APL/UPL, 205/295 APL/UPL, 205/295 Series Magnetic Circuit Protectors Introduction | 168 Single & Multi-Pole | 169 Barriers | 171 Configurations | 172 Operating Characteristics | 174 Delay Curves | 175 Specifications | 180 Decision Tables | 186 APL/UPL, 205/295 Series Hydraulic Magnetic Circuit Protectors INTRODUCTION The APL/UPL magnetic circuit protector provides reliable, low-cost power switching, circuit protection and circuit control. The handle opens and closes a circuit, under normal load conditions, similar to an ON-OFF switch. Upon overload, the internal mechanism trips, opens the contacts and forcibly returns the handle to the OFF position. Since the protector is "trip free," the internal contacts will not remain closed in the presence of an overload, even though the handle is held in the ON position. The APL/UPL line offers many configurations including series, shunt and relay with a choice of delays and ratings. APL/UPL multi-pole assemblies are available with a mix of current ratings, delays and internal circuit configurations. 168 APL/UPL, 205/295 Series - Introduction While designed for industrial, military and information processing applications, the APL is suitable for use in any situation where precision operation is required. Most versions of the APL family are recognized by UL per UL STD. 1077 as supplementary protectors and certified by CSA per CSA STD. C22.2-No. 235 as supplementary protectors and are designated with the UPL prefix. Additionally, many versions of the UPL comply with the spacing requirements covered by IEC specifications 950 and 601 and VDE specifications 0642 (EN60934) and are VDE approved and CE Compliant. Please contact the factory for assignment of a part number. http://airpax.sensata.com/ APL/UPL, 205/295 205/295 Dust Sealed Protector Combining the proven mechanism of the APL/UPL circuit protector with a unique case design, the 205 version provides increased voltage ratings plus a dust proof enclosure. All openings in the case (including arc blowout vent and handle) have been sealed with resilient rubber or mylar. In addition, case sections have been designed with tongue and groove construction to provide an overlapping closure. These features make the 205 ideal for applications in harsh environments where reliable protection is essential. 205 breakers have standard full load current ratings from 0.050 amperes to 100 amperes and voltage ratings to 65Vdc and 277/480Vac. Like all Airpax magnetic protectors, the trip current rating is not affected by ambient temperature. The 205 is recognized by UL and certified by CSA under the Component program. Non UL-recognized versions of this series are designated 295. 2.020 MAX. [51.31] APL/UPL Single Pole Toggle .150 [3.81] 2.530 MAX. [64.26] .675 [17.14] 205/295 Single Pole Toggle .402 [10.21] 6-32 THD. (M3 ISO. THD. OPTIONAL) .187 [4.75] DEEP (TWO PLACES) Note: Tolerance .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. .220 [5.59] 1.438 [36.53] ON 2.060 .010 [52.32 0.25] ON .750 MAX. [19.05] http://airpax.sensata.com/ APL/UPL, 205/295 Series - Single Pole 169 Multi-Pole Circuit Protectors Mounting Details Multi-pole protectors are combined in an assembly with the actuating handles linked and the trip mechanisms internally coupled. A fault in either protected circuit opens all poles simultaneously. Applications include use in two-phase circuits, single-phase three-wire systems or in two or more related but electrically isolated circuits. A mix of delays, ratings and configurations is possible, with the series type having any of the auxiliary switches listed. Combinations up to nine poles are available. One Pole .755 [19.18] O 2X .156 [3.96] 2.060 [52.32] 1.448 [36.78] .432 [10.97] Multi-Pole Dimensions 2 pole "A" 1.515 [38.48] max 3 pole "A" 2.265 [57.53] max 4 pole "A" 3.015 [76.58] max 5 pole "A" 3.765 [95.63] max 6 pole "A" 4.515 [114.68] max 7 pole "A" 5.265 [133.73] max 8 pole "A" 6.015 [152.78] max 9 pole "A" 6.765 [171.83] max Two Pole 1.530 [38.86] O 4X .156 [3.96] 1.448 [36.78] 2.060 [52.32] Note: Dimension "A" varies with # of poles .432 [10.97] .750 [19.05] "A" (SEE TABLE) Three Pole 2.280 [57.91] ON ON 1.448 [36.78] O 6X .156 [3.96] 2.060 [52.32] .75 .015 [19.05 .38] (TYP) .432 [10.97] .750 [19.05] .750 [19.05] Panel Mounting Tolerances: .005 [.13] unless noted. 