Type: MXPRT M X Se r i e s Phase Failure, Phase Sequence and Under Voltage plus Time Delay 17.5mm DIN rail housing True R.M.S. Microprocessor based (self checking) Monitors own supply and detects an Under voltage condition on one or more phases Measures phase to phase voltages Detects incorrect phase sequence and phase loss Adjustment for under voltage trip level Adjustment for time delay (from an under voltage condition) 1 x SPDT relay output 8A Intelligent LED indication for supply and relay status * FUNCTION DIAGRAM Phases reversed L1 L2 L3 Hyst. Under trip Output Td t t tr Td time delay automatically cancelled as phase drops below 2nd trip point * INSTALLATION AND SETTING * * BEFORE INSTALLATION, ISOLATE THE SUPPLY. Installation work must be carried out by qualified personnel. Connect the unit as required. The Connection Diagram below shows a typical installation, whereby the supply to a load is being monitored by the Phase monitoring relay. If a fault should occur (i.e. fuse blowing), the relay will de-energise and assuming control of the external Contactor, de-energise the Contactor as well. Applying power. * Set the adjustments "