contains all the measurement types and measuring ranges of the analog input module, including their codes. Enter these codes at bytes 2 to 13 in data record 1 (refer to the previous figure.) Note The front connector of the analog input module must be wired in accordance with the measuring range! S7-300 Module data 558 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.9 Parameters of analog input module SM 331; AI 8 x 13 Bit Table A- 23 Measuring ranges codes of the analog input module Measurement type Code Measuring range Code disabled 2#0000 disabled 2#0000 Voltage 2#0001 50 mV 2#1011 500 mV 2#0011 1V 2#0100 5V 2# 0110 1 V to 5 V 2#0111 Current 2#0010 Resistance 2#0101 Thermoelectric resistance (linear) 2#1001 0 V to 10 V 2#1000 10 V 2#1001 0 mA to 20 mA 2#0010 4 mA to 20 mA 2#0011 20 mA 2#0100 600 2#0110 6 k 2#1000 PTC 2#1111 Pt 100 Klima 2#0000 Pt 100 Standard 2#0010 Ni 100 Klima 2#0001 Ni 100 Standard 2#0011 Ni 1000 / LG-Ni 1000 Klima 2#1010 Ni 1000 / LG-Ni 1000 Standard 2#0110 KTY83/110 2#1100 KTY84/130 2#1101 Temperature coefficient The table below lists the temperature coefficient codes to be entered at bytes 10 to 13 of data record 1 (refer to previous figure.) Table A- 24 Temperature measurement codes of the analog input module Temperature coefficient Measuring range Code Pt 0.003850 //C (ITS-90) Pt 100 2#0100 Ni 0.006180 //C Ni 100 / Ni 1000 2#1000 Ni 0.005000 //C LG-Ni 1000 2#1010 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 559 Parameter sets of signal modules A.10 Setting of the analog input module SM 331; AI 8 x 16 Bit (6ES7331-7NF10-0AB0) A.10 Setting of the analog input module SM 331; AI 8 x 16 Bit (6ES7331-7NF10-0AB0) Parameter The table below contains all settings you can set for isolated digital output modules SM 331; AI 8 x16 Bit (6ES7331-7NF10-0AB0). This comparison shows which specific method you can use to configure the various parameters: SFC55 "WR_PARM" STEP 7 programming device Parameters set in STEP 7 can also be transferred to the module using SFC56 or SFC57. Table A- 25 Parameters for the electrically isolated analog input module SM 331; AI 8 x 16 Bit Parameters Data record no. Configurable using... ... SFC55 Diagnostics: Group diagnostics 0 ...Programming device no yes no yes yes yes yes yes yes yes yes yes Noise suppression yes yes Measuring method yes yes Measuring range yes yes Smoothing yes yes High limit yes yes Low limit yes yes Diagnostics: with wirebreak monitoring Hardware interrupt when limit exceeded 1 Diagnostics interrupt enable End-of-cycle alarm enable Module operating mode 128 Note To enable diagnostic interrupts in the user program at data record 1, you first need to enable diagnostics at data record 0 in STEP 7. S7-300 Module data 560 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.10 Setting of the analog input module SM 331; AI 8 x 16 Bit (6ES7331-7NF10-0AB0) Structure of data record 1 The figure below shows the structure of data record 1 for the parameters of the electrically isolated analog input module SM 331; AI 8 x 16 bit. You enable a parameter by setting a logical "1" at the corresponding bit in byte 0. Figure A-17 Data record 1 for parameters of SM 331; AI 8 x 16 Bit S7-300 Module data Manual, 06/2017, A5E00105505-AJ 561 Parameter sets of signal modules A.10 Setting of the analog input module SM 331; AI 8 x 16 Bit (6ES7331-7NF10-0AB0) Structure of data record 128 The figure below shows the structure of data record 128 for the parameters of the electrically isolated analog input module SM 331; AI 8 x 16 bit. Figure A-18 Data record 128 for parameters of SM 331; AI 8 x 16 Bit S7-300 Module data 562 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.10 Setting of the analog input module SM 331; AI 8 x 16 Bit (6ES7331-7NF10-0AB0) Figure A-19 Data record 128 for parameters of SM 331; AI 8 x 16 Bit (continued) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 563 Parameter sets of signal modules A.10 Setting of the analog input module SM 331; AI 8 x 16 Bit (6ES7331-7NF10-0AB0) Figure A-20 Data record 128 for parameters of SM 331; AI 8 x 16 Bit (continued) S7-300 Module data 564 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.10 Setting of the analog input module SM 331; AI 8 x 16 Bit (6ES7331-7NF10-0AB0) Figure A-21 Data record 128 for parameters of SM 331; AI 8 x 16 Bit (continued) Note The representation of limits matches the analog value representation. Observe range limits when setting the limit values. Module operating modes The table below lists the operating mode codes to be entered at byte 0 of data record 128 (see the previous figure.) Table A- 26 Operating mode codes of SM 331; AI 8 x 16 Bit Module operating mode Code 8 channels 2#00000000 4 channels 2#00000001 Noise suppression The table below lists the frequency codes to be entered at byte 1 of data record 128 (see the previous figure.) 4-channel mode only works if 50 Hz, 60 Hz and 400 Hz noise suppression is set. Table A- 27 Noise suppression codes of SM 331; AI 8 x 16 Bit Noise suppression Code 400 Hz 2#00 60 Hz 2#01 50 Hz 2#10 50 Hz, 60 Hz and 400 Hz 2#11 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 565 Parameter sets of signal modules A.10 Setting of the analog input module SM 331; AI 8 x 16 Bit (6ES7331-7NF10-0AB0) Measuring methods and ranges The table below lists the measuring ranges of the electrically isolated analog input module SM 331; AI 8 x 16 bit. The table below shows the measuring method and range codes. Enter these codes according to the required measuring range at the relevant byte of data record 128 (see previous figure.) Table A- 28 Measuring range codes of SM 331; AI 8 x 16 Bit Measuring method Code Measuring range Code Disabled 2#0000 Disabled 2#0000 Voltage 2#0001 5 V 1 V to 5 V 10 V 2#0110 2#0111 2#1001 Current (4-wire transducer) 2#0010 0 mA to 20 mA 4 mA to 20 mA 20 mA 2#0010 2#0011 2#0100 Settings of input smoothing The table below lists the smoothing settings of the electrically isolated analog input module SM 331; AI 8 x 16 Bit. Enter these codes according to the required smoothing at the relevant byte of data record 128 (see previous figure.) Table A- 29 Smoothing codes of SM 331; AI 8 x 16 Bit Smoothing settings Code None 2#00 Low 2#01 Average 2#10 High 2#11 See also Analog modules (Page 300) S7-300 Module data 566 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.11 Parameters of analog input module SM 331; AI 6 x TC isolated A.11 Parameters of analog input module SM 331; AI 6 x TC isolated Parameter The table below shows all parameters you can set at analog input module SM 331; AI 6 x TC. The comparison illustrates the parameters you can edit: In STEP 7 Using SFC55 "WR_PARM" Parameters set in STEP 7 can also be transferred to the module using SFC56 and SFC57 (refer to the STEP 7 manuals). Parameters Data record number Programmable, using ... ... SFC55 ... PG Diagnostics: Channel 0 No Yes Diagnostics: For wire break 0 No Yes Hardware interrupt when limit exceeded 1 Yes Yes Diagnostic interrupt enable 1 Yes Yes Temperature unit 1 Yes Yes Activation of auto-calibration 1 Yes Yes Interference frequency suppression 1 Yes Yes Measurement type 1 Yes Yes Measuring range 1 Yes Yes Measured value smoothing 1 Yes Yes Response to open thermocouple 1 Yes Yes External reference junction 1 Yes Yes Temperature coefficient 1 Yes Yes High limit 128 Yes Yes Low limit 128 Yes Yes Note To enable diagnostic interrupts in the user program at data record 1, you first need to enable diagnostics at data record 0 in STEP 7. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 567 Parameter sets of signal modules A.11 Parameters of analog input module SM 331; AI 6 x TC isolated Structure of data record 1 The figure below shows the structure of data record 1 for the parameters of analog input module SM 331; AI 6 x TC. You enable a parameter by setting a logical "1" at the corresponding bit. Figure A-22 Structure of data record 1 for AI 6 x TC S7-300 Module data 568 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.11 Parameters of analog input module SM 331; AI 6 x TC isolated Structure of data record 128 The figure below shows the structure of data record 128 for the parameters of analog input module SM 331; AI 6 x TC. Figure A-23 Structure of data record 1 for AI 6 x TC (cont.) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 569 Parameter sets of signal modules A.11 Parameters of analog input module SM 331; AI 6 x TC isolated Figure A-24 Data record 128 for AI 6 x TC Note The representation of limits matches the analog value representation. When defining limit values, take the measuring range limits into account. Temperature measurement The table below contains the coding you must enter at byte 0 of data record 1 for the various temperature measurements. Temperature unit for linearization Code Celsius 2#00 Fahrenheit 2#01 Kelvin 2#10 S7-300 Module data 570 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.11 Parameters of analog input module SM 331; AI 6 x TC isolated Interference frequency suppression The table below contains the coding you must enter at byte 1 of data record 1 for the various frequencies. Interference frequency suppression Code 400 Hz 2#00 60 Hz 2#01 50 Hz 2#10 10 Hz 2#11 Measurement types and measuring ranges The table below contains all measuring ranges for the module, together with the associated codes. Enter these codes at the corresponding bytes of data record 1. Measurement type Code Measuring range Code disabled 2#0000 disabled 2#0000 Voltage 2#0001 80 mV 250 mV 500 mV 1V 25 mV 50 mV 2#0001 2#0010 2#0011 2#0100 2#1010 2#1011 TC-L00C 2#1010 B N E R S J L T K U C TxK/XK(L) 2#0000 2#0001 2#0010 2#0011 2#0100 2#0101 2#0110 2#0111 2#1000 2#1001 2#1010 2#1011 2#1011 B N E R S J L T K U C TxK/XK(L) 2#0000 2#0001 2#0010 2#0011 2#0100 2#0101 2#0110 2#0111 2#1000 2#1001 2#1010 2#1011 Thermocouple, linear, 0 C reference temperature TC-L50C Thermocouple, linear, 50 C reference temperature S7-300 Module data Manual, 06/2017, A5E00105505-AJ 571 Parameter sets of signal modules A.11 Parameters of analog input module SM 331; AI 6 x TC isolated Measurement type TC-IL Code Code B N E R S J L T K U C TxK/XK(L) 2#0000 2#0001 2#0010 2#0011 2#0100 2#0101 2#0110 2#0111 2#1000 2#1001 2#1010 2#1011 2#1110 B N E R S J L T K U C TxK/XK(L) 2#0000 2#0001 2#0010 2#0011 2#0100 2#0101 2#0110 2#0111 2#1000 2#1001 2#1010 2#1011 Thermocouple, linear, internal comparison TC-EL: Measuring range 2#1101 Thermocouple, linear, external comparison Smoothing The table below lists all smoothing codes to be entered at the corresponding byte of data record 1. Smoothing Code None 2#00 Low 2#01 Average 2#10 High 2#11 Response to open thermocouple The table below lists the codes for the reaction to an open thermocouple to be entered at the corresponding byte of data record 1. Response to open thermocouple Code Overflow 2#0 Underflow 2#1 S7-300 Module data 572 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.11 Parameters of analog input module SM 331; AI 6 x TC isolated External reference junction The table below lists the codes for the external reference junction, to be entered at the corresponding byte of data record 1. Selection of an external reference junction Code Local thermoresistor 2#0 Remote thermoresistor 2#1 Temperature coefficient The table below lists the codes for the temperature coefficient, to be entered at the corresponding byte of data record 1. Temperature coefficient Code Pt 0.003850 //C (IPTS-68) 2#0000 Pt 0.003916 //C 2#0001 Pt 0.003902 //C 2#0010 Pt 0.003920 //C 2#0011 Pt 0.003850 //C (ITS-90) 2#0100 Pt 0.003910 //C (GOST) 2#0101 Note When selecting a temperature coefficient by writing data record 1 via an SFC or a GSD file, the same temperature coefficient must be specified for every channel which uses the external reference junction. If you select different temperature coefficients, this will lead to a parameter fault. