https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page1/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge arresters consisting of base element and protective connector with high-capacity varistor, for mounting on
NS 35/7.5, 1-channel
Your advantages
Plug-in direction parallel to the conductor axis
Versions with and without floating remote indication contact
Rack-mount 2U panel applications
Accepts Type 1 and Type 2 VAL-MS plugs.
Coding when protective plug is inserted for the first time
DIN rail mounting
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4055626063058
Weight per Piece (excluding packing) 145.830 g
Custom tariff number 85363090
Country of origin Germany
Technical data
Dimensions
Height 77.1 mm
Width 17.6 mm
Depth 89.2 mm
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page2/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Technical data
Ambient conditions
Degree of protection IP20
IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude max. 2000 m
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification II
T2
EN type T2
Mode of protection L-PEN
(L+) - (L-)
(L-) - PE
(L+) - PE
Mounting type DIN rail: 35 mm
Color black
Housing material PBT
Degree of pollution 2
Flammability rating according to UL 94 V0
Type DIN rail module, two-section, divisible
Number of positions 1
Surge protection fault message Optical, remote indicator contact
Protective circuit
Nominal voltage UN60 VDC
-48 VDC (RRH)
Nominal frequency fN50 Hz (60Hz)
Maximum continuous voltage UC75 VAC
100 VDC
Maximum continuous operating voltage UC (L-N) 75 VAC
100 VDC
Maximum continuous operating voltage UC (L-PEN) 75 VAC
100 VDC
Rated load current IL80 A
Residual current IPE ≤ 0.45 mA
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page3/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Technical data
Protective circuit
Standby power consumption PC≤ 35 mVA
Nominal discharge current In (8/20) µs 15 kA
Nominal discharge current In (8/20) µs (L-N) 15 kA
Nominal discharge current In (8/20) µs (L-PEN) 15 kA
Maximum discharge current Imax (8/20) µs 40 kA
Maximum discharge current Imax (8/20) µs (L-N) 40 kA
Maximum discharge current Imax (8/20) µs (L-PEN) 40 kA
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up≤ 0.55 kV
Voltage protection level Up (L-N) ≤ 0.55 kV
Voltage protection level Up (L-PEN) ≤ 0.55 kV
Residual voltage Ures ≤ 0.55 kV (at In)
≤ 0.425 kV (at 10 kA)
≤ 0.325 kV (at 5 kA)
≤ 0.275 kV (at 3kA)
TOV behavior at UT100 VAC (5s / withstand mode)
TOV behavior at UT (L-N) 100 VAC (5s / withstand mode)
TOV behavior at UT (L-PEN) 100 VAC (5s / withstand mode)
Response time tA≤ 25 ns
Response time tA (L-N) ≤ 25 ns
Response time tA (L-PEN) ≤ 25 ns
Max. backup fuse with V-type through wiring 80 A AC (gG)
Max. backup fuse with branch wiring 125 A AC (gG)
Indicator/remote signaling
Switching function Changeover contact
Operating voltage 5 VAC ... 250 VAC
125 VAC (UL)
125 VDC (200 mA DC)
Operating current 5 mA AC ... 1.5 A
1 A (UL)
1 A (30VDC)
Connection method Screw connection
Screw thread M2
Tightening torque 0.25 Nm
4 lbf-in. (UL)
Stripping length 7 mm
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page4/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Technical data
Indicator/remote signaling
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section AWG 28 ... 16
30 ... 14 (UL)
Connection data
Connection method Biconnect terminal blocks
Screw thread M5
Tightening torque 3 Nm ... 4.5 Nm (UL)
27 lbf-in. ... 40 lbf-in. (UL)
Stripping length 16 mm
Conductor cross section flexible min. 1.5 mm²
Conductor cross section flexible max. 25 mm²
Conductor cross section solid min. 1.5 mm²
Conductor cross section solid max. 35 mm²
Conductor cross section AWG 15 ... 2 (IEC)
10 ... 2 (UL)
Connection method Screw connection
Screw thread M5
Tightening torque 4.5 Nm
30 lbf-in. (UL)
