Device circuit breakers
Selective power distribution:
branch out, individual adaptation,
modular extension
A constant energy supply and secure
data links are especially important for the
operational reliability of electrical systems,
installations, and devices.
Phoenix Contact meets all of these
requirements with the TRABTECH
product line. Coordinated solutions
consisting of surge protection, monitoring,
device circuit breakers and EMC products
offer consistently high power and signal
quality for maximum availability.
Interference-free mains supply
and signal transmission
Device circuit breakers as a modularly expandable system
or electronic multi-channel variant with comprehensive
functions.
2 PHOENIX CONTACT
Selective fuse protection for circuits
Reliable protection in the event of harmful overload and
short-circuit currents
System failures can be caused by various factors. A permanent overload, for
example, can damage the load and lead to the downtime of the system or a
system part.
Provide selective fuse protection for the control circuits in your systems in
order to increase system availability.
In practice, around 90% of all systems are operated with 24 V DC control
voltages.
High-quality device circuit
breakers provide safety for
your systems
Page 4 /5
CBM multi-channel electronic device
circuit breakers
Page 6 /7
Electronic device circuit breakers
Page 8 /9
Thermomagnetic device
circuit breakers
Page 10 /11
Thermal device circuit breakers
Page 12 /13
Device circuit breaker board
Page 14 /15
Product overview
Page 16 21
Device circuit breakers
and QUINT POWER
Page 22 /23
QUINT POWER
Page 24 /25
TRIO POWER and CBM
Page 26 /27
Table of contents
The different nominal currents of the various loads
illustrate the usefulness of selective protection for
the individual circuits. And you will find the perfect
device circuit breaker for almost any nominal current.
Valves
Motors
Relays
Programmable controllers
Sensors/actuators
Typical nominal currents
of electrical loads
0.5 A to 4 A
1 A to 12 A
1 A to 8 A
0.5 A to 5 A
0.5 A to 2 A
PHOENIX CONTACT 3
Device circuit breakers are a key factor
in high system availability. In the event of
overload and short circuit, they selectively
shut down the faulty circuit. All other
system parts remain in operation.
Thermal circuit breakers
Thermomagnetic circuit breakers
Electronic circuit breakers
Multi-channel, electronic circuit
breakers
High-quality device circuit breakers
provide security for your systems
Versatile use –
Device circuit breakers with various tripping technologies
We offer the right solution for every application.
Select the right circuit breaker plus a base element with push-in or
screw connection technology.
Shutdown behavior of device circuit breakers
Tripping time in the
case of overload
Tripping time in the
event of a short circuit
Your application is
optimally protected in
the event of
Thermal
circuit breakers
Suitable Unsuitable Overload
Thermomagnetic
circuit breakers
Suitable Ideal Overload
Short circuit
Long cable paths
(SFB tripping
characteristic)
Electronic
circuit breakers
Ideal Ideal Overload
Short circuit
Long cable paths
(active current limitation)
4 PHOENIX CONTACT
0
I
A
IN
12 x IN
15 x IN
10 x IN
6 x IN
2 x IN
4 x IN
Individual adaptationModular extension Branch out
With the unique bridge system from the
CLIPLINE complete range of accessories,
the device circuit breakers can also
be combined easily and individually.
Potentials of the same type can be
connected quickly and safely.
You can extend the power distribution,
modify the signal string or bridge the
auxiliary voltage for the electronic
device circuit breakers without this
resulting in significant wiring costs.
It couldn't be easier. Enhance your
system with additional device circuit
breakers in no time at all. It is even
possible to pre-wire your system on-site
with a customized plug selection. The
uniform, plug-in housing concept as well
as the bridgeability of the base elements
simplify installation.
Thermomagnetic device circuit breakers
with the SFB tripping characteristic*
provide maximum overcurrent protection
– even in large systems with long cable
paths. The characteristic curve:
Prevents the device from being shut
down unnecessarily early in the event
of brief current increases during
operation, such as starting currents
Prevents excessively long overload
currents that may be linked to
hazardous heat buildup in the
equipment
F characteristic curve
SFB characteristic curve
M characteristic curve
Selective protectionMulti-channel protection Distribute effortlessly
To trigger device circuit breakers
magnetically and therefore quickly,
power supplies have to provide a
multiple of the nominal current for
a short time. This current reserve is
available with QUINT POWER with
SFBTechnology* and up to six times
the nominal current for 12 ms.
The multi-channel electronic device
circuit breaker provides protection for
four or eight loads, depending on the
version. The individual channels can
be configured individually and have an
electronic locking mechanism to prevent
accidental changes. The status of each
channel is displayed directly on the
device and can also be queried as group
remote signaling using the connections
provided for this purpose.
Device circuit breaker boards combine
the advantages of CB device circuit
breakers with easy and space-saving
potential distribution. The switching
states of the circuit breakers are
monitored and provided as group
remote signaling in two groups via
connection terminal blocks. Protect up
to four loads simultaneously per channel.
There is also the connection option
for external relay contacts, such as for
safety-oriented shutoff.
*SFB = Selective fuse breaking/selective shutdown PHOENIX CONTACT 5
6 PHOENIX CONTACT
The multi-channel, electronic device circuit
breakers are optimally suited for use in
machine building, process engineering and
control and systems manufacturing.
The voltage remains at a constant level
due to the dynamic limiting of the current.
Other loads will not be influenced.
The individual adjustability of the 4 and
8-channel devices provides a convenient
and space-saving solution for any
application.
