Specifications are subject to change without notice (18.09.06) 1
Monitoring Relays
Product Description Ordering Key
Housing
Function
Type
Item number
Output
Power supply
Measuring range
TRMS AC/DC over or under current
monitoring relay
Current measuring through internal shunt
Selection of measuring range by DIP-switches
Measuring ranges from 0.1 mA to 10 A AC/DC
Adjustable current on relative scale
Adjustable hysteresis on relative scale
Adjustable delay function (0.1 to 30 s)
Programmable latching or inhibit at set level
Output: 8 A SPDT relay N.D. or N.E. selectable
For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DIB01) or plug-in module (PIB01)
22.5 mm Euronorm housing (DIB01)
or 36 mm plug-in module (PIB01)
LED indication for relay, alarm and power supply ON
Galvanically separated power supply
Input (current level)
DIB01 Terminals Y1, Y2
PIB01 Terminals 5, 7
Measuring ranges
Direct Internal resist. Max. curr.
Selectable by DIP-switch
..5MA: 0.1 to 1 mA AC/DC 50 50 mA
0.2 to 2 mA AC/DC 50 50 mA
0.5 to 5 mA AC/DC 50 50 mA
Max. current for 1 s 100 mA
..50MA: 1to 10 mA AC/DC 5150 mA
2to 20 mA AC/DC 5 150 mA
5to 50 mA AC/DC 5 150 mA
Max. current for 1 s 500 mA
1-Phase True RMS AC/DC Over or Under Current
Types DIB01, PIB01
Input Specifications
DIB 01 C B23 5A
DIB01 and PIB01 are precise
TRMS AC/DC over or under
current (selectable by DIP-
switch) monitoring relays.
Direct measuring or through
current transformer.
Owing to the built-in latch
function, the ON-position of
the relay output can be
maintained. Inhibit function
can be used to avoid relay
operation when not desired
(maintenance, transitions).
The LED's indicate the state
of the alarm and the output
relay. Through the built-in
shunt it is possible to moni-
tor loads up to 10 A AC/DC.
DIB01 PIB01
Measuring ranges (cont.)
Internal resist. Max. curr
.
..500MA:10 to 100 mA AC/DC 0.5 700 mA
20 to 200 mA AC/DC 0.5 700 mA
50 to 500 mA AC/DC 0.5 700 mA
Max. current for 1 s 1.4 A
..5A: 0.1 to 1 A AC/DC 0.05 6 A
0.2 to 2 A AC/DC 0.05 6 A
0.5 to 5 A AC/DC 0.05 6 A
Max. current for 1 s 15 A
..10A: 1to 10 A AC/DC 3 m11 A
Max. current for 1 s 15 A
Type Selection
Mounting Output Measuring range Supply: 24 VDC Supply: 48 VDC Supply: 24/48 VAC Supply: 115/230 VAC
DIN-rail SPDT 0.1 to 5 mA AC/DC DIB 01 C 724 5mA DIB 01 C 748 5mA DIB 01 C B48 5mA DIB 01 C B23 5mA
1to 50 mA AC/DC DIB 01 C 724 50mA DIB 01 C 748 50mA DIB 01 C B48 50mA DIB 01 C B23 50mA
10 to 500 mA AC/DC DIB 01 C 724 500mA DIB 01 C 748 500mA DIB 01 C B48 500mA DIB 01 C B23 500mA
0.1 to 5 A AC/DC DIB 01 C 724 5A DIB 01 C 748 5A DIB 01 C B48 5A DIB 01 C B23 5A
1to 10 A AC/DC DIB 01 C 724 10A DIB 01 C 748 10A DIB 01 C B48 10A DIB 01 C B23 10A
Plug-in SPDT 0.1 to 5 mA AC/DC PIB 01 C 724 5mA PIB 01 C 748 5mA PIB 01 C B48 5mA PIB 01 C B23 5mA
1to 50 mA AC/DC PIB 01 C 724 50mA PIB 01 C 748 50mA PIB 01 C B48 50mA PIB 01 C B23 50mA
10 to 500 mA AC/DC PIB 01 C 724 500mA PIB 01 C 748 500mA PIB 01 C B48 500mA PIB 01 C B23 500mA
0.1 to 5 A AC/DC PIB 01 C 724 5A PIB 01 C 748 5A PIB 01 C B48 5A PIB 01 C B23 5A
1to 10 A AC/DC PIB 01 C 724 10A PIB 01 C 748 10A PIB 01 C B48 10A PIB 01 C B23 10A
2Specifications are subject to change without notice (18.09.06)
DIB01, PIB01
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals:
A1, A2 or A3, A2 (DIB01)
2, 10 or 11, 10 (PIB01)
724: 24 VDC ± 20%, insulated
784: 48 VDC ± 20%, insulated
B48: 24/48 VAC ± 15%
45 to 65 Hz, insulated
B23: 115/230 VAC ± 15%
45 to 65 Hz, insulated
Dielectric voltage DC supply AC supply
Supply to input 2kV 4 kV
Supply to output 4 kV 4 kV
Input to output 4 kV 4 kV
Rated operational power
AC 4 VA
DC 3 W
Supply Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
Reaction time (input signal variation from
-20% to +20% or from
+20% to -20% of set value)
AlarmON delay <100 ms
Alarm OFF delay < 100 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Delay ON alarm ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green
Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON LED, yellow
Environment (EN 60529)
Degree of protection IP 20
Pollution degree 3 (DIB01), 2 (PIB01)
Operating temperature -20 to 60°C, R.H. < 95%
Storage temperature-30 to 80°C, R.H. < 95%
Housing
Dimensions DIB01 22.5 x 80 x 99.5 mm
PIB01 36 x 80 x 94 mm
Weight Approx. 150 g
Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approvals UL, CSA (except 748)
CE Marking Yes
EMC
Electromagnetic Compatibillity
Immunity According to EN 61000-6-2
Emission According to EN 61000-6-3
General Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2
Resistive loads AC 1 8 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life 30 x 106operations
Electrical life 105operations
(at 8 A, 250 V, cos ϕ=1)
Operating frequency 7200 operations/h
Dielectric strength
Dielectric voltage
2kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Output Specifications
Measuring ranges (cont.)
