Weidmuller, Canada
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (877) 300-5635
Email: info1@weidmuller.ca
Website: www.weidmuller.ca
Weidmuller, Mexico
Blvd. Hermanos Serdán 698,
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: clientes@weidmuller.com.mx
Website: www.weidmuller.com.mx
Weidmuller, United States
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: info@weidmuller.com
Website: www.weidmuller.com
Compared to traditional fuse installation, the UL489/CSA C22.2
No.5-02, UL1077/CSA C22.2 No.235 compliant circuit breakers
listed here assist with the complex task of selecting correct types
and characteristics and offer a less bulky installation solution.
Ourrange of miniature, molded-case circuit breakers, in combination
with our accessories for factory or on-site installation, offer enhanced
control and monitoring capabilities. Installation kits include all parts
and instructions to make the on-site job easy.
We supply UL489/CSA C22.2 No.5-02 and UL1077/CSA C22.2
No.235 compliant 1, 2 and 3-pole-type circuit breakers from 0.5 to
60 Ampere and with type C and D characteristics.
Attachments such as neutral switches, auxiliary contacts and shunt
trips are also available for this system. All accessories for modern
busbar installations are available in compliance with the relevant
UL standards.
Datasheet
BR & SU Series
UL489/CSA C22.2 No.5-02 (Branch rated) Circuit Breakers
UL1077/CSA C22.2 No.235 Supplementary Protectors
NEW
2
Branch Circuit Breakers
Application Schematic
Sizing of main branch circuit protector according
to table 430.52 in NEC®
Dual Element (Time Delay) Fuse
Maximum fuse = largest motor FLA x 175 %
+ FLA of all other motors and general loads in group
Inverse Time Breaker
Maximum circuit breaker = largest motor FLA x 250 %
+ FLA of all other motors and general loads in group
(for other fuse/breaker types see table 430.52)
Power Circuit
Outlet
Power Circuit
Power
Transformer
Control Circuit
Control Transformer
Power
Transformer
UL1077
UL1077
UL1077
Fixed mounted
cabinet /panel heater
(resistive loads)
UL489
UL489
UL489
UL489
UL489
UL489
M M
UL489
UL489
3
Branch Circuit Breakers
Branch Circuit Breakers
AC Version, C and D Characteristics
Single Pole - D Curve Single Pole - C Curve
Current Ratings
(amps) Part No. Description Part No. Description
0.5 BR1D05AC Branch / 1P Cct Brkr / D Curve / 0.5A BR1C05AC Branch / 1P Cct Brkr / C Curve / 0.5A
1BR1D1AC Branch / 1P Cct Brkr / D Curve / 1A BR1C1AC Branch / 1P Cct Brkr / C Curve / 1A
2BR1D2AC Branch / 1P Cct Brkr / D Curve / 2A BR1C2AC Branch / 1P Cct Brkr / C Curve / 2A
3BR1D3AC Branch / 1P Cct Brkr / D Curve / 3A BR1C3AC Branch / 1P Cct Brkr / C Curve / 3A
5BR1D5AC Branch / 1P Cct Brkr / D Curve / 5A BR1C5AC Branch / 1P Cct Brkr / C Curve / 5A
10 BR1D10AC Branch / 1P Cct Brkr / D Curve / 10A BR1C10AC Branch / 1P Cct Brkr / C Curve / 10A
15 BR1D15AC Branch / 1P Cct Brkr / D Curve / 15A BR1C15AC Branch / 1P Cct Brkr / C Curve / 15A
20 BR1D20AC Branch / 1P Cct Brkr / D Curve / 20A BR1C20AC Branch / 1P Cct Brkr / C Curve / 20A
25 BR1D25AC Branch / 1P Cct Brkr / D Curve / 25A BR1C25AC Branch / 1P Cct Brkr / C Curve / 25A
30 BR1D30AC Branch / 1P Cct Brkr / D Curve / 30A BR1C30AC Branch / 1P Cct Brkr / C Curve / 30A