170 APL/UPL, 205/295 - Multi-Pole http://airpax.sensata.com/ APL/UPL, 205/295 BARRIERS There are three barrier styles available for the 205/295, 215/285 protectors. Barrier style "B" is supplied for voltages between 200Vac and 250Vac inclusive. Barrier style "D" is required for voltages above 250Vac. Barrier style "C" is available for voltages up to 200Vac and is required when current ratings exceed 50 amperes. APL/UPL multipole protectors can be supplied with barriers at customer option. Consult factory. Barrier Style B 2.000 .020 [50.80 0.51] .990 .020 [25.15 0.51] 3.990 .020 [101.35 0.51] Barrier Style C .990 .020 [25.15 0.51] 2.490 .020 [63.25 0.51] Barrier Style D .900 .020 [22.86 0.51] 2.000 .020 [50.80 0.51] .990 .020 [25.15 0.51] 3.990 .020 [101.35 0.51] Note: Tolerance .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. http://airpax.sensata.com/ APL/UPL, 205/295 Series - Barriers 171 APL/UPL, 205/295 CONFIGURATIONS Series Trip The most popular configuration for magnetic protectors is the series trip where the sensing coil and contacts are in series with the load being protected. The handle position conveniently indicates circuit status. In addition to providing conventional over-current protection, it's simultaneously used as an on-off switch. Auxiliary Switch (Applies to Series Trip Only) This is furnished as an integral part of a series pole in single or multi-pole assemblies. Isolated electrically from the protector's circuit, the switch works in unison with the power contacts and provides indication at a remote location of the protector's on-off status. Auxiliary switch contacts actuate simultaneously with the main breaker contacts, and will open regardless of whether the breaker contacts are opened manually or electrically. For auxiliary switch ratings below 6Vac or 5Vdc, an auxiliary switch with gold contacts is available. Gold contacts are not recommended for load current above 100 milliamps. The contacts on our optional RS auxiliary switch will open only in the event of an electrical trip of the circuit breaker. Relay Trip This permits the overload sensing coil to be placed in a circuit which is electrically isolated from the trip contacts. The coil may be actuated by sensors monitoring pressure, flow, temperature, speed, etc. Other typical applications include crowbar, interlock and emergency/rapid shutdown circuitry. Trip may be accomplished by voltage or current, which must be removed immediately upon tripping. Dual Coil Dual coil protectors provide remote shut down option and normal overcurrent protection in the confines of a single breaker pole. This construction saves space by eliminating the need for an additional pole for the voltage trip function. Voltage Trip Sometimes called "dump circuits" or "panic trip circuits," these units make it possible to open main power contacts with lower power inputs from one or more sources. This configuration is becoming increasingly more important for sensitive circuitry and denser packaging in automation systems. Available in series, shunt, relay or dual coil configurations. Shunt Trip The shunt trip is designed for controlling two separate loads with one assembly. The control is established by providing overload protection for the critical load. When the current through this load becomes excessive and reaches the trip point, the protector will open and remove power from both loads simultaneously. The total current rating of both loads must not exceed the maximum contact rating. 172 APL/UPL, 205/295 - Configurations http://airpax.sensata.com/ APL/UPL, 205/295 Series Trip (See Note A) .675 .050 (17.15 1.27) .625 .031 (15.88 0.79) .281 .020 (7.14 0.51) .281 .020 (7.14 0.51) .280 (7.11) 1.940 (49.28) 1.940 [49.28] LINE LINE LOAD LOAD ( 50 AMP) (>50 AMP) Series Trip with Auxiliary Switch 1.290 .031 (32.77 0.79) .187 [4.75] .295 [7.49] .280 .031 (7.11 0.79) RS .110 [2.79] 1.056 .031 (26.82 0.79) REC 4 REG 4 .648 .031 (16.46 0.79) .312 [7.92] LINE .187 [4.75] NC BREAKER IN OFF POSITION NO REC 5 REG 5 C LOAD Shunt, Relay and Dual Coil .625 .031 [15.88 0.79] .281 .020 [7.14 0.51] .625 .031 [15.88 0.79] .281 .020 [7.14 0.51] 1.275 .020 [32.38 0.51] 1.940 [49.28] 1.940 [49.28] .667 .020 [16.94 0.51] .667 .020 [16.94 0.51] LINE LOAD LINE LINE LINE COIL LINE COIL LINE COIL LOAD COIL LOAD Notes: Tolerance .