Surge protection device-CN-UB/E-BB-2817686
Technical data
General
Design Attachment plug
Direction of action Line-Shield/Earth Ground
Protective circuit
IEC test classification C2
C3
D1
VDE requirement class C2
C3
D1
Maximum continuous operating voltage UC180 V DC
130 V AC
Maximum continuous voltage UC (wire-ground) 180 V DC
130 V AC
Nominal current IN5 A (25 °C)
Operating effective current IC at UC≤ 1 µA
Residual current IPE ≤ 2 µA
Nominal discharge current In (8/20) µs (Core-Earth) 5 kA
Nominal discharge current In (8/20) µs (Core-Shield) 5 kA
Nominal discharge current In (8/20) µs (Shield-Earth) 5 kA
Total surge current (8/20) µs 10 kA
Nominal pulse current Ian (10/1000) µs (Core-Earth) 100 A
Output voltage limitation at 1 kV/µs (Core-Earth) spike ≤ 470 V
Output voltage limitation at 1 kV/µs (Core-Shield) spike ≤ 590 V
Output voltage limitation at 1 kV/µs (Shield-Earth) spike ≤ 470 V
Output voltage limitation at 1 kV/µs (Core-Earth) static ≤ 470 V
≤ 33 V
Output voltage limitation at 1 kV/µs (Shield-Earth) static ≤ 33 V
Residual voltage at In, (conductor-ground) ≤ 160 V (1.5 m cable)
Residual voltage at In, (conductor-shield) ≤ 55 V
Residual voltage at In, (shield-ground) ≤ 160 V (1.5 m cable)
Voltage protection level UP (Core-Earth) ≤ 500 V (C2, 10 kV/5 kA)
Voltage protection level UP (Core-Shield) ≤ 700 V (C2, 10 kV/5 kA)
Voltage protection level UP (Shield-Earth) ≤ 500 V (C2, 10 kV/5 kA)
Response time tA (Core-Earth) ≤ 100 ns
Response time tA (Core-GND) ≤ 100 ns
Response time tA (Shield-Earth) ≤ 100 ns