CBM multi-channel electronic
device circuit breakers
Independent channels
4/8 x 2.5 mm
Remote indication
contact
Early warning
at 80% of the
configured
nominal current
Supply
2 x 16 mm
Nominal current
configuration from
0.5 to 10A
Reset input
Electronic locking
of the configured
nominal current
Your advantages:
The nominal current assistant facilitates the setting
of nominal currents and provides optimal system
protection
Undervoltages and surge voltages will be identified,
loads will be switched off reliably
The electronic locking mechanism prevents accidental
changes to the current values
Fine nominal current graduations from 0.5 to 10 A in
just one device
Dynamic current limiting for a better utilization of the
upstream power supply unit
Width: 41 mm
t
x IN
0,5
1000
100
10
1
0,1
0,01
2
1,3
1,5
0,5 ... 1 A
s
1,1
t
x IN
0,5
1000
100
10
1
0,1
0,01
2
1,3 1,5
2 ... 10 A
s
1,1
Reset
13
14
DC OK
24-28V
+
+
-
-
-
L / +
N / -
Input 100-240V
AC
Output 24V 20A
DC
L
N
PE
IN+IN-
DC OK
SIGNALSOUT+
1
2
3
4
5
6
7
8
13
14
1
2
1
2
1
2
3
4
5
6
7
8
RST
I >
80%
1
0,5
2
4
610
1
0,5
2
4
610
1
0,5
2
4
610
1
0,5
2
4
610
1
0,5
2
4
610
1
0,5
2
4
610
1
0,5
2
4
610
1
0,5
2
4
610
I>80%
+
OK
PHOENIX CONTACT 7
Tripping characteristics
Illustration of application
By using multi-channel electronic
device circuit breakers, the project
engineering for a switchgear is
significantly more simple and
more easily understandable. The
configurable nominal currents can
be used to adjust the required
protection for the load used. This
makes the devices very well-suited
for protecting relays, programmable
controllers, motors, sensors/actuators
and valves.
Also, the signaling always keeps the
user up-to-date about the operating
state of the system. The reset input
can be used to remotely switch back
on paths that have been switched off.
The multi-channel electronic device
circuit breakers differentiate between
three states: normal operating state,
overload and short circuit. In the range
between 1.1 and 1.3 times the nominal
current, an overload is detected and
switched off after thirty seconds for
safety reasons. If the flowing current is
over 1.3 times the nominal current, it is
detected as a short circuit and actively
limited depending on the configured
current. Switching off in case of short
circuit occurs after 20 milliseconds.
This allows the supply voltage to
remain consistent, while other
loads can continue to run without
interruption.
Electronic device circuit breakers are often
used in automation and communication
technology.
The active current limitation prevents the
interruption of the output voltage at the
switched-mode power supply unit in the
event of an error. All other circuits remain
unaffected.
Electronic device circuit breakers
Negative bridge shaft
Two-piece/plug-in
Supply up to 6 mm
Negative supply
Bridge shaft supply
Function display
Connected through
Current limitation
Switched off
Marking option
Plug locking
Coding between plug and
base element
On/off switch (reset)
N/C contact, N/O contact,
status + reset or
status + control
Power distribution, 2 x 4 mm2
Your advantages:
Compact design with precise nominal current levels
Sophisticated remote signaling concept enables
monitoring from any location
The reset or control input can be switched by
means of remote control
Active current limitation, even when switching
capacitive loads
Supply/remote signaling can be bridged with CLIPLINE
complete accessories
Variable connection technology: either push-in or
screw connection
8 PHOENIX CONTACT
M1A
4
3A
on
r
e
s
e
t
2A
on
r
e
s
e
t
PLC
2A
on
r
e
s
e
t
1A
on
r
e
s
e
t
230 V
F1 F2 F3 F4
0
10
1
0,1
0,01
100
1000
123
Tripping characteristics
Illustration of application
Switching time [s]
Multiples of IN
Electronic device circuit breakers
are ideal for protecting relays,
programmable controllers, motors,
sensors/actuators, and valves, for
example.
In the event of a short circuit,
electronic device circuit breakers trip
within a few milliseconds. Here the
current is limited to 1.25 times the
nominal current. Even with a high
cable resistance, the circuit breakers
disconnect the circuit within the
shortest possible time.
CB E …
PHOENIX CONTACT 9
The thermomagnetic device circuit breakers
are used in information and communication
technology as well as process engineering.
Due to the various tripping characteristics,
the circuit breakers can be used in a
range of applications. The reactivation
and immediate remote signaling of the
operating state ensure availability.
Thermomagnetic
device circuit breakers
Two-piece/plug-in
Supply up to 6 mm
Plug locking
Coding between plug and
base element
On/off switch
Remote indication contact
11/C, 14/NO
Power distribution, 2 x 4 mm2
Bridge shaft remote signaling
Remote indication contact
12/NC
Marking option
Bridge shaft supply
Your advantages:
Compact design with precise nominal current levels
Sophisticated remote signaling concept enables
monitoring from any location
Maximum overcurrent protection over long cable paths
thanks to SFB tripping characteristic
Supply/remote signaling can be bridged with CLIPLINE
complete accessories
Protect 230/240 V AC control voltage with the aid of
the M1 characteristic curve (based on characteristic C)
Variable connection technology: either push-in or
screw connection
10 PHOENIX CONTACT
M6A
2 8 8 1 A
M 1
PLC
230 V
AC
AC
F1 F2 F3 F4
Schaltzeit [s]
Vielfache von IN
10000
1000
100
10
1
0,1
0,01
0,001
12 20
440
610 100 220
440
610 100
8...16 A0,5...6 A
10000
1000
100
10
1
0,1
0,01
0,001 12 20
440
610 100 220
440
610 100
8...16 A0,5...6 A
10000
1000
100
10
1
0,1
0,01
0,001
12 20
440
610 100 220
440
610
100
8...16 A
0,5...6 A
Tripping characteristics
SFB M1 F1
Illustration of application
With thermomagnetic device circuit
breakers, the tripping time depends
on the type of overload. In the
event of an overload, the load is
disconnected from the power supply
by means of time-delayed thermal
tripping. If there is a high overload
current or even a short circuit, the
magnetic tripping interrupts the circuit
in a matter of milliseconds. Protective
devices should be selected with the
most suitable characteristic curve in
relation to the area of application,
the load, and the protection
requirements.
