1
3-Phase AC Filters / DC Filters FMAC RAIL
https://www.schurter.com /PG80
EMC Products
1- stage filter for 3-phase systems, DIN rail mounting
See below:
Approvals and Compliances
Description
- 3 phase line filter with standard attenuation
Applications
- Especially designed for electric switch and control cabinets
- Suitable for use in equipment according to IEC/UL 62368-1
Weblinks
pdf data sheet, html datasheet, General Product Information, Approvals,
Distributor-Stock-Check, Detailed request for product, Microsite
Technical Data
Rated Current 3 - 20 A @ Ta 40 °C
Rated voltage 480 VAC, 50/60 Hz
Approval for 3 - 20 A @ Ta 40 °C / 480 VAC; 50/60 Hz
Overload Current 1.5 x Ir for 1 minute, per hour
Leakage Current standard < 0.5 mA (440 V / 50 Hz)
Dielectric Strength 480 VAC:
2.25 kVDC between L-L
3 kVDC between L-PE
Test voltage (2 sec)
Number of Filter Stages 1-stage
Weight 0.4 kg
Material: Housing Metal
Sealing Compound UL 94V-0
Mounting DIN rail mounting
Terminal Bolts and nuts M4, Quick connect ter-
minal for PE
Operating Temperature -25 °C to 100 °C
Climatic Category 25/100/21 acc. to IEC 60068-1
Degree of Protection IP20 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class I acc. to IEC 61140
MTBF > 200'000 h acc. to MIL-HB-217 F
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree-
ments by SCHURTER.
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: FMAC
Approval Logo Certificates Certification Body Description
VDE Approvals VDE Certificate Number: 40030735
UL Approvals UL UL File Number: E72928
Application standards
Application standards where the product can be used
Organization Design Standard Description
Designed for applications acc. IEC/UL 62368-1 IEC 62368-1 includes the basic requirements for safety of audio, video,
information technology and office equipment.
2
3-Phase AC Filters / DC Filters
FMAC RAIL https://www.schurter.com /PG80
EMC Products
Compliances
The product complies with following Guide Lines
Identification Details Initiator Description
CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
RoHS SCHURTER AG Directive RoHS 2011/65/EU, Amendment (EU) 2015/863
China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
Dimension [mm]
(6.5)
max. 61
1)
(75)
max. 102
EN 60715
35x7.5
2)
11.511.513
max. 61
27 16
max. 48
L2L3
L1
L2’L3L1
3)
4)
1) Line
2) Load
3) Tightening torque 0.6-0.8 Nm, Screw 4mm²
4) Quick connect terminal 6.3x0.8mm
Technical data to the filter components
Rated Current [A] Rated Voltage [VAC] L [mH] C1 [nF] C2 [nF]
10 - 1 100 4.7
20 - 0.22 100 22
3 - 3 100 4.7
6 - 2 100 4.7
3
3-Phase AC Filters / DC Filters FMAC RAIL
https://www.schurter.com /PG80
EMC Products
Diagrams
1)
2)
1) Line
2) Load
Attenuation Loss - - - - 50 differential mode _____ 50 common mode
Standard version
3 A 6 A 10 A 20 A
All Variants
Rated Current [A] Tripped
Power Dissi-
Leakage Cur-
rent [mA] @ 440V,
Contact Resistance
[m]
Weight
[g]
Screw clamps
[mm2] 2)
Order Number
10 2.6 0.02 8.5 395 g 4FMAC-3RYB-1010
20 4.9 0.08 4.1 395 g 4FMAC-3RYB-2010
3 1.1 0.02 40 355 g 4FMAC-3RYB-0310
6 2.3 0.02 21 375 g 4FMAC-3RYB-0610
Most Popular.
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
1) Leakage current according IEC 60939-1
2) Maximum conductor cross section (wire gauge) to be used; a comparative table for AWG and mm² values can be found in
the general product information
https://www.schurter.com/en/FAQ#10
Packaging unit 5 Pcs
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
17.08.2020