060816/7
LEM www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. Page 1/2
IPN = 2 .. 200A
AC Current transducer AK-B420L
A Split Core transducer for the electronic measurement AC sinusoidal
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). Jumper selectable
ranges and 4-20mA current output.
Electrical data
Primary Nominal Current Analogue Output Signal1) Type RoHS
IPN (A.t.RMS) IOUT (mA) Date Code
2,5 4-20 AK 5 B420L JULY 2006
10,20,50 4-20 AK 50 B420L MAY 2006
100,150,200 4-20 AK 200 B420L planned
Vc Supply voltage (Loop powered) 24 V DC
RLLoad resistance see power supply diagram
VbRated voltage (CAT III, PD2) 150 VAC
VdRMS Isolation voltage test, 50 Hz, 1mn 3 kV AC
fFrequency bandwith 20-100 Hz
Accuracy - Dynamic performance data
XAccuracy @ IPN, TA=25°C ± 1%
trResponse time @ 90% of IPN < 300 mS
General data
TAAmbient operating temperature (0-95% RH) -20..+50 °C
TSAmbient storage temperature -20..+85 °C
mMass 120 g
Safety IEC 61010-1
EMC EN 61326
Note : 1) For 4-20mA output model, no saturation output up to 25mA.
Features
AC sinusoïdal measurement
Average responding
Split core box
Current output
Loop powered transducers
Panel mounting
Jumper selectable ranges
Advantages
Large aperture
High isolation between primary and
secondary circuits
Easy to mount
Applications
Automation systems
Analog current reading for remote
monitoring (e.g. motor).
Data loggers
Self-powered transducer does not
drain data logger batteries.
Panel meters
Simple connection displays power
consumption.
Options on request
DIN mounting
LEM www.lem.com
Page 2/2
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. 060816/7
Dimensions AK-B420L (unit : mm, 1mm = 0.0394 inch)
Mechanical characteristics
General tolerance ± 1 mm
Primary aperture 21.7 mm sq.
Panel mounting 2 holes 4.5mm
Distance between holes 77.3 mm
Connections
2 x UNC8 Cylindric Head
Power Supply diagram
Remark
Temperature of the primary conductor should not
exceed 60°C.
25
20
10
15
5