New Cooper Bussmann
A/C Disconnect Model
Loaded With Features &
Convenience
Simplify your installation and power disconnection process
with a series of new Cooper Bussmann Air Conditioner Disconnects.
The new fusible and non-fusible, all in one, Bussmann A/C
disconnects with integrated GFCI receptacle meets NEC®
ground fault requirements.
Disconnect With GFCI Receptacle:
• Combines two installations into one
• All GFCI units meet NEC®Ground Fault Requirements
in 210.63, 210.8, 406.8(B)(1)
• Provides a safe additional power source for
contractors and homeowners
Cooper Bussmann A/C Disconnects Also
Meet Requirements For Other Single-Phase
Applications Including:
• Heat pumps
• Swimming pools
• Spas
• Whirlpools
• Pump houses
NOTE: The 20A Ground Fault Receptacle must be wired to a
separate 120V branch circuit than the pullout circuit
Save Money &
Installation Time
©2012 Cooper Bussmann S t. Lou i s , MO 6 3 178
636-394-2877 www.cooperbussmann.com
Pr i n t e d i n U SA Reorder # 3116 7-30-12-5M
B222-60F B222-60NF B222-60FGF
Technical Specifications
Cooper Disconnect Max HP Wire Size Approximate Dimensions
Bussmann Description Amp Rating Range Cu/Al Enclosure Fuse in Inches Weight
Part Number Non-Fused Rating 120V 240V 60C or 75C Type Class Height Width Depth lbs
B222-60NF 60A, Pull Out 60A 3 10 #14-3 NEMA 3R * 8.80 5.50 2.50 3.29
B222-60NFGF 60A, Pull Out 60A 3 10 #14-3 NEMA 3R * 13.00 7.50 4.75 8.00
w/ GFCI
B222-60NFNA 60A, Switch 60A * 10 #14-3 NEMA 3R * 8.80 5.50 3.63 3.29
Part Number Fused
B221-30F 30A, Pull Out 30A 1.5 3 #14-3 NEMA 3R H or R 8.80 5.50 2.50 3.29
B221-30FGF 30A, Pull Out 30A 1.5 3 #14-3 NEMA 3R H or R 13.00 7.50 4.75 8.00
with GFCI
B222-60F 60A, Pull Out 60A 3 10 #14-3 NEMA 3R H or R 8.80 5.50 2.50 3.29
B222-60FGF 60A, Pull Out 60A 3 10 #14-3 NEMA 3R H or R 13.00 7.50 4.75 8.00
with GFCI
Fused And Non-Fused Features:
• A/C disconnects meet NEC®Code Requirements
under articles 440.14
• GFCI units meet NEC®Code Requirements under
articles 210.63, 210.8, and 406.8(B)(1).
• NEMA 3R rainproof enclosures.
• Two-position pullout handle locks safety shield when
in the ON position. (Not available on GF or NA units.)
Pullout handle can be stored in the compartment in
the off position.
• Safety shield can be removed without tools.
(not available on GFCI units)
• Knockouts on back, bottom and both sides.
• Padlockable.
• UL Listed and CSA Certified.
• Suitable for use as service entrance equipment
applications when used with field installable
ground bar.
* Upstream overcurrent protection device (OCPD) not to exceed 30 Amps.