AApppplliiccaattiioonn
For energy management systems and
instrumentation.
FFrreeqquueennccyy
50-400 Hz.
IInnssuullaattiioonn lleevveell
0.6 kV, 10 kV BIL full wave.
CCoonnssttrruuccttiioonn
The core and windings are encased in U.L.
approved plastic.
CCoonnttiinniioouuss TThheerrmmaall CCuurrrreenntt RRaattiinngg FFaaccttoorr
1.33 at 30°C amb.,
1.0 at 55°C amb.
• Terminals are 8-32 brass studs with one
flatwasher, lockwasher and regular nut.
• Flexible leads UL 1015 105oC, CSA
Approved, #16 AWG, 24” long
• Approximate Weight: 1.5 Lbs. WINDOW SIZE
1411 - 600 2.00” X 5.50”
1411 - 601 4.50” X 4.50”
These transformers are designed for assembly to an existing electrical installation
without the need for dismantling the primary bus or cables.
PRODUCT PROFILE
CURRENT TRANSFORMER
MODELS 1411-600 & 601
SPLIT CORE
REGULATORY AGENCY APPROVALS
Manufactured to meet the requirements of
ANSI/IEEE C57.13.
Classified by U.L. in accordance with IEC 44-1
SPECIFICATIONS
Publication 1411-PP006A-EN-P – August 2005 Copyright ©2005 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
CAUTION :
Proper safety precautions must be followed during
installation by a trained electrician. Never install while
bus is energized.
The current transformer must have its secondary
terminals short circuited or the burden connected, before
energizing the primary circuit.
*
Modell 1411-600
Modell 1411-601