Switching time [s]
Multiples of IN
AC tripping range
Thermomagnetic device circuit
breakers are ideal for protecting
programmable controllers, valves,
motors and frequency inverters, for
example.
PHOENIX CONTACT 11
Thermal device circuit breakers
provide optimum protection for inductive
loads against overload in power distribution
systems in control cabinet engineering and
systems manufacturing. The integrated
switching function enables the device to
be switched on again immediately and
therefore ensures the availability of the
system.
Thermal device circuit breakers
Power distribution, 1 x 6 mm2
Base element with and without LED display
Plug-in
Bridge shaft supply
Marking option
Supply up to 6 mm2
On switch
On/off switch
Very slim design
Your advantages:
Compact design with precise nominal current levels
Fits in all fuse holders designed for flat-type fuse
inserts in accordance with ISO8820-3 (DIN72581-3)
Can be used to protect integrated circuits in all
battery and onboard systems in the DC voltage range
Supply can be bridged with CLIPLINE complete
accessories
Protect 230/240 V AC control voltage with the aid of
the TCP … A products
12 PHOENIX CONTACT
M
1A
1.01.0 1.0 2.0
DC
DC
F1 F2 F3 F4
F1 F2 F3 F4
230 V
0,1 0,1
11
10 10
102102
103103
104104
0,4 12 10 20
44
0,4 12 10 20
-40°C
-40°C
+23°C +23°C
+85°C
+85°C
7, 5A- 30 A5A
246810 20 30
10,8
10
3
10
4
10
2
10
1
0,1
0,2 5-4A
6-10A
Tripping characteristics
Illustration of application
Thermal device circuit breakers are
ideal for protecting motors, lighting,
solenoid valves, transformers and
onboard networks, for example.
The tripping time of the thermal
device circuit breakers varies with the
pending overload current. As can be
seen in the characteristic curves, the
circuit breaker trips more quickly as
the overload increases. The protective
function provided by a bimetal reacts
at a defined tripping temperature. With
a relatively low overload current, it
therefore takes longer for the connected
load to be disconnected from the power
supply.
Switching time [s]
Switching time [s]
TCP/DC 32V TCP … A
Multiples of IN
Multiples of IN
PHOENIX CONTACT 13
The multi-channel device circuit breaker
boards are used in standard machine
production or in control and process
engineering, for example.
Due to the central potential distribution,
installation time is reduced to a minimum.
The boards are very versatile as they can
be fitted individually with thermomagnetic
and electronic circuit breakers.
Device circuit breaker board
Group remote signaling
divided into 2 groups
Fuse protection of up to
12 A per channel
Up to 60 A supply,
4 x 16 mm
Connection for external
relay contacts, e.g.
safety relays
Thermomagnetic
and electronic circuit
breakers can be used
UM-PRO panel mounting base
with increased temperature
resistance
4 x 2.5 mm terminal
outputs (+/-) per
channel, protected
Plug-in of push-in terminal blocks
Your advantages:
Reduced installation time thanks to multi-channel
device circuit breaker board (4/8/12 channels)
Compact design saves up to 35% space
Fuse protection of up to 12 A per channel provides
optimum protection for the connected loads
Thanks to the effortless potential distribution, four
loads can be protected per channel
Integrated group remote signaling ensures
that you are always kept informed
High current carrying capacity of the board supports
supply of up to 60A
Looped-in relay contacts are also protected using the
device circuit breaker
Configuring the inserted
circuit breakers with
DIP switch
14 PHOENIX CONTACT
B2 errorB1 on
X31
S1 CB E1
CB TM1
4-
3-
2-
1-
4+
3+
2+
1+
34
33
4-
3-
2-
1-
4+
3+
2+
1+
34
33
4-
3-
2-
1-
4+
3+
2+
1+
34
33
4-
3-
2-
1-
4+
3+
2+
1+
34
33
SFB
2A
SFB
2A 6A
on
off
r
e
s
e
t
1+
2+
1-
2-
X21 DC24V/60A
6A
on
off
r
e
s
e
t
F1 F2 F3 F4
L ogi c
K1
K2
A1 Y1 13 23 31
A2 Y2 14 24 32
High operational reliability thanks to redundant power supply
Illustration of application
The device circuit breaker boards
offer connection options for up to
five loads per mode of protection.
Therefore, the boards combine the
advantages of the device circuit
breaker series CB TM1... and CB E1...
with easy and space-saving potential
distribution.
Group remote signaling is evaluated,
for example, using a programmable
controller.
Also, for each channel, the device
circuit breaker board provides the
option of connecting external relay
contacts, such as for safety switching
devices.
Ensure high availability and productivi-
ty levels for your control and process
engineering system.
