METSEPM5330 Product datasheet Characteristics PM5330 powermeter w modbus - upto 31st H 256K 2DI/2DO 35alarms - flush mount Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Training Objectives : Compliant Main Range PowerLogic Product name PowerLogic PM5000 Device short name PM5330 Product or component type Power meter Complementary Power quality analysis up to the 31st harmonic Device application Power monitoring Multi-tariff Type of measurement Current Voltage Frequency Power factor Energy Active and reactive power Supply voltage 100...415 V AC 45...65 Hz 125...250 V DC Network frequency 50 Hz 60 Hz [In] rated current 1A 5A Type of network 3P + N 3P 1P + N Maximum power consumption in VA 10VA at 415V Ride-through time 80ms 120 V AC typical 100ms 230 V AC typical 100ms 415 V AC typical Display type Backlit LCD May 20, 2021 1 Display resolution 128 x 128 pixels Sampling rate 64 samples/cycle Measurement current 10...9000mA Analogue input type Voltage (impedance 5 MOhm) Current (impedance 0.3 mOhm) Measurement voltage 35...690V AC 45...65 Hz between phases 20...400V AC 45...65 Hz between phase and neutral Frequency measurement range 45...65Hz Number of inputs 2 digital Measurement accuracy Active energy +/- 0.5 % Reactive energy +/- 2 % Active power +/- 0.5 % Apparent power +/- 0.5 % Frequency +/- 0.05 % Power factor +/- 0.005 Current +/- 0.5 % Voltage +/- 0.5 % Accuracy class Class 0.5S active energy conforming to IEC 62053-22 Number of outputs 2 relay 2 digital Information displayed Tariff (4) Communication port protocol Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500V JBUS Communication port support RS485 Data recording Maintenance logs Time stamping Alarm logs Data logs Min/max of instantaneous values Event logs Memory capacity 256 kB Connections - terminals Voltage circuit: screw terminal block4 Control circuit: screw terminal block2 Current transformer: screw terminal block6 Input/output circuit: screw terminal block6 Relay output: screw terminal block4 Ethernet network: RJ45 connector Mounting mode Flush-mounted Mounting support Framework Standards UL 61010-1 IEC 62053-22 IEC 61557-12 EN 50470-3 IEC 60529 IEC 62053-24 EN 50470-1 Product certifications CE conforming to IEC 61010-1 CULus conforming to UL 61010-1 Width 96mm Depth 72mm Height 96mm Net weight 430g Environment Electromagnetic compatibility Limits for harmonic current emissions class A conforming to IEC 61000-3-2 Electrostatic discharge level 4 conforming to IEC 61000-4-2 Conducted RF disturbances level 3 conforming to IEC 61000-4-6 Magnetic field at power frequency level 4 conforming to IEC 61000-4-8 Conducted and radiated emissions class B conforming to EN 55022 IP degree of protection IP52 front: conforming to IEC 60529 IP30 body: conforming to IEC 60529 Relative humidity 5...95% at 50C 2 Pollution degree 2 Ambient air temperature for operation -25...70C Ambient air temperature for storage -40...85C Operating altitude 2000 m Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Weight 550g Package 1 Height 11cm Package 1 width 12.6cm Package 1 Length 12.6cm Unit Type of Package 2 S03 Number of Units in Package 2 12 Package 2 Weight 6.91kg Package 2 Height 30cm Package 2 width 30cm Package 2 Length 40cm Unit Type of Package 3 P06 Number of Units in Package 3 96 Package 3 Weight 58.52kg Package 3 Height 80cm Package 3 width 80cm Package 3 Length 60cm Offer Sustainability Sustainable offer status Green Premium product REACh Regulation REACh Declaration EU RoHS Directive Compliant EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins 3