http://www.tracopower.com Page 3
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
General Specifications
Temperature ranges – Operating (ambient temp.) – 25 °C…+70 °C max.
– Derating above 50 °C 2% /°C
– Storage (non operating) – 25 °C…+85 °C
Humidity (non condensing) 95 % rel H max.
Temperature coef ficient 0.02 % / °C
Switching frequency 80 kHz typ. (Pulswidth modulation)
Efficiency – TIS 75 ... TIS 300 85 % typ.
– TIS 500 90 % typ.
– TIS 600 88 % typ.
Isolation according to EN 60950, UL 1950, UL 508C
Reliability, calculated MTBF (MIL-HDBK-217 E) – TIS 75 /150 450000 h @ +25°C/ 420000 h @ +25°C
– TIS 300 /500 360000 h @ +25°C/ 340000 h @ +25°C
– TIS 600 300000 h @ +25°C
Safety standards IEC 60950, EN 60950 (SELV),
UL/cUL 1950, UL 508C
Safety approvals UL/cUL 1950 recognized, File E18138
UL/cUL 508C listed, File E210002
UL/cuL 1604 listed, File E213613
(Class I,Division
2, Groups A, B, C and D hazardous locations)
CB-Scheme
Electromagnetic compatibility (EMC), Emissions EN 50081-1 / EN 50081-2
– Conducted RI suppression on input EN 55011 class B, EN 55022 class B,
FCC part 15, level B
– Radiated RI suppression EN 55011 class A, EN 55022 class A,
FCC part 15, level A
Electromagnetic compatibility (EMC), Immunity EN 50082-2
– Electrostatic discharge (ESD) IEC / EN 61000-4-2 4 kV / 8 kV
– Radiated RF field immunity IEC / EN 61000-4-3 10 V / m
– Electrical fast transient / burst immunity IEC / EN 61000-4-4 2 kV
– Surge immunity IEC / EN 61000-4-5 2 kV / 4 kV
– Immunity to conducted RF disturbances IEC / EN 61000-4-6 10 V
– Power frequency field immunity IEC / EN 61000-4-8 30 A / m
Safety class Degree of Protection 1 (IEC 536)
Case protection IP 20 (IEC 529)
Environment – Vibration IEC 60068-2-6,1 gn, 200 sweeps, each axis
– Shock IEC 60068-2-27, 15 gn, 11 ms, each axis
Enclosure material Aluminium (chassis) / stainless steel (cover)
Mounting (snap-on with selflocking spring) for 35 mm DIN-rails as per EN 50022
Connection Plugable screw terminals (plugs included)
(TIS 600: screw terminal blocks)
Industrial Power Supplies
TIS Series 75-600 Watt