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 573 Parameter sets of signal modules A.12 Parameters of analog output modules A.12 Parameters of analog output modules Parameters The table below lists all parameters you can set for analog output modules. The comparison shows: which parameters you can edit in STEP 7, and which parameters you can change using SFC55 "WR_PARM". Parameters set in STEP 7 can also be transferred to the module using SFC56 and SFC57. Table A- 30 Parameters of analog output modules Parameters Data record number Programmable, using ... ... SFC55 ... PG Diagnostics: Group diagnostics 0 No Yes Diagnostic interrupt enable 1 Yes Yes Reaction to CPU STOP Yes Yes Output type Yes Yes Output range Yes Yes Substitute value Yes Yes Note To enable diagnostic interrupts in the user program at data record 1, you first need to enable diagnostics at data record 0 in STEP 7. S7-300 Module data 574 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.12 Parameters of analog output modules Structure of data record 1 The figure below shows the structure of data record 1 for the parameters of analog output modules. You enable diagnostic interrupts by setting a logic "1" at the corresponding bit of byte 0. Figure A-25 Data record 1 for the parameters of analog output modules S7-300 Module data Manual, 06/2017, A5E00105505-AJ 575 Parameter sets of signal modules A.12 Parameters of analog output modules Output types and output ranges The table below lists all output types/ranges of the analog output modules, including their codes. Enter these codes at bytes 2 to 5 in data record 1 (refer to the previous figure.) Table A- 31 Output range codes of analog output modules Output type Code disabled Voltage Current Output range Code 2#0000 disabled 2#0000 2#0001 1 V to 5 V 2#0111 0 V to 10 V 2#1000 10 V 2#1001 0 mA to 20 mA 2#0010 4 mA to 20 mA 2#0011 20 mA 2#0100 2#0010 See also Analog modules (Page 300) S7-300 Module data 576 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.13 Parameters of analog output module SM 332; AO 8 x 12 Bit A.13 Parameters of analog output module SM 332; AO 8 x 12 Bit Parameter The table below shows all parameters you can set at analog output module SM 332; AO 8 x 12 Bit. The comparison shows: which parameters you can edit in STEP 7, and which parameters you can change using SFC 55 "WR_PARM". Parameters set in STEP 7 can also be transferred to the module using SFC 56 and SFC 57. Table A- 32 Parameters of SM 332; AO 8 x 12 Bit Parameters Data record number Programmable, using ... Diagnostics: Group diagnostics 0 no yes Diagnostics interrupt enable 1 yes yes Reaction to CPU STOP yes yes Output type yes yes Output range yes yes ... SFC 55 ... PG Note To enable diagnostics interrupts in the user program at data record 1, you first need to enable diagnostics at data record 0 in STEP 7. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 577 Parameter sets of signal modules A.13 Parameters of analog output module SM 332; AO 8 x 12 Bit Structure of data record 1 The figure below shows the structure of data record 1 for the parameters of SM 332; AO 8 x 12 Bit. You enable diagnostics interrupts by setting a logic "1" at the corresponding bit of byte 0. Figure A-26 Data record 1 for the parameters of analog output modules S7-300 Module data 578 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.13 Parameters of analog output module SM 332; AO 8 x 12 Bit Output type and output range The table lists the output types/ranges of SM 332; AO 8 x 12 Bit, including their codes. Enter these codes at bytes 2 to 9 in data record 1 (refer to the previous figure.) Table A- 33 Output range codes of analog output module SM 332; AO 8 x 12 Bit Output type Code Output range Code Disabled 2#0000 Disabled 2#0000 Voltage 2#0001 1 V to 5 V 0 V to 10 V 10 V 2#0111 2#1000 2#1001 Current 2#0010 0 mA to 20 mA 4 mA to 20 mA 20 mA 2#0010 2#0011 2#0100 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 579 Parameter sets of signal modules A.14 Parameters of analog IO modules A.14 Parameters of analog IO modules Parameter The table below lists all parameters you can set for analog IO modules. The comparison illustrates the parameters you can edit: in STEP 7 using SFC 55 "WR_PARM" Parameters set in STEP 7 can also be transferred to the module using SFC 56 and SFC 57 (refer to the STEP 7 manuals). Table A- 34 Parameters of analog IO modules Parameters Measuring method Data record number 1 Programmable, using ... ... SFC 55 ... PG yes yes Measuring range yes yes Integration time yes yes Output type yes yes Output range yes yes S7-300 Module data 580 Manual, 06/2017, A5E00105505-AJ Parameter sets of signal modules A.14 Parameters of analog IO modules Structure of data record 1 The figure below shows the structure of data record 1 for the parameters of analog IO modules. You enable a parameter by setting a logic "1" at the corresponding bit of byte 0. Figure A-27 Data record 1 for the parameters of analog IO modules S7-300 Module data Manual, 06/2017, A5E00105505-AJ 581 Parameter sets of signal modules A.14 Parameters of analog IO modules Measuring methods and ranges The table below lists all measuring methods/ranges of analog IO modules, including their codes. Enter these codes at bytes 2 to 5 in data record 1 (refer to the previous figure.) Table A- 35 Measuring range codes of analog IO modules Measuring method Code Measuring range Code disabled Voltage 2#0000 disabled 2#0000 2#0001 0 V to 10 V 2#1000 Resistance (4-wire connection) 2#0100 10 k 2#1001 Thermal resistance + linearization 4-wire connection 2#1000 Pt 100 Klima 2#0000 Output types and output ranges The table below lists all output types/ranges of analog IO modules, including their codes. Enter these codes at bytes 6 and 7 of data record 1 (refer to the previous figure.) Table A- 36 Output range codes of analog IO modules Output type Code Output range Code disabled Voltage 2#0000 disabled 2#0000 2#0001 0 V to 10 V 2#1000 S7-300 Module data 582 Manual, 06/2017, A5E00105505-AJ B Diagnostics data of signal modules B.1 Evaluating diagnostic data of signal modules in the user program Introduction This appendix describes the diagnostic data structure in system data. You should be sufficiently familiar with this structure if you want to evaluate the diagnostics data of the signal module in the STEP 7 user program. Diagnostics data are saved to data records The diagnostics data for a module is stored in data records 0 and 1. Data record 0 contains 4 bytes of diagnostics data describing the current state of the module. Data record 1 contains the 4 bytes of diagnostics data also stored in data record 0, plus additional module-specific diagnostics data, which describes the status of a channel or a channel group. Further references For detailed information on the evaluation of the diagnostics data of signal modules in the user program and on corresponding SFCs, refer to the STEP 7 manuals. S7-300 Module data 583 Manual, 06/2017, A5E00105505-AJ Diagnostics data of signal modules B.2 Structure and content of diagnostics data, byte 0 and up B.2 Structure and content of diagnostics data, byte 0 and up Introduction The section below describes the structure and content of the various bytes in diagnostics data. General rule: A fault is indicated by a logic "1" at the relevant bit. Bytes 0 and 1 (data records 0 and 1) Figure B-1 Bytes 0 and 1 of diagnostics data S7-300 Module data 584 Manual, 06/2017, A5E00105505-AJ Diagnostics data of signal modules B.2 Structure and content of diagnostics data, byte 0 and up Bytes 2 and 3 (data records 0 and 1) Figure B-2 Bytes 2 and 3 of diagnostics data S7-300 Module data Manual, 06/2017, A5E00105505-AJ 585 Diagnostics data of signal modules B.2 Structure and content of diagnostics data, byte 0 and up Bytes 4 to 6 info block (data record 1) Bytes 4 to 6 form the info block, which contains information relating to the channel type, the length of the diagnostic information, and the number of channels. Figure B-3 Bytes 4 to 6 of diagnostics data S7-300 Module data 586 Manual, 06/2017, A5E00105505-AJ Diagnostics data of signal modules B.2 Structure and content of diagnostics data, byte 0 and up Byte 7 channel fault vector and up (data record 1) Figure B-4 Byte 7 of diagnostics data The channel fault vector is at least 1 byte long. For modules with more than 8 channels, the channel fault vector occupies several bytes. The channel-specific diagnostics data comes after the channel fault vector; refer to section Channel-specific diagnostics data (Page 588). If another channel type is available (see Figure "Bytes 4 to 6 of diagnostics data"), the channel type with the same structure as that described above (channel type, length of diagnostics data, number of channels of the same type, channel fault vector, channelspecific diagnostics data of the channel type) follows after the channel-specific diagnostics data. