https://www.phoenixcontact.com/us/products/2700487
09/03/2014Page1/4
base unit-NLC-055-100A-08I-04QRA-05A-2700487
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
100...240VAC Nanoline base unit. Equipped with 8 digital inputs and 4 relay output channels. Additional I/O
channels can be added using a maximum of three I/O extension modules. Optional communication modules
provide network or serial connectivity. Optional Operator Panel provides user interface. Programming is via
nanoNavigator.
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 360.0 GRM
Custom tariff number 85371099
Country of origin India
Technical data
Dimensions
Width 80.5 mm
Height 103.5 mm
Depth 60 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 90 %
Supply
Power supply connection Screw connection
Supply voltage 240 V AC (Power available to the I/O and Communications modules)
Max. current consumption 70 mA (at 110 V AC)
Typical current consumption 50 mA (at 230 V AC)
Software interfaces
https://www.phoenixcontact.com/us/products/2700487
09/03/2014Page2/4
base unit-NLC-055-100A-08I-04QRA-05A-2700487
Technical data
Software interfaces
Programming tool nanoNavigator 3 or above
Digital inputs
Input name Digital inputs
Description of the input EN 61131-2 type 1 NPN/PNP
Connection method Screw connection
Number of inputs 8
Typical response time 20 ms (on)
Input voltage range "0" signal 0 V ... 25 V
Input voltage range "1" signal 80 V ... 250 V
Nominal input current at UIN 0.4 mA (On: 120 V AC)
Digital outputs
Output name Relay output
Output description Relay output
Connection method Screw connection
Number of outputs 4
Protective circuit External protection required
Maximum output current per channel 5 A
Maximum output current per module / terminal block 20 A
Maximum output current per module 5 A
Nominal load, ohmic 600 W (@ 24 ohms)
General
Mounting type DIN rail
Classifications
eCl@ss
eCl@ss 4.0 27240101
eCl@ss 4.1 27240101
eCl@ss 5.0 27242216
eCl@ss 5.1 27242216
eCl@ss 6.0 27242216
eCl@ss 7.0 27242216
eCl@ss 8.0 27242216
ETIM
ETIM 3.0 EC001417
https://www.phoenixcontact.com/us/products/2700487
09/03/2014Page3/4
base unit-NLC-055-100A-08I-04QRA-05A-2700487
Classifications
ETIM
ETIM 4.0 EC001417
ETIM 5.0 EC001417
UNSPSC
UNSPSC 6.01 43172015
UNSPSC 7.0901 43201404
UNSPSC 11 43172015
UNSPSC 12.01 43201404
UNSPSC 13.2 43201404
Approvals
Approvals
Approvals
UL Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
Drawings
https://www.phoenixcontact.com/us/products/2700487
09/03/2014Page4/4
base unit-NLC-055-100A-08I-04QRA-05A-2700487
Dimensioned drawing
PWR
RUN
nanoLine
12
80,5 60
103,5
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com