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. ATerminal sizes: 10-32 THD (<50 AMP), 1/4 -28 THD (>50 AMP) Metric Terminals (Optional), M5 x 0.8 THD (<50 AMP). B Minimum useable thread length: 10-32 THD (.250 on breakers without terminal boards, .160 with terminal boards) 1/4 -28 THD (.200). V. COIL LOAD LOAD RELAY LOAD SHUNT TRIP http://airpax.sensata.com/ DUAL COIL LOAD DUAL RATING RELAY RELAY TRIP DUAL COIL NO VOLTAGE TRIP APL/UPL, 205/295 Series - Configurations 173 APL/UPL, 205/295 OPERATING CHARACTERISTICS 0.050 AMPS to 50 Amps - Percentage of Rated Current vs Trip Time in Seconds at +25C Voltage 400 Hz DC 50/60 Hz DC 50/60 Hz Delay 100% 125% (Note A) 150% 200% 400% 600% 800% 1000% 40 No Trip May trip .050 max. .040 max. .030 max. .025 max. .020 max. .018 max. 41 No Trip May trip .6 to 7 .2 to 2 .020 to .4 .007 to .25 .004 to .15 .004 to .040 42 No Trip May trip 5 to 70 2 to 22 .4 to 3.8 .015 to 2 .006 to .4 .004 to .1 43 No Trip May trip 40 to 280 9 to 70 1.3 to 15 .2 to 3.75 .023 to .6 .010 to .050 49 No Trip .180 max. .120 max. .050 max. .022 max. .017 max. .017 max. .017 max. 50 No Trip May trip .032 max. .024 max. .020 max. .018 max. .016 max. .015 max. 51 No Trip .70 to 8 .40 to 4 .1 to 1.7 .02 to .30 .008 to .15 .004 to .06 .004 to .030 52 No Trip 8 to 100 3 to 30 .7 to 10 .18 to 2.5 .030 to 1 .004 to .5 .004 to .3 53 No Trip 80 to 600 30 to 300 10 to 100 1.5 to 15 .1 to 5 .008 to .3 .007 to .07 59 No Trip .100 max. .070 max. .032 max. .020 max. .016 max. .016 max. .016 max. 60 No Trip May trip .040 max. .035 max. .030 max. .025 max. .020 max. .018 max. 61 No Trip 1 to 18 .4 to 4 .180 to 1.8 .03 to .3 .009 to .15 .003 to .1 .003 to .08 62 No Trip 10 to 120 6 to 60 2 to 22 .2 to 2 .05 to .75 .015 to .15 .01 to .10 69 No Trip .180 max. .120 max. .050 max. .022 max. .017 max. .017 max. .017 max. 64 No Trip .7 to 10 .35 to 4.5 .15 to 1.5 .05 to .4 .025 to .3 .020 to .22 .015 to .15 65 No Trip 8 to 80 5.5 to 55 2 to 20 .5 to 5 .2 to 2 .06 to 1 .016 to .60 66 No Trip 50 to 700 30 to 350 10 to 100 1.5 to 20 .7 to 7 .1 to 3 .02 to 2 70 No Trip May trip .040 max .035 max. .030 max. .025 max. .020 max. .018 max. 71 No Trip .35 to 14 .18 to 7.5 .10 to 3 .025 to 1 .015 to .30 .01 to .15 .007 to .10 72 No Trip 6.5 to 115 3 to 65 1.2 to 20 .08 to 3 .018 to 2.5 .015 to .80 .009 to .25 73 No Trip 45 to 700 25 to 400 10 to 175 .75 to 20 .12 to 4.5 .025 to 1 .01 to .25 ABOVE 50 Amps - Percentage of Rated Current vs Trip Time in Seconds at +25C Voltage DC 50/60 Hz Delay 100% 125% (Note A) 150% 200% 400% 600% 800% 1000% 50 No Trip May trip .100 max. .070 max. .032 max. .020 max. .020 max. .020 max. 51 No Trip .5 to 8 .3 to 4 .1 to 1.7 .02 to .3 .08 to .150 .004 to .060 .004 to .03 52 No Trip 2.5 to 100 1.5 to 40 .62 to 15 .15 to 2.5 .03 to 1 .004 to .5 .004 to .3 59 No Trip .100 max. .070 max. .032 max. .020 max. .016 max. .016 max. .016 max. 60 No Trip May trip .120 max. .050 max. .022 max. .017 max. .017 max. .017 max. 61 No Trip .7 to 18 .35 to 4 .130 to 1.8 .030 to .3 .008 to .150 .003 to .1 .003 to .08 62 No Trip 10 to 120 6 to 60 2 to 22 .2 to 2 .050 to .750 .007 to .15 .005 to .10 69 No Trip .180 max. .120 max. .050 max. .022 max. .017 max. .017 max. .017 max. 64 No Trip May trip .2 to 8 .15 to 7.6 .05 to .73 .025 to .3 .020 to .22 .015 to .15 65 No Trip May trip 3 to 55 2 to 20 .3 to 5 .13 to 2 .06 to 1 .016 to .60 Notes: All trip curves and trip currents are specified with the protector mounted in the normal vertical position at ambient temperature of +25 C. Protectors do not carry current prior to application of overload. A: 130% for delays 49, 135% for delays 71, 72 and 73 Inrush Pulse Tolerance (typ) The following table provides a comparison of inrush pulse tolerance with and without the inertial delay feature for each of the 50/60Hz delays. Pulse tolerance is defined as a single pulse of half sine wave peak current amplitude of 8 milliseconds duration that will not trip the circuit breaker. 174 APL/UPL, 205/295 - Operating Characteristics All trip curves and trip currents are specified with the breaker mounted in the normal vertical position at ambient temperature of +25C. Protectors do not carry current prior to application of overload. http://airpax.sensata.com/ Delay Pulse Tolerance 61, 62 12 times (approx.) rated current 61F, 62F 20 times (approx.) rated current 64, 65, 66 20 times (approx.) rated current 64F, 65F, 66F 35 times (approx.) rated current A choice of delays are offered for 60Hz applications. Delays 60 and 69 are fast acting non-delayed tripping to protect sensitive electronic equipment (not recommended where known inrush exists). Delay 61 has a short delay for general purpose applications. Delay 62 is long enough to start certain types of motors and most transformers and capacitor loads. Delay 63 is an extra long delay primarily for special motor applications. Note: These limits do not apply to dual coil and tapped coil units 10000 10000 1000 1000 DELAY 60 DELAY 61 TIME IN SECONDS 10 1 MAY TRIP 100 MAY TRIP 100 TIME IN SECONDS APL/UPL, 205/295 60Hz Delay Curves (typ) PULSE TOLERANCES 10 1 .1 .1 .01 .01 .001 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 0 100 150 200 125 300 500 600 700 800 900 1000 900 1000 MAY TRIP 1000 MAY TRIP 10000 10000 1000 DELAY 62 DELAY 69 100 TIME IN