This can be achieved with a redundant
switchgear structure. In this case,
two 24 V DC power supplies are
decoupled via a redundancy module
thereby offering superior system
availability.
The doubled supply of the device
circuit breaker board also offers
the option of configuring redundant
wiring.
PHOENIX CONTACT 15
Product overview
Electronic device circuit breakers
Product code CBM multi-channel device circuit breaker
Channels 4 8
Group remote signaling Channels 1-4 Channels 1-8
Max. supply current 40 A 80 A
CBM E4 24DC/0.5-10A NO-R
Order No. 2905743
CBM E8 24DC/0.5-10A NO-R
Order No. 2905744
16 PHOENIX CONTACT
Product code CB device circuit breakers
Fuse type E electronic
Number of positions 1
Nominal voltage 24 DC
Type NO
N/O contact
NC
N/C contact
S-R status output
and reset input
Nominal current
1 A CB E1 24DC/1A NO P
Order No. 2800901
CB E1 24DC/1A NC P
Order No. 2800915
CB E1 24DC/1A S-R P
Order No. 2800908
2 A CB E1 24DC/2A NO P
Order No. 2800902
CB E1 24DC/2A NC P
Order No. 2800916
CB E1 24DC/2A S-R P
Order No. 2800909
3 A CB E1 24DC/3A NO P
Order No. 2800903
CB E1 24DC/3A NC P
Order No. 2800917
CB E1 24DC/3A S-R P
Order No. 2800910
4 A CB E1 24DC/4A NO P
Order No. 2800904
CB E1 24DC/4A NC P
Order No. 2800918
CB E1 24DC/4A S-R P
Order No. 2800911
6 A CB E1 24DC/6A NO P
Order No. 2800905
CB E1 24DC/6A NC P
Order No. 2800919
CB E1 24DC/6A S-R P
Order No. 2800912
8 A CB E1 24DC/8A NO P
Order No. 2800906 CB E1 24DC/8A S-R P
Order No. 2800913
10 A
CB E1 24DC/10A NO P
Order No. 2800907 CB E1 24DC/10A S-R P
Order No. 2800914
Type S-C
Status output
and control input
SI-R
Inverted status output
and reset input
SI-C
Inverted status output
and control input
Nominal current
1 A CB E1 24DC/1A S-C P
Order No. 2800922
CB E1 24DC/1A SI-R P
Order No. 2905799
CB E1 24DC/1A SI-C P
Order No. 2905806
2 A CB E1 24DC/2A S-C P
Order No. 2800923
CB E1 24DC/2A SI-R P
Order No. 2905800
CB E1 24DC/2A SI-C P
Order No. 2905807
3 A CB E1 24DC/3A S-C P
Order No. 2800924
CB E1 24DC/3A SI-R P
Order No. 2905801
CB E1 24DC/3A SI-C P
Order No. 2905808
4 A CB E1 24DC/4A S-C P
Order No. 2800925
CB E1 24DC/4A SI-R P
Order No. 2905802
CB E1 24DC/4A SI-C P
Order No. 2905809
6 A CB E1 24DC/6A S-C P
Order No. 2800926
CB E1 24DC/6A SI-R P
Order No. 2905803
CB E1 24DC/6A SI-C P
Order No. 2905810
8 A CB E1 24DC/8A S-C P
Order No. 2800927
CB E1 24DC/8A SI-R P
Order No. 2905804
CB E1 24DC/8A SI-C P
Order No. 2905811
10 A
CB E1 24DC/10A S-C P
Order No. 2800928
CB E1 24DC/10A SI-R P
Order No. 2905805
CB E1 24DC/10A SI-C P
Order No. 2905812
Electronic device circuit breakers
NO: normally open
NC: normally closed
S-R: status out – reset in
S-C: status out – control in
SI-R: status out inverted – reset in
SI-C: status out inverted – control in
reset in: restart with impulse
control in: switching on and off with applying 24 V DC
status out: in the case of active load output, a high signal (24 V DC) is issued
status out inverted: in the case of active load output, a low signal (0 V DC) is issued
PHOENIX CONTACT 17
Thermomagnetic device circuit breakers, 1 and 2-pos.