40 BR1D40AC Branch / 1P Cct Brkr / D Curve / 40A BR1C40AC Branch / 1P Cct Brkr / C Curve / 40A
50 BR1D50AC Branch / 1P Cct Brkr / D Curve / 50A BR1C50AC Branch / 1P Cct Brkr / C Curve / 50A
60 BR1D60AC Branch / 1P Cct Brkr / D Curve / 60A BR1C60AC Branch / 1P Cct Brkr / C Curve / 60A
Double Pole - D Curve Double Pole - C Curve
Current Ratings
(amps) Part No. Description Part No. Description
0.5 BR2D05AC Branch / 2P Cct Brkr / D Curve / 0.5A BR2C05AC Branch / 2P Cct Brkr / C Curve / 0.5A
1BR2D1AC Branch / 2P Cct Brkr / D Curve / 1A BR2C1AC Branch / 2P Cct Brkr / C Curve / 1A
2BR2D2AC Branch / 2P Cct Brkr / D Curve / 2A BR2C2AC Branch / 2P Cct Brkr / C Curve / 2A
5BR2D5AC Branch / 2P Cct Brkr / D Curve / 5A BR2C5AC Branch / 2P Cct Brkr / C Curve / 5A
10 BR2D10AC Branch / 2P Cct Brkr / D Curve / 10A BR2C10AC Branch / 2P Cct Brkr / C Curve / 10A
15 BR2D15AC Branch / 2P Cct Brkr / D Curve / 15A BR2C15AC Branch / 2P Cct Brkr / C Curve / 15A
20 BR2D20AC Branch / 2P Cct Brkr / D Curve / 20A BR2C20AC Branch / 2P Cct Brkr / C Curve / 20A
25 BR2D25AC Branch / 2P Cct Brkr / D Curve / 25A BR2C25AC Branch / 2P Cct Brkr / C Curve / 25A
30 BR2D30AC Branch / 2P Cct Brkr / D Curve / 30A BR2C30AC Branch / 2P Cct Brkr / C Curve / 30A
40 BR2D40AC Branch / 2P Cct Brkr / D Curve / 40A BR2C40AC Branch / 2P Cct Brkr / C Curve / 40A
50 BR2D50AC Branch / 2P Cct Brkr / D Curve / 50A BR2C50AC Branch / 2P Cct Brkr / C Curve / 50A
60 BR2D60AC Branch / 2P Cct Brkr / D Curve / 60A BR2C60AC Branch / 2P Cct Brkr / C Curve / 60A
Triple Pole - D Curve Triple Pole - C Curve
Current Ratings
(amps) Part No. Description Part No. Description
1BR3D1AC Branch / 3P Cct Brkr / D Curve / 1A BR3C1AC Branch / 3P Cct Brkr / C Curve / 1A
2BR3D2AC Branch / 3P Cct Brkr / D Curve / 2A BR3C2AC Branch / 3P Cct Brkr / C Curve / 2A
5BR3D5AC Branch / 3P Cct Brkr / D Curve / 5A BR3C5AC Branch / 3P Cct Brkr / C Curve / 5A
10 BR3D10AC Branch / 3P Cct Brkr / D Curve / 10A BR3C10AC Branch / 3P Cct Brkr / C Curve / 10A
15 BR3D15AC Branch / 3P Cct Brkr / D Curve / 15A BR3C15AC Branch / 3P Cct Brkr / C Curve / 15A
20 BR3D20AC Branch / 3P Cct Brkr / D Curve / 20A BR3C20AC Branch / 3P Cct Brkr / C Curve / 20A
25 BR3D25AC Branch / 3P Cct Brkr / D Curve / 25A BR3C25AC Branch / 3P Cct Brkr / C Curve / 25A
30 BR3D30AC Branch / 3P Cct Brkr / D Curve / 30A BR3C30AC Branch / 3P Cct Brkr / C Curve / 30A
40 BR3D40AC Branch / 3P Cct Brkr / D Curve / 40A BR3C40AC Branch / 3P Cct Brkr / C Curve / 40A
50 BR3D50AC Branch / 3P Cct Brkr / D Curve / 50A BR3C50AC Branch / 3P Cct Brkr / C Curve / 50A
60 BR3D60AC Branch / 3P Cct Brkr / D Curve / 60A BR3C60AC Branch / 3P Cct Brkr / C Curve / 60A
4
Branch Circuit Breakers
Accessories for Branch Circuit Breakers
Standards UL489 and CSA C22.2 No. 5-02
Rated operating currents
10 A /240 V AC
3 A / 110 V DC
1 A / 220 V DC
Minimum contact load 1 mA at 24 V DC
Conductor cross sections
Type of conductor *) min. max.
Single wire 1.0 mm2 (AWG18) 2.5 mm2 (AWG14)
Stranded wire 1.0 mm2 (AWG18) 1.5 mm2 (AWG16)
Stranded wire with ferrule 1.0 mm2 (AWG18) 1.5 mm2 (AWG16)
Torque max. 0.8 Nm (7 lb.in)
*) Stripped length 8 - 9 mm ( ) values in brackets = measurement units for North America
Lock-off/Lock-on device
Weight
g/Each
Packing
Unit
Part
No.
2 10 LD10
Module Type of Contact Contacts Weight
g / Each
Packing
Unit Part No.