Standard CT (examples) AACrms Max. curr.
TADK2 50 A/5 A 5 to 50 A 60 A
TAD2 150 A/5 A 15 to 150 A 180 A
TAD6 400 A/5 A 40 to 400 A 480 A
TAD12 1000 A/5 A 100 to 1000 A 1200 A
TACO200 6000 A/5 A 600 to 6000 A 7200 A
Note:
The input voltage cannot
raise over 300 VAC/DC with
respect to ground (PIB01 only)
Contact input
DIB01 Terminals Z1, Y1
PIB01 Terminals 8, 9
Disabled > 10 k
Enabled < 500
Latch disable > 500 ms
Input Specifications (cont.)
Specifications are subject to change without notice (18.09.06) 3
Adjust the input range set-
ting the DIP switches 1 and
2as shown below (except
for models DIB01xxx10A
and PIB01xxx10A).
Select the desired function
setting the DIP switches 3 to
6(1 to 4 for DIB01xxx10A
and PIB01xxx10A) as shown
below.
To access the DIP switches
open the grey plastic cover
as shown below.
Selection of level and time
delay:
Upper knob:
Setting of hysteresis on rela-
tive scale: 0 to 30% on set
value.
Centre knob:
Current level setting on rela-
tive scale: 10 to 110% on
full scale.
Lower knob:
Setting of delay on alarm
time on absolute scale (0.1
to 30 s).
DIB01, PIB01
Function/Range/Level and Time Delay Setting
Mode of Operation
DIB01 and PIB01 monitor
both AC and DC over or
under current through an
internal shunt.
Example 1
(connection between termi-
nals Z1, Y1 or 8, 9 - latching
function enabled)
The relay operates and latch-
esin operating position
when the measured value
exceeds (or drops below) the
set level for more than the
set delay time. Provided that
the current has dropped
below (or has exceeded) the
set point (see hysteresis set-
ting), the relay releases when
the interconnection between
terminals Z1, Y1 or 8, 9 is
interrupted or the power
supply is interrupted as well.
The red LED flashes until the
delay time has expired or the
measured value comes back
toanon-alarm value (see
hysteresis setting).
Example 2 (Stardard CT)
(no connection between ter-
minals Z1, Y1 or 8, 9 - latch
function disabled)
The relay operates when the
measured value exceeds (or
drops below) the set level for
more than the set delay time.
It releases when the current
drops below (or exceeds) the
set level (see hysteresis set-
ting) or when power supply
is interrupted.
Note
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay activation.
10 A Models
Other Models
Relay working mode
ON: Normally De-energized
OFF: Normally Energized
Power ON delay
ON: 6 s ± 0.5 s
OFF: 1 s ± 0.5 s
Contact input
ON: Latch function enable
OFF: Inhibit function enable
Monitoring function
ON: Over current
OFF: Under current
Relay working mode
ON: Normally De-energized
OFF: Normally Energized
Measuring range
SW1 ON ON OFF
SW2 OFF ON ON
5MA 1mA 2mA 5mA
50MA 10 mA 20 mA 50 mA
500MA 100 mA 200 mA 500 mA
5A 1 A 2 A 5 A
Power ON delay
ON: 6 s ± 0.5 s
OFF: 1 s ± 0.5 s
Contact input
ON: Latch function enable
OFF: Inhibit function enable
Monitoring function
ON: Over current
OFF: Under current
4Specifications are subject to change without notice (18.09.06)
Operation Diagrams
Wiring Diagrams
DIB01, PIB01
Over current - N.D. relay
Under current - N.D. relay
Under current - Latch function - N.D. relay
Over current - Inhibit function - N.D. relay
Example1
N (-)
PE
m
Z1
Y1
Y2
A1 A3
A2 15
16 18
L
Latch/Inhibit
Contact
Example2
N (-)
m
Z1
Y1
Y2
A1 A3
A2 15
16 18
L
I
I
24/48VDC(+)
48/230VAC24/115VAC
24/48VDC(+)
48/230VAC24/115VAC
DIB01
Example1
N (-)
PE
m
89
5
7
10 1
43
L
Latch/Inhibit
Contact
Example2
N (-)
m
89
5
7
10 1
43
L
112
I
I
24/48VDC(+)
48/230VAC24/115VAC
24/48VDC(+)
48/230VAC24/115VAC
PIB01
Specifications are subject to change without notice (18.09.06) 5
36
80
94
28.5
63
90
22.5
80
83.5
99.5
63
28.5
Dimensions
DIN-rail Plug-in
DIB01, PIB01