SECONDS 100 TIME IN SECONDS 400 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT 10 1 10 1 .1 .1 .01 .01 .001 .001 0 100 150 200 125 300 400 500 600 700 PERCENT OF RATED CURRENT http://airpax.sensata.com/ 800 900 1000 0 100 150 200 125 300 400 500 600 700 800 PERCENT OF RATED CURRENT APL/UPL, 205/295 Series - Delay Curves 175 Delays 64, 65 and 66 Delays 64, 65 and 66 are the latest 50/60Hz delays with short, medium and long trip times respectively. The patented protector design provides both increased tolerance to high inrush induced nuisance tripping and longer trip times at 600 percent. These delays are ideally suited for applications where thermal devices are presently used, such as motor protection or where short duration, high inrush currents are experienced. As shown in a typical motor start-up curve, the delay 66 will provide locked rotor and overload protection. Nuisance tripping is avoided since acceptable short periods of overload will not trip the protector. 10000 1000 1000 DELAY 64 100 TIME IN SECONDS TIME IN SECONDS 100 DELAY 65 MAY TRIP MAY TRIP 10000 10 1 10 1 .1 .1 .01 .01 .001 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 0 100 150 200 125 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT MAY TRIP 10000 1000 DELAY 66 TIME IN SECONDS 100 10 1 .1 .01 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 176 APL/UPL, 205/295 - Delay Curves http://airpax.sensata.com/ APL/UPL, 205/295 DC/50/60Hz Delay Curves (typ) (Multi-frequency) A choice of delays is offered for combined DC and 50/60Hz operation. Delay 70 is fast acting, non-delayed tripping to protect sensitive electronic equipment (not recommended where known inrush exists). Delay 71 has a short delay for general purpose applications. Delay 72 is long enough to start certain types of motors and most transformer and capacitor loads. Delay 73 is an extra long delay primarily for special motor applications. 10000 10000 1000 DELAY 70 100 10 TIME IN SECONDS MAY TRIP TIME IN SECONDS 100 DELAY 72 MAY TRIP 1000 1 .1 10 1 .1 .01 .01 .001 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 0 100 150 200 125 300 PERCENT OF RATED CURRENT 10000 500 600 700 800 900 1000 900 1000 1000 MAY TRIP DELAY 71 DELAY 73 100 TIME IN SECONDS 100 MAY TRIP 10000 1000 TIME IN SECONDS 400 PERCENT OF RATED CURRENT 10 1 .1 10 1 .1 .01 .01 .001 .001 0 100 150 200 125 300 400 500 600 700 PERCENT OF RATED CURRENT http://airpax.sensata.com/ 800 900 1000 0 100 150 200 125 300 400 500 600 700 800 PERCENT OF RATED CURRENT APL/UPL, 205/295 Series - Delay Curves 177 10000 MAY TRIP 1000 DELAY 52 100 TIME IN SECONDS DC Delay Curves (typ) A choice of delays is offered for DC applications. Delays 50 and 59 provide fast acting, non-delayed tripping to protect sensitive electronic equipment (not recommended where known inrush exists). Delay 51 has a short delay for general purpose applications. Delay 52 is long enough to start certain types of motors. Delay 53 is an extra long delay used primarily for special motor applications. 10 1 .1 .01 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 900 1000 900 1000 PERCENT OF RATED CURRENT 10000 10000 1000 DELAY 50 DELAY 53 100 TIME IN SECONDS 100 10 MAY TRIP TIME IN SECONDS MAY TRIP 1000 1 10 1 .1 .1 .01 .01 .001 .001 0 100 150 200 125 300 400 500 600 700 800 900 0 1000 100 150 200 125 300 600 700 800 1000 DELAY 51 DELAY 59 MAY TRIP 1000 100 TIME IN SECONDS 100 TIME IN SECONDS 500 10000 10000 10 1 10 1 .1 .1 .01 .01 .001 .001 0 100 150 200 125 300 400 500 600 700 800 900 PERCENT OF RATED CURRENT 178 400 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT APL/UPL, 205/295 - Delay Curves 1000 0 100 150 200 125 300 400 500 600 700 800 PERCENT OF RATED CURRENT http://airpax.sensata.com/ APL/UPL, 205/295 10000 1000 MAY TRIP DELAY 42 100 TIME IN SECONDS 400Hz Delay Curves (typ) A choice of delays is offered for 400Hz applications. Delays 40 and 49 are fast acting, non-delayed tripping to protect sensitive electronic equipment (not recommended where known inrush exists). Delay 41 has a short delay for general purpose applications. Delay 42 is long enough to start certain types of motor and most transformers and capacitor loads. Delay 43 is an extra long delay primarily for special motor applications. 