Product code CB device circuit breakers
Fuse type TM thermomagnetic
Function 1 changeover contact
Number of positions 1
Characteristic curve SFB M1 F1
Nominal current
0.5 A
CB TM1 0.5A SFB P
Order No. 2800835
CB TM1 0.5A M1 P
Order No. 2800846
CB TM1 0.5A F1 P
Order No. 2800857
1 A CB TM1 1A SFB P
Order No. 2800836
CB TM1 1A M1 P
Order No. 2800847
CB TM1 1A F1 P
Order No. 2800858
2 A CB TM1 2A SFB P
Order No. 2800837
CB TM1 2A M1 P
Order No. 2800848
CB TM1 2A F1 P
Order No. 2800859
3 A CB TM1 3A SFB P
Order No. 2800838
CB TM1 3A M1 P
Order No. 2800849
CB TM1 3A F1 P
Order No. 2800860
4 A CB TM1 4A SFB P
Order No. 2800839
CB TM1 4A M1 P
Order No. 2800850
CB TM1 4A F1 P
Order No. 2800861
5 A CB TM1 5A SFB P
Order No. 2800840
CB TM1 5A M1 P
Order No. 2800851
CB TM1 5A F1 P
Order No. 2800862
6 A CB TM1 6A SFB P
Order No. 2800841
CB TM1 6A M1 P
Order No. 2800852
CB TM1 6A F1 P
Order No. 2800863
8 A CB TM1 8A SFB P
Order No. 2800842
CB TM1 8A M1 P
Order No. 2800853
CB TM1 8A F1 P
Order No. 2800864
10 A CB TM1 10A SFB P
Order No. 2800843
CB TM1 10A M1 P
Order No. 2800854
CB TM1 10A F1 P
Order No. 2800865
12 A CB TM1 12A SFB P
Order No. 2800844
CB TM1 12A M1 P
Order No. 2800855
CB TM1 12A F1 P
Order No. 2800866
16 A CB TM1 16A SFB P
Order No. 2800845
CB TM1 16A M1 P
Order No. 2800856
CB TM1 16A F1 P
Order No. 2800867
Function 2 changeover contacts
Number of positions 2
Characteristic curve SFB M1 F1
Nominal current
0.5 A
CB TM2 0.5A SFB P
Order No. 2800868
CB TM2 0.5A M1 P
Order No. 2800879
CB TM2 0.5A F1 P
Order No. 2800890
1 A CB TM2 1A SFB P
Order No. 2800869
CB TM2 1A M1 P
Order No. 2800880
CB TM2 1A F1 P
Order No. 2800891
2 A CB TM2 2A SFB P
Order No. 2800870
CB TM2 2A M1 P
Order No. 2800881
CB TM2 2A F1 P
Order No. 2800892
3 A CB TM2 3A SFB P
Order No. 2800871
CB TM2 3A M1 P
Order No. 2800882
CB TM2 3A F1 P
Order No. 2800893
4 A CB TM2 4A SFB P
Order No. 2800872
CB TM2 4A M1 P
Order No. 2800883
CB TM2 4A F1 P
Order No. 2800894
5 A CB TM2 5A SFB P
Order No. 2800873
CB TM2 5A M1 P
Order No. 2800884
CB TM2 5A F1 P
Order No. 2800895
6 A CB TM2 6A SFB P
Order No. 2800874
CB TM2 6A M1 P
Order No. 2800885
CB TM2 6A F1 P
Order No. 2800896
8 A CB TM2 8A SFB P
Order No. 2800875
CB TM2 8A M1 P
Order No. 2800886
CB TM2 8A F1 P
Order No. 2800897
10 A CB TM2 10A SFB P
Order No. 2800876
CB TM2 10A M1 P
Order No. 2800887
CB TM2 10A F1 P
Order No. 2800898
12 A CB TM2 12A SFB P
Order No. 2800877
CB TM2 12A M1 P
Order No. 2800888
CB TM2 12A F1 P
Order No. 2800899
16 A CB TM2 16A SFB P
Order No. 2800878
CB TM2 16A M1 P
Order No. 2800889
CB TM2 16A F1 P
Order No. 2800900
18 PHOENIX CONTACT
Thermal circuit breakers
Product code Thermal circuit breakers
Number of positions 1
Characteristic curve T1
Function Can be switched on and off
Nominal current
0.1 A TCP 0,1A Order No. 0712107
0.25
A TCP 0,25A Order No. 0712123
0.5 A TCP 0,5A Order No. 0712152
1 A TCP 1A Order No. 0712194
2 A TCP 2A Order No. 0712217
3 A TCP 3A Order No. 0712233
4 A TCP 4A Order No. 0712259
6 A TCP 6A Order No. 0712275
8 A TCP 8A Order No. 0712291
10 A TCP 10A Order No. 0712314
Product code Thermal circuit breakers
Number of positions 1
Characteristic curve T1
Function Reclosable
Nominal current
5 A TCP 5/DC32V Order No. 0700005
7.5 A TCP 7,5/DC32V Order No. 0700007
10 A TCP 10/DC32V Order No. 0700010
15 A TCP 15/DC32V Order No. 0700015
20 A TCP 20/DC32V Order No. 0700020
25 A TCP 25/DC32V Order No. 0700025
30 A TCP 30/DC32V Order No. 0700030
40 A TCP 40/DC32V Order No. 0700040
Product code Flat-type fuse terminal block
Function Without LED display With LED display,
12 V
With LED display,
24 V
ST 4-FSI/C
Order No. 3036372
ST 4-FSI/C-LED 12
Order No. 3036495
ST 4-FSI/C-LED 24
Order No. 3036505
UK 6-FSI/C
Order No. 3118203
UK 6-FSI/C-LED12
Order No. 3001925
UK 6-FSI/C-LED24
Order No. 3001938
PHOENIX CONTACT 19
Device circuit breaker board
Product code CBB device circuit breaker board
Mounting Thermomagnetic and electronic device circuit breaker
CB TM1 ... and CB E1 ... NO
Channels 4 8 12
Group remote signaling 2 x 2 2 x 4 2 x 6
Max. supply current 48 A 60 A 60 A
CBB 04 2x2RC-PT
Order No. 2905238
CBB 08 2x4RC-PT
Order No. 2905240
CBB 12 2x6RC-PT
Order No. 2905241
Select the right CB TM1... or CB E1... device circuit breakers according to the application.
Mounting Thermomagnetic device circuit breaker
CB TM1 ...
Channels 4 8 12
Group remote signaling 2 x 2 2 x 4 2 x 6
Max. supply current 48 A 60 A 60 A
CBB TM 04 2 x 2RC P-PT
Order No. 2801481
CBB TM 08 2 x 4RC P-PT
Order No. 2801482
CBB TM 12 2 x 6RC P-PT
Order No. 2801483
20 PHOENIX CONTACT
Accessories
For more bridges and marking material, see main catalog or website.
