Part Number: 9421
Electronic, 8 C #22 Str TC, PVC Ins, PVC Jkt, CMG
Product Description
Electronic, 8 Conductor 22AWG (7x30) Tinned Copper, PVC Insulation, PVC Outer Jacket, CMG
Technical Specifications
Physical Characteristics (Overall)
Conductor
AWG Stranding Material No. of Conductors
22 7x30 TC - Tinned Copper 8
Conductor Count: 8
Conductor Size: 22 AWG
Insulation
Material Nominal Wall Thickness
PVC - Polyvinyl Chloride 0.011 in
Color Chart
Color
Black
White
Red
Green
Brown
Blue
Orange
Yellow
Outer Shield Material
Material
Unshielded
Outer Jacket Material
Material Nominal Diameter Nominal Wall Thickness
PVC - Polyvinyl Chloride 0.229 in 0.032 in
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR
15.6 Ohm/1000ft
Capacitance
Nom. Capacitance Conductor to Conductor
34 pF/ft
Inductance
Nominal Inductance
0.17 µH/ft
Current
Max. Recommended Current [A]
2.1 Amps per conductor @ 25°C A
Voltage
UL Description UL Voltage Rating
CMG 300 V RMS
UL AWM Style 2576 150 V RMS
Temperature Range
UL Temp Rating: 80°C (UL AWM Style 2576)
Operating Temp Range: -20°C To +80°C
Mechanical Characteristics
Bulk Cable Weight: 33 lbs/1000ft
Max Recommended Pulling Tension: 71 lbs
Min Bend Radius/Minor Axis: 2.5 in
Standards
NEC Articles: 800
NEC/(UL) Specification: CMG
CEC/C(UL) Specification: CMG
UL AWM Style: UL Style 2576 (150 V 80°C)
CSA AWM Specification: FT4
CPR Euroclass: Eca
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2003/96/EC (BFR): Yes
EU Directive 2011/65/EU (ROHS II): Yes
EU Directive 2012/19/EU (WEEE): Yes
EU Directive 2015/863/EU: Yes
EU Directive Compliance: EU Directive 2003/11/EC (BFR)
EU CE Mark: Yes
EU RoHS Compliance Date (yyyy-mm-dd): 2005-04-01
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Flammability, LS0H, Toxicity Testing
UL Flammability: UL1685 FT4 Loading
CSA Flammability: FT4
ISO/IEC Flammability: IEC 60332-1-2
UL voltage rating: 300 V RMS
Plenum/Non-Plenum
Plenum (Y/N): No
Part Number
Variants
Item # Color UPC Footnote
9421 060100 Chrome 612825244257
9421 0601000 Chrome 612825244264 C
9421 060500 Chrome 612825244271 C
9421 0605000 Chrome 612825244288
9421 060U1000 Chrome 612825244233
9421 060U500 Chrome 612825244240
Footnote: C - CRATE REEL PUT-UP.
History
Update and Revision: Revision Number: 0.276 Revision Date: 07-11-2019
© 2019 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without
notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages
(including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief
at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product
Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and
regulations based on their individual usage of the product.