PRODUCT PROFILE CURRENT TRANSFORMER MODELS 1411-600 & 601 Application For energy management systems and instrumentation. SPLIT CORE Frequency 50-400 Hz. Insulation level 0.6 kV, 10 kV BIL full wave. Construction The core and windings are encased in U.L. approved plastic. Continious Thermal Current Rating Factor 1.33 at 30C amb., 1.0 at 55C amb. * Terminals are 8-32 brass studs with one flatwasher, lockwasher and regular nut. * Flexible leads UL 1015 105oC, CSA Approved, #16 AWG, 24" long * Approximate Weight: 1.5 Lbs. WINDOW SIZE 1411 - 600 2.00" X 5.50" 1411 - 601 4.50" X 4.50" These transformers are designed for assembly to an existing electrical installation without the need for dismantling the primary bus or cables. REGULATORY AGENCY APPROVALS Manufactured to meet the requirements of ANSI/IEEE C57.13. Classified by U.L. in accordance with IEC 44-1 SPECIFICATIONS CAUTION : Proper safety precautions must be followed during installation by a trained electrician. Never install while bus is energized. The current transformer must have its secondary terminals short circuited or the burden connected, before energizing the primary circuit. Modell 1411-600 Modell 1411-601 * Publication 1411-PP006A-EN-P - August 2005 Copyright (c)2005 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.