10 1 .1 .01 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 900 1000 900 1000 PERCENT OF RATED CURRENT MAY TRIP 1000 1000 DELAY 40 TIME IN SECONDS TIME IN SECONDS DELAY 43 100 100 10 1 10 1 .1 .1 .01 .01 .001 MAY TRIP 10000 10000 .001 0 100 150 200 125 300 400 500 600 700 800 900 0 1000 100 150 200 125 300 400 500 600 700 800 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT 10000 10000 1000 1000 DELAY 49 DELAY 41 100 10 1 10 MAY TRIP TIME IN SECONDS MAY TRIP TIME IN SECONDS 100 1 .1 .1 .01 .01 .001 0 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 100 150 200 130 300 400 500 600 700 800 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT http://airpax.sensata.com/ APL/UPL, 205/295 Series - Delay Curves 179 APL/UPL Specifications Trip Free Will trip open on overload, even when the handle is forcibly held on or restrained. This prevents operator from damaging the circuit by holding the handle in the ON position. Dual Coil Ratings 5-65Vdc and 5-250Vac for three terminal configurations. 5-120Vac and 5-120Vdc for four terminal configurations. Not available in delays 64, 65 and 66. Trip Indication The operating handle moves positively to the OFF position on overload. APL Ratings Ambient Operation Operates normally in temperatures between -40C and +85C. Insulation Resistance Not less than 100 megohms at 500Vdc. Dielectric Strength Withstands 1500Vac at 60Hz for 60 seconds or 1800Vac for one second from terminal to terminal, and from auxiliary switch terminal to main terminal. Endurance Per UL 1077 (6000 operations at rated load plus 4000 operations with no load). Tested at a maximum rate of 6 times per minute. Rating above 50 amperes operate a minimum of 5000 operations. Shock Withstands 100G or more without tripping while carrying full rated current per MIL-Std-202, Method 213, Test Condition I. Instantaneous types (delay 40, 50, 60 and 49, 59, 69) and dual coil configurations are tested at 80% of rated current. Protectors mounted in the handle down position are to be tested with no current applied (per MIL-PRF-55629). Vibration Withstands 10G without tripping while carrying full rated current per MIL-Std-202, Method 204, Test Condition A. Instantaneous types (delay 40, 50, 60 and 49, 59, 69) and dual coil configurations are tested at 80% of rated current. Approximate Weight Per Pole 0.050-50 amperes, 65Vdc, 250Vac maximum, 50/60Hz or 400Hz. 51-100 amperes at 65Vdc and 120Vac maximum. Ratings of 0.050-20 amperes at 277Vac, 50/60Hz are available upon request. Auxiliary Switch Ratings (APL/UPL, 205/295) REC4 and REC5 are rated at 10 amperes, 250Vac or 3 amperes, 50Vdc. REG4 and REG5 are rated at 0.1 amperes, 125Vac. UPL Ratings UPL protectors are UL STD. 1077 (File No. E-66410) and CSA STD. C22.2-No. 235 (File No. LR-26229) recognized as supplementary protectors in the following configurations and ratings. Consult factory for further information. Configurations Series, Shunt, Relay, Auxiliary Switch, Switch Only, Dual Coil, No Voltage. Poles One through nine. Moisture Resistance Designed to meet the requirements of MIL-PRF-55629 when tested in accordance with Method 106 of MIL-Std-202. Salt Spray (Corrosion) Designed to meet the requirements of MIL-PRF-55629 when tested in accordance with Method 101 of MIL-Std-202. RECOMMENDED TORQUE SPECIFICATIONS Ounces Grams Component Torque (in-lbs) 3.7 103 6-32 Mounting Inserts 6 to 8 M3 Mounting Screws 4 to 5 10-32 Screw Terminals 13 to 14 M5 Stud Terminals 13 to 14 1/4 - 20 Stud Terminals 25 to 30 Where applicable, mechanical support must be provide to the terminals when applying torque 180 APL/UPL, 205/295 - APL/UPL Specifications http://airpax.sensata.com/ APL/UPL, 205/295 APL/UPL - Nominal DCR / IMPEDANCE Current Ratings (Amps) Resistance (ohms) Impedance (ohms) Impedance (ohms) DC Delays AC, 50/60Hz Delays AC, 400Hz Delays 50 59 51, 52, 53 Dual Coil 51, 52, 53 60 69 600, 61, 62 71, 72, 73 64, 65, 66 Dual Coil 61, 62 40, 49 41, 42, 43 0.05 162 540 460 640 174 419 582 691 1975 1195 0.10 35.4 105 155 150 42.5 103.4 119.0 160 495 284 0.50 1.2 4.2 4.5 5.6 1.9 4 4.1 6.2 22 12 1.0 .236 1.02 1.2 1.41 .41 .955 1.08 1.56 5.01 2.72 5.0 .021 .048 .059 .070 .030 .045 .048 .068 .240 .140 10.0 .0060 .0121 .0140 .0160 .0075 .0105 .0134 .0174 .0520 .0283 15.0 .0040 .0067 .0092 .0100 .0038 .0068 .0070 .0120 .0260 .0140 20.0 .0032 .0047 .0052 .0070 .0024 .0049 .0050 .0069 .0140 .0088 30.0 .0021 .0036 .0036 .0040 .0022 .0032 .0035 .0037 .0079 .0043 50.0 .0020 .0024 .0026 .0023 .0020 .0020 .0025 .0030 .0036 .0028 Notes: DCR and impedance based on 100% rated current applied and stablized a minimum of one hour. Tolerance: .02 amperes to 2.5 amperes, 20%; 2.6 amperes to 20 amperes, 25%; 21 amperes to 50 amperes, 50%. Consult factory for special values and for coil impedance of delays not shown APL/UPL - RATINGS Configurations Series and Shunt Relay Switch Only Current Ratings (Amps) Maximum Voltage Ratings Interrupting Capacity (Amps) Series Fuse 0.050 - 50 65Vdc 5000 None 0.050 - 100 65Vdc 3000 None 0.050 - 60 120Vac (50/60Hz) 1000 None 0.050 - 50 120Vac (50/60Hz) 5000 4X (120 max.) 0.050 - 20 277Vac (50/60Hz) 5000 4X 0.050 - 50 250Vac (50/60Hz) 5000 4X (120 max.) 0.050 - 50 120Vac (400Hz) 1500 None 21 - 50 250Vac (400Hz) 1000 None 0.050 - 20 250Vac (400Hz) 2100 None 0.050 - 50 50Vdc -- -- 0.050 - 50 120Vac (50/60Hz) -- -- 0.050 - 50 120Vac (400Hz) -- -- 0.050 - 50 250Vac (50/60Hz-400Hz) -- -- 50 amperes max. 65Vdc -- -- -- 100 amperes max. 32Vdc -- -- -- 50 amperes max. 250Vac (50/60Hz) -- -- -- 50 amperes max. 250Vac (400Hz) -- -- -- Notes: DC units do not require series fusing. 