Pluggable Module - Optocoupler 1/1 Front-entry , DC 5 V Data sheet 1 + A1 + A2 A2 - 3 2 - Item-No. Description Optocoupler, input DC 5 V, output DC 24 V, positive switching * Installation on terminal block for pluggable module. 286-752/002-000 RL Pack.-unit pcs 1 Technical Data Input nominal voltage UN Input voltage range Input current range Current at UN DC 5 V DC 2-6.25 V 3.3-18.5 mA 14 mA Output nominal voltage Output voltage range Max. permissible continuous current DC 24 V DC 20-30 V 500 mA Reverse voltage Transistor/triac DC 80 V Switch on/switch off time <5 s / <10 s Max. frequency 25 kHz Leakage current at UN 2.5 A Collector/emitter voltage drop UCE sat 1.2 V Max.output (reverse current) 12 mA Test voltage input/output 2.5 kVrms Nominal voltage acc. to VDE 0110 / 1.89 250 V / 4 kV / 3 Ambient operating temperature -25 C...+40 C Storage temperature -40 C...+70 C Module dimensions (W x H) (15 x 82,5*) mm / (0.591 x 3.25*) in * from upper edge of DIN 35 rail Standards / prescriptions Accessories Terminal block Dimensions (W x D) WAGO Kontakttechnik GmbH & Co. KG Subject to design changes 12.06.2007 / d475200e.doc Postfach 2880 * D-32385 Minden Hansastr. 27 * D-32423 Minden Tel.: Fax.: IEC 664/ IEC 664A/ DIN VDE 0110 Pollution degree 2 Overvoltage category III 280-609 (17 x 73) mm / (0.669 x 2.874) in 05 71 / 8 87-0 E-Mail: 05 71 / 8 87-169 Web: info@wago.com http://www.wago.com