https://www.phoenixcontact.com/us/products/2817437 Lightning arrester type 1 - FLT 35 CTRL-1.5/I - 2817437 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Type 1 / Class I / B arrester (lightning current arrester) with encapsulated arc chopping spark gap and ignition electronics with control lamp, 1-channel. Protection level: 1.5 kV. Housing width: 17.5 mm (1 Div.) The illustration shows version FLT 35 CTRL-0,9/l Key commercial data Packing unit 1 pc Weight per Piece (excluding packing) 192.6 GRM Custom tariff number 85363030 Country of origin Germany Technical data Dimensions Height 89.8 mm Width 17.7 mm Depth 65.5 mm Horizontal pitch 1 Div. Ambient conditions Degree of protection IP20 Ambient temperature (operation) -40 C ... 85 C Permissible humidity (operation) 95 % General Housing material PA Inflammability class according to UL 94 V0 Color black Standards for air and creepage distances IEC 60664-1 VDE 0110-1 10/17/2014 Page 1 / 5 https://www.phoenixcontact.com/us/products/2817437 Lightning arrester type 1 - FLT 35 CTRL-1.5/I - 2817437 Technical data General Mounting type DIN rail: 35 mm Type Rail-mountable module, one-piece Surge protection fault message Optical Direction of action 1L-N/PE Protective circuit IEC test classification I T1 EN type T1 Nominal voltage UN 230 V AC Maximum continuous operating voltage UC 260 V AC Maximum continuous operating voltage UC (L-N) 260 V AC Maximum continuous operating voltage UC (L-PEN) 260 V AC Nominal frequency fN 50 Hz 60 Hz Residual current IPE 2.5 mA Operating effective current IC at UN 2.5 mA Nominal discharge current In (8/20) s 35 kA Nominal discharge current In (8/20) s (L-N) 35 kA Nominal discharge current In (8/20) s (L-PEN) 35 kA Impulse discharge current (10/350) s charge 17.5 As Impulse discharge current (10/350)s, specific energy 305 kJ/ Impulse discharge current (10/350)s, peak value limp 35 kA 100% lightning impulse sparkover voltage (1.2/50)s 1.5 kV 100% lightning impulse sparkover voltage (1.2/50)s (L-N) 1.5 kV 100% lightning impulse sparkover voltage (1.2/50)s (L-PEN) 1.5 kV Voltage protection level Up 1.5 kV Voltage protection level Up (L-N) 1.5 kV Voltage protection level Up (L-PEN) 1.5 kV Response time 100 ns Response time (L-N) 100 ns Response time (L-PEN) 100 ns Max. backup fuse with branch wiring 125 A (gL) Short-circuit resistance IP with max. backup fuse (effective) 25 kA Short-circuit current self-quenching 3 kA (260 V) Follow current quenching capacity If (L-N) 3 kA (260 V) Follow current quenching capacity If (L-PEN) 3 kA (260 V) 10/17/2014 Page 2 / 5 https://www.phoenixcontact.com/us/products/2817437 Lightning arrester type 1 - FLT 35 CTRL-1.5/I - 2817437 Technical data Connection, protective circuit Connection method Screw connection Connection type IN Biconnect screw terminal block Connection type OUT Biconnect screw terminal block Connection method Biconnect terminal block Screw thread M5 Tightening torque 4.5 Nm Stripping length 14.5 mm Conductor cross section stranded min. 0.5 mm Conductor cross section stranded max. 25 mm Conductor cross section solid min. 0.5 mm Conductor cross section solid max. 35 mm Conductor cross section AWG/kcmil min. 20 Conductor cross section AWG/kcmil max 2 Standards and Regulations Standards/regulations IEC 61643-1 1998-02 E DIN VDE 0675-6 1989-11 E DIN VDE 0675-6/A1 1996-03 E DIN VDE 0675-6/A2 1996-10 IEC 61312-1 1995-02 Classifications eCl@ss eCl@ss 4.0 27140201 eCl@ss 4.1 27140201 eCl@ss 5.0 27140201 eCl@ss 5.1 27140201 eCl@ss 6.0 27140201 eCl@ss 7.0 27140201 eCl@ss 8.0 27140201 ETIM ETIM 2.0 EC000381 ETIM 3.0 EC000381 ETIM 4.0 EC000381 ETIM 5.0 EC000381 10/17/2014 Page 3 / 5 https://www.phoenixcontact.com/us/products/2817437 Lightning arrester type 1 - FLT 35 CTRL-1.5/I - 2817437 Classifications UNSPSC UNSPSC 6.01 30212010 UNSPSC 7.0901 39121610 UNSPSC 11 39121610 UNSPSC 12.01 39121610 UNSPSC 13.2 39121620 Approvals Approvals Approvals GOST Ex Approvals Approvals submitted Approval details GOST Drawings Dimensioned drawing Circuit diagram 90 45 58 L/N( ) 51,5 65,5 L/N( ) 10/17/2014 Page 4 / 5 https://www.phoenixcontact.com/us/products/2817437 Lightning arrester type 1 - FLT 35 CTRL-1.5/I - 2817437 Catalog photo Figure may contain other products. Phoenix Contact 2014 (c) - all rights reserved http://www.phoenixcontact.com 10/17/2014 Page 5 / 5