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 587 Diagnostics data of signal modules B.3 Channel-specific diagnostics data B.3 Channel-specific diagnostics data Introduction The channel-specific diagnostic data follow the channel error vector. The number of bytes used per channel for channel-specific diagnostics depends on the number of bits entered in byte 5 "Length of the diagnostic information". The following figures show the assignment of the diagnostic byte for a channel or a channel group of the special module. The following generally applies: When an error occurs, the corresponding bit is set to "1". A description of possible causes of the fault and corresponding corrective measures can be found in the section "Diagnostics of the modules". Digital input channel of the SM 321; DI 16 x 24 V DC; with process and diagnostic interrupt Figure B-5 Diagnostic byte for a digital input channel der SM 321; DI 16 x DC 24 V Digital output channel of the SM 322; DO DC 8 x 24 V/0.5 A; with diagnostic interrupt Figure B-6 Diagnostic byte for a digital output channel of the SM 322; DO DC 8 x 24 V/0.5 A S7-300 Module data 588 Manual, 06/2017, A5E00105505-AJ Diagnostics data of signal modules B.3 Channel-specific diagnostics data Analog input channel of the SM 331 module with diagnostic capability Figure B-7 Diagnostic byte for an analog input channel of an SM 331 with diagnostic capability Analog output channel of the SM 332 module with diagnostic capability Figure B-8 Diagnostic byte for an analog output channel of an SM 332 with diagnostic capability S7-300 Module data Manual, 06/2017, A5E00105505-AJ 589 Diagnostics data of signal modules B.4 Diagnosis data from the SM 322; DO 16 x DC24 V/0.5 A (6ES7322-8BH10-0AB0) B.4 Diagnosis data from the SM 322; DO 16 x DC24 V/0.5 A (6ES7322-8BH10-0AB0) Introduction The section below describes the structure and content of the various bytes in diagnostics data. In the bytoes 0...3, module errors are reported - errors that affect the entire module. Starting at byte 4, channel-specific errors are reported. General rule: A fault is indicated by a logic "1" at the relevant bit. Byte 0 to byte 3 (diagnostic data records 0 and 1) Through entries in the diagnostic bytes byte 0 (bit 4...7) byte 2 and byte 3, module errors are reported, which cannot be turned off through the setting of the module. S7-300 Module data 590 Manual, 06/2017, A5E00105505-AJ Diagnostics data of signal modules B.4 Diagnosis data from the SM 322; DO 16 x DC24 V/0.5 A (6ES7322-8BH10-0AB0) Byte 4 to byte 6 infoblock (diagnostic data record 1) Byte 7 and 8 channel error vector (Diagnostic data record 1) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 591 Diagnostics data of signal modules B.4 Diagnosis data from the SM 322; DO 16 x DC24 V/0.5 A (6ES7322-8BH10-0AB0) Byte 9 to byte 24 cable diagnostics (diagnostic data record 1) Through byte 9 to byte 24 channel-specific errors are reported. S7-300 Module data 592 Manual, 06/2017, A5E00105505-AJ Diagnostics data of signal modules B.5 Diagnostics data of SM 331; AI 6 x TC isolated B.5 Diagnostics data of SM 331; AI 6 x TC isolated Introduction The section below describes the structure and content of the various bytes in diagnostics data. General rule: A fault is indicated by a logic "1" at the relevant bit. Byte 0 to byte 3 (diagnostic data records 0 and 1) Figure B-9 Diagnostic data records 0 and 1 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 593 Diagnostics data of signal modules B.5 Diagnostics data of SM 331; AI 6 x TC isolated Byte 4 to byte 13 (diagnostic data record 1) Figure B-10 Diagnostic data record 1 S7-300 Module data 594 Manual, 06/2017, A5E00105505-AJ Diagnostics data of signal modules B.5 Diagnostics data of SM 331; AI 6 x TC isolated Byte 14 to byte 23 (diagnostic data record 1) Figure B-11 Diagnostic data record 1 (continued) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 595 Diagnostics data of signal modules B.6 Diagnostics data of SM 338; POS-INPUT B.6 Diagnostics data of SM 338; POS-INPUT Introduction The next section describes the structure and contents of the various bytes in diagnostic data of the position detection module SM 338; POS-INPUT. General rule: A fault is indicated by a logic "1" at the relevant bit. You will find a description of possible causes of problems and appropriate remedies in the section titled Position detection module SM 338; POS-INPUT. Bytes 0 and 1 Figure B-12 Bytes 0 and 1 in diagnostics data of SM 338; POS-INPUT S7-300 Module data 596 Manual, 06/2017, A5E00105505-AJ Diagnostics data of signal modules B.6 Diagnostics data of SM 338; POS-INPUT Bytes 2 to 7 Figure B-13 Bytes 2 and 7 in diagnostics data of SM 338; POS-INPUT Bytes 8 to 10 Data record 1 contains the channel-specific diagnostic data, starting at bytes 8 to 10. The figure below shows the assignment of the diagnostic byte for a channel of SM 338; POS-INPUT. Figure B-14 Diagnostics byte for a channel of SM 338; POS-INPUT S7-300 Module data Manual, 06/2017, A5E00105505-AJ 597 Dimensional drawings C Introduction This appendix contains the dimensional drawings of the most important components of an S7-300. The specified dimensions are required to determine the dimensions of an S7-300 configuration. Make allowances for the dimensions of an S7-300 configuration when you install the system in cabinets, control rooms, etc. This appendix does not include the dimensional drawings of S7-300 or M7-300 CPUs, or of IM 153-1. These are included in the relevant manuals. Contents This appendix contains the dimensional drawings of the S7-300 components listed below. Mounting rails Power supply modules Interface modules Signal modules Accessories S7-300 Module data Manual, 06/2017, A5E00105505-AJ 598 Dimensional drawings C.1 Dimensional drawings of the mounting rails C.1 Dimensional drawings of the mounting rails Standard mounting rail 483 mm The figure below shows the dimensional drawing of the 483 mm standard rail. Figure C-1 Dimensional drawing of the 483 mm standard rail Standard mounting rail 530 mm The figure below shows the dimensional drawing of the 530 mm standard rail. Figure C-2 Dimensional drawing of the 530 mm standard rail S7-300 Module data Manual, 06/2017, A5E00105505-AJ 599 Dimensional drawings C.1 Dimensional drawings of the mounting rails Standard mounting rail 830 mm The figure below shows the dimensional drawing of the 830 mm standard rail. Figure C-3 Dimensional drawing of the 830 mm standard rail Standard mounting rail 2000 mm The figure below shows the dimensional drawing of the 2000 mm standard rail. Figure C-4 Dimensional drawing of the 2000 mm standard rail S7-300 Module data 600 Manual, 06/2017, A5E00105505-AJ Dimensional drawings C.1 Dimensional drawings of the mounting rails Mounting rail 160 mm The figure below shows the dimensional drawing of the 160 mm mounting rail. Figure C-5 Dimensional drawing of the mounting rail with standard width of 160 mm. Mounting rail 482.6 mm The figure below shows the dimensional drawing of the 482.6 mm mounting rail. Figure C-6 Dimensional drawing of the mounting rail with standard width of 482.6 mm. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 601 Dimensional drawings C.1 Dimensional drawings of the mounting rails Mounting rail 530 mm The figure below shows the dimensional drawing of the 530 mm mounting rail. Figure C-7 Dimensional drawing of the mounting rail with standard width of 530 mm. Mounting rail 830 mm The figure below shows the dimensional drawing of the 830 mm mounting rail. Figure C-8 Dimensional drawing of the mounting rail with standard width of 830 mm. S7-300 Module data 602 Manual, 06/2017, A5E00105505-AJ Dimensional drawings C.1 Dimensional drawings of the mounting rails Mounting rail 2000 mm The figure below shows the dimensional drawing of the 2000 mm mounting rail. Figure C-9 Dimensional drawing of the 2000 mm mounting rail S7-300 Module data Manual, 06/2017, A5E00105505-AJ 603 Dimensional drawings C.1 Dimensional drawings of the mounting rails Mounting rail for the "Insertion and Removal" function The figure below shows the dimensional drawing of the mounting rail for the "Insertion and Removal" function with active bus module, S7-300 module and explosion-proof partition. The mounting rail has a length of 482.6 mm or 530 mm. Explosion-proof partition S7-300 module active bus module Mounting rail for the "Insertion and Removal" function S7-300 Module data 604 Manual, 06/2017, A5E00105505-AJ Dimensional drawings C.1 Dimensional drawings of the mounting rails C.1.1 Bus modules The figure below shows the dimension drawing of the active bus module for the "Insertion and Removal" function. Bus modules BM PS/IM (...7HA) BM IM/IM (...7HD) BM 2 x 40 (...7HB) BM 1 x 80 (...7HC) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 605 Dimensional drawings C.2 Dimensional drawings of the power supply modules C.2 Dimensional drawings of the power supply modules PS 307 2 A The drawing below shows the dimensions of power supply module PS 307; 2 A. Figure C-10 Power supply module PS 307; 2 A S7-300 Module data 606 Manual, 06/2017, A5E00105505-AJ Dimensional drawings C.2 Dimensional drawings of the power supply modules PS 307 5 A (6ES7307-1EA01-0AA0) The drawing below shows the dimensions of power supply module PS 307; 5 A. Figure C-11 Power supply module PS 307; 5 A PS 307; 10 A with 313/314/315/ 315-2 DP CPU The figures below show the dimensional drawings of a configuration consisting of a power supply module PS 307; 10 A and a 313/314/315/315-2 DP CPU. Observe the dimensions derived from the use of a power connector when wiring the PS 307; 10 A to the CPU. Figure C-12 Dimensional drawing of power supply module PS 307; 10 A with CPU 313/314/315/3152 DP, front view S7-300 Module data Manual, 06/2017, A5E00105505-AJ 607 Dimensional drawings C.2 Dimensional drawings of the power supply modules PS 307; 10 A with 313/314/315/ 315-2 DP CPU The side view drawing below shows the dimensions of power supply module PS 307; 10 A with 313/314/315/315-2 DP CPU. Figure C-13 Dimensional drawing power supply module PS 307; 10 A with CPU 313/314/315/315-2 DP, side view S7-300 Module data 608 Manual, 06/2017, A5E00105505-AJ Dimensional drawings C.2 Dimensional drawings of the power supply modules PS 305 2 A, PS 307 5 A (6ES7307-1EA80-0AA0) and PS 307 10 A The following image shows the drawing of the power supply modules PS 305; 2 A, PS 307 5 A and PS 307; 10 A. Figure C-14 Power supply module PS 307; 10 A S7-300 Module data Manual, 06/2017, A5E00105505-AJ 609 Dimensional drawings C.3 Dimensional drawings of the interface modules C.3 Dimensional drawings of the interface modules IM 360 The figure below shows the dimensional drawing of interface module IM 360. Figure C-15 Interface module IM 360 IM 361 The figure below shows the dimensional drawing of interface module IM 361. Figure C-16 Interface module IM 361 S7-300 Module data 610 Manual, 06/2017, A5E00105505-AJ Dimensional drawings C.3 Dimensional drawings of the interface modules IM 365 The figure below shows the dimensional drawing of interface module IM 365. Figure C-17 Interface module IM 365 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 611 Dimensional drawings C.4 Dimensional drawings of the signal modules C.4 Dimensional drawings of the signal modules Signal module The figure below shows the dimensional drawing of the signal module. The signal module design may differ. The specified dimensions are always the same. * With front door, elevated design Figure C-18 Signal module S7-300 Module data 612 Manual, 06/2017, A5E00105505-AJ Dimensional drawings C.4 Dimensional drawings of the signal modules 64-channel signal module The figure below shows the dimension drawing for 64-channel I/O modules. Figure C-19 64-channel signal module S7-300 Module data Manual, 06/2017, A5E00105505-AJ 613 Dimensional drawings C.5 Dimensional drawings of accessories C.5 Dimensional drawings