277Vac: A circuit protector with this voltage rating is intended for 277Vac per pole single phase source only usage. (e.g.) If a two or three pole breaker is marked 277Vac, all line terminals must be connected to the same phase, assuming the 277Vac is taken from line to neutral of a three phase 277/480Vac system. http://airpax.sensata.com/ APL/UPL, 205/295 Series - APL/UPL Specifications 181 205/295 Specifications Trip Free Will trip open on overload, even when the handle is forcibly held on or restrained. This prevents operator from damaging the circuit by holding the handle in the ON position. Dual Coil Ratings 5-65Vdc and 5-250Vac for three terminal configurations. 5-120Vac and 5-120Vdc for four terminal configurations. Not available in delays 64, 65 and 66. Trip Indication The operating handle moves positively to the OFF position on overload. 295 Ratings 0.05-100 amperes, 65Vdc, 0.050-60 amperes, 250Vac maximum, 50/60Hz or 400Hz. 51-100 amperes at 65Vdc and 120Vac maximum. 30 amperes at 277/480Vac for 3 phase WYE Connected applications only. Ratings to 20 amperes at 277Vac, 50/60Hz are available upon request. Ambient Operation Operates normally in temperatures between -40C and +85C. Insulation Resistance Not less than 100 megohms at 500Vdc. Dielectric Strength Withstands 1500Vac at 60Hz for 60 seconds or 1800Vac for one second from terminal to terminal, and from auxiliary switch terminal to main terminal. Endurance Per UL 1077 (6000 operations at rated load plus 4000 operations with no load). Tested at a maximum rate of six times per minute. Rating above 50 amperes operate a minimum of 5000 operations. 205 Ratings 205 protectors are UL (File No. E-66410) and CSA (File No. LR-26229) recognized as Component Appliance Controls in the following configurations and ratings. 205D Ratings 205D protectors are UL-1500 (Marine Ignition Protection) recognized at 65Vdc or 250Vac to 60 amperes maximum at 1000 AIC. Consult factory for application details. Configurations Series, Shunt, Relay, Auxiliary Switch, Switch Only. Poles One through nine. 205/295 - Nominal DCR / IMPEDANCE Current Ratings (Amps) Resistance (ohms) DC Delays Impedance (ohms) Impedance (ohms) AC, 50/60Hz Delays AC, 400Hz Delays 50 59 51, 52, 53 Dual Coil 51, 52, 53 0.05 162 540 506 576 174 419 582 691 1975 1195 0.10 35.4 105 125 150 42.5 103.4 119.0 160 495 284 0.50 1.2 4.2 4.5 5.6 1.9 4 4.1 6.2 22 12 1.0 .236 1.02 1.2 1.41 .41 .955 1.08 1.56 5.01 2.72 5.0 .021 .048 .059 .070 .030 .045 .048 .068 .240 .140 10.0 .0060 .0121 .0140 .0160 .0075 .0105 .0134 .0174 .0520 .0283 15.0 .0040 .0067 .0092 .0100 .0038 .0068 .0070 .0120 .0260 .0140 20.0 .0032 .0047 .0052 .0070 .0024 .0049 .0050 .0069 .0140 .0088 30.0 .0021 .0036 .0036 .0040 .0022 .0032 .0035 .0037 .0079 .0043 50.0 .0020 .0024 .0026 .0023 .0020 .0020 .0025 .0030 .0036 .0028 60 69 600, 61, 62 71, 72, 73 64, 65, 66 Dual Coil 61, 62 40, 49 41, 42, 43 Notes: DCR and impedance based on 100% rated current applied and stablized a minimum of one hour. Tolerance: .02 amperes to 2.5 amperes, 20%; 2.6 amperes to 20 amperes, 25%; 21 amperes to 50 amperes, 50%. Consult factory for special values and for coil impedance of delays not shown 182 APL/UPL, 205/295 - 205/295 Specifications http://airpax.sensata.com/ APL/UPL, 205/295 205/295 - RATINGS Configurations Series and Shunt Series Only Relay Switch Only Current Ratings (Amps) Maximum Voltage Ratings Interrupting Capacity (Amps) Series Fuse 0.050 - 50 65Vdc 5000 None 0.050 - 100 65Vdc 3000 None 0.050 - 60 120Vac (50/60Hz) 1000 None 0.050 - 50 120Vac (50/60Hz) 5000 4X (125 max.) 0.050 - 20 277Vac (50/60Hz) 5000 4X 0.050 - 50 250Vac (50/60Hz) 5000 4X (125 max.) 0.050 - 50 120Vac (400Hz) 1500 None 21 - 50 250Vac (400Hz) 1000 None 0.050 - 20 250Vac (400Hz) 2100 None 0.050 - 30 277/480Vac (50/60Hz) 5000 4X (80A max.) 0.050 - 30 277/480Vac (50/60Hz) 1500 None 0.050 - 50 50Vdc -- -- 0.050 - 50 120Vac (50/60Hz) -- -- 0.050 - 50 120Vac (400Hz) -- -- 0.050 - 50 250Vac (50/60Hz-400Hz) -- -- 50 amperes max. 65Vdc -- -- -- 100 amperes max. 32Vdc -- -- -- 50 amperes max. 250Vac (50/60Hz) -- -- -- 50 amperes max. 250Vac (400Hz) -- -- -- Notes: DC units do not require series fusing. 