Wind CUBEFuse
For Wind Power Generation Applications
0712 BU-SB12615 Page 1 of 2 Data Sheet 9009
Catalog Symbol: WCF_RN
Description: Finger-safe, fast-acting CUBEFuse for wind
power generation.
Electrical Characteristics: Maximum clearing time at 200%
rated current:
• 4 Minutes for 1 to 30A fuses
• 6 Minutes for 35 to 60A fuses
• 8 Minutes for 70 to 100A fuses
Agency Information:
• UL Recognized Fuse: Guide JFHR, File E56412
• cURus component certified C22.2
Other Ratings/Specifications:
Watts Loss at Rated Current: WCF15RN: 3.48W
WCF30RN: 5.45W
WCF60RN: 7.27W
WCF100RN: 11.50W
Operating and Storage Temperature Range: -40 to 90°C
Material Specifications:
• Case: Glass filled PES (Polyethersulfone)
• Terminals: Copper alloy
• Terminal plating: Electroless tin
Installation:
Fits 690V WCF holders as listed in the table
Application:
• Wind Systems:
- Transformer protection
- Pitch and speed control
- Turbine HVAC and lighting
Ratings:
Volts — 690Vac
Amps — 1-100A
IR — 50kA AC (1-60A)
IR — 30kA AC (70-100A)
Catalog Numbers (amp rating)
Non-Indicating Wind CUBEFuse
WCF1RN WCF15RN WCF35RN WCF60RN WCF100RN
WCF3RN WCF20RN WCF40RN WCF70RN
WCF6RN WCF25RN WCF45RN WCF80RN
WCF10RN WCF30RN WCF50RN WCF90RN
Amp Carton Weight Per Carton
Rating Qty. lbs kg
WCF1-30A 12 1.39 0.63
WCF35-60A 12 1.42 0.65
WCF70-100A 6 1.74 0.79
Carton Quantity and Weight
Features and Product Benefits
Maximize uptime and reliability using fuses designed and
recognized to UL 248 for low voltage fuses
Fast-acting protection specifically designed for low-fault
current conditions that occur in wind power generation
systems
Minimize chances of equipment failure and personnel injury
when using full range fuses having fast response time to
low-magnitude faults
Simplify compatibility with readily available industry
standard Class CF holders while minimizing panel space by
up to 80%
Meets all UL specified overload opening requirements
Minimizes incident energy and reduces arc flash hazards
utilizing Class J electrical characteristics
Finger-safe feature minimizes exposure to live parts,
reducing hazard to personnel
Wind CUBEFuse Holders
Catalog Numbers
(amps) Fits 690V Wind CUBEFuse Holder
Non-Indicating TCFH30NW TCFH60NW TCFH100NW
WCF1RN XX X
WCF3RN XX X
WCF6RN XX X
WCF10RN XX X
WCF15RN XX X
WCF20RN XX X
WCF25RN XX X
WCF30RN XX X
WCF35RN XX
WCF40RN XX
WCF50RN XX
WCF60RN XX
WCF70RN X
WCF80RN X
WCF90RN X
WCF100RN X
0712 BU-SB12615 Page 2 of 2 Data Sheet 9009
WCF_RN Dimensions in (mm)
Time-Current Characteristic Curves–Average Melt
Current Limitation Curves
100A
60A
10A
15A
20A
30A
40A
50A
1A
3A
6A
0.01
0.1
1
10
100
1000
1
10
100
1,000
10,000
TIME IN SECONDS
CURRENT IN AMPS
30A
60A
15A
100A
40A
50A
1,000
10,000
100,000
INSTANTANEOUS PEAK LET THRU CURRENT IN AMPSPS
PROSPECTIVE SHORT-CIRCUIT CURRENT SYMMETRICAL RMS AMPS
B
300,000
A
Fuse Dimensions - in (mm)
Amps ABCDEFG
1-15 1.88 0.75 1.00 0.23 0.04 0.63 0.28
(47.75) (19.05) (25.40) (5.84) (1.02) (15.93) (7.11)
20 1.88 0.75) 1.00 0.31 0.04 0.63 0.28
(47.75) (19.05) (25.40) (7.87) (1.02) (15.93) (7.11)
25-30 1.88 0.75 1.00 0.31 0.04 0.63 0.28
(47.75) (19.05) (25.40) (7.87) (1.02) (15.93) (7.11)
35-40 2.13 1.00 1.13 0.36 0.04 0.63 0.38
(54.10) (25.40) (28.58) (9.10) (1.02) (15.93) (9.65)
45-50 2.13 1.00 1.13 0.44 0.04 0.63 0.38
(54.10) (25.40) (28.58) (11.13) (1.02) (15.93) (9.65)
60 2.13 1.00 1.13 0.44 0.04 0.63 0.38
(54.10) (25.40) (28.58) (11.13) (1.02) (15.93) (9.65)
70 3.01 1.00 1.26 0.49 0.06 0.58 0.38
(76.45) (25.40) (32.00) (12.45) (1.60) (14.78) (9.65)
80-90 3.01 1.00 1.26 0.49 0.06 0.58 0.38
(76.45) (25.40) (32.00) (12.45) (1.60) (14.78) (9.65)
100 3.01 1.00 1.26 0.57 0.06 0.58 0.38
(76.45) (25.40) (32.00) (14.48) (1.60) (14.78) (9.65)
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of
this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical informa-
tion that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of
any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
All 690V 100, 60 and 30A Wind CUBEFuse holders can be
dovetail together for the required number of poles.
Wind CUBEFuse Holders
Catalog Amp
Numbers Range
TCFH30NW 1-30
TCFH60NW 1-60
TCFH100NW 1-100
690V Fuse Holder Catalog Numbers
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Cooper Bussmann:
TCFH100NW TCFH30NW TCFH60NW WCF100RN WCF10RN WCF15RN WCF1RN WCF20RN WCF25RN
WCF35RN WCF3RN WCF40RN WCF45RN WCF50RN WCF60RN WCF6RN WCF70RN WCF80RN WCF90RN