Auxiliary contact, for mounting on the right
½ 1 auxiliary contact 1NO 35 6 BAU10
½ 2 auxiliary contacts 1NO + 1NC 40 6 BAU11
BAU10
14
13
BAU11
23
24 12
11
5
Branch Circuit Breakers
Accessories for Branch Circuit Breakers
Mounting Instructions of Accessories
Applies to BNS... and BST:
The accessory devices BNS... and BST can be installed onthe
right or left.
Mounting
1. Bring the blue knobs of all devices into the “OFF” position
2. Remove grey cover from the switching device and
attachment
3. Insert drive plate between the switching device and BNS...
or BST
4. Insert connecting pin into the knob (insertion depth
approx. 7 mm)
5. Combine switching device and BNS... or BST
6. Screw the devices together (observe correct screw length)
Applies to BAU...
The auxiliary contact BAU... can only be installed
on the right.
Installation
1. Flick the blue switches of all devices to the “OFF” position
2. Remove the grey cover from the switching device and
attachment
3. Combine switching device and BAU...
4. Insert connection screws and connect the two devices by
turning the screws 90°
5. After installation, close and open to check correct operation
Applies to all switching devices
BNS..., BST and BAU...
The load and mains can be connected into either the top or
bottom (Line/Load Reversible).
Design of the terminals
Optical detection of screw position
Increased breaking resistance if the screwdriver becomes
jammed
Universal connecting terminals, suitable for connecting all
known cable lugs such as ring or forked cable lugs and pin
terminals
Ring cable lugs can be connected by opening the flap and
removing the connecting screw
Can also be used for applications that require ring cable
lugs (e.g. nuclear power stations)
DIN EN 50274, VDE 0660-514 compliant protection
against contact with live parts is fully guaranteed
Neutral switch/
Shunt trip
Neutral switch/
Shunt trip
Auxiliary
contact
Switching
device
Auxiliary
contact
Switching
device
1. Box terminal for solid
conductors flexible
conductors with or
without cable lug
2. Screw terminal for
forked cable lug
3. Screw terminal for ring
cable lug (ring tongue)
Mounting
screw 34 mm
(see accessories
page 6)
6
Branch Circuit Breakers
Busbar and Accessories for Branch Circuit Breakers (UL489/CSA C22.2 No.5-02)
Packing
Unit Part No.
10 pieces MS34
Packing
Unit Part No.
100 pieces TPC
Mounting screw 34 mm
to connect the auxiliary contact
and shunt trip or neutral switch
to the switching devices
Touch-protection caps
to cover the connecting screws
on the switching devices, neutral
switches and shunt trips for
increased touch protection
Description Part No.
Busbar/Branch Protection/1ph/6Poles BB106
Busbar/Branch Protection/1ph/12Poles BB112
Busbar/Branch Protection/1ph/18Poles BB118
Busbar/Branch Protection/1ph/12Poles BB206
Busbar/Branch Protection/2ph/12Poles BB212
Busbar/Branch Protection/2ph/18Poles BB218
Busbar/Branch Protection/3ph/6Poles BB306
Busbar/Branch Protection/3ph/12Poles BB312
Busbar/Branch Protection/3ph/18Poles BB318
PwrFeed Term - 35mm² BPF35
PwrFeed Term - 50mm² BPF50
Touch Protection 3Caps BTPC100
Criteria:
for MCBs according to UL489
available in 1-3 phase types
addable system
Designed for a load up to 115A
suitable accessories as connection terminals and contact protection
Busbars may not be shortened
BTPC100
BPF35
BPF50
7
Branch Circuit Breakers
Characteristic * C D
Application
Lighting
Wiring protection
Control circuits
Business equipment
Appliances
Motors low inrush
Transformers
Power supplies
Heaters
Motors high inrush
Reactive load
Number of poles 1 - 3; 1 + N; 3 + N
Standards UL489 and CSA-22.2 Nr. 5-09
Interrupting capacity 10 kA
Back-up fuse ≤ 10 kA interrupting capacity none
Rated voltage AC 50/60 Hz 0.3 - 32 A 277 / 480 V
Rated voltage AC 50/60 Hz 40 - 63 A 240 V
Rated current range 0.5 - 60 A 0.5 - 60 A
Thermal not tripping
I1 (A) > 1 h 1.05 x In1.05 x In
Thermal tripping
I2 (A) < 1 h 1.35 x In1.35 x In
Electromagnetic not tripping
I4 (A) > 0.1 s 5 x In10 x In
Electromagnetic tripping
