For more Information
please call
1-800-Belden1
General Description:
18 AWG solid bare copper conductors, conductors cabled, PVC insulation, overall Beldfoil® shield (100%
coverage), 22 AWG stranded TC drain wire, PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
418 Solid BC - Bare Copper
Total Number of Conductors: 4
Insulation
Insulation Material:
Insulation Material Wall Thickness (mm)
PVC - Polyvinyl Chloride 0.4318
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® (Z-Fold®) Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
22 7x30 TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 0.9398
Overall Cable
Overall Cabling Color Code Chart:
Number Color
1Black
2Red
3Yellow
4Blue
Overall Nominal Diameter: 6.680 mm
Mechanical Characteristics (Overall)
Operating Temperature Range: -40°C To +105°C
UL Temperature Rating: 105°C
Bulk Cable Weight: 71.434 Kg/Km
Max. Recommended Pulling Tension: 440.372 N
Min. Bend Radius/Minor Axis: 69.850 mm
Page 1 of 3 08-21-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
9578 Multi-Conductor - Power-Limited Fire Protective Signaling Circuit Cables
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: CMR, FPLR
NEC Articles: 760
CEC/C(UL) Specification: FAS105
AWM Specification: UL Style 2464 (300 V 80°C)
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Other Specification: California State Fire Marshall
Flame Test
UL Flame Test: UL1666 Vertical Shaft
CSA Flame Test: FT4
Plenum/Non-Plenum
Plenum (Y/N): No
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/m)
0.554489
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
141.083
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
259.855
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
20.9984
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
38.3877
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
3.2 Amps per conductor @ 25°C
Put Ups and Colors:
Item # Putup Ship Weight Color Notes Item Desc
Page 2 of 3 08-21-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
9578 Multi-Conductor - Power-Limited Fire Protective Signaling Circuit Cables
9578 0021000 305 MT 23.133 KG RED C 4 #18 PVC SHLD PVC
Notes:
C = CRATE REEL PUT-UP.
Revision Number: 4 Revision Date: 10-03-2012
© 2013 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3 08-21-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
9578 Multi-Conductor - Power-Limited Fire Protective Signaling Circuit Cables