Stripping length 16 mm
Conductor cross section flexible min. 1.5 mm²
Conductor cross section flexible max. 25 mm²
Conductor cross section solid min. 1.5 mm²
Conductor cross section solid max. 35 mm²
Conductor cross section AWG 15 ... 2
10 ... 2 (UL)
UL specifications
SPD Type 4CA
Maximum continuous operating voltage MCOV 75 VAC
Maximum continuous operating voltage MCOV (L-N) 75 VAC
Maximum continuous operating voltage MCOV (L-G) 75 VAC
Maximum continuous operating voltage MCOV (L+) - (L-) 100 VDC
Maximum continuous operating voltage MCOV (L+/L-) - G 100 VDC
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page5/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Technical data
UL specifications
Nominal voltage 60 VDC
Mode of protection L-L
L-G
(L+) - (L-)
(L+) - G
(L-) - G
Power distribution system Single phase
Voltage protection rating VPR 500 V
Voltage protection rating VPR (L-N) 0.5 kV
Voltage protection rating VPR (L+) - (L-) 0.33 kV
Voltage protection rating VPR (L+/L-) -G 0.33 kV
Measured limiting voltage MLV (L-N) 630 V
Measured limiting voltage MLV 630 V
Nominal discharge current In10 kA
Nominal discharge current In (L-N) 10 kA
Nominal discharge current In (L+) - (L-) 10 kA
Nominal discharge current In (L+/L-) - G 10 kA
UL indicator/remote signaling
Operating voltage 125 VAC
Operating current 1 A AC
Tightening torque 2 lbf-in. ... 4 lbf-in.
Conductor cross section AWG 30 ... 14
UL connection data
Conductor cross section AWG 10 ... 2
Tightening torque 30 lbf-in.
Standards and Regulations
Standards/regulations EN61643-11/A11 2007
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page6/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Dimensional drawing
21,22
5,02
54,02
77,06
76
29,79
17,6
40,9345,6
103,35
Circuit diagram
12 14
11
FM
N/PEN
L
Classifications
eCl@ss
eCl@ss 10.0.1 27130805
eCl@ss 11.0 27130805
eCl@ss 4.0 27130800
eCl@ss 4.1 27130800
eCl@ss 5.0 27130800
eCl@ss 5.1 27130800
eCl@ss 6.0 27130800
eCl@ss 7.0 27130805
eCl@ss 9.0 27130805
ETIM
ETIM 6.0 EC000941
ETIM 7.0 EC000941
UNSPSC
UNSPSC 13.2 39121620
UNSPSC 18.0 39121620
UNSPSC 19.0 39121620
UNSPSC 20.0 39121620
UNSPSC 21.0 39121620
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / cULus Recognized
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page7/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Approvals
Ex Approvals
Approval details
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330181
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330181
cULus Recognized
Accessories
Accessories
Bridge
Wiring bridge-MPB 18/1- 2-2809209
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 2-pos.
Wiring bridge-MPB 18/1- 3-2809212
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 3-pos.
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page8/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Accessories
Wiring bridge-MPB 18/1- 4-2809225
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 4-pos.
Wiring bridge-MPB 18/1- 6-2748564
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 6-pos.
Wiring bridge-MPB 18/1- 7 BU-2856278
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 7-pos., color: Blue
Wiring bridge-MPB 18/1- 8 BU-2858470
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 8-pos., color: Blue
Wiring bridge-MPB 18/1- 8-2748577
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 8-pos.
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page9/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Accessories
Wiring bridge-MPB 18/1- 9-2748580
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 9-pos.
Wiring bridge-MPB 18/1-12-2748593
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 12-pos.
Wiring bridge-MPB 18/1-57-2809238
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 57-pos.
Wiring bridge-MPB 18/3- 6-2809241
Wiring bridge for modules with connecting pitch 17.5 mm, 3-phase, 6-pos.