Product code Base element
Screw connection
technology
Push-in connection
technology
Solder base element for
PCBs
CB 1/10-1/10 UT-BE
Order No. 2801305
CB 1/6-2/4 PT-BE
Order No. 2800929
CB S-BE
Order No. 2905067
Note: supply can be loaded with up to 41 A if two bridges are connected.
Product code Bridge plug for base element
CB PT Bridge
Order No. 2801014
CB RC Bridge
Order No. 2801616
Bridge between 1 and 2 Bridge between 11 and 14
Product code Base element and jumpers
Number of positions
2 FBL 2-6 Order No. 3030336
3 FBL 3-6 Order No. 3030242
4 FBL 4-6 Order No. 3030255
5 FBL 5-6 Order No. 3030349
10 FBL 10-6 Order No. 3030271
20 FBL 20-6 Order No. 3030365
50 FBL 50-6 Order No. 3032224
Product code Front cutting tool for jumpers
CUTFOX-FBL
Order No. 1212124
PHOENIX CONTACT 21
Device circuit breakers
and QUINT POWER
The configuration matrix can help with
the secondary-side planning of your power
supply unit. It describes the maximum
cable lengths depending on:
The device circuit breaker
The conductor cross section
The performance class of the power
supply unit
Additional support is available from our
online configurator and the online project
engineering matrix.
QUINT POWER and device circuit breaker with
SFB characteristic curve
The combination of QUINT POWER power supplies
and thermomagnetic device circuit breakers with SFB
characteristic curve provides you with the following
advantages:
Short circuit triggering after at least 10 milliseconds for
safe operation of your controller
Substantial reduction of tolerances; this causes the
required release current to be reduced
Safe shutoff of faulty paths through electrical isolation
22 PHOENIX CONTACT
CB Internal resistance
CB 1A 1.1 
CB 2A 0.32 
CB 3A 0.14 
1. Calculation of the maximum resistance:
Rmax = U
ICB x IFactor
= 24 V =1.6 
1 A x 15
2. Calculation of the maximum cable resistance:
RCable max = Rmax - RCB
=1.6  - 1.1 
=0.5 
3. Now all the necessary information is available in order to calculate
the maximum cable lengths using the following formula:
=R x A
ρ
ρ = specific resistance (copper 0.01786)
A = cross section/conductor
=0.5 x 1.5
0.01786 = 42 m
(forward and return line):
Cable calculations
Some information is needed in order
to calculate the conductor lengths.
This basic data includes the output
voltage of the power supply (U), the
rated current of the device circuit
breaker (ICB) and the conductor
cross sectionof the cable to be
used. Thecharacteristic curves of
the respective device circuit breaker
types areusedas a basis for this.
IFactor
Cable lengths
The values specified relate to the
distance ( ) from the power supply unit
to the load. Boundary parameters
for the calculation:
CB TM1 x A SFB P
device circuit breaker
Electromagnetic tripping
at the latest at:
- 10 times the rated current
- Ambient temperature: +20°C
- Power supply QUINT POWER
with SFB technology
The internal resistance of the device
circuit breakers is taken into account.
In addition to the short-circuit current,
the relevant power supply unit also
supplies half the nominal current for
paths connected in parallel.
Power supply Load
[Conductor cross section] mm0.75 11.5 2.5 4
Distance in m
24 V / 5 A
CB TM1 1A SFB P 27 36 54 91
CB TM1 2A SFB P 10 13 20 34
24 V/10 A
CB TM1 1A SFB P 27 36 54 91
CB TM1 2A SFB P 18 25 37 63
CB TM1 3A SFB P 11 15 22 38
Extract from the configuration matrix. The complete matrix can be found at:
phoenixcontact.com > Products > Protective devices > Device circuit breakers
Distance ( ) = 21 m
PHOENIX CONTACT 23
QUINT POWER – Power supply units
for superior system availability
Benefit from the functional advantages of
the QUINT POWER power supplies. The
unique SFB technology and preventive
function monitoring increase the availability
of your application.
Quick tripping of device circuit breakers
Dynamic power reserve SFB technology with up to 6 times
the nominal current for 12 milliseconds
Reliable starting of heavy loads
Static POWER BOOST power reserve with up to 1.5 times
the nominal current on a permanent basis
Preventive function monitoring
Warns of critical operating states before faults occur by
permanently monitoring the output voltage and current,
remote monitoring using active switching output and
floating relay contact
Worldwide use
Thanks to the wide range input and international approval
package
High operational reliability
due to high MTBF > 500,000h, long power failure buffering
times > 20ms, high electric strength of single-phase devices
of up to 300VAC
Parallel connection possible
for increased performance and redundancy
Three-phase devices
Error-free operation, even in the event of a permanent
phase failure, high surge resistance of up to 6kV thanks to
integrated gas-filled surge arrester
Compensation of voltage drops
Output voltage can be set on front side. The voltage range
of 5 to 56 V DC can be covered with three power supply
units with output voltages of 12, 24, and 48 V DC.
