V10
2
INPUT SPECIFICATIONS:
Voltage …....………....…..............…………………..……………… 90~264Vac
Frequency ………………………………..………………………..... 47 to 63Hz
Inrush Current ……………………… Cold Start @25℃ 100A max. @240Vac
Conducted EMI …………………………..……………… CISPR/FCC Class B
Isolation ……………………………………………… Input to output = 4k Vac
Leakage Current …………………………………………………… 0.1mA max.
OUTPUT SPECIFICATIONS:
Hold-up Time ………………………………………......… 16ms typ. @115Vac
Short Circuit Protection …………….....……….. Hiccup Mode (Auto Recover)
Over Voltage Protection …………….…...……..... TVS Component to Clamp
Temperature Coefficient …………………….................................. ±0.05%/℃
GENERAL SPECIFICATIONS:
SAFETY AND EMC:
Operating Temperature ............................... -20 ~ 60℃ (see derating curve)
Emission and lmmunity ………… EN55011, EN60601-1-2, EN61000-3-2
Storage Temperature …………………………...….......……........-20 ~ 85℃
EN61000-3-3
Humidity …………………..….......………........ 93% RH max. Non condensing
Safety
(Medical 3
)
……………………………………… IEC60601-1, EN60601-1
Cooling ………………………………….…………………… Natural Convection
UL ANSI/AAMI ES60601-1
Switching Frequency ……………………….…………………… 70KHz Typical
NOTE:
MTBF ……… MIL-HDBK-217F, GB, at 25℃/115VAC ………. 150Khrs min.
1. Voltage setpoint at 60% full load.
Altitude ………………………………………….………………………… 3000m
2. Add a 0.1uF ceramic capacitor and a 10uF E.L. capacitor to output for
Dimensions …….……. 5.591x2.283x1.457 inches (142.00x58.00x37.00mm)
Ripple & Noise measuring @20MHz BW.
Weight …………………... ……………………………………………………485g
3. Line regulation measured from 100Vac to 240Vac, full load.
AC Inlet ………………………………. …………………… …………
4. Load regulation measured from 60% to 100% full load and from 60%
to 20% load (60% +/- 40% full load)
5. Typical efficiency with 230 VAC and max. load at 25°C.
Typical at 25˚C, nominal line and 75% load, unless otherwise Specified