https://www.phoenixcontact.com/in/products/2904600
01/19/2017Page1/9
Power supply unit-QUINT4-PS/1AC/24DC/5-2904600
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB(selective
fuse breaking) technology, and NFC interface, input: 1-phase,output:24VDC/5 A
Product Description
The fourth generation of the high-performance QUINTPOWER power supplies ensures superior system availability by means of new functions.
Signaling thresholds and characteristic curves can be individually adjusted via the NFC interface.
The unique SFB technology and preventive function monitoring of the QUINTPOWER power supply increase theavailability of your application.
Why buy this product
SFB technology trips standard circuit breakers selectively, loads that are connected in parallel continue working
Preventive function monitoring indicates critical operating states before errors occur
Signaling thresholds and characteristic curves that can be adjusted via NFC maximize system availability
Easy system extension thanks to static boost; starting of difficult loads thanks to dynamic boost
High degree of immunity, thanks to integrated gas-filled surge arrester and mains failure bridging time of more than 20 milliseconds
Robust design thanks to metal housing and wide temperature range from -40°C to +70°C
Worldwide use thanks to the wide range input and international approval package
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4046356985321
Weight per Piece (excluding packing) 990.583 g
Custom tariff number 85044030
Country of origin Thailand
Technical data
Dimensions
Width 36 mm
Height 130 mm
Depth 125 mm
https://www.phoenixcontact.com/in/products/2904600
01/19/2017Page2/9
Power supply unit-QUINT4-PS/1AC/24DC/5-2904600
Technical data
Dimensions
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 39 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Noise immunity Immunity according to EN 61000-6-1 (residential), EN 61000-6-2
(industrial), and EN 61000-6-5 (power station equipment zone 1, 2)
Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
Input data
Nominal input voltage range 100 V AC ... 240 V AC
110 V DC ... 250 V DC
Input voltage range 100 V AC ... 240 V AC -15% ... +10%
110 V DC ... 250 V DC -18% ... +40%
Dielectric strength maximum 300 V AC 60 s
AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
Discharge current to PE < 3.5 mA
Current consumption 1.7 A (100 V AC)
1.5 A (120 V AC)
0.9 A (230 V AC)
0.8 A (240 V AC)
Nominal power consumption 135 W
Inrush surge current typ. 14 A (at 25 °C)
Power failure bypass ≥ 24 ms (120 V AC)
≥ 32 ms (230 VAC)
Input fuse 6.3 A (slow-blow, internal)
Choice of suitable circuit breakers 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Type of protection Transient surge protection
Protective circuit/component Varistor, gas-filled surge arrester
Output data
Nominal output voltage 24 V DC
Setting range of the output voltage (USet)24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (IN)5 A
Static Boost (IStat.Boost)6.25 A
Dynamic Boost (IDyn.Boost)10 A (5 s)
Selective Fuse Breaking (ISFB)30 A (15 ms)
Derating > 60 °C (2.5 %/K)
https://www.phoenixcontact.com/in/products/2904600
01/19/2017Page3/9
Power supply unit-QUINT4-PS/1AC/24DC/5-2904600
Technical data
Output data
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Control deviation < 0.5 % (Static load change 10% ... 90%)
< 4 % (Dynamic load change 10% ... 90%, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 30 mVPP (with nominal values)
Output power 120 W
Typical response time 300 ms (from SLEEP MODE)
Maximum power dissipation in no-load condition < 3 W (120 V AC)
< 3 W (230 V AC)
General
Net weight 0.7 kg
Efficiency typ. 88.8 % (120 V AC)
typ. 89.2 % (230 V AC)
Insulation voltage input/output 4 kV AC (type test)
2.4 kV AC (routine test)
Protection class I
MTBF (IEC 61709, SN 29500) > 1440000 h (25 °C)
> 895000 h (40°C)
> 421000 h (60°C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Alignable: 5 mm horizontally, 15 mm next to active components, 50 mm
vertically
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 30
Conductor cross section AWG max. 12
Stripping length 6.5 mm
Connection data, output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 30
Conductor cross section AWG max. 12
https://www.phoenixcontact.com/in/products/2904600
01/19/2017Page4/9
Power supply unit-QUINT4-PS/1AC/24DC/5-2904600
Technical data
Connection data, output
Stripping length 6.5 mm
Connection data for signaling
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Noise emission Additional basic standard EN 61000-6-5 (immunity in power station)
Noise immunity Immunity according to EN 61000-6-1 (residential), EN 61000-6-2
(industrial), and EN 61000-6-5 (power station equipment zone 1, 2)
Standards/regulations EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN61000-4-6
EN 61000-4-8
EN 61000-4-11
EN 61000-4-9
EN 61000-4-12
EN 61000-4-16
EN 61000-4-18
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Standard - power supply devices for low voltage with DC output EN 61204-3
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV)
EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2
Shipbuilding approval DNV GL, PRS, BV, LR, ABS
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
https://www.phoenixcontact.com/in/products/2904600
01/19/2017Page5/9
Power supply unit-QUINT4-PS/1AC/24DC/5-2904600
Technical data
Standards and Regulations
Vibration (operation) 5 Hz - 100 Hz resonance search 2.3g, 90 min., resonance frequency
2.3g, 90 min. (according to DNV GL Class C)
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Approval - requirement of the semiconductor industry with regard to
mains voltage dips SEMI F47-0706 Compliance Certificate; EN 61000-4-11
Rail applications EN50121-3-2
Overvoltage category (EN 60950-1) II
Overvoltage category (EN 61010-1) II
Overvoltage category (EN 62477-1) III
Drawings
Block diagram
NFC
POut
OVP
"C
+
+
-
-
13
14
Rem
SGnd
Out 1
Out 2
!