Wiring bridge-MPB 18/4- 8-2809283
Wiring bridge for modules with connecting pitch 17.5 mm, 4-phase, 8-pos.
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page10/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Accessories
Wiring bridge-MPB 18/4-12-2809296
Wiring bridge for modules with connecting pitch 17.5 mm, 4-phase, 12-pos.
Wiring bridge-MPB F200X16/ 1GS-2818339
Wiring bridge flexible, diameter 16 mm², with a fork-type cable lug on one side, length: 200 mm
Wiring bridge-MPB F400X16/ 1GS-2818342
Wiring bridge flexible, diameter 16 mm², with a fork-type cable lug on one side, length: 400 mm
Wiring bridge-MPB F600X16/ 1GS-2818355
Wiring bridge flexible, diameter: 16 mm², with a fork-type cable lug on one side, length: 600 mm
Wiring bridge-MPB F600X16/ 1GS-2818355
Wiring bridge flexible, diameter: 16 mm², with a fork-type cable lug on one side, length: 600 mm
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page11/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Accessories
Wiring bridge-MPB F400X16/ 1GS-2818342
Wiring bridge flexible, diameter 16 mm², with a fork-type cable lug on one side, length: 400 mm
Wiring bridge-MPB F200X16/ 1GS-2818339
Wiring bridge flexible, diameter 16 mm², with a fork-type cable lug on one side, length: 200 mm
Wiring bridge-MPB 18/1-10/1.0.0-2830443
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 10 pitches with contact sequence 1-0-0
Wiring bridge-MPB 18/4-12-2809296
Wiring bridge for modules with connecting pitch 17.5 mm, 4-phase, 12-pos.
Wiring bridge-MPB 18/4- 8-2809283
Wiring bridge for modules with connecting pitch 17.5 mm, 4-phase, 8-pos.
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page12/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Accessories
Wiring bridge-MPB 18/3- 6-2809241
Wiring bridge for modules with connecting pitch 17.5 mm, 3-phase, 6-pos.
Wiring bridge-MPB 18/1-57-2809238
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 57-pos.
Wiring bridge-MPB 18/1-12-2748593
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 12-pos.
Wiring bridge-MPB 18/1- 9-2748580
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 9-pos.
Wiring bridge-MPB 18/1- 8-2748577
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 8-pos.
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page13/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Accessories
Wiring bridge-MPB 18/1- 6-2748564
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 6-pos.
Wiring bridge-MPB 18/1- 4-2809225
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 4-pos.
Wiring bridge-MPB 18/1- 3-2809212
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 3-pos.
Wiring bridge-MPB 18/1- 2-2809209
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 2-pos.
Device marking
Zack marker strip-ZBN 18:UNBEDRUCKT-2809128
Zack marker strip, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type: snap
into tall marker groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page14/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Accessories
Feed-through terminal block
Feed-through terminal block-DK-BIC-35-2749880
Feed-through terminal block for VAL and FLT applications
Labeled device marker
Marker for terminal blocks-ZBN 18,LGS:ERDE-2749589
Marker for terminal blocks, Strip, white, labeled, horizontal: Grounding symbol, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Marker for terminal blocks-ZBN 18,LGS:L1-N,ERDE-2749576
Marker for terminal blocks, Strip, white, labeled, horizontal: L1, L2, L3, N, GND, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Marker pen
Marker pen-B-STIFT-1051993
Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm
Spare parts
https://www.phoenixcontact.com/us/products/2906280
03/28/2021Page15/15
Type 2 surge protection device-VAL-US 60/O-FM-2906280
Accessories
Type 2 surge protection plug-VAL-US-48/40-P-2910333
UL Recognized type 2 SPD and IEC type 2 surge protection plug with a varistor and thermal disconnect for use with VAL-
US base elements, mechanical and visual fault warning
Type 2 surge protection base element-VAL-MS-T1/T2 BE/O-FM-2905652
Base element for type 1/2 arresters from the VALVETRAB MS T1/T2 product range, with remote indication contact.
Version: 1-channel
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com