I5 (A) < 0.1 s 10 x In16 x In
Reference calibration temperature
of the thermal tripping
40 °C
Influence of the ambient temperature on the thermal release: Decrease of
the current values with higher ambient temperature and increase with lower
temperatures of approximately 5 % per 10 °C difference in temperature
Frequency range of the
electromagnetic trip
16 ⅔ to 60 Hz
With higher frequencies, the electromagnetic tripping values increase by
approximately a factor of 1.1 at 100 Hz; 1.2 at 200 Hz; 1.3 at 300 Hz; 1.4 at 400
Hz; 1.5 for DC
Ambient temperature -25 °C to +55 °C
Storage temperature -40 °C to +70 °C
Device depth according to DIN 43880 68 mm
Mechanical life 10,000 switching cycles (ON / OFF)
Protection cover Finger safe and safe to back of hand according to DIN EN 50274, VDE 0660-514
Degree of protection acc. EN / IEC 60529 IP20
Installation position any
Mounting DIN-rail according to DIN EN 60715 35 mm
Lockability The handle can be secured against manual switching in the on and off position
by a lead seal
Climatic resistance Humid heat constant according to DIN EN 60068-2-78
Humid heat cycle according to DIN EN 60068-2-30
Vibration resistance > 15 g according to DIN EN 60068-2-59 during a load with I1
Resistance to mechanical shocks 25 g 11 ms
Approvals - BR... items cULus marking, UL file E359964, ref standards UL489 and
CAN/CSA-C22.2 No. 5 (2002)
Approvals - BAU..., BNS..., BST... items cULus marking, UL file E362204, ref standards UL489 and
CAN/CSA-C22.2 No. 5 (2002)
Approvals - BB..., BPF..., BTPC... items pending
Technical Data for Branch Circuit Breakers (AC)
Test currents
* Other switching devices in B and Z characteristics available on request
Interrupting capacity acc. to IEC 60947-2, DIN EN 60947-2
Characteristic * C, D
1pole 0.5 - 60 A 240 V 15 kA
2pole / 3pole 0.5 - 60 A 415 V 15 kA
2pole / 3pole 40 - 60 A 415 V 10 kA
8
Branch Circuit Breakers
Conductor Cross Sections
Box Terminal Bottom Box Terminal Top
Type of conductor *) max. min. max. min.
Single wire 35 mm2 (AWG2) 1.0 mm2 (AWG18) 25 mm2 (AWG3) 1.0 mm2 (AWG18)
Multiple wire 35 mm2 (AWG2) 16 mm2 (AWG6) 25 mm2 (AWG3) 16 mm2 (AWG6)
Stranded wire 25 mm2 (AWG3) 1.0 mm2 (AWG18) 16 mm2 (AWG6) 1.0 mm2 (AWG18)
Stranded wire
with ferrule 16 mm2 (AWG6) 1.0 mm2 (AWG18) 16 mm2 (AWG6) 1.0 mm2 (AWG18)
Busbar cable lug up to 3 mm thickness up to 1.5 mm thickness
Combined,
conductor and
busbar or
cable lug
up to 35 mm2 and
up to 2 mm thickness not possible
Torque max. 2.5 Nm (22.2 lb.in)
Technical Data for Branch Circuit Breakers
*) Stripped lengths: 12 - 14 mm at the bottom, 10 - 12 mm at the top
( ) values in brackets = measurement units for North America Copper conductor with sheath insulation for 60/75 °C
Internal Resistance for Product Range BR
Rated Current
[A]
Trip Characteristic
C [Ohm] D [Ohm]
0.3 16.8620 16.8620
0.5 6.8540 6.0009
1.0 1.7000 1.7560
1.6 0.5870 0.5870
2.0 0.4190 0.4190
3.0 0.2020 0.2020
4.0 0.1090 0.1090
5.0 0.0654 0.0654
6.0 0.0528 0.0491
8.0 0.0278 0.0240
10 0.0216 0.0187
12 0.0084 0.0085
13 0.0084 0.0085
15/16 0.0085 0.0076
20 0.0067 0.0064
25 0.0050 0.0041
30/32 0.0032 0.0027
40 0.0025 0.0022
50 0.0019 0.0018
60 0.0018 0.0017
Dimension drawings product range BR
1-pole 2-pole 3-pole
9
Branch Circuit Breakers
Curves for Branch Circuit Breakers
10-3
4x10-3
10-2
4x10-2
10-1
0,4
1
4
10
1
4
10
40
60
N
123456 8102040 10016
Product Range BR
Minutes
Seconds
Tripping
time t
Multiple of rated current
C and D characteristic AC ln = 0.5 - 10 A
BR models
CD
10-3
4x10-3
10-2
4x10-2
10-1
0,4
1
4
10
1
4
10
40
60
N
123456 8102040 10016
Product Range BR
Tripping
time t
Minutes
Seconds
Multiple of rated current
C and D characteristic AC ln = 12 - 60 A
BR models
DC
AC
1.05-1.35xl 1.05-1.35xl
10
Supplementary Circuit Breakers
Supplementary Circuit Breakers
Our range of UL1077/CSA C22.2 No.235 supplementary
protectors can be used where additional
protection is required in control circuits. Combined with the accessories
it also offers enhanced
monitoring
and control capabilities.