of accessories Shield connection element The figure below shows the dimensional drawing of the shield connecting element used two signal modules. Figure C-20 2 signal modules with shield connecting element S7-300 Module data 614 Manual, 06/2017, A5E00105505-AJ Dimensional drawings C.5 Dimensional drawings of accessories 40-pin terminal block The figure below shows the dimension drawing of the 40-pin terminal block for 64-channel signal modules. Figure C-21 40-pin terminal block S7-300 Module data Manual, 06/2017, A5E00105505-AJ 615 Spare parts and accessories for S7-300 modules D Spare parts The table below lists the S7-300 parts you can order separately or later. Table D- 1 Accessories and spare parts S7-300 parts Order number Bus connector 6ES7390-0AA00-0AA0 Connection comb between power supply and CPU (older generation, before 2003) 6ES7390-7BA00-0AA0 Labeling strips for * Modules with 20-pin front connector: - (petrol) - (light beige) - (yellow) - (red) 6ES7392-2AX00-0AA0 6ES7392-2BX00-0AA0 6ES7392-2CX00-0AA0 6ES7392-2DX00-0AA0 Labeling strips for * * Modules with 40-pin front connector: - (petrol) - (light beige) - (yellow) - (red) Instructions for printing labeling strips using print templates 6ES7392-2AX10-0AA0 6ES7392-2BX10-0AA0 6ES7392-2CX10-0AA0 6ES7392-2DX10-0AA0 On the Internet (http://www.siemens.com/automation/service&sup port) Entry ID: 11978022 Slot number plate 6ES7912-0AA00-0AA0 Front connector 20-pin * Screw terminal technology (1 unit) * Screw technology (100 units) * Spring clamp technology (1 unit) * Spring clamp technology (100 units) 6ES7392-1AJ00-0AA0 6ES7392-1AJ00-1AB0 6ES7392-1BJ00-0AA0 6ES7392-1BJ00-1AB0 Front connector 40-pin * Screw technology (1 unit) * Screw technology (100 units) * Spring clamp technology (1 unit) * Spring clamp technology (100 units) 6ES7392-1AM00-0AA0 6ES7392-1AM00-1AB0 6ES7392-1BM01-0AA0 6ES7392-1BM01-1AB0 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 616 Spare parts and accessories for S7-300 modules S7-300 parts Order number Front connector for 2 ribbon cable connections * * screw terminal technology Spring clamp technology 6ES7921-3AB00-0AA0 6ES7921-3AA00-0AA0 Front connector for 4 ribbon cable connections * Spring clamp technology 6ES7921-3AA20-0AA0 Round-sheath ribbon cable (16-pole) * Unshielded 30 m * Unshielded 60 m * Shielded 30 m * Shielded 60 m 6ES7923-0CD00-0AA0 6ES7923-0CG00-0AA0 6ES7923-0CD00-0BA0 6ES7923-0CG00-0BA0 Connectors, 16-pin, set of 8 (insulation displacement terminals) 6ES7921-3BE10-0AA0 Shield connection element 6ES7390-5AA00-0AA0 Shield terminal element for * 2 cables, each with a shield diameter of 2 to 6 mm * 1 cable with a shield diameter of 3 to 8 mm * 1 cable with a shield diameter of 4 to 13 mm 6ES7390-5AB00-0AA0 6ES7390-5BA00-0AA0 6ES7390-5CA00-0AA0 Measuring range module for analog modules 6ES7974-0AA00-0AA0 Fuse set for digital output modules 6ES7973-1HD00-0AA0 - 6ES7322-1FF01-0AA0 - 6ES7322-1FH00-0AA0 - 6AG1322-1FF01-2AA0 (contains 10 fuses and 2 fuse holders) Fuse set for digital output module * 6ES7973-1GC00-0AA0 6ES7322-1CF00-0AA0 (contains 10 fuses) Connecting cable for IM 360 and IM 361, or IM 361 and IM 361 * 1m * 2.5 m * 5m * 10 m 6ES7368-3BB01-0AA0 6ES7368-3BC51-0AA0 6ES7368-3BF01-0AA0 6ES7368-3CB01-0AA0 Connecting cable between the 64-channel modules: SM 321, 6ES7321-1BP00-0AA0 sinking/sourcing, SM 322, 6ES7322-1BP00-0AA0 sourcing, SM 322, 6ES7322-1BP50-0AA0 sinking and 40-pin terminal block (screw terminal, spring clamp technology) * 1.0 m * 2.5 m * 5.0 m 6ES7392-4BB00-0AA0 (2 units) 6ES7392-4BC50-0AA0 (2 units) 6ES7392-4BF00-0AA0 (2 units) S7-300 Module data Manual, 06/2017, A5E00105505-AJ 617 Spare parts and accessories for S7-300 modules S7-300 parts Order number Terminal block 40-pin for 64-channel modules * Screw terminal technology * Spring clamp technology Front door, elevated design for 32-channel modules (5 units) incl. labeling strips and connection diagram 6ES7392-1AN00-0AA0 (2 units) 6ES7392-1BN00-0AA0 (2 units) 6ES7328-0AA00-7AA0 Information about front connector selection Your can find more information on front connector selection for the various SIMATIC S7-300 modules on the Internet (http://support.automation.siemens.com/WW/view/en/23060726). S7-300 Module data 618 Manual, 06/2017, A5E00105505-AJ Directive on handling Electrostatic-Sensitive Devices (ESD) E Introduction In this appendix, we explain the meaning of "electrostatic-sensitive devices" the precautions you must take when handling and working with electrostatic sensitive modules. E.1 Definition of ESD Definition All electronic modules are equipped with large-scale integrated ICs or components. Due to their design, these electronic elements are highly sensitive to overvoltage, and thus to any electrostatic discharge. These Electrostatic Sensitive Ddevices/Modules are commonly abbreviated ESD. The common international designation ESD stands for Electrostatic Sensitive Device. ESD modules are identified by the following symbol: CAUTION ESD devices can be destroyed by voltages well below the threshold of human perception. These static voltages develop when you touch a component or electrical connection of a device without having drained the static charges present on your body. The electrostatic discharge current may lead to latent failure of a module, that is, this damage may not be significant immediately, but in operation may cause malfunction. S7-300 Module data 619 Manual, 06/2017, A5E00105505-AJ Directive on handling Electrostatic-Sensitive Devices (ESD) E.2 Electrostatic charging of the body E.2 Electrostatic charging of the body Electrostatic charging Any person with a non-conductive connection to the electrical potential of its surroundings may be exposed to electrostatic charge. The figure below shows the maximum electrostatic voltage which may build up on a person coming into contact with the materials indicated. These values correspond to IEC 801-2 specifications. Synthetic material Wool antistatic materials, such as wood or concrete S7-300 Module data 620 Manual, 06/2017, A5E00105505-AJ Directive on handling Electrostatic-Sensitive Devices (ESD) E.3 Basic protective measures against electrostatic discharge E.3 Basic protective measures against electrostatic discharge Ensure sufficient grounding Make sure all persons, workplaces and packaging are sufficiently grounded when handling ESD components. This prevents electrostatic charge. Avoid direct contact You should only touch ESD components if unavoidable (for example, during maintenance work). Handle the modules without touching any chip pins or PCB traces. In this way, the discharged energy can not affect the sensitive devices. Discharge your body before you start taking any measurements on a module. Do so by touching grounded metallic parts. Always use grounded measuring instruments. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 621 Service & support F.1 F Service & support Technical support You can contact Technical Support for all Industry Automation products by means of the Internet Web form for the Support Request on the Internet (http://www.siemens.com/automation/support-request) Additional information on our technical support is available on the Internet (http://www.siemens.com/automation/service). Service & support on the Internet In addition to our documentation, we offer a comprehensive knowledge base on the Internet. On the Internet (http://www.siemens.com/automation/service&support). There you will find: Our Newsletter, which constantly provides you with the latest information about your products. The documents you require, via our service & support search facility. A forum, where users and experts from all over the world exchange their experiences. Your local contact for Automation & Drives from our contact database. Information about on-site service, repairs, spare parts, and much more. Additional support If you have any questions relating to the products described in this manual and cannot find the answers in this documentation, please contact your Siemens partner at the appropriate office or sales and service location. The contact details for your partner are available on the Internet (http://www.automation.siemens.com/partner/). A guide to the technical documentation provided for the various SIMATIC products and systems is available on the Internet (http://www.siemens.com/simatic-tech-doku-portal). The online catalog and order system is available on the Internet (http://www.siemens.com/automation/mall). Training center Siemens offers various courses to get you started with the S7-300 and the SIMATIC S7 automation system. Please contact your regional training center or the central training center in Nuremberg (ZIP code: 90327). Additional information is available on the Internet (http://www.siemens.com/sitrain). S7-300 Module data Manual, 06/2017, A5E00105505-AJ 622 Safety-relevant symbols G.1 G Safety-related symbols for devices without Ex protection The following table contains an explanation of the symbols located in your SIMATIC device, its packaging or the accompanying documentation. Symbol Meaning General warning sign Caution/Notice You must read the product documentation. The product documentation contains information about the potential risks and enable you to recognize risks and implement countermeasures. Read the information provided by the product documentation. ISO 7010 M002 Ensure the device is only installed by electrically skilled person. IEC 60417 No. 6182 Note that connected mains lines must be designed according to the expected minimum and maximum ambient temperature. Note that the device must be constructed and connected in accordance with EMC regulations. Note that a 230 V device can be exposed to electrical voltages which can be dangerous. ANSI Z535.2 Note that a device of Protection Class III may only be supplied with a protective low voltage according to the standard SELV/PELV. IEC 60417-1-5180 "Class III equipment" Be aware that the device is only approved for the industrial field and only for indoor use. Note that an enclosure is required for installing the device. Enclosures are considered: * Standing control cabinet * Serial control cabinet * Terminal boxes * Wall enclosure S7-300 Module data Manual, 06/2017, A5E00105505-AJ 623 Safety-relevant symbols G.2 Safety-related symbols for devices with Ex protection G.2 Safety-related symbols for devices with Ex protection The following table contains an explanation of the symbols located in your SIMATIC device, its packaging or the accompanying documentation. Symbol Meaning The assigned safety symbols apply to devices with Ex approval. You must read the product documentation. The product documentation contains information about the potential risks and enable you to recognize risks and implement countermeasures. Read the information provided by the product documentation. ISO 7010 M002 Ensure the device is only installed by electrically skilled person. IEC 60417 No. 6182 Observe the mechanical rating of the device. Note that connected mains lines must be designed according to the expected minimum and maximum ambient temperature. Note that the device must be constructed and connected in accordance with EMC regulations. When the device is under voltage, note that it may not be installed or removed, or plugged or pulled. Note that a 230 V device can be exposed to electrical voltages which can be dangerous. ANSI Z535.2 Note that a device of Protection Class III may only be supplied with a protective low voltage according to the standard SELV/PELV. IEC 60417-1-5180 "Class III equipment" Be aware that the device is only approved for the industrial field and only for indoor use. S7-300 Module data 624 Manual, 06/2017, A5E00105505-AJ Safety-relevant symbols G.2 Safety-related symbols for devices with Ex protection Symbol Meaning For Zone 2 potentially explosive atmospheres, be aware that the device may only be used when it is installed in an enclosure with a degree of protection IP54. For Zone 22 potentially explosive atmospheres, be aware that the device may only be used when it is installed in an enclosure with a degree of protection IP6x. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 625 List of abbreviations H.1 H List of abbreviations Abbreviations Explanations AC Alternating current ADC Analog-to-Digital Converter AI Analog input AO Analog output AS Automation system COMP+ / - Compensation line (positive / negative) CP Communications processor CPU Central Processing Unit of the PLC DAC Digital-to-Analog Converter DB Data block DC Direct current DI Digital input DO Digital output ESD Electrostatic sensitive devices EMC Electromagnetic Compatibility EPROM Erasable Programmable Read-Only Memory SSV Set substitution value FB Function block FC Function FEPROM Flash Erasable Programmable Read-Only Memory ES Encoder supply I+ Measuring line for current input IC+ / - Constantcurrent line (positive negative) KV+ / - Cold spot comparison (positive / negative) L+ Power supply 24 VDC HLV Hold last valid value FOC Fiber-optic conductor M Ground M+ / - Measuring line (positive / negative) MANA Reference potential of the analog measuring circuit MPI Multipoint interface OB Organization block OP Operator panel S7-300 Module data 626 Manual, 06/2017, A5E00105505-AJ List of abbreviations H.1 List of abbreviations Abbreviations Explanations OS Operator system P5V Power supply for module logic PIO Process Image of Outputs PII Process Image of Inputs PG Programming device PS Power supply QI: Analog output current QV: Analog output voltage RAM Random Access Memory RL: Load impedance S+/- Sensor line (positive / negative) SF "Group error" LED SFB System function block SFC System function SM Signal module PLC Programmable logic controller SSI Synchronous serial interface TD HMI (Text Display) U+ Measuring line for voltage input CMV Common Mode Voltage Viso Potential difference between MANA and local ground sign Sign S7-300 Module data Manual, 06/2017, A5E00105505-AJ 627 Glossary 2-/3-/4-wire connection Methods of connecting resistance thermometers / resistances to the front connector of the module, or loads to the voltage output of an analog input module. 2-wire transducer (passive sensor) / 4-wire transducer (active sensor) Type of transducer ( 2-wire transducers: power supply via terminals of the analog input module; 4-wire transducers: power supply via separate terminals of the transducer.) Absolute encoder Determines the distance traveled by reading a numerical value: When using absolute encoders with serial interface (SSI), the path information is transferred synchronously and serially according to the SSI protocol (synchronous serial interface). Address Represents the identifier of a specific address or address range. Examples: input I 12.1; flag word MW 25; data block DB 3. Article number Order number Backplane bus Serial data bus for module intercommunication, and power distribution to the modules. Bus connectors interconnect the modules. Basic conversion time Time required for the actual coding of a channel (integration time, plus all times required by the internal control, i.e. the channel is fully processed when this time has expired. Basic error limit Represents the operational limit at 25 C, relative the module's rated range. Basic execution time Cycle time of an analog IO module when all of its channels are enabled. Equivalent to "number of channels x basic conversion time." S7-300 Module data 628 Manual, 06/2017, A5E00105505-AJ Glossary Bus A transfer medium that interconnects several nodes. Data may be transferred in serial or parallel mode, using electrical or fiber-optic conductors. Bus segment Self-contained part of a bus system. Bus segments are coupled by means of Repeater. Calibration Refers to the process of determining the relationship between the measured or expected value of the output variable and the associated true or correct value of the measured variable provided as the input variable, for a specific measuring device and under particular circumstances. Common mode voltage (CMV) The voltage common to all terminals of a group, measured between this group and any reference point (usually ground potential.) Communications processor Programmable communications module, used for networking, PtP coupling, for example. Compensating box Can be used for temperature measurements using thermocouples connected to analog input modules. Represents a compensation circuit used to compensate temperature fluctuation at the Reference junction. Configuring Refers to the selection and assembly of automation system components, or to software installation and adaptation to a specific process (by programming the modules, for example.) CP Communications processor CPU Central Processing Unit of the Automation System. A CPU stores and executes the user program. It contains the operating system, memory, processing unit and communications interfaces. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 629 Glossary Cycle time Denotes the time a CPU requires for a single execution of the user program. Default setting A useful setting which is used whenever the user does not enter a different value. Destruction limit Permissible limit of the input voltage / output current. The accuracy of measurements may deteriorate if this limit is violated. If the destruction limit is considerably exceeded, this may destroy the internal measuring circuit. Diagnostic interrupt Module diagnostics function report errors to the CPU by means of diagnostic interrupts. The CPU operating system calls OB 82 when a diagnostic interrupt is generated. Diagnostics Generic term for System diagnostics, hardware error diagnostics, and user-specific diagnostics. Diagnostics buffer The diagnostics buffer represents a backup memory in the CPU, used to store diagnostics events in their order of occurrence. In STEP 7 (PLC Module status), the user can read data from the diagnostics buffer to determine the precise cause of error. Diagnostics data All diagnostics events are logged at the CPU and entered in Diagnostics buffer. If an error OB exists, the buffer is started. Direct access Denotes access of the CPU to a module via the backplane bus, while bypassing the Process image. electrically disconnected The reference potential of the control and load voltage circuits at electrically isolated IO modules are isolated galvanically, for example, using optocouplers, relay contacts or transformers. IO circuits can be connected to a common reference potential. S7-300 Module data 630 Manual, 06/2017, A5E00105505-AJ Glossary electrically interconnected The reference potential of the control and load voltage circuits of non-isolated IO modules are electrically interconnected. Equipotential bonding Electrical connection (equipotential conductor) of electrical equipment and external conductive objects to the same or near to same potential, in order to prevent the development of disturbance and dangerous potentials between those objects. FREEZE STEP 7 parameter for the SM 338; POS-INPUT position detection module. FREEZE is a control command (function), used to freeze actual encoder values of SM 338. Ground The conductive earth whose electrical potential can be set equal to zero at any point. Ground potential may be different from zero in the area of grounding electrodes. The term "reference ground" is frequently used to describe this situation. grounding Grounding means, to connect an electrically conductive component via an equipotential grounding system to a grounding electrode (one or several conductive components with low impedance contact to earth.) Hardware interrupt Function initiated by interrupt-triggering modules, based on specific events in the process (high or low limit violated, module has completed cyclic conversion of channels.) The hardware interrupt is reported to the CPU, The CPU executes the assigned Organization block according to interrupt priority. Hold last value (HLV) The module retains the last value output before the CPU went into STOP. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 631 Glossary Input delay STEP 7 parameter for digital input modules. The input delay function is used to suppress coupled disturbance. This includes pulse-shaped disturbance within the range from 0 ms to the set input delay The input delay tolerance is defined in the technical data of the module. The length of suppressed pulse-shaped disturbance is determined by the length of the input delay. The permissible input delay is determined by the line length between the encoder and the module. Unshielded encoder supply lines of a grater length (more than 100 m) require a long delay setting. Integration time STEP 7 parameter for analog input modules. The integration time is equivalent to the inverse value of the noise suppression frequency in ms. Interface, multi-point MPI Interference frequency suppression STEP 7 parameter for analog input modules. The frequency of AC mains may corrupt measured values, in particular in the low voltage ranges, and when thermocouples are being used. At this parameter, the user defines the mains frequency prevailing on his system. Interrupt SIMATIC S7 knows 28 different priority classes which control user program execution. These priority classes include interrupts, such as hardware interrupts. When an interrupt occurs, the operating system automatically calls an assigned organization block, in which the user can program the desired response (e.g. in an FB). Interrupt, diagnostics Diagnostic interrupt Interrupt, end of cycle hardware interrupt Interrupt, hardware hardware interrupt S7-300 Module data 632 Manual, 06/2017, A5E00105505-AJ Glossary Linearity error Denotes the maximum deviation of the measured/output value from the ideal linear relationship between the measured/output signal and the digital value. Defined as a percentage, relative to the rated range of the analog module. Logic block A SIMATIC S7 logic block contains elements of the STEP 7 user program. In contrast, a data block only contains data. Available logic blocks: Organization Blocks (OBs), Function Blocks (FBs), Functions (FCs), System Function Blocks (SFBs), System Functions (SFCs). Measuring range module Modules installed on analog input modules for the adaptation to different measuring ranges. Monoflop time STEP 7 parameter for the SM 338; POS-INPUT position detection module. The monoflop time is equivalent to interval between two SSI message frames ( Absolute encoder.) MPI Multi-Point Interface. SIMATIC S7 interface for programming devices. Allows central access to remote programmable modules (CPUs, CPs), Text Displays und Operator Panels. MPI nodes can intercommunicate. OB Organization Block Operating mode Definition of this term: 1. selection of a CPU operating state using the mode selector switch or a PG 2. the type of program execution at the CPU 3. an analog input module parameter in STEP 7 Operating state Operating states known to SIMATIC S7 automation systems: STOP, STARTUP, RUN and STOP. Operational limit Represents the measuring/output error of an analog module across the entire permissible temperature range, based on the module's rating. