wiSeries Wireless DIN Rail Monitoring
and Control Device
The new NEWPORT wi®Series DIN Rail wireless monitoring
and control device is compatible with a large and growing
number of NEWPORT wireless sensors:
UWTC “Universal Wireless Thermocouple” Type J, K, T, E,
R, S, B, N, & C.
UWRTD “Universal Wireless RTD”.
zSeries wireless End Devices with sensors for Temperature,
Humidity & Barometric Pressure.
The wiSeries wiDR DIN Rail Monitor & Controller can monitor
up to eight (8) wireless sensors.
The compact instrument connects directly to an Ethernet
network and the Internet and features NEWPORT’s award-
winning embedded Web Server. It is easily configured and
monitored with a Web browser over the Ethernet network or
the Internet.
Alternatively, the wiDR DIN Rail Monitor &
Controller can instead be connected to the
USB port of a single computer with a “USB
Ethernet Adapter” that are inexpensive and
widely available.
wiSeries
Main Menu
CHART
(2 Seconds/Div)
1 Minute
1 Minute
1 Day
1 Week
1 Month
1 Year
0
5
C/Div
50 1200
300
100%
0%
10
%/Div
90
hPa/Div
ChPa
Tue Feb 5 10:19:10 PDT 2008Tue Feb 5 10:18:10 PDT 2008
http://192.168.1.200
Min / Max Temp
48.0/21.0
P1 Process
P2 Sensor 2
P3 Process
P4 Process
P5 Process
P6 Process
P7 Process
P8 Sensor 8
A1 Ambient
A2 Sensor 2
A3 Ambient
A4 Ambient
A5 Ambient
A6 Ambient
A7 Ambient
A8 Sensor 8
Save Current Graph
UWTC
User-friendly, Simple to
Configure
Wireless Inputs:
Thermocouple, RTD,
Temperature + Humidity
+ Barometric Pressure
Embedded Ethernet
(standard)
2 Alarm Outputs: Solid
State Relays (SSR’s), dc
Pulse, Mechanical
Relays, Analog Voltage
& Current
Free Software
DIN Rail Monitor & Controller
zED-TH
$
395
wiDR
External
Temperature
Lug Mount
Probe
Industrial Probe
Temperature Humidity /
Barometric Pressure
External
Temperature
Stick Probe
MONITOR AND ALARM
The wiDR meter-controller comes standard with a
choice of either two Form C relays, or two SSR’s
(solid state relays) that can be used for control
functions or alarms. The wiDR meter can monitor
alarm conditions for any or all of the wireless
sensors. For example, the wiDR meter can be set
up to trip an alarm if any one of the sensors
indicated it was above or below a pre-set alarm
point.
MONITOR & CONTROL LOCALLY AND OVER
THE INTERNET
The new NEWPORT®wiSeries wireless monitoring
and control system provides local monitoring and
control, along with remote Web-based monitoring of
temperature from T/C’s, RTD’s, and semiconductor
sensors, as well as RH, and barometric pressure.
The wireless sensors transmit up to 1000m (3280’)*
--without obstructions or interference, to a wiSeries
monitor-controller connected directly to an Ethernet
network and the Internet. The wireless system
complies with IEEE 802.15.4 operating at 2.4 GHz.
* Distances for UWTC-1, UWRTD-1: up to 60m
(200 ft), UWTC-2, UWRTD-2: up to 120m (400 ft),
zED-*-P: up to 1000m (3280 ft), all distances are
without obstructions or interference.
The NEWPORT wiSeries system let’s you monitor
and record temperature, relative humidity, and
barometric pressure over an Ethernet network or the
Internet without any special software--just your Web
Browser.
WIRELESS SENSORS
NEWPORT offers a wide and growing selection of
wireless sensors for a variety of applications.
Depending on application, the wireless sensors are
powered by 2 AA batteries, a single lithium battery
(approx. AA size), or an external AC Adapter that
operates on any voltage worldwide from 100 to 240
VAC.
Wireless sensors are available with external probes
appropriate for an almost unlimited variety of
industrial and commercial applications.
ETHERNET
The wiDR is an independent node on the network
sending and receiving data in standard TCP/IP
packets. It is easily configured from a Web Browser
and can be password protected. From within an
Ethernet LAN or over the Internet, the user simply
types the IP address (such as 192.168.1.200) or an
easy to remember name (such as "Oven 5" or) and
the wiSeries meter serves a Web Page with the
current readings.
ALARM AND EMAIL
The wiDR monitor-controller can trigger an alarm if
variables go above or below a set point that you
determine. Your alarm can be sent by email to a
single user or to a group distribution list, including
text messages to cell phones and PDA’s. The
NEWPORT "Mail Notifier" software is a free and
easy program for this application.
The wiDR monitor-controllers operate on any AC
voltage worldwide from 100 to 240 Vac and 50 to
60Hz. The monitor-controller connects directly to an
Ethernet Network or the Internet. Unlike an RS232
or USB device, it does not require a host computer.