Single Pole - D Curve Single Pole - C Curve
Current Ratings
(amps) Part No. Description Part No. Description
0.5 SU1D05AC Suppl / 1P Cct Brkr / D Curve / 0.5A SU1C05AC Suppl / 1P Cct Brkr / C Curve / 0.5A
1SU1D1AC Suppl / 1P Cct Brkr / D Curve / 1A SU1C1AC Suppl / 1P Cct Brkr / C Curve / 1A
2SU1D2AC Suppl / 1P Cct Brkr / D Curve / 2A SU1C2AC Suppl / 1P Cct Brkr / C Curve / 2A
3SU1D3AC Suppl / 1P Cct Brkr / D Curve / 3A SU1C3AC Suppl / 1P Cct Brkr / C Curve / 3A
5SU1D5AC Suppl / 1P Cct Brkr / D Curve / 5A SU1C5AC Suppl / 1P Cct Brkr / C Curve / 5A
10 SU1D10AC Suppl / 1P Cct Brkr / D Curve / 10A SU1C10AC Suppl / 1P Cct Brkr / C Curve / 10A
15 SU1D15AC Suppl / 1P Cct Brkr / D Curve / 15A SU1C15AC Suppl / 1P Cct Brkr / C Curve / 15A
20 SU1D20AC Suppl / 1P Cct Brkr / D Curve / 20A SU1C20AC Suppl / 1P Cct Brkr / C Curve / 20A
25 SU1D25AC Suppl / 1P Cct Brkr / D Curve / 25A SU1C25AC Suppl / 1P Cct Brkr / C Curve / 25A
30 SU1D30AC Suppl / 1P Cct Brkr / D Curve / 30A SU1C30AC Suppl / 1P Cct Brkr / C Curve / 30A
40 SU1D40AC Suppl / 1P Cct Brkr / D Curve / 40A SU1C40AC Suppl / 1P Cct Brkr / C Curve / 40A
50 SU1D50AC Suppl / 1P Cct Brkr / D Curve / 50A SU1C50AC Suppl / 1P Cct Brkr / C Curve / 50A
60 SU1D60AC Suppl / 1P Cct Brkr / D Curve / 60A SU1C60AC Suppl / 1P Cct Brkr / C Curve / 60A
Double Pole - D Curve Double Pole - C Curve
Current Ratings
(amps) Part No. Description Part No. Description
0.5 SU2D05AC Suppl / 2P Cct Brkr / D Curve / 0.5A SU2C05AC Suppl / 2P Cct Brkr / C Curve / 0.5A
1SU2D1AC Suppl / 2P Cct Brkr / D Curve / 1A SU2C1AC Suppl / 2P Cct Brkr / C Curve / 1A
2SU2D2AC Suppl / 2P Cct Brkr / D Curve / 2A SU2C2AC Suppl / 2P Cct Brkr / C Curve / 2A
5SU2D5AC Suppl / 2P Cct Brkr / D Curve / 5A SU2C5AC Suppl / 2P Cct Brkr / C Curve / 5A
10 SU2D10AC Suppl / 2P Cct Brkr / D Curve / 10A SU2C10AC Suppl / 2P Cct Brkr / C Curve / 10A
15 SU2D15AC Suppl / 2P Cct Brkr / D Curve / 15A SU2C15AC Suppl / 2P Cct Brkr / C Curve / 15A
20 SU2D20AC Suppl / 2P Cct Brkr / D Curve / 20A SU2C20AC Suppl / 2P Cct Brkr / C Curve / 20A
25 SU2D25AC Suppl / 2P Cct Brkr / D Curve / 25A SU2C25AC Suppl / 2P Cct Brkr / C Curve / 25A
30 SU2D30AC Suppl / 2P Cct Brkr / D Curve / 30A SU2C30AC Suppl / 2P Cct Brkr / C Curve / 30A
40 SU2D40AC Suppl / 2P Cct Brkr / D Curve / 40A SU2C40AC Suppl / 2P Cct Brkr / C Curve / 40A
50 SU2D50AC Suppl / 2P Cct Brkr / D Curve / 50A SU2C50AC Suppl / 2P Cct Brkr / C Curve / 50A
60 SU2D60AC Suppl / 2P Cct Brkr / D Curve / 60A SU2C60AC Suppl / 2P Cct Brkr / C Curve / 60A
CUS
11
Supplementary Circuit Breakers
* additional electromagnetic protection
Rated
Current
in A
Rated
Voltage
Volt AC
Weight
g / Each
Packing
Unit
Test Currents *
Electromagnetic
Part No.
