Data sheet PRO MAX 120W 24V 5A Weidmuller Interface GmbH & Co. KG Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com PROmax offers diverse solutions for demanding automation. Our high performance and durable PROmax switchmode power supply units are designed for especially demanding requirements. PROmax reliably copes with continuous overload of up to 20% or short-term peak loads of 300% occurring with high control cabinet temperatures. High boost capability and full power are also made possible in a wide temperature range. Our switch-mode power supply units can be used around the world and are also suitable for confined spaces thanks to their low width. Together with our uninterruptible DC USPs, the diode modules or CAP modules, you can create a power supply solution that is tailored to your requirements. General ordering data Version Order No. Type GTIN (EAN) Qty. Power supply, switch-mode power supply unit, 24 V 1478110000 PRO MAX 120W 24V 5A 4050118285956 1 pc(s). Creation date February 17, 2021 9:18:08 PM CET Catalogue status 12.02.2021 / We reserve the right to make technical changes. 1 Data sheet PRO MAX 120W 24V 5A Weidmuller Interface GmbH & Co. KG Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com Technical data Dimensions and weights Depth Height Net weight Width (inches) 125 mm 130 mm 858 g 1.575 inch Depth (inches) Height (inches) Width 4.921 inch 5.118 inch 40 mm Operating temperature -25 C...70 C Temperatures Storage temperature Humidity at operating temperature -40 C...85 C 5...95 %, no condensation Environmental Product Compliance REACH SVHC Lead 7439-92-1 3000m, 3000-6000m derating, @ 6000m 75% Load Certificate No. (cURus) 1A @ 230 VAC / 2,5A @ 115 VAC AC input voltage range DC current consumption Frequency range AC Inrush current Recommended back-up fuse Nominal output current for Unom Output voltage Output voltage, max. Output voltage, note Protection against inverse voltage Residual ripple, breaking spikes Rated data UL Operating altitude E255651 Input AC current consumption Connection system DC input voltage range Input fuse (internal) Rated input voltage Surge protection Screw connection 80...370 V DC Yes 100...240 V AC (widerange input) Varistor 85...277 V AC 1,5A @ 370 VDC / 2,5A @ 120 VDC 45...65 Hz max. 15 A 6 A, Char. B, circuit breaker, 6 A, char. C circuit breaker Output Connection system Output power Output voltage Output voltage, min. Parallel connection option Rated output voltage Screw connection 120 W 22.5...29.5 V (adjustable via potentiometer) 22.5 V yes, max. 5 24 V DC 1 % 5 A @ 60 C 24 V 29.5 V (adjustable via potentiometer) Yes < 50 mVss @ UNenn, Full Load Creation date February 17, 2021 9:18:08 PM CET Catalogue status 12.02.2021 / We reserve the right to make technical changes. 2 Data sheet PRO MAX 120W 24V 5A Weidmuller Interface GmbH & Co. KG Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com Technical data General data AC failure bridging time @ Inom Degree of efficiency Earth leakage current, max. MTBF min. 20 ms 89% 3.5 mA >500.000h (25C, IEC 61709 (SN29500)) -25 C...70 C Operating temperature Protection against reverse voltages from the load 30...35 V DC Status indication LED red/green and relay (21.6 V DC LED green, relay on/ 20.6 LED red, relay off) Current limiting Derating Housing version Mounting position, installation notice Power factor (approx.) Short-circuit protection Surge voltage category > 120% IN > 60C / 75% @ 70C Metal, corrosion resistant Horizontal on TS35 mounting rail. 50 mm of clearance at top & bottom for air circ. Can mount side by side with no space in between. > 0.90 @ 230 V AC Yes III EMC / shock / vibration Interference immunity test acc. to Shock resistance IEC 60068-2-27 Noise emission in accordance with EN 55024, EN 55032, IEC61000-3-2,-3, EN55032 IEC61000-4-2,-3,-4,-5,-6,-8,-11 Vibration resistance IEC 60068-2-6 30 g in all directions Class B 2.3 g Insulation coordination Humidity at operating temperature Pollution severity Surge voltage category 5...95 %, no condensation 2 III Insulation voltage, input/output Protection class 4 kV I, with PE connection For use with electronic equipment Protective separation / protection against electrical shock Acc. to EN50178 / VDE0160 VDE0100-410 / acc. to DIN57100-410 Electrical safety (applied standards) Electrical machine equipment Protection against dangerous shock currents Safety transformers for switch-mode power supplies Acc. to EN60204 Acc. to VDE0106-101 According to EN 61558-2-16 Connection data (input) Conductor cross-section, AWG/kcmil , max. Conductor cross-section, flexible , min. Conductor cross-section, rigid , min. Wire connection cross section, flexible (input), max. 10 0.22 mm 0.18 mm 4 mm Conductor cross-section, AWG/kcmil , min. Conductor cross-section, rigid , max. Connection system 26 6 mm Screw connection Connection data (output) Conductor cross-section, AWG/kcmil , max. Conductor cross-section, flexible , max. Conductor cross-section, rigid , max. Connection system 12 4 mm 6 mm Screw connection Conductor cross-section, AWG/kcmil , min. Conductor cross-section, flexible , min. Conductor cross-section, rigid , min. Number of terminals 26 0.5 mm 0.5 mm 8 (++,---,11,13,14) Creation date February 17, 2021 9:18:08 PM CET Catalogue status 12.02.2021 / We reserve the right to make technical changes. 3 Data sheet PRO MAX 120W 24V 5A Weidmuller Interface GmbH & Co. KG Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com Technical data Signalling Contact load (NO contact) Status indication max. 30 V DC / 1 A LED red/green and relay (21.6 V DC LED green, relay on/ 20.6 LED red, relay off) Floating contact Yes TAA00000TT E258476 GERMLLOYD CULUSEX Certificate No. (cURus) Certificate no. (cULusEX) Institute (cULus) Institute (cURus) E255651 E470829 CULUS CURUS EC002540 27-04-07-01 27-04-07-01 ETIM 7.0 ECLASS 9.1 ECLASS 11.0 EC002540 27-04-07-01 27-04-07-01 Approvals Certificate No. (GERMLLOYD) Certificate no. (cULus) Institute (GERMLLOYD) Institute (cULusEX) Classifications ETIM 6.0 ECLASS 9.0 ECLASS 10.0 Approvals Approvals ROHS UL File Number Search Conform E258476 Downloads Approval/Certificate/Document of Conformity Engineering Data Engineering Data User Documentation Declaration of Conformity STEP EPLAN, WSCAD, Zuken E3.S Operating instructions Creation date February 17, 2021 9:18:08 PM CET Catalogue status 12.02.2021 / We reserve the right to make technical changes. 4 Data sheet PRO MAX 120W 24V 5A Weidmuller Interface GmbH & Co. KG Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com Drawings Electric symbol Derating curve Derating curve Creation date February 17, 2021 9:18:08 PM CET Catalogue status 12.02.2021 / We reserve the right to make technical changes. 5