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 633 Glossary Organization block OBs form the interface between the CPU operating system and the user program. The sequential order of user program execution is defined in the organization blocks. Parameters 1. Tag of a Code block 2. Tag used to set one or several properties of a module. Each module is supplied with default parameters which users may edit in STEP 7. PG Programming device Process image The CPU saves the signal states of analog IO modules to a process image. We distinguish between the process image of inputs (PII) and outputs (PIO). The input modules read the process image of inputs (PII) before the operating system executes the user program. The operating system transfers the process image of outputs (PIO) to the output modules at the end of program execution. Product version Differentiates products of the same order number. The product version is incremented in the case of upwards compatible enhancements of functionality, production-specific changes (use of new components/parts), and fixes. Programming device A programming device (PG) is a special compact PC (Personal Computer) suitable for use in industry. A PG is fully equipped for programming SIMATIC automation systems. Reference junction When operating thermocouples on analog input modules: point of known temperature (for example, compensating box.) Reference potential Potential from which the voltages of participating circuits are derived and measured. Repeat accuracy Denotes the maximum deviation between measured/output values, if the same input or output signal is repeatedly set. Repeat accuracy refers to the rated range of the module, and applies to its settled temperature state. S7-300 Module data 634 Manual, 06/2017, A5E00105505-AJ Glossary Repeater Equipment used to amplify bus signals, and couple bus segments across greater distances Resolution Number of bits representing the value of analog modules in binary format. The resolution is module-specific. It is also determined by the integration time of analog input modules. The precision of the measured value resolution increases with the length of the integration time. The maximum resolution is 16 bits + sign. Response to open thermocouple STEP 7 parameter for analog input modules operating with thermocouples. This parameter defines whether the module outputs an "Overflow" (7FFFH) or "Underflow" (8000H) value when it detects an open thermocouple. Restart At its restart (initiated by setting the mode selector switch from STOP to RUN, or after POWER ON), the CPU first executes restart OB 100, and then continues with cyclic program execution (OB1.) During its restart, the CPU reads the Process image of inputs (PIO), and then executes the STEP 7 user program, starting at the first statement in OB1. Retentivity Data areas in data blocks (DBs), timers, counters and flags are considered retentive if their content is not lost as a result of restart or power off. Scaling STEP 7 parameter for the SM 338; POS-INPUT position detection module. Scaling rightaligns the Absolute encoder value in the address space; irrelevant places are discarded. Segment Bus segment SFC System Function Signal module Signal modules (SMs) form the interface between the process and the automation system. These are available as digital and analog input/output and IO modules. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 635 Glossary Smoothing STEP 7 parameter for analog input modules. The measured values are smoothed by digital filtering. Users can select module-specific filter properties, i.e. none, low, medium or high. The time constant of the digital filter increases in proportion to the degree of smoothing. STARTUP STARTUP mode initiates the transition from STOP to RUN mode. STARTUP can be triggered by setting the mode selector, by power on, or by an operator action on the programming device. S7-300 performs a restart. Substitution value Values output by faulty signal output modules to the process, or used to substitute a process value of a faulty signal input module in the user program. Users can program the substitute values in STEP 7 (hold last value, substitution value 0 or 1.) Those values must be set at the outputs when the CPU goes into STOP. System diagnostics Denotes the detection, evaluation and reporting of error events within the automation system. Examples of such errors are: program errors, or module failure. System errors may be indicated by LED displays, or in STEP 7. System Function A System Function (SFC) is an integral function of the CPU operating system, and can be called in the STEP 7 user program as required. Temperature coefficient STEP 7 parameter for analog input modules, for temperature measurements taken with resistance thermometers (RTD.) The selected temperature coefficient is specific to the resistance thermometer being used (to DIN standard.) Temperature error Denotes the drift of measured/output values, caused by fluctuation of the ambient temperature at an analog module. It is defined in % per Kelvin, relative to the rated range of the analog module. Temperature error of internal compensation Only applies to the measurement of thermocouples. Defines the error to add to the actual temperature error, when "internal comparison" mode is selected. The error is defined either as a percentile value relative to the physical rated range of the analog module, or as an absolute value in C. S7-300 Module data 636 Manual, 06/2017, A5E00105505-AJ Glossary Total current Total current of all output channels of a digital output module. ungrounded no galvanic connection to ground potential User program Contains statements, tags and data for processing signals which can control a plant or process. It is assigned to a programmable module (CPU, FM, for example) and can be organized in smaller units (blocks). Wirebreak Parameter in STEP 7. A wirebreak check is used to monitor line continuity between the encoder and input, or between the actuator and output. The module detects a wirebreak based on a current flow at the appropriately programmed input/output. S7-300 Module data Manual, 06/2017, A5E00105505-AJ 637 Index 2 2-wire connection Resistance thermometer, 248 Voltage output, 259 2-wire transducer, 245 3 3-wire connection, 248 4 40-pin terminal block Dimensional drawing, 615 SM 321, DI 64 x DC 24 V, sinking/sourcing, 64 SM 321, DO 64 x DC 24 V, 0.3 A sourcing, 121 SM 322, DO 64 x DC 24 V, 0.3 A Sinking, 129 4-wire connection Resistance thermometer, 247 Voltage output, 258 4-wire transducer, 246 A Absolute value encoder (SSI) SM 338, POS-INPUT, 505 Accessories, 616 Actuators see also Connect loads/actuators, 257 Addressing SM 334, SM 338, POS-INPUT, 507 SM 334 Unused channels, SM 331 Parameters, Technical specifications, SM 331 Isochronous mode, Measurement types and measuring ranges, Properties, Supplementary information, Wiring diagram, Ambient conditions Climatic, 24 Mechanical, 23 Operating condition, 23 SIPLUS S7-300, 30 Analog functions, STEP 7 blocks, 300 Analog input module Causes of error and troubleshooting, 297 Common-mode error, 297 Configuration error, 297 Dataset 1, structure, 535 Diagnostics messages, 296 isolated, non-isolated, 239 Load voltage missing, 297 Overflow, 297 Parameters, 294, 534 Programming error, 297 Underflow, 297 Wirebreak, Wiring and connecting thermocouples, 249 Analog input modules SM 331, AI 2 x 12 Bit, 367 SM 331, AI 6 x TC isolated, 412 SM 331, AI 8 x 12 Bit, 353 SM 331, AI 8 x 13 Bit, 340 SM 331, AI 8 x 14 Bit High Speed, 329 SM 331, AI 8 x 16 Bit, 307, 318 SM 331, AI 8 x RTD, 380 SM 331, AI 8 x TC, 396 Analog input/output module SM 334, AI 4/AO 2 x 12 Bit, 484 Analog IO module Dataset 1, structure, 581 Parameters, 580 SM 334, AI 4/AO 2 x 8/8 Bit, 476 Analog module Analog value processing, 238 Determination of the measuring error/output error, 288 Diagnostics, 295 Dimensional drawing, 612 Group error LED, 295 Interrupts, 298 Power failure, 286 programming, 294 Reaction, 285 Start up, step, 301 Analog output channel Conversion time, 292 S7-300 Module data 638 Manual, 06/2017, A5E00105505-AJ Index Analog output module Causes of error and troubleshooting, 297 Configuration error, 297 Dataset 1, structure, 575 Diagnostic messages, 296 isolated, non-isolated, 257 Load voltage missing, 297 Parameters, 574 Programming error, 297 Short-circuit to M, 297 Wirebreak, Analog output modules SM 332, AO 2 x 12 Bit, 468 SM 332, AO 4 x 12 Bit, 460 SM 332, AO 4 x 16 Bit, 450 SM 332, AO 8 x 12 Bit, 442 Analog value Conversion, 261 Sign, 261 STEP 7 blocks, 300 Analog value processing Connecting loads/actuators, 257 Current transducers, 245 Introduction, 238 Resistance thermometer, 247 Resistors, 247 Thermocouples, 249 Transducers, 239 Voltage transducers, 244 Analog-to-digital conversion, 289 Approval, 14 CSA, 16 FM, 17 Marine, 18 UL, 15 Use in industrial environments, 18 Use in residential areas / mixed areas, 18 Auxiliary voltage missing SM 338, POS-INPUT, 510 B Basic error limit, 288 Basic knowledge required, 3 C Causes of error and remedies SM 321, DI 16 x DC 24 V, 89 SM 321, DI 16 x DC 24 V/125 V, 100 SM 322, DO 8 x AC 120/230 V/2 A ISOL, 196 SM 322, DO 8 x DC 24 V/0.5 A, 180 SM 322, DO 8 x Rel. AC 230 V/5 A (5HF00), 215 Causes of error and troubleshooting Analog input module, 297 Analog output module, 297 SM 338, POS-INPUT, 510 Changes in the manual, 3 Changes in the manual, 3 Channel fault SM 338, POS-INPUT, 510, 510 Channel information available SM 338, POS-INPUT, 510 Channel-specific diagnostics, 588 