277Vac: A circuit protector with this voltage rating is intended for 277Vac per pole single phase source only usage. (e.g.) 60 ampere units and 277/480Vac units require a 2 x 4 inch interphase barrier for mulitpole units. If a two or three pole protector is marked 277Vac, all line terminals must be connected to the same phase, assuming the 277 Vac is taken from line to neutral of a three phase 277/480Vac system. http://airpax.sensata.com/ APL/UPL, 205/295 Series - 205/295 Specifications 183 205/295, MPL Specifications Auxiliary Switch Ratings (APL/UPL, 205/295) REC4 and REC5 are rated at 10 amperes, 250Vac or 3 amperes, 50Vdc. REG4 and REG5 are rated at 0.1 amperes, 125Vac. Moisture Resistance Designed to meet the requirements of MIL-PRF-55629 when tested in accordance with Method 106 of MIL-Std-202. Salt Spray (Corrosion) Designed to meet the requirements of MIL-PRF-55629 when tested in accordance with Method 101 of MIL-Std-202. MPL Ratings MPL protectors are UL (File No. E-41607) and CSA (File No. LR-26229) recognized as manual, across the line starters, in the following configurations and ratings. Consult factory for further information. 184 APL/UPL, 205/295 - MPL Specifications Configurations Series only with and without auxiliary switch. Poles One, two or three. Shock Withstands 100G or more without tripping while carrying full rated current per MIL-Std-202, Method 213, Test Condition I. Instantaneous types (delay 40, 50, 60 and 49, 59, 69) are tested at 80% of rated current. Breakers mounted in the handle down position are to be tested with no current applied (per MIL-PRF-55629). Vibration Withstands 10G without tripping while carrying full rated current per MIL-Std-202, Method 204, Test Condition A. Instantaneous types (delay 40, 50, 60 and 49, 59, 69) are tested at 80% of rated current. http://airpax.sensata.com/ APL/UPL, 205/295 RECOMMENDED TORQUE SPECIFICATIONS Approximate Weight Per Pole Component Torque (in-lbs) Ounces Grams 6-32 Mounting Inserts 6 to 8 3.7 103 M3 Mounting Screws 4 to 5 10-32 Screw Terminals 13 to 14 M5 Stud Terminals 13 to 14 1/4 - 20 Stud Terminals 25 to 30 Where applicable, mechanical support must be provide to the terminals when applying torque MPL - RATINGS Current Ratings (Amps) Maximum Voltage Ratings Horsepower, Single Phase Ratings Three Phase (Note A) 0.050 - 50 65Vdc 1 -- 0.050 - 50 120Vac (50/60Hz) 3 7.5 0.050 - 20 240Vac (50/60Hz) 3 5 0.050 - 20 277Vac (50/60Hz) 3 5 Note: AC units require maximum of 4X rated series fusing: DC units do not require series fusing. A: Two or three poles breaking http://airpax.sensata.com/ APL/UPL, 205/295 Series - MPL Specifications 185 APL/UPL DECISION TABLES How to Order The ordering code for APL/UPL circuit protectors may be determined by following the steps in the decision tables shown here. The coding given permits a self-assigning part number; other configurations may require a factory assigned part number. Typical examples are units with mixed ratings, combinations of styles or constructions not listed in the third decision table, etc. With these, it is suggested that order entry be by description and/or drawings and a part number will be assigned. Additionally, it is a standard policy to establish a factory assigned part number wherever a descriptive drawing exists to provide cross reference, traceability and manufacturing control. When specifying a protector for AC motor start or high inrush applications, the peak amplitude and surge duration should be specified for factory assistance in rating selection. Notes: AThe most common current values for 100% of rated current are those listed. Please consult an Airpax office orsales representative for other values. BAll APL/UPL protectors are constructed with stainless steel springs and plated parts. As noted in the specifications, all meet normal requirements for moisture and salt spray resistance. If fungus resistance is required in addition to moisture and salt spray resistance, special procedures and markings are employed. CTerminals will be supplied as #10-32 threaded studs up to 50 amperes. Above this amperage terminals will be 1/4-28 threaded studs. All standard units will be supplied with a hex nut and two flat washers on each threaded terminal. DWhen metric threaded inserts are specified, breakers rated at 50 amperes and below will be supplied with metric threaded terminals. For breakers rated above 50 amperes, 1/4 -28 threaded terminals will be supplied. E Black handle standard. For example, the code shown is the code for a two pole UPL protector with series trip, 20 ampere