Easy-to-maintain connection technology
with coded COMBICON connectors (up to and
including10 A)
Robust design
Metal housing and wide temperature range of -25°C to
+70°C
Minimize installation costs
Third negative terminal as the grounding terminal block
All features at a glance
24 PHOENIX CONTACT
Input voltage range Output current /
POWER BOOST / SFB
Magnetic fuse tripping
up to
Setting range of the
output voltage
Dimensions
W x H x D
QUINT POWER 1~
QUINT-PS/1AC/24DC/3.5
Order No. 2866747
85 V AC … 264 V AC
90 V DC … 350 V DC
3.5 A / 4 A / 15 A B2 18 V DC … 29.5 V DC 32 x 130 x 125
QUINT-PS/1AC/24DC/5
Order No. 2866750
85 V AC … 264 V AC
90 V DC … 350 V DC
5 A / 7.5 A / 30 A B2, B4, C2 18 V DC … 29.5 V DC 40 x 130 x 125
QUINT-PS/1AC/24DC/10
Order No. 2866763
85 V AC … 264 V AC
90 V DC … 350 V DC
10 A / 15 A / 60 A B2, B4, B6, C2, C4 18 V DC … 29.5 V DC 60 x 130 x 125
QUINT-PS/1AC/24DC/20
Order No. 2866776
85 V AC … 264 V AC
90 V DC … 350 V DC
20 A / 26 A / 120 A B2, B4, B6, B10, B16,
C2, C4, C6
18 V DC … 29.5 V DC 90 x 130 x 125
QUINT-PS/1AC/24DC/40
Order No. 2866789
85 V AC … 264 V AC
90 V DC … 350 V DC
40 A / 45 A / 215 A B2, B4, B6, B10, B16,
B25, C2, C4, C6, C13
18 V DC … 29.5 V DC 180 x 130 x 125
QUINT-PS/1AC/12DC/15
Order No. 2866718
85 V AC … 264 V AC
90 V DC … 350 V DC
15 A / 16 A / 60 A B2, B4, B6, C2, C4 5 V DC … 18 V DC 60 x 130 x 125
QUINT-PS/1AC/12DC/20
Order No. 2866721
85 V AC … 264 V AC
90 V DC … 350 V DC
20 A / 26 A / 120 A B2, B4, B6, B10, C2,
C4, C6
5 V DC … 18 V DC 90 x 130 x 125
QUINT-PS/1AC/48DC/5
Order No. 2866679
85 V AC … 264 V AC
90 V DC … 350 V DC
5 A / 7.5 A / 30 A B2, B4, C2 30 V DC …56 V DC 60 x 130 x 125
QUINT-PS/1AC/48DC/10
Order No. 2866682
85 V AC … 264 V AC
90 V DC … 350 V DC
10 A / 13 A / 60 A B2, B4, B6, C2, C4 30 V DC …56 V DC 90 x 130 x 125
QUINT-PS/1AC/48DC/20
Order No. 2866695
85 V AC … 264 V AC
90 V DC … 350 V DC
20 A / 22.5 A / 100 A B2, B4, B6, B10, C2,
C4, C6
30 V DC …56 V DC 180 x 130 x 125
QUINT POWER 3~
QUINT-PS/3AC/24DC/5
Order No. 2866734
320 V AC … 575 V AC
450 V DC … 800 V DC
5 A / 7.5 A / 30 A B2, B4, C2 18 V DC … 29.5 V DC 40 x 130 x 125
QUINT-PS/3AC/24DC/10
Order No. 2866705
320 V AC … 575 V AC
450 V DC … 800 V DC
10 A / 15 A / 60 A B2, B4, B6, C2, C4 18 V DC … 29.5 V DC 60 x 130 x 125
QUINT-PS/3AC/24DC/20
Order No. 2866792
320 V AC … 575 V AC
450 V DC … 800 V DC
20 A / 26 A / 120 A B2, B4, B6, B10, B16,
C2, C4, C6
18 V DC … 29.5 V DC 69 x 130 x 125
QUINT-PS/3AC/24DC/40
Order No. 2866802
320 V AC … 575 V AC
450 V DC … 800 V DC
40 A / 45 A / 215 A B2, B4, B6, B10, B16,
B25, C2, C4, C6, C13
18 V DC … 29.5 V DC 96 x 130 x 176
QUINT-PS/3AC/48DC/20
Order No. 2320827
320 V AC … 575 V AC
450 V DC … 800 V DC
20 A / 22.5 A / 100 A B2, B4, B6, B10, C2,
C4, C6
30 V DC … 56 V DC 96 x 130 x 176
QUINT POWER CO, with protective coating for 100% humidity
QUINT-PS/1AC/24DC/5/CO
Order No. 2320908
85 V AC … 264 V AC
90 V DC … 350 V DC
5 A / 7.5 A / 30 A B2, B4, C2 18 V DC … 29.5 V DC 40 x 130 x 125
QUINT-PS/1AC/24DC/10/CO
Order No. 2320911
85 V AC … 264 V AC
90 V DC … 350 V DC
10 A / 15 A / 60 A B2, B4, B6, C2, C4 18 V DC … 29.5 V DC 60 x 130 x 125
QUINT-PS/1AC/24DC/20/CO
Order No. 2320898
85 V AC … 264 V AC
90 V DC … 350 V DC
20 A / 26 A / 120 A B2, B4, B6, B10, B16,
C2, C4, C6
18 V DC … 29.5 V DC 90 x 130 x 125
QUINT-PS/3AC/24DC/20/CO
Order No. 2320924
320 V AC … 575 V AC
450 V DC … 800 V DC
20 A / 26 A / 120 A B2, B4, B6, B10, B16,
C2, C4, C6
18 V DC … 29.5 V DC 69 x 130 x 125
DC/DC converters
QUINT-PS/24DC/24DC/5
Order No. 2320034
18 V DC … 32 V DC 5 A / 6.25 A / 30 A B2, B4, C2 18 V DC … 29.5 V DC 32 x 130 x 125
QUINT-PS/24DC/24DC/10
Order No. 2320092
18 V DC … 32 V DC 10 A / 12.5 A / 60 A B2, B4, B6, C2, C4 18 V DC … 29.5 V DC 48 x 130 x 125
QUINT-PS/24DC/24DC/20
Order No. 2320102
18 V DC … 32 V DC 20 A / 25 A / 120 A B2, B4, B6, B10, B16,
C2, C4, C6
18 V DC … 29.5 V DC 82 x 130 x 125
QUINT-PS/24DC/12DC/8
Order No. 2320115
18 V DC … 32 V DC 8 A / 10 A / 48 A B2, B4, C2 5 V DC … 18 V DC 32 x 130 x 125
QUINT-PS/24DC/48DC/5
Order No. 2320128
18 V DC … 32 V DC 5 A / 6.25 A / 30 A B2, B4, C2 30 V DC … 56 V DC 48 x 130 x 125
QUINT-PS/12DC/12DC/8
Order No. 2905007
9 V DC … 18 V DC 8 A / 10 A / 48 A B2, B4, C2 5 V DC … 18 V DC 32 x 130 x 125
QUINT-PS/48DC/48DC/5
Order No. 2905008
30 V DC … 60 V DC 5 A / 6.25 A / 30 A B2, B4, C2 30 V DC … 56 V DC 48 x 130 x 125
PHOENIX CONTACT 25
TRIO POWER and CBM –
The perfect team for very high
system availability
The combination of the CBM multi-channel
electronic device circuit breakers and the
TRIO POWER power supplies with push-
in connection technology can help you
increase the availability of your systems and
machines.