Code type SM 338, POS-INPUT, 505 Common-mode error Analog input module, 297 Compensate reference junction temperature, 251 Configuration error Analog input module, 297 Analog output module, 297 SM 338, POS-INPUT, 510 Connect current transducer, 245 2-wire transducer, 245 4-wire transducer, 246 Connect voltage transducer, 244 Connecting loads/actuators 2-wire connection, 259 4-wire connection, 258 Current output, 260 Introduction, 257 Voltage output, 258 Connecting measuring transducers Isolated measuring encoders, 240 Non-isolated sensors, 241 Principles, 239 Connecting resistance thermometers, 247 2-wire connection, 248 3-wire connection, 248 4-wire connection, 247 Conversion of analog values, 261 Conversion time Analog input channels, 289 Analog output channel, 292 CSA approval, 16 Cycle time Analog input channels, 289 Analog output channels, 292 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 639 Index D Data records for diagnostic data, 583 for parameters, 522 Dataset 1, structure Analog input module, 535 Analog IO module, 581 Analog output module, 575 Digital input module, 525, 526 Digital output module, 529 SM 322, DO 16 x DC 24 V/0.5 A (8BH10), 531 SM 327, DI 8/DO 8 x DC 24 V/0.5 A, 236 SM 331, AI 6 x TC isolated, 568 SM 331, AI 8 x 13 Bit, 557 SM 331, AI 8 x 16 Bit, 561 SM 331, AI 8 x RTD, 539 SM 331, AI 8 x TC, 549 SM 332, AO 8 x 12 Bit, 578 Dataset 128, structure SM 331, AI 6 x TC isolated, 569 SM 331, AI 8 x 16 Bit, 562 SM 331, AI 8 x RTD, 540 SM 331, AI 8 x TC, 550 Degree of protection IP 20, 25 Diagnostic interrupt of analog modules, 298 SM 321, DI 16 x DC 24 V, 92 SM 321, DI 16 x DC 24 V/125 V, 101 SM 322, DO 8 x DC 24 V/0.5 A, 182 SM 322, DO 8 x Rel. AC 230 V/5 A (5HF00), 215 SM 338, POS-INPUT, 511 Diagnostic interrupt enable SM 338, POS-INPUT, 505, 505 Diagnostic messages, 59, 295, 509 of analog output modules, 296 reading, 509 SM 321, DI 16 x DC 24 V, 88 SM 321, DI 16 x DC 24 V/125 V, 99 Diagnostics Digital modules, 59 of analog modules, 295 SM 338, POS-INPUT, 509, 510 Diagnostics data channel-specific, 588 Data record, 583 Channel-specific, for SM 338, SM 331, AI 6 x TC isolated, 593 SM 338, POS-INPUT, 596 Diagnostics data entry, 287 Diagnostics interrupt SM 322, DO 8 x AC 120/230 V/2 A ISOL, 197 Diagnostics messages of the analog input modules, 296 SM 322, DO 16 x DC 4 V/0.5 A (8BH10), 153 SM 322, DO 8 x AC 120/230 V/2 A ISOL, 196 SM 322, DO 8 x DC 24 V/0.5 A, 179 SM 322, DO 8 x Rel. AC 230 V/5 A (5HF00), 214 Digital I/O module SM 323, DI 16/DO 16 x DC 24 V/0.5 A, 222 SM 323, DI 8/DO 8 x DC 24 V/0.5 A, 227 SM 327, DI 8/DO 8 x DC 24 V/0.5 A, programmable, 231 Digital input module Dataset 1, structure, 525, 526 Parameters, 524, 526 SM 321, DI 16 x AC 120/230 V, 111 SM 321, DI 16 x DC 24 V, 76 SM 321, DI 16 x DC 24 V High Speed, 78 SM 321, DI 16 x DC 24 V, source input, 103 SM 321, DI 16 x DC 24 V, with process and diagnostic interrupt, 80 SM 321, DI 16 x DC 24 V/125V, with process and diagnostic interrupt, 94 SM 321, DI 16 x DC 48-125 V, 108 SM 321, DI 16 x UC 24/48 V, 105 SM 321, DI 32 x AC 120 V, 73 SM 321, DI 32 x AC 120/230 V ISOL, 117 SM 321, DI 32 x DC 24 V, 70 SM 321, DI 64 x DC 24 V, sinking/sourcing, 63 SM 321, DI 8 x AC 120/230 V, 114 digital module Start up, step, 57 Digital module, 48 Diagnostics, 59 Dimensional drawing, 612 Group error LED, 60 programming, 58 Digital output module Dataset 1, structure, 529 Parameter, 528 SM 322, DO 16 x AC 120/230 V/1 A, 167 SM 322, DO 16 x DC 24 V/0.5 A (1BH01), 143 SM 322, DO 16 x DC 24 V/0.5 A High Speed, 157 SM 322, DO 16 x UC 24/48 V, 161 SM 322, DO 32 x AC 120/230 V/1 A, 139 SM 322, DO 32 x DC 24 V/0.5 A, 135 SM 322, DO 64 x DC 24 V, 0.3 A, sinking, 128 SM 322, DO 64 x DC 24 V/0.3 A sourcing, 120 SM 322, DO 8 x AC 120/230 V/2 A, 187 SM 322, DO 8 x AC 120/230 V/2 A ISOL, 191 SM 322, DO 8 x DC 24 V/0.5 A with diagnostic interrupt, 174 S7-300 Module data 640 Manual, 06/2017, A5E00105505-AJ Index SM 322, DO 8 x DC 24 V/2 A, 170 SM 322, DO 8 x DC 48-125 V/1.5 A, 183 Dimensional drawing, 598 40-pin terminal block, 615 Analog module, 612 Bus module for "hot swapping", 605 Digital module, 612 Interface module, 610 Mounting rail, 599 Shield connection element, 614 Signal module, 612 DM 370 Properties, 496 Technical data, 498 DM 370 dummy module, 496 Documentation landscape Classification, 3 SM 321, DI 16 x DC 24 V/125 V, 101 when limit is exceeded, 298 I Group error LED Analog module, 295 Digital module, 60 SM 338, POS-INPUT, 509 Guide for the manual, 5 IEC 61131, 17 IM 360 Dimensional drawing, 610 Properties, 516 Technical data, 517 IM 361 Dimensional drawing, 610 Properties, 518 Technical data, 519 IM 365 Dimensional drawing, 611 Properties, 520 Technical data, 521 Inbetriebnahme Analog modules, 301 digital module, 57 Interface module, 515 Dimensional drawing, 610 IM 360, 516 IM 361, 518 IM 365, 520 Internal error SM 338, POS-INPUT, 510 Internet Service & support, 622 Interrupts SM 322, DO 8 x DC 24 V/ 0.5 A, enabling, 298, 511 of analog modules, 298 SM 321, DI 16 x DC 24 V, 91 SM 321, DI 16 x DC 24 V/125 V, 100 SM 322, DO 8 x AC 120/230 V/2 A ISOL, 196 SM 322, DO 8 x Rel. AC 230 V/5 A (5HF00), 215 SM 338, POS-INPUT, 511 Isochronous mode, 85 SM 331, SM 321, DI 16 x DC 24 V, 86 SM 332, AO 4 x 16 Bit, 458 SM 338, 500 Isolation test, 25 H L Hardware interrupt End of cycle, 299 SM 321, DI 16 x DC 24 V, 92 Load voltage missing Analog input module, 297 Analog output module, 297 E Electromagnetic compatibility (EMC), (See EMV) Electrostatic discharge, 19 EMC (Electromagnetic compatibility) disturbance variables, 19 EMV (Electromagnetic compatibility), 19 Encoder error SM 338, POS-INPUT, 510 Error of an analog module, 288 F FM approval, 17 Freeze function SM 338, POS-INPUT, 506 G S7-300 Module data Manual, 06/2017, A5E00105505-AJ 641 Index M Manual purpose, 3 Marine approval, 18 Measurement types and measuring ranges SM 331, SM 331, AI 2 x 12 Bit, 376 SM 331, AI 6 x TC isolated, 423 SM 331, AI 8 x 12 Bit, 363 SM 331, AI 8 x 13 Bit, 348 SM 331, AI 8 x 16 Bit, 313, 323 SM 331, AI 8 x RTD, 387 SM 331, AI 8 x TC, 404 SM 334, AI 4/AO 2 x 12 Bit, 491 SM 334, AI 4/AO 2 x 8/8 Bit, 482 Measuring method Analog input channels, 282 Measuring range module, 282 Changing the position, 283 Measuring ranges Analog input channels, 282 Module error SM 338, POS-INPUT, 510 Module overview, 49, 302 Analog I/O modules, 306 Analog input modules, 302 Analog output modules, 305 Digital I/O modules, 56 Digital input modules:, 49 Digital output modules, 52 Interface modules, 515 Other signal modules, 493 Relay output modules, 55 Module parameters SM 321, DI 16 x DC 24 V, 86 Monoflop time SM 338, POS-INPUT, 506 N no parameters SM 338, POS-INPUT, 510 O OB40, 92, 101, 298 Start information, 299 OB82, 92, 101, 182, 197, 215, 298 Operating state of the CPU, 286 Operational limit, 288 Order number 6AG1305-1BA80-2AA0, 42 6AG1307-1EA80-2AA0, 45 6AG1321-1BH02-2AA0, 76 6AG1321-1BL00-2AA0, 70 6AG1321-1CH20-2AA0, 108 6AG1321-1FF01-2AA0, 114 6AG1321-7BH01-2AB0, 80 6AG1322-1BH01-2AA0, 143 6AG1322-1CF00-2AA0, 183 6AG1322-1FF01-2AA0, 187 6AG1322-1HF10-2AA0, 216 6AG1322-8BF00-2AB0, 174 6AG1322-8BH10-7AB0, 147 6AG1323-1BH01-2AA0, 227 6AG1331-7KB02-2AB0, 367 6AG1332-5HB01-2AB0, 468 6AG1332-5HD01-7AB0, 460 6AG1332-5HF00-2AB0, 442 6AG1332-7ND02-4AB0, 450 6AG1334-0KE00-2AB0, 484 6AG1365-0BA01-2AA0, 520 6ES7 338-4BC01-0AB0, 499 6ES7307-1BA01-0AA0, 33 6ES7307-1EA01-0AA0, 36 6ES7307-1KA02-0AA0, 39 6ES7321-1BH02-0AA0, 76 6ES7321-1BH10-0AA0, 78 6ES7321-1BH50-0AA0, 103 6ES7321-1BL00-0AA0, 70 6ES7321-1BP00-0AA0, 63 6ES7321-1CH00-0AA0, 105 6ES7321-1CH20-0AA0, 108 6ES7321-1EL00-0AA0, 73 6ES7321-1FF01-0AA0, 114 6ES7321-1FF10-0AA0, 117 6ES7321-1FH00-0AA0, 111 6ES7321-7BH01-0AB0, 80 6ES7321-7EH00-0AB0, 94 6ES7322-1BF01-0AA0, 170 6ES7322-1BH10-0AA0, 157 6ES7322-1BL00-0AA0, 135 6ES7322-1BP00-0AA0, 120 6ES7322-1BP50-0AA0, 128 6ES7322-1CF00-0AA0, 183 6ES7322-1FF01-0AA0, 187 6ES7322-1FH00-0AA0, 167 6ES7322-1FL00-0AA0, 139 6ES7322-1HF01-0AA0, 203 6ES7322-1HF10-0AA0, 216 6ES7322-1HH01-0AA0, 198 6ES7322-5FF00-0AB0, 191 S7-300 Module data 642 Manual, 06/2017, A5E00105505-AJ Index 6ES7322-5GH00-0AB0, 161 6ES7322-5HF00-0AB0, 208 6ES7322-8BF00-0AB0, 174 6ES7322-8BH10-0AB0, 147 6ES7323-1BH01-0AA0, 227 6ES7323-1BL00-0AA0, 222 6ES7327-1BH00-0AB0, 231 6ES7331-1KF02-0AB0, 340 6ES7331-7HF00-0AB0, 329 6ES7331-7HF01-0AB0, 329 6ES7331-7KB02-0AB0, 367 6ES7331-7KF02-0AB0, 353 6ES7331-7NF00-0AB0, 307 6ES7331-7NF10-0AB0, 318 6ES7331-7PE10-0AB0, 412 6ES7331-7PF01-0AB0, 380 6ES7331-7PF11-0AB0, 396 6ES7332-5HB01-0AB0, 468 6ES7332-5HD01-0AB0, 460 6ES7332-5HF00-0AB0, 442 6ES7332-7ND02-0AB0, 450 6ES7334-0CE01-0AA0, 476 6ES7334-0KE00-0AB0, 484 6ES7360-3AA01-0AA0, 516 6ES7361-3CA01-0AA0, 518 6ES7365-0BA01-0AA0, 520 6ES7370-0AA01-0AA0, 496 6ES7374-2XH01-0AA0, 494 Output range SM 332, AO 2 x 12 Bit, 473 SM 332, AO 4 x 12 Bit, 465 SM 332, AO 4 x 16 bit, 456 SM 332, AO 8 x 12 Bit, 447 SM 334, AI 4/AO 2 x 12 Bit, 491 SM 334, AI 4/AO 2 x 8/8 Bit, 482 Overflow Analog input module, 297 Overvoltage protection, 61 P Parameter Digital output module, 528 SFCs, 522 Parameters, 58 Analog input module, 294, 534 Analog IO module, 580 Analog output module, 574 changing in the user program, 294 Data record, 522 Digital input module, 524, 526 dynamic, 294 SM 338, POS-INPUT, 505 static, 294 Parameters of modules SM 331, SM 321, DI 16 x DC 24 V/125 V, 98 SM 321, DO 16 x DC 24 V/0.5 A (8BH10), 152 SM 322, DO 16 x DC 24 V/0.5 A (8BH10), 530 SM 322, DO 16 x UC 24/48 V, 165 SM 322, DO 8 x AC 120/230 V/2 A ISOL, 195 SM 322, DO 8 x DC 24 V/0.5 A with diagnostic interrupt, 178 SM 322, DO 8 x Rel. AC 230 V/5 A (5HF00), 214 SM 327, DI 8/DO 8 x DC 24 V/0.5 A, programmable, 235 SM 331, AI 2 x 12 Bit, 378 SM 331, AI 6 x TC isolated, 424, 567 SM 331, AI 8 x 12 Bit, 365 SM 331, AI 8 x 16 Bit, 314, 324, 336, 560 SM 331, AI 8 x RTD, 389, 538 SM 331, AI 8 x TC, 405, 548 SM 332, AO 4 x 12 Bit, 466 SM 332, AO 4 x 16 Bit, 457 SM 332, AO 8 x 12 Bit, 448, 474, 577 SM 334, AI 4/AO 2 x 12 Bit, 490 Parameters, incorrect SM 338, POS-INPUT, 510 PARM_MOD, SFC 57, 522 POS input module SM 338, 499 Position Documentation structure, 3 Position decoder module SM 338, POS-INPUT, 499 Power failure of the analog module, 286 SM 321, DI 16 x DC 24 V, 90 SM 322, DO 8 x DC 24 V/0.5 A with diagnostic interrupt, 181 Power supply module, (See also PS 305, PS 307) PS 305 2 A, 42 PS 307 10 A, 39 PS 307 2 A, 33 PS 307 5 A, 36 Programming Digital modules, 58 in user program, 522 of analog modules, 294 Programming error Analog input module, 297 Analog output module, 297 SM 338, POS-INPUT, 510 Protection class, 25 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 643 Index PS 305 2 A Dimensional drawing, 609 Properties, 42 Schematic circuit diagram, 43 Technical specifications, 44 Wiring diagram, 42 PS 307 10 A Dimensional drawing, 609 Schematic circuit diagram, 40 Technical specifications, 41 Wiring diagram, 39 PS 307 2 A Dimensional