Not Tripping
I4 A Tripping I5 A
Neutral switch
0.5 - 60 277/480 150 5 400 700 SNS63A
Switching Devices Supplementary Protector
Triple Pole - D Curve Triple Pole - C Curve
Current Ratings
(amps) Part No. Description Part No. Description
1SU3D1AC Suppl / 3P Cct Brkr / D Curve / 1A SU3C1AC Suppl / 3P Cct Brkr / C Curve / 1A
2SU3D2AC Suppl / 3P Cct Brkr / D Curve / 2A SU3C2AC Suppl / 3P Cct Brkr / C Curve / 2A
5SU3D5AC Suppl / 3P Cct Brkr / D Curve / 5A SU3C5AC Suppl / 3P Cct Brkr / C Curve / 5A
10 SU3D10AC Suppl / 3P Cct Brkr / D Curve / 10A SU3C10AC Suppl / 3P Cct Brkr / C Curve / 10A
15 SU3D15AC Suppl / 3P Cct Brkr / D Curve / 15A SU3C15AC Suppl / 3P Cct Brkr / C Curve / 15A
20 SU3D20AC Suppl / 3P Cct Brkr / D Curve / 20A SU3C20AC Suppl / 3P Cct Brkr / C Curve / 20A
25 SU3D25AC Suppl / 3P Cct Brkr / D Curve / 25A SU3C25AC Suppl / 3P Cct Brkr / C Curve / 25A
30 SU3D30AC Suppl / 3P Cct Brkr / D Curve / 30A SU3C30AC Suppl / 3P Cct Brkr / C Curve / 30A
40 SU3D40AC Suppl / 3P Cct Brkr / D Curve / 40A SU3C40AC Suppl / 3P Cct Brkr / C Curve / 40A
50 SU3D50AC Suppl / 3P Cct Brkr / D Curve / 50A SU3C50AC Suppl / 3P Cct Brkr / C Curve / 50A
60 SU3D60AC Suppl / 3P Cct Brkr / D Curve / 60A SU3C60AC Suppl / 3P Cct Brkr / C Curve / 60A
CUS
12
Supplementary Circuit Breakers
Accessories for Supplementary Circuit Breakers
Auxiliary contact
Module Type of Contact Contacts Part No. Weight
g / Each
Packing
Unit
½ 1 auxiliary contact 1NO SAU10 35 10
½ 2 auxiliary contacts 1NO + 1NC SAU11 40 10
Shunt trip
Module Rated Operating Voltage Max. Operating Current at
Un (t < 10 ms) Part No. Weight
g / Each
Packing
Unit
1 24 V UC 0.6 A SST24V 105 5
1 110 - 240 V UC, 415 V AC 0.25 A at 110 V SST110V 105 5
0.5 A at 240 V
0.58 A at 277 V
Lock-off/Lock-on device
Packing
Unit
Weight
g / Each
Part
No.
10 2 LD10
Standards Acc. to IEC 60947-5-1, DIN EN 60947-5-1, VDE 0660-200, UL508
Rated operating currents
10 A /240 V AC
3 A / 110 V DC
1 A / 220 V DC
Minimum contact load 1 mA at 24 V DC
Conductor cross sections
Type of conductor *) min. max.
Single wire 1.0 mm2 (AWG18) 2.5 mm2 (AWG14)
Stranded wire 1.0 mm2 (AWG18) 1.5 mm2 (AWG16)
Stranded wire with ferrule 1.0 mm2 (AWG18) 1.5 mm2 (AWG16)
Torque max. 0.8 Nm (7 lb.in)
*) Stripped length 8 - 9 mm
SAU10
14
13
SAU11
23
24 12
11
CUS
13
Accessories for
Supplementary Circuit Breakers
Mounting Instructions of Accessories
Applies to SNS63A and SAU...:
The accessory devices SNS63A and SAU... can be
installed on the right or left. The auxiliary contact H...
UM can only be installed on the right.
Mounting:
1. Flick the blue switches of all devices to the “OFF”
position
2. Remove the grey cover from the switching device
and attachment
3. Insert the drive plate between the switching
device and SNS63A and SAU...
4. Insert the connecting pin into the switch (insertion
depth approx. 7 mm)
5. Combine switching device and SNS63A and SAU...
6. Screw devices together(observe correct screw
length)
Applies to SAU...:
The auxiliary contact SAU... can only be installed on
the right.
