Surge Protection Made Simple
Photovoltaic Applications
Modular DIN Rail SPD Solutions
0111 BU-SB11015 Page 1 of 2 Data Sheet 2055
Description
The Cooper Bussmann®multi-pole, modular Surge Protective Device
(SPD) (with three-step DC switching device) features
easy
ID™ visual
indication and optional remote contact signaling (floating changeover
contact) for use in PV systems.
These complete surge protective devices are suitable for all
PV systems in accordance with UL 1449 3rd Edition and
IEC 60364-7-712. Includes a five year limited warranty.
These prewired solutions consist of a base and locking modules that
feature a combined disconnection and short-circuiting (shunting)
device with safe electrical isolation to prevent fire damage due to DC
arcs. An integrated DC fuse allows safe module replacement without
arc formation.
In case of insulation faults in the generator circuit, a reliable and
tested fault-resistant Y circuit prevents damage to the surge
protective devices.
www.cooperbussmann.com/surge
Module Circuit DiagramsDimensions - mm
12
11
14
DC+/– DC–/+
BSPH_____YPV(R)
Shown with optional remote contact signaling
BSPH_____YPV(R)
Shown with optional remote contact signaling
Remote Signal
Contact Available
Visual Status Indication
Short-Circuit Interrupting (SCI) Technology
The green and red visual indicator flags show the module
protective status (green = good, red = replace). Apart from this
visual indication, the remote signaling option features a three
terminal floating changeover contact that can be used as a
make or break contact depending on the particular monitoring
system design employed.
1. Original State 2. Disconnection Device Response
3. Arc Extinguishes 4. Safe Electrical Isolation
Fuse Open
Thermal Disconnector
MOV
Fuse Closed
Arc
1234
0111 BU-SB11015 Page 2 of 2 Data Sheet 2055
© 2011 Cooper Bussmann
www.cooperbussmann.com
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Ordering Information
Nominal PV System Voltage 600Vdc 1000Vdc 1200Vdc
Catalog Numbers: Without Remote Signaling BSPH3600YPV BSPH31000YPV BSPH31200YPV
(Base + Modules) With Remote Signaling BSPH3600YPVR BSPH31000YPVR BSPH31200YPVR
Replacement Modules: Outer (2) BPH300YPV BPH500YPV BPH600YPV
Center (1) BPM300YPV BPM500YPV BPM600YPV
Specifications
Nominal PV System Voltage 600V 1000V 1200V
MCOV [UCPV]700Vdc 1170Vdc 1200Vdc
Max System Discharge Current (8/20 µs) [Imax] 40kA 40kA 30kA
Voltage Protection Level [UP]<_2.5kV <_4.0kV <_4.5kV
Voltage Protection Level at 5kA [UP]<_2.0kV <_3.5kV <_4.0kV
Integrated Fuse Breaking Capacity/Interrupting Rating 30kA/1000Vdc 30kA/1000Vdc 30kA/1200Vdc
Technology Short-Circuit Interruption (SCI) Overcurrent Protection
Operating Temperature Range [TU] -40°C to +80°C
Nominal Discharge Current (8/20 µs) [(DC+/DC-) --> PE] [In] 12.5kA
Response Time [tA] <_25ns
Operating State/Fault Indication Green (good)/Red (replace)
Conductor Ratings and Cross-Sectional Area: Minimum 60/75°C 1.5mm2/14AWG Solid/Flexible
Maximum 60/75°C 35mm2/2AWG Stranded/25mm2/4AWG Flexible
Mounting 35mm DIN Rail per EN 60715
Enclosure Material UL 94V0 Thermoplastic
Degree of Protection IP20
Capacity 3 Modules, DIN 43880
Standards Information: UL UL 1449 3rd Edition (Type 2)*
IEC IEC 61643-11 Type 2, IEC 61643-1 Class II
Product Warranty Five Years**
Remote Contact Signaling
Remote Contact Signaling Type Changeover Contact
AC Switching Capacity (Volts/Amps) 250V/0.1A
DC Switching Capacity (Volts/Amps) 250V/0.1A; 125V/0.2A; 75V/0.5A
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals 60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Ordering Information Order from Catalog Numbers Above
* Does not apply to 1200Vdc.
** See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
*** BSPH31000YPV(R) 1000Vdc one energized pole/mode requires the following:
1. Use a suitable electrical insulator to keep a 10mm min. safety distance from the PV-SPD and other grounded parts in the housing as shown
2. No metal covers are in the area of the module release buttons as shown.
Typical Application Schematics
Equipment
Grounding
Conductor
Common
Equipment
Grounding
Conductor
Common
Equipment
Grounding
Conductor
Common
Steel panel wall
20
No metal covers
or parts allowed
Isolator/
insulator
M5
Application A
Two energized poles/modes
600, 1000 & 1200Vdc systems
Application B
One energized pole/mode
600Vdc & 1000Vdc*** systems only
Application C
One energized pole/mode
600Vdc & 1000Vdc*** systems only
(Max. system discharge current
(8/20 µs) [Imax] 25kA)
1000Vdc One energized pole/
mode mounting detail.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Eaton:
BSPH31000YPV BSPH31000YPVR