rating, 50/60Hz. short time delay construction in all poles. To determine the ordering number for your particular APL/UPL unit, simply follow the steps shown. You may use this number to place an order or as a reference for further questions you may have. 186 APL/UPL, 205/295 - APL/UPL Decision Tables http://airpax.sensata.com/ APL/UPL, 205/295 UPL 11 - 1 - 61- 203 http://airpax.sensata.com/ APL/UPL, 205/295 Series - APL/UPL Decision Tables 187 205/295 DECISION TABLES How to Order The ordering code for 205/295 circuit protectors may be determined by following the steps in the decision tables shown here. For example, the code shown is the code for a UL recognized, two pole protector with series trip, 20 ampere rating at 240Vac max., 50/60Hz short time delay construction in all poles. To determine the ordering number for your particular 205/295 unit, simply follow the steps shown. You may use this number to place an order or as a reference for further questions you may have. 1 First Decision 3 Third Decision Internal Configuration -0 Switch only (Omit 4th and 5th decisions) -1 Series -1REC4 Series with auxiliary switch *.110 quick connect terminals -1REC5 Series wtih auxiliary switch *.187 quick connect terminals -1REG4 Series with auxiliary switch (gold contacts) *.110 quick connect terminals -1RS Series with alarm switch electrical trip turret terminals -3 Shunt -5 Relay Type 205 Dust sealed protector UL ratings and construction 205D Marine ignition protected 295 Dust sealed protector Multi-pole units with mixed construction, poles numbered left to right when viewed from terminal end. *Can be used for Solder Terminals also. 2 Second Decision Poles -0* Switch only (no overload sensing) -1 Single pole unit -11 Two pole unit -111 Three pole unit -1111 Four pole unit Example: 205 - 11 -1 - 61- 4 - 203 1 2 3 4 5 6 *Use 0 in place of 1 when ordering switch only. Notes: AThe most common current values for 100% of rated current are those listed. Please consult an Airpax office or sales representative for other values. BAll 205/295 protectors are constructed with stainless steel springs and plated parts. As noted in the specifications, all meet normal requirements for moisture and salt spray resistance. If fungus resistance is required in addition to moisture and salt spray resistance, special procedures and markings are employed. DFor detailed barrier and wiring information, request Airpax specification AM-433. EWhen metric threaded inserts are specified, breakers rated at 50 amperes and below will be supplied with metric threaded terminals. For breakers rated above 50 amperes, 1/4-28 threaded terminals will be supplied. FAvailable in multi-pole, series only for multiphase applications. CTerminals will be supplied as #10-32 threaded studs up to 50 amperes. Above this amperage terminals will be 1/4 -28 threaded studs. All standard units will be supplied with a hex nut and 2 flat washers on each threaded terminal. 188 APL/UPL, 205/295 - APL/UPL Decision Tables http://airpax.sensata.com/ APL/UPL, 205/295 6 Sixth Decision (Note A) Nominal Amperage Rating Current Code 5 Fifth Decision Maximum Voltage Rating 4 Fourth Decision Hz and Delay 40* 400Hz 150% instant trip 41* 400Hz short delay 42* 400Hz long delay 43* 400Hz motor start 49* 50 400Hz 130% instant trip DC 150% instant trip -1 32Vdc -2 65Vdc -3 120Vac -4 250Vac (single phase) -4A 250Vac multi-phase style B barrier required -5 277/480Vac* (series only - notes D and F.) Y connection only -6 277 Vac* -7 125/250Vac (205 D) -8 65Vdc/250Vac (70-73 delay) *30 Amp max. Ratings (Amps) 101 .100 251 .250 501 .500 751 .750 102 1.0 252 2.50 502 5.0 752 7.50 103 10.0 153 15.0 203 20.0 303 30.0 353 35.0 403 40.0 51 DC short delay 52 DC long delay 503 *50.0 53* DC motor start 603 60.0 59 DC 125% instant trip 703 70.0 60 50/60Hz 150% instant trip 803 80.0 61 50/60Hz short delay 903 90.0 62 50/60Hz long delay 104 *100.0 64 50/60Hz short delay (high pulse) Standard current ratings listed. For other ratings, please consult the factory. 65 50/60Hz long delay (high pulse) *Switch only ratings. 66* 50/60Hz motor start (high pulse) 69 50/60Hz 125% instant trip 70* DC-50/60Hz 150% instant trip 71* DC-50/60Hz short delay 72* DC-50/60Hz long delay 73* DC-50/60Hz motor start delay For addition of inertial delay, add an "F" to any delay number, except 40, 50, 60 and 70. *Not available above 50 amperes. http://airpax.sensata.com/ 7 Seventh Decision Optional -A Metric thread mounting inserts and terminals (note E) -H International handle markings -M Fungus (note B) -O Black handle (standard handle color is white) APL/UPL, 205/295 Series - APL/UPL Decision Tables 189