UR SERIES
VOLTAGE CONTROL RELAY
UL listed CSA recognized
•AC or DC Voltage Control
•Manual or Automatic Operation
•Adjustable Threshold
•5 to 50% Hysteresis Range
•LED Relay Status Indicator
SPECIFICATIONS:
Input . . . . . . . . . . . . . . . . . . . . . . . . 24 VDC, 24, 48, 110, 220 VAC
±15%, 50/60 Hz
Power consumption . . . . . . . . . . . 24 VAC: 1 VA
48 VAC: 1.2 VA
110 VAC: 3.5 VA
220 VAC: 7 VA
Control Input Acceptance load (input)
Range Resistance Permanent Less than
AC or DC (max) 10ms peak max.
0.1 to 10 V 10 kΩ50 V 100 V
0.4 to 40 V 40 kΩ100 V 300 V
4 to 400 V 400 kΩ440 V 750 V
Hysteresis selection . . . . . . . . . . . 5 to 50% of set point
Repeat accuracy . . . . . . . . . . . . . . ±2% at a constant ambient
Output Relay . . . . . . . . . . . . . . . . . SPDT Relay
Contact material . . . . . . . . . . . . . . AgCdO
Maximum loading . . . . . . . . . . . . . 10 A AC resistive 8 A DC inductive
Maximum switching voltage . . . . . 250 VAC 250 VDC
Relay maximum power rating . . . . 2200 VA
Transient protection . . . . . . . . . . . 2500 volts 30 W
Mechanical life of relay . . . . . . . . . 30 x 106operations
Electrical life of relay . . . . . . . . . . . 2 x 105at 2400 VA resistive load
Repetition accuracy . . . . . . . . . . . ±0.5% at a constant ambient
Response time . . . . . . . . . . . . . . . . 100 ms on make
200 ms on break
Operating temperature . . . . . . . . . -4°F to +140°F -20°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . . 7 oz. (200g)
Option: 24 VDC power – the voltage and the measured current must be
from separate sources.
MOUNTING
D= DIN-rail mounting
L= 11 pin plug-in
SERIES
UR
UR SP50
D
MOUNTING
UR
SERIES
24A
INPUT POWER
INPUT POWER
24A = 24VAC
24D = 24VDC
48A = 48VAC
110A = 110VAC
220A = 220VAC
WIRING DIAGRAM:
ORDERING INFORMATION:
1. AC/DC voltage control without latching:
The output relay is energized when the voltage (AC peak voltage)
exceeds the selected threshold. It de-energizes when the voltage
falls below the hysteresis setting (5 to 50%) or when supply breaks.
The hysteresis is controlled by a potentiometer and its selection does
not change the chosen threshold.
2. AC/DC voltage control with latching:
The output relay is energized when the voltage reaches the selected
threshold and stays latched in this position. The contact between ter-
minal B1 and M (or 8 or 9) should be opened or the input power of
the device interrupted to reset.