Both products are perfectly matched to the
requirements in machine building, forming
an extremely slim 24 V power supply for
superior system availability.
The common advantages:
Saves space in the control cabinet thanks to narrow
design of both products
High system availability thanks to the optimum
combination of power supply and device protection
Quick and tool-free installation thanks to push-in
technology
A wide variety of application areas thanks to wide
temperature range and high shock and vibration
resistance
26 PHOENIX CONTACT
Input voltage range Output current/
dynamic boost
Setting range of the output
voltage
Dimensions
W x H x D
TRIO POWER 1~
TRIO-PS-2G/1AC/24DC/3/C2LPS
Order No. 2903147
85 V AC … 264 V AC
110 V DC … 250 V DC
3 A / 4.5 A 24 V DC … 28 V DC 30 x 130 x 115
TRIO-PS-2G/1AC/24DC/5
Order No. 2903148
85 V AC … 264 V AC
110 V DC … 250 V DC
5 A / 7.5 A 24 V DC … 28 V DC 35 x 130 x 115
TRIO-PS-2G/1AC/24DC/10
Order No. 2903149
85 V AC … 264 V AC
110 V DC … 250 V DC
10 A / 15 A 24 V DC … 28 V DC 42 x 130 x 160
TRIO-PS-2G/1AC/24DC/20
Order No. 2903151
85 V AC … 264 V AC
110 V DC … 250 V DC
20 A / 30 A 24 V DC … 28 V DC 68 x 130 x 160
TRIO POWER 3~
TRIO-PS-2G/3AC/24DC/5
Order No. 2903153
3x 320 V AC … 575 V AC
600 V DC
5 A / 7.5 A 24 V DC … 28 V DC 35 x 130 x 115
TRIO-PS-2G/3AC/24DC/10
Order No. 2903154
2x/3x 320 V AC … 575 V AC
600 V DC
10 A / 15 A 24 V DC … 28 V DC 45 x 130 x 160
TRIO-PS-2G/3AC/24DC/20
Order No. 2903155
2x/3x 320 V AC … 575 V AC
600 V DC
20 A / 30 A 24 V DC … 28 V DC 65 x 130 x 160
The features of TRIO POWER at a glance
Reliable starting of difficult loads
The dynamic BOOST supplies 1.5 times the
nominal current for 5 seconds
Active function monitoring
Remote monitoring of the output voltage using
floating relay contact
High operational reliability due to robust
design in terms of shock, vibration and electric
strength. High MTBF (Mean Time Between
Failure) and temperature range between
-25°C and +70°C as well as device startup at
-40 °C (type-tested)
Three-phase devices
Error-free function, even if one phase fails
permanently
Input voltage range for DC voltage of
110to250 V DC or 600 V DC
Minimize installation costs
Third negative terminal block used as a
grounding terminal block
Compensation of voltage drops by means of
output voltage that can be adjusted on the
front
PHOENIX CONTACT 27
TT 03-14.001.L3 Printed in Germany
MNR 52000955/2015-03-20/03 © PHOENIX CONTACT 2015
Always up-to-date, always available to you. Here
you'll find everything on our products, solutions
and service:
phoenixcontact.com
Product range
Cables and wires
• Connectors
• Controllers
Electronics housing
Electronic switchgear and
motor control
Fieldbus components and systems
Functional safety
HMIs and industrial PCs
I/O systems
Industrial communication technology
Industrial Ethernet
Installation and mounting material
Lighting and signaling
Marking and labeling
Measurement and control technology
Modular terminal blocks
• Monitoring
PCB terminal blocks and
PCB connectors
Power supply units and UPS
Protective devices
Relay modules
Sensor/actuator cabling
• Software
Surge protection and interference filters
System cabling for controllers
• Tools
Wireless data communication
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstraße 8
32825 Blomberg, Germany
Phone: + 49 5235 3-00
Fax: + 49 5235 3-41200
E-mail: info@phoenixcontact.com
phoenixcontact.com
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Phoenix Contact:
2905743