https://www.phoenixcontact.com/us/produkte/2838526
04.10.2012Page2/7
Surge protection connector-CTM 2X1-110AC-2838526
Technical data
General
Ambient temperature (operation) -25 °C ... 75 °C
Mounting type On CT-TERMIBLOCK and LSA-PLUS disconnect strip
Design LSA-PLUS module
Number of positions 2
Degree of protection IP20
Direction of action Line-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software
version: From SW rev. 1.10
Width 9.5 mm
Height 21 mm
Depth 53.5 mm
Protective circuit
IEC category B2
IEC category C1
IEC category C2
IEC category C3
IEC category D1
VDE requirement class B2
VDE requirement class C1
VDE requirement class C2
VDE requirement class C3
VDE requirement class D1
Nominal voltage UN 110 V AC
Maximum continuous operating voltage UC ± 180 V DC
Maximum continuous voltage UC (wire-ground) ± 180 V DC
Nominal current IN 380 mA (25°C)
Operating effective current IC at UC ≤ 5 µA
Ground conductor current IPE ≤ 2 µA
Nominal discharge surge current In (8/20) µs (Core-Earth) 5 kA
Total surge current (8/20) µs 10 kA
Max. discharge surge current Imax (8/20) µs maximum (Core-
Earth) 10 kA (in total)
Nominal pulse current Ian (10/1000) µs (Core-Earth) 100 A
Lightning test current (10/350) µs, peak value limp 1 kA
Output voltage limitation at 1 kV/µs (Core-Earth) spike ≤ 260 V
Output voltage limitation at 1 kV/µs (Core-Earth) static ≤ 15 V
Residual voltage at In, (conductor-ground) ≤ 10 V
Residual voltage with Ian (10/1000)µs (conductor-ground) ≤ 10 V
Protection level UP (Core-Earth) ≤ 260 V (C2, 10 kV/5 kA, spike)
Protection level UP (Core-Earth) ≤ 10 V (C2, 10 kV/5 kA, static)
Protection level UP (Core-Earth) ≤ 260 V (C3, 7.5 kV/100 A, spike)
Protection level UP (Core-Earth) ≤ 10 V (C3, 7.5 kV/100 A, static)
Response time tA (Core-Earth) ≤ 1 ns