Installation:
1. Flick the blue switches of all devices to the “OFF”
position
2. Remove the grey cover from the switching device
3. Combine switching device and SAU...
4. Insert connection screws and connect the two
devices by turning the screws by 90°
5. After installation close and open to check
operation
Applies to all switching devices
SAU..., SNS and SST...
Design of the terminals
Optical detection of screw position
Increased breaking resistance if the screwdriver
becomes jammed
Universal connecting terminals, suitable for
connecting all known cable lugs such as ring or
forked cable lugs and pin terminals
Ring cable lugs can be connected by opening the
flap and removing the connecting screw
Can also be used for applications that require ring
cable lugs (e.g. nuclear power stations)
DIN EN 50274, VDE 0660-514 compliant
protection against contact with live parts is fully
guaranteed
Neutral switch/
Shunt trip
Neutral switch/
Shunt trip
Auxiliary
contact
Switching
device
Auxiliary
contact
Switching
device
1. Box terminal for solid
conductors flexible
conductors with or
without cable lug
2. Screw terminal for
forked cable lug
3. Screw terminal for
ring cable lug (ring
tongue)
Mounting
screw 34 mm
(see accessories
page 6)
Supplementary Circuit Breakers
CUS
14
Supplementary Circuit Breakers
Description Part No.
Busbar/Supplementary Protection/1ph/6Poles SB106
Busbar/Supplementary Protection/1ph/12Poles SB112
Busbar/Supplementary Protection/Aux/1ph/37Poles SB1A37
Busbar/Supplementary Protection/2ph/12Poles SB212
Busbar/Supplementary Protection/2ph/18Poles SB218
Busbar/Supplementary Protection/Aux/2ph/38Poles SB2A38
Busbar/Supplementary Protection/3ph/12Poles SB312
Busbar/Supplementary Protection/3ph/39Poles SB339
Busbar/Supplementary Protection/Aux/3ph/48Poles SB3A48P
PwrFeed Term - 35mm² SPF35
PwrFeed Term - 50mm² SPF50
PwrFeed Term - 95mm² SPF95
Touch Protection 5Caps STPC
Endcap/1P busbars SEC1P
Endcap/multi-P busbars SECMP
SPF35
Ue1000 V AC/DC
f 50/60 Hz
Uimp
le115 A
#1-10 AWG 60°C Cu
0.56 in
All SB models
Ue1P 600 V AC 1000V DC
2/3P 600V AC
f50/60 Hz
Uimp
le18mm² / 25mm²
Infeed at the start of the busbar 80A@40 °C / 100A@30°C
Infeed at the center of the busbar 160A@40°C / 200A@30°C
SPF50
Ue1000V AC/DC
f 50/60 Hz
Uimp
le115 A
#1-14 AWG 75°C Cu
0.56 in
SPF95
Ue600V AC/DC
f50/60 Hz
Uimp
le200 A
#1-4/0 AWG 75°C Cu
1 in
Produktbild / Product picture / Photo du produit
STPC
SPF50
SECMP
Z2
Z2
1-14 AWG Copper wire
max 35Ib-in
1-10 AWG Copper wire
max 50Ib-in
1.2.
1.3.
1.1.
SPF35
Z2
1.