drawing, 606 Properties, 33 Schematic circuit diagram, 34 Technical specifications, 35 PS 307 5 A Drawing (-1EA80-), 609 Properties, 45 Schematic circuit diagram, 37, 46 Technical specifications, 38 Wiring diagram, 36, 45 PS 307 5A Drawing (-1EA01-), 607 S Scaling SM 338, POS-INPUT, 503, 506 Service & support, 622 SF LED, (See group error LED) SM 338, POS-INPUT, 509 SFC 57 PARM_MOD, 522 SFC51, 92, 101, 182, 197, 215, 298 SFC55 WR_PARM, 522 SFC56 WR_DPARM, 522 SFC59, 92, 101, 182, 197, 215, 298 Shield connection element, drawing, 614 Shipping conditions, 21 Short-circuit to M Analog output module, 297 Sign Analog value, 261 Signal module Dimensional drawing, 612 Overview, 493 Simulator module SM 374, IN/OUT 16, 494 SIPLUS S7-300 module, 26 SM 321, DI 16 x AC 120/230 V Properties, 111 Technical specifications, 112 Wiring diagram, 111 R SM 321, DI 16 x DC 24 V Rail dimensioned drawing, 599 Causes of error and troubleshooting, 89 Rated voltage, 25 Diagnostic interrupt, 92 Relay output module Diagnostic messages, 88 SM 322, DO 16 x Rel. 120/230 V AC, 198 Hardware interrupt, 92 SM 322, DO 8 x Rel. 230 V AC, 203 Interrupts, 91 SM 322, DO 8 x Rel. 230 V AC / 5 A (1HF10), 216 Isochronous mode, 86 SM 322, DO 8 x Rel. 230 V AC / 5 A (5HF00), 208 Parameters, 86 Power supply, 90 Representation of analog values, 261, 261 Properties, 76 Binary representation of input ranges, 262 redundant sensor supply, 81 binary representation of output ranges, 279 Shunt circuit of the sensors, 82 For current measuring ranges, 265, 265 Technical specifications, 77 for resistance Wiring diagram, 76 thermometers, 266, 267, 267, 268, 269, 269, 270, 2 70, 271, 271, 272, 273, 274, 274, 275, 275, 276, 27 SM 321, DI 16 x DC 24 V High Speed Properties, 78 6, 277, 278 Technical specifications, 79 For voltage measuring ranges, 263, 264, 264 Wiring diagram, 78 for voltage output ranges, 280 SM 321, DI 16 x DC 24 V, source input in the current output ranges, 281 Properties, 103 of resistive transducers, 266 Technical specifications, 104 Resolution, 261 Wiring diagram, 103 SM 321, DI 16 x DC 24 V, with process and diagnostic interrupt Properties, 80 S7-300 Module data 644 Manual, 06/2017, A5E00105505-AJ Index Technical specifications, 83, 96 Wiring diagram, 81 SM 321, DI 16 x DC 24 V/125 V Causes of error and troubleshooting, 100 Diagnostic interrupt, 101 Diagnostic messages, 99 Hardware interrupt, 101 Interrupts, 100 Parameters, 98 Shunt circuit of the sensors, 95 SM 321, DI 16 x DC 24 V/125 V, with process and diagnostic interrupt Properties, 94 Wiring diagram, 95 SM 321, DI 16 x DC 48-125 V Properties, 108 Technical specifications, 109 Wiring diagram, 108 SM 321, DI 16 x UC 24/48 V Properties, 105 Technical specifications, 106 Wiring diagram, 105 SM 321, DI 32 x AC 120 V Properties, 73 Technical specifications, 74 Wiring diagram, 73 SM 321, DI 32 x AC 120/230 V ISOL Properties, 117 Technical specifications, 118 Wiring diagram, 117 SM 321, DI 32 x DC 24 V Properties, 70 Technical specifications, 71 Wiring diagram, 70 SM 321, DI 64 x DC 24 V, sinking/sourcing 40-pin terminal block, 64 Properties, 63 Technical specifications, 66 Wiring diagram, 63 SM 321, DI 8 x AC 120/230 V Properties, 114 Technical specifications, 115 Wiring diagram, 114 SM 321, DO 64 x DC 24 V, 0.3 A sourcing 40-pin terminal block, 121 Properties, 120 Technical specifications, 123 Wiring diagram, 120 SM 322, DO 16 x AC 120/230 V/1 A Properties, 167 Technical specifications, 168 Wiring diagram, 167 SM 322, DO 16 x DC 24 V/0.5 A (1BH01) Properties, 143 Technical specifications, 145 Wiring diagram, 144 SM 322, DO 16 x DC 24 V/0.5 A (8BH10) Dataset 1, structure, 531 Diagnostic data records, 590 Diagnostics, 153 Discrepancy error monitoring, 154 Firmware update, 154 I&M data (identification data), 155 Parameter, 530 Properties, 147 Technical specifications, 150 Wiring diagram, 149 SM 322, DO 16 x DC 24 V/0.5 A High Speed Properties, 157 Technical specifications, 159 Wiring diagram, 158 SM 322, DO 16 x Rel. 120/230 V AC Properties, 198 Technical specifications, 200 Wiring diagram, 199 SM 322, DO 16 x UC 24/48 V Parameters, 165 Properties, 161 Technical specifications, 162 Wiring diagram, 162 SM 322, DO 32 x AC 120/230 V/1 A Properties, 139 Technical specifications, 141 Wiring diagram, 140 SM 322, DO 32 x DC 24 V/0.5 A Properties, 135 Technical specifications, 137 Wiring diagram, 136 SM 322, DO 64 x DC 24 V, 0.3 A, sinking 40-pin terminal block, 129 Properties, 128 Supplementary information, 132 Technical specifications, 130 Wiring diagram, 128 SM 322, DO 8 x AC 120/230 V/2 A Properties, 187 Technical specifications, 189 Wiring diagram, 188 SM 322, DO 8 x AC 120/230 V/2 A ISOL Causes of error and troubleshooting, 196 Diagnostic messages, 196 Diagnostics interrupt, 197 Interrupts, 196 Load restrictions, 197 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 645 Index Parameters, 195 Properties, 191 Technical specifications, 193 Wiring diagram, 192 SM 322, DO 8 x DC 24 V/0.5 A with diagnostic interrupt Causes of error and troubleshooting, 180 Diagnostic interrupt, 182 Diagnostics messages, 179 Interrupts, 182 Parameters, 178 Power supply, 181 Properties, 174 Technical specifications, 176 Wiring diagram, 175 SM 322, DO 8 x DC 24 V/2 A Properties, 170 Technical specifications, 171 Wiring diagram, 171 SM 322, DO 8 x DC 48-125 V/1.5 A Properties, 183 Technical specifications, 185 Wiring diagram, 184 SM 322, DO 8 x Rel. 230 V AC Properties, 203 Technical specifications, 204 Wiring diagram, 204 SM 322, DO 8 x Rel. 230 V AC / 5 A (1HF10) Properties, 216 Technical specifications, 218 Wiring diagram, 217 SM 322, DO 8 x Rel. 230 V AC / 5 A (5HF00) Properties, 208 Technical specifications, 210 Wiring diagram, 209 SM 322, DO 8 x Rel. AC 230 V/5 A (5HF00) Causes of error and troubleshooting, 215 Diagnostic interrupt, 215 Diagnostics messages, 214 Interrupts, 215 Parameters, 214 SM 323, DI 16/DO 16 x DC 24 V/0.5 A Properties, 222 Technical specifications, 224 Wiring diagram, 223 SM 323, DI 8/DO 8 x DC 24 V/0.5 A Properties, 227 Technical specifications, 228 Wiring diagram, 228 SM 327, DI 8/DO 8 x DC 24 V/0.5 A, programmable Dataset 1, structure, 236 Parameters, 235 Properties, 231 Technical specifications, 232 Wiring diagram, 232 SM 331, AI 2 x 12 Bit Measurement types and measuring ranges, 376 Parameters, 378 Supplementary information, 379 SM 331, AI 2 x 12-bit Properties, 367 Technical specifications, 372 Wiring diagram, 368 SM 331, AI 6 x TC isolated Calibration, 434 Dataset 1, structure, 568 Dataset 128, structure, 569 Diagnostics data, 593 Firmware update, 431 I&M data (identification data), 433 Measurement types and measuring ranges, 423 Parameter, 424, 567 Properties, 412 Supplementary information, 425 Technical specifications, 416 Terminal assignment, 413 SM 331, AI 8 x 12 bit Parameters, 365 SM 331, AI 8 x 12 Bit Measurement types and measuring ranges, 363 Supplementary information, 366 SM 331, AI 8 x 12-bit Properties, 353 Technical specifications, 359 Wiring diagram, 354 SM 331, AI 8 x 13 Bit Dataset 1, structure, 557 Measurement types and measuring ranges, 348 Properties, 340 Supplementary information, 350 Wiring diagram, 340 SM 331, AI 8 x 14 Bit High Speed Technical specifications, 332 SM 331, AI 8 x 16 Bit Dataset 1, structure, 561 Dataset 128, structure, 562 High-speed update of measured values, 308 Measurement types and measuring ranges, 323 Measurement types and ranges, 313 Parameter, 314, 324, 336 Parameters, 560 Properties, 307, 318 Supplementary information, 315, 325 S7-300 Module data 646 Manual, 06/2017, A5E00105505-AJ Index Technical specifications, 311, 320 Wiring diagram, 309, 319 SM 331, AI 8 x RTD Dataset 1, structure, 539 Dataset 128, structure, 540 Measurement types and measuring ranges, 387 Parameters, 389, 538 Properties, 380 Supplementary information, 391 Technical specifications, 383 Wiring diagram, 381 SM 331, AI 8 x TC Dataset 1, structure, 549 Dataset 128, structure, 550 Measurement types and measuring ranges, 404 Parameter, 405 Parameters, 548 Properties, 396 Supplementary information, 407 Technical specifications, 399 Wiring diagram, 396 SM 332, AO 2 x 12 Bit Output range, 473 Properties, 468 Supplementary information, 475 Technical specifications, 471 Wiring diagram, 468 SM 332, AO 4 x 12 Bit Output range, 465 Parameters, 466 Properties, 460 Supplementary information, 467 Technical specifications, 463 Wiring diagram, 460 SM 332, AO 4 x 16 bit Output range, 456 SM 332, AO 4 x 16 Bit Isochronous mode, 458 Parameters, 457 Technical specifications, 453 SM 332, AO 4 x 16 Bit, isochrone Properties, 450 Supplementary information, 459 Wiring diagram, 450 SM 332, AO 8 x 12 Properties, 442 Supplementary information, 449 Wiring diagram, 442 SM 332, AO 8 x 12 Bit Dataset 1, structure, 578 Output range, 447 Parameter, 448 Parameters, 474, 577 Technical specifications, 445 SM 334, AI 4/AO 2 x 12 Bit Measurement types and measuring ranges, 491 Output range, 491 Parameters, 490 SM 334, AI 4/AO 2 x 12-bit Properties, 484 Technical specifications, 486 Wiring diagram, 484 SM 334, AI 4/AO 2 x 8/8 Bit Addresses, 482 Measurement types and measuring ranges, 482 Output types and output ranges, 482 Technical specifications, 479 Unused channels, 483 Wiring diagram, 476 SM 338 Cyclic encoder value acquisition, 502 Isochronous encoder value acquisition, 502 Isochronous mode, 500 POS input module, 499 SM 338, POS-INPUT Absolute value encoder (SSI), 505 Addressing, 507 Auxiliary voltage missing, 510 Causes of error and troubleshooting, 510 Channel error, 510 Channel fault, 510 Channel information available, 510 Code type, 505 Configuration error, 510 Diagnostic interrupt, 511 Diagnostic interrupt enable, 505, 505 Diagnostics, 509 Diagnostics data, 596, 597 Encoder error, 510 External error, 510 Freeze function, 506 Group error LED, 509 Incorrect parameters, 510 Internal error, 510 Interrupts, 511 Module error, 510 Monoflop time, 506 no parameters, 510 Programming error, 510 Scaling, 503, 506 SF LED, 509 Technical data, 512 Transmission rate, 505 S7-300 Module data Manual, 06/2017, A5E00105505-AJ 647 Index Watchdog time-out, 510 Wiring diagram, 501 SM 374, IN/OUT 16 Properties, 494 Technical data, 495 Smoothing of analog input values, 290 Spare parts, 616 Standards, 14 STEP 7 blocks for analog functions, 300 Storage conditions, 21 T Technical specifications EMV (Electromagnetic compatibility), 19 Shipping and storage conditions, 21 Standards and approvals, 14 Test voltage, 25 Thermocouple external compensation, 254 General, 249 Internal compensation, 253 Operating principle, 251 Reference junction, 251, 255 Structure, 250 Training center, 622 Transmission rate SM 338, POS-INPUT, 505 U UL approval, 15 Underflow Analog input module, 297 W Watchdog time-out SM 338, POS-INPUT, 510 Wirebreak Analog input module, Analog output module, WR_DPARM, SFC 56, 522 WR_PARM, SFC 55, 522 S7-300 Module data 648 Manual, 06/2017, A5E00105505-AJ