active
PFC
L1+
N-
Diagram
0,0
0,5
1,0
1,5
2,0
2,5
3,0
0 1 2 4 6 8 10
I [A]
Out
I [A]
In
= U : 120 V AC/U : 24 V DC
In Out
= U : 230 V AC/U : 24 V DC
In Out
!
"
3 5 7 9
!
"
Diagram
0,4
0,5
0,6
0,7
0,8
0,9
1,0
I [A]
Out
Power Factor
12345678910
= U : 120 V AC/U : 24 V DC
In Out
= U : 230 V AC/U : 24 V DC
In Out
!
"
"
!
Diagram
70
75
80
85
90
95
I [A]
Out
Eta [%]
= U : 120 V AC/U : 24 V DC
In Out
= U : 230 V AC/U : 24 V DC
In Out
!
"
1 2 3 4 5 6 7 8 9 10
!
"
https://www.phoenixcontact.com/in/products/2904600
01/19/2017Page6/9
Power supply unit-QUINT4-PS/1AC/24DC/5-2904600
Diagram
H [m]
[%]
0
25
50
75
100
125
150
175
200
225
"
#
POut
!
"
#
= P 125 % 40 °C
Stat. $
= PDyn. 200 % 60 °C$
= PN100 % 60 °C$
0 1000 2000 3000 4000 5000
!
Dimensional drawing
NFC
> 100% Boost
> 75%
> 50% Pout
DC OK
Uout
29,5V
24V
QUINT POWER
Output DC 24V 5A
+ +
Input AC 400-500 V
L1/ L2 L3/+
13
14
Rem
SGnd
Out 1
Out 2
Signal Ground
NFC
> 100% Boost
> 75%
> 50% POut
DC OK
UOut
29,5V
24V
QUINT POWER
Output DC 24V 5A
+ +
13
14
Rem
SGnd
Out 1
Out 2
Signal
Input AC 100-240 V
N/- L/+
36
130
65
Dimensional drawing
122
125
130
80
45
131
Schematic diagram
Housing
Output
PE
Input Signaling
C
ABD
B
L
N
(+)
(-)
+
Classifications
eCl@ss
eCl@ss 5.1 27242213
eCl@ss 6.0 27049005
eCl@ss 8.0 27049002
eCl@ss 9.0 27040701
ETIM
ETIM 5.0 EC002540
ETIM 6.0 EC002540
UNSPSC
UNSPSC 13.2 39121004
https://www.phoenixcontact.com/in/products/2904600
01/19/2017Page7/9
Power supply unit-QUINT4-PS/1AC/24DC/5-2904600
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / EAC / UL Listed / cUL Listed / DNV GL / PRS / CSA / Bauartgeprüft / cULus Recognized
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
EAC RU C-
DE.A*30.B.01082
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
DNV GL https://www.dnvgl.com/ TAA00000BV
PRS http://www.prs.pl/ TE/2104/880590/16
CSA http://www.csagroup.org/services/testing-
and-certification/certified-product-listing/ 70076170
https://www.phoenixcontact.com/in/products/2904600
01/19/2017Page8/9
Power supply unit-QUINT4-PS/1AC/24DC/5-2904600
Approvals
Bauartgeprüft SI-SIQ BG 005/038
cULus Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Accessories
Accessories
Assembly adapter
Assembly adapters-UWA 182/52-2938235
Universal wall adapter for securely mounting the power supply in the event of strong vibrations. The power supply is
screwed directly onto the mounting surface. The universal wall adapter is attached at the top/bottom.
Assembly adapters-UWA 130-2901664
2-piece universal wall adapter for securely mounting the power supply in the event of strong vibrations. The profiles
that are screwed onto the side of the power supply are screwed directly onto the mounting surface. The universal wall
adapter is attached on the left/right.
Assembly adapters-QUINT-PS-ADAPTERS7/1-2938196
Assembly adapter for QUINT-PS... power supply on S7-300 rail
Device protection
Type 3 surge protection device-PLT-SEC-T3-230-FM-2905229
Pluggable device protection, according to type 3/class III, for 1-phase power supply networks with separate N and PE
(3-conductor system: L1, N, PE), with integrated surge-proof fuse and remote indication contact. Also suitable for DC
applications.
https://www.phoenixcontact.com/in/products/2904600
01/19/2017Page9/9
Power supply unit-QUINT4-PS/1AC/24DC/5-2904600
Accessories
Programming adapter
Programming adapter-TWN4 MIFARE NFC USB ADAPTER-2909681
Near Field Communication (NFC) programming adapter with USB interface for the wireless configuration of NFC-
capable products from PHOENIX CONTACT with software. No separate USB driver is required.
Phoenix Contact 2017 © - all rights reserved
http://www.phoenixcontact.com