Z2
1-10 AWG Copper wire
max 50Ib-in
SEC1P
3
2
1
SPF95
1-4/0 AWG Copper wire
max 175 Ib-in
SPF35
Busbar and Accessories for Supplementary Circuit Breakers
(UL1077/CSA C22.2 No.235 )
General Data
CUS
15
Supplementary Circuit Breakers
Characteristic C D
Application
Lighting,Control circuits
Wiring protection,
Business equipment
Appliances
Control transformers
Power supplies
Reactive load
Number of poles 1 - 3; 1 + N; 3 + N
Standards UL1077 and CSA-22.2 No.235
Interrupting capacity see data sheet for use in the USA and Canada
Current limiting class 3
Max. back-up fuse see data sheet for use in the USA and Canada
Rated voltage AC 277 / 480 V
Rated current range 0.5 - 60 A 0.5 - 60 A
Test currents
Thermal not tripping
I1 (A) > 1 h 1.13 x In1.13 x In
Thermal tripping
I2 (A) < 1 h 1.45 x In1.45 x In
Electromagnetic not tripping
I4 (A) > 0,1 s 5 x In10 x In
Electromagnetic tripping
I5 (A) < 0,1 s 10 x In16 x In
Reference calibration temperature
of the thermal tripping
30° C + 5° C
Influence of the ambient temperature on the thermal release: Decrease of the current values
with higher ambient temperature and increase with lower temperatures of approximately
5% per 10°C difference in temperature
Frequency range of the
electromagnetic trip
16 2/3 to 60 Hz
Ambient temperature -25 °C to +55 °C
Storage temperature -40 °C to +70 °C
Device depth according to DIN 43880 68 mm
Mechanical live 10,000 cycles (ON / OFF)
Protection cover Finger safe and safe to back of hand according to DIN EN 50274/ VDE0660-514
Insulation group acc. to DIN/VDE 0110 C at 250 V AC
B at 400 V AC
Degree of protection acc. to EN/IEC 60529 IP20
Installation position any
Mounting DIN-rail according to DIN EN 60715 35 mm
Lockability The handle can be secured against manual switching in the on and off position by a lead seal
Climatic resistance Humid heat constant according to DIN EN 60068-2-78
Humid heat cycle according to DIN EN 60068-2-30
Vibration resistance > 15 g according to DIN EN 60068-2-59 during a load with I1
Resistance to mechanical shocks 25g 11ms
Approvals - SU... items cRUus marking, UL file E359481, ref standards UL1077 and CSA-C22.2 No. 235
Approvals - SAU..., SNS..., SST... items UL marking, UL file E362205, ref standards UL1077 and CSA-C22.2 No. 14
Approvals - SB..., SPF..., STPC..., SEC... items pending
Technical Data for Supplementary Circuit Breakers CUS
16
Supplementary Circuit Breakers
Conductor cross sections
Box Terminal Bottom Box Terminal Top
Type of conductor *) max. min. max. min.
Single wire 35 mm2 (AWG2) 1 mm2 (AWG18) 25 mm2 (AWG3) 1 mm2 (AWG18)
Multiple wire 35 mm2 (AWG2) 16 mm2 (AWG6) 25 mm2 (AWG3) 16 mm2 (AWG6)
Stranded wire 25 mm2 (AWG3) 1 mm2 (AWG18) 16 mm2 (AWG6) 1 mm2 (AWG18)
Stranded wire with ferrule 16 mm2 (AWG6) 1 mm2 (AWG18) 16 mm2 (AWG6) 1 mm2 (AWG18)
Busbar cable lug up to 3 mm thickness up to 1.5 mm thickness
Torque max. 2.3 Nm (20 lb.in)
Interrupting capacity and maximum back-up fuse for use in the USA and Canada
Characteristic C and D
Standards UL1077 and CSA-22.2 No.235
Number of poles
Maximum
rated voltage
[V]
Rated current
[A]
Interrupting capacity
[kA]
Maximum
back-up fuse
[A]
Interrupting capacity
at rated voltage
Ambient temperature
40 °C
1 / 1 + N 277 0.5 - 10 10 70 A
1 / 1 + N 277 12 - 60 10 4 x In
2 / 3 / 3 + N 480 0.5 - 10 10 70 A
2 / 3 / 3 + N 480 12 - 60 10 4 x In
*) Stripped length: bottom 12 - 14 mm, top 10 - 12 mm
Internal resistance for Product Range SU
Rated Current
[A]
Trip Characteristic
C
[Ohm]
D
[Ohm]
0.5 6.8540 6.0009
1.0 1.7000 1.7560
2.0 0.4190 0.4190
3.0 0.2020 0.2020
4.0 0.1090 0.1090
5.0 0.0654 0.0654
6.0 0.0528 0.0491
8.0 0.0278 0.0240
10 0.0216 0.0187
12/13 0.0084 0.0085
15/16 0.0085 0.0076
20 0.0067 0.0064
25 0.0050 0.0041
30/32 0.0032 0.0027
40 0.0025 0.0022
50 0.0019 0.0018
60 0.0018 0.0017
Technical Data for Supplementary Circuit Breakers CUS
17
Supplementary Circuit Breakers
N
123456 8102040100
10
4x10
10
4x10
10
0,4
1
4
10
1
4
10
40
60
-1
-2
-2
-3
-3
16
N
123456 8102040100
10
4x10
10
4x10
10
0,4
1
4
10
1
4
10
40
60
-1
-2
-2
-3
-3
BCBC DD
B, C and D characteristic ln = 12 - 60 A
SU models
Minutes
Minutes
Seconds
Seconds
Multiple of rated currentMultiple of rated current
B, C and D characteristic ln = 0.5 - 10 A
SU models
Dimension Drawings for SU models
1-pole 3-pole2-pole
Curves for Supplementary Circuit Breakers
1.13-1.45 x l 1.13-1.45 x l
0.4 0.4
CUS
18
Notes
19
Notes
20 Subject to technical changes · 06/13 · 2.5M · LIT1221