Channel 12
Please refer to local regulations for the allowed maximum transmit power
Transmit Power
Reset
PID 13106 (version x.x)
iSeries Firmware Version x.x
Input
Setpoints & On/Off
Alarm 2
Alarm 1
Passcode ID
Display
Permanent Store
Enable Standby Mode Before Configuring Unit
Scrolling
Main Menu
CONTROLLER SETUP
Setup
Transmit Power
Misc.
Monitor
CONTROLLER SETUP
http://192.168.1.200Address
Update
Update
Update
20dBm
End Device ID -
SPECIFICATIONS
Control Output 1 & 2
Relay: 250Vac or 30Vdc @ 3A (resistive load);
configurable for ON/OFF
Output 1:
SPDT type, can be configured as Alarm 1 output.
Output 2:
SPDT type, can be configured as Alarm 2 output
SSR:
20-265Vac @ 0.05 - 0.5A (resistive load); continuous
DC Pulse: Non-Isolated; 10 Vdc @ 20 mA
Alarm 1 & 2 (programmable)
Type: Same as Output 1 and 2
Operation: High/low, above/below, band,
latch/unlatch, normally open/normally closed and
process/deviation
Analog Output (programmable): Non-Isolated,
Retransmission 0 to 10Vdc or 0 to 20mA, 500 max
(Output 1 only). Accuracy is ± 1% of FS when
following conditions are satisfied.
1) Input is not scaled below 1% of Input FS.
2) Analog Out is not scaled below 3% of Output FS.
Network and Communications
Ethernet: Standard Compliance IEEE 802.3 10Base-T
Supported Protocols: TCP/IP, ARP, HTTPGET
Connection: Screw terminals
General
Dimensions:
93 H x 39 W x 125 mm D (3.64 x 1.55 x 4.93")
Operating Temperature:
0 to 55°C (32 to 131°F), 90% RH non-condensing
Line Voltage/Power: 90 - 240 Vac ±10%, 50 - 400
Hz*, 110 - 375 Vdc, equivalent voltage
* No CE compliance above 60 Hz
Low Voltage/Power Option:
24 Vac**, 20 - 36 Vdc. External power source must
meet Safety Agency Approvals
** Units can be powered safely with 24Vac power, but no
certification for CE are claimed
DIN Rail Monitor & Controller
Other outputs options are available, please contact our Sales Department.
For Low Power Option (
12-36Vdc, 24Vac)
add -DC
to end of part number: wiDR33-Z-DC $395 + 25 = $420.
To Order (Specify Model No.)
Model No. Price Description
wiDR33-U
$395 Wireless Meter/Controller for UWTC units with 2 Relays: Form “C” SPDT 3 A @ 120 Vac, 3 A @
240 Vac, Embedded Ethernet, 90-240 Vac/dc, 50-400 Hz
wiDR44-U
395 For UWTC units with Two Pulsed 10 Vdc @ 20 mA (for use with external SSR)
wiDR52-U
395 For UWTC units with Analog Output selectable as retransmission of process value;
0 to 10 Vdc or 0-20 mA @ 500 ohm max. and SSR
wiDR53-U
395 For UWTC units with Analog Output 0 to 10 Vdc or 0-20 mA @ 500 ohm max. and Form “C” Relay
wiDR22-Z
395 For zSeries units with Two Solid State Relays (SSR's): 0.5 A @ 120/240 Vac continuous
wiDR23-Z
395 For zSeries units with
SSR and
Form “C”
Relay
wiDR24-Z
395 For zSeries units with
SSR and
Pulsed 10 Vdc @ 20 mA (for use with external SSR)
wiDR54-Z
395 For zSeries units with Analog Output 0 to 10 Vdc or 0-20 mA @ 500 ohm max. and Pulsed 10 Vdc @
20 mA (for use with external SSR) and SSR
EMBEDDED WEBSERVER
The NEWPORT wiSeries wireless sensor system is
easy to install, simple to operate, and features
NEWPORT’s award-winning iServer technology with
an Embedded Web Server that requires no special
software.
CHARTS AND GRAPHS
The NEWPORT wiDR monitor serves Active Web
Pages to display real time readings and charts of
temperature, humidity, and barometric pressure. You
can also log data in standard data formats for use in
a spreadsheet or data acquisition program such as
Excel or Visual Basic. NEWPORT offers a free and
easy to use program for logging data to Excel.
The virtual chart viewed on the web page is a
JAVA™ Applet that records a chart over the LAN or
Internet in real time. With the NEWPORT wiSeries
system there is no need to invest time and money
learning a proprietary software program to log or
chart the data.
Chart scales are fully adjustable on the fly. For
example, the chart can display one minute, one
hour, one day, one week, one month or one year.
Temperature and humidity can be charted across
the full span (-40 to 125°C, and 0 to 100% RH) or
within any narrow range such as (20 to 30°C).
wiSeries
Sensor 8
Sensor 1
ID: 1 Strength: 100%Sequence: 10 Success: 100% Battery: 3.78V Update: 5sec Running
ID: 8 Strength: 94%Sequence: 24 Success: 100% Battery: 3.67V Update: 5sec Running
Temperature Readings of up to 8 Sensors
QUALITY and TECHNOLOGY
Designed and manufactured in the USA, the
innovative NEWPORT®wiSeries of meters &
controllers features an extended one (1) YEAR