3−line filters
for converters and power electronics
520/300 V, 50/60 Hz, 35 ... 230 A, 50 °C
Ordering code: B84143A*R410, B84143B*R410
Date: 2009−08−03
Version: 02
EPCOS AG 2008. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the
information contained therein without EPCOS’ prior express consent is prohibited.
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
Construction
3−line filter
Metal case
Book size
Features
High insertion loss
Easy to install
Compact design
Degree of protection IP 20 1)
Design complies with IEC 60939, UL 1283, CSA 22.2 No.8
Optimized for long motor cable and operation under full load
B84143A*R410: UL− and cUL approval
Applications
Frequency converters and regenerative frequency converters (AFE) for motor drives, e.g.
elevators
machine tool building
pumps
traction systems
conveyor systems
HVAC systems (heating, ventilation and air conditioning)
Terminals
Finger−save terminal blocks
Marking
Marking on component:
manufacturers logo, ordering code, rated voltage, rated frequency, rated current,
rated temperature, climatic category, date code
Minimum marking on packaging:
manufacturers logo, ordering code, date code, quantity
1) To IEC 60529:2001
Please read Important notes and Cautions and
warnings at the end of this document.
Page 2 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
Typical circuit diagram of B84143A0035R410, B84143A0200R410, B84143A0230R410
LINE LOAD
Typical circuit diagram of B84143A0050R410, B84143A0080R410,
B84143A0110R410, B84143A0150R410
LINE LOAD
Typical circuit diagram of B84143B0200R410, B84143B0230R410
LINE LOAD
Please read Important notes and Cautions and
warnings at the end of this document.
Page 3 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
Technical data and measuring conditions
Rated voltage UR520/300 V AC
Rated frequency fR50/60 Hz
Test voltage line to line for 2 s Utest 2240 V DC
Test voltage line to case for 2 s Utest 2720 V DC
Rated temperature TR50 °C
Overload capability (thermal)
for 3 min per hour or
for 30 s per hour 1.5 x IR
2.5 x IR
Climatic category (IEC 60068−1) 25/100/21
Characteristics and ordering codes
UR
AC IRTerminal
cross
section
Ileak 2) Rtyp Approx.
weight Ordering code Approvals
V A mm2mA mkg
520/300 35 10 14 2.9 2.5 B84143A0035R410 X X
50 25 15 1.6 4.5 B84143A0050R410 X X
80 50 15 0.9 8.5 B84143A0080R410 X X
110 50 15 0.65 9.0 B84143A0110R410 X X
150 95 15 0.6 13.5 B84143A0150R410 X X
200 95 10 0.3 14.0 B84143A0200R410 X X
230 95 10 0.25 14.5 B84143A0230R410 X X
200 95 18 0.39 19.0 B84143B0200R410
230 95 18 0.35 19.0 B84143B0230R410
X = approval granted
2) Calculation according draft proposal IEC 60939−1 Ed. 3 (2008−10−29), annex A, ”Calculation of leakage current”.
Please read Important notes and Cautions and
warnings at the end of this document.
Page 4 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
Dimensional drawings
B84143A0035R410
Terminals 10mm2
Tightening torque 1.5 − 1.8Nm
Terminals 10mm2
Tightening torque 1.5 − 1.8Nm
Marking
Load
Line
All dimensions in mm
Tightening torque 20.1Nm
PE M5 x 19
View A
Tightening torque 20.1Nm
PE M5 x 19
Please read Important notes and Cautions and
warnings at the end of this document.
Page 5 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
B84143A0050R410
Terminals 25mm2
Tightening torque 4 − 4.5Nm
Terminals 25mm2
Tightening torque 4 − 4.5Nm
Marking All dimensions in mm
PE M6 x 23.5
Tightening torque 30.15mm
PE M6 x 23.5
Tightening torque 30.15mm
LoadLine
View A
Please read Important notes and Cautions and
warnings at the end of this document.
Page 6 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
B84143A0080R410, B84143A0110R410
Terminals 50mm2
Tightening torque 6−8Nm
Marking
All dimensions in mm
PE M10 x 38
Tightening torque 101mm
PE M10 x 38
Tightening torque 101mm
Terminals 50mm2
Tightening torque 6−8Nm
LoadLine
Please read Important notes and Cautions and
warnings at the end of this document.
Page 7 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
B84143A0150R410, B84143A0200R410, B84143A0230R410
PE M10 x 38
Tightening torque 101mm
PE M10 x 38
Tightening torque 101mm
Terminals 95mm2
Tightening torque 15−20Nm
Terminals 95mm2
Tightening torque 15−20Nm Marking
All dimensions in mm
LoadLine
Please read Important notes and Cautions and
warnings at the end of this document.
Page 8 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
B84143B0200R410, B84143B0230R410
PE M10 x 38.5
Tightening torque 101mm PE M10 x 38.5
Tightening torque 101mm
Terminals 95mm2
Tightening torque 15−20Nm
Terminals 95mm2
Tightening torque 15−20Nm
Marking
All dimensions in mm
LoadLine
View A
Please read Important notes and Cautions and
warnings at the end of this document.
Page 9 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143A0080R410
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84143A0110R410
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84143A0050R410
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84143A0035R410
f
104105106107108
Hz
dB
0
20
40
60
80
100
Please read Important notes and Cautions and
warnings at the end of this document.
Page 10 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143A0230R410
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84143A0200R410
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84143A0150R410
f
104105106107108
Hz
dB
0
20
40
60
80
100
Please read Important notes and Cautions and
warnings at the end of this document.
Page 11 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143B0230R410
f
104105106107108
Hz
dB
0
20
40
60
80
100
B84143B0200R410
f
104105106107108
Hz
dB
0
20
40
60
80
100
Please read Important notes and Cautions and
warnings at the end of this document.
Page 12 of 14
B84143−*−R410−02−7659
3−line filters B84143A*R410, B84143B*R410
for converters and power electronics
Caution and warnings
Please note the advices in our data book “EMC Filters” (latest edition); attention should
be paid to the chapter “General safety notes”.
It shall be ensured that only qualified persons (electricity specialists) are engaged on work
such as planning, assembly, installation, operation, repair and maintenance. They must
be provided with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge.
Dangerous voltages can continue to exist at the filter terminals for longer than five min-
utes even after the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is
installed and the last to be disconnected. Depending on the magnitude of the leakage cur-
rents, the particular specifications for making the protective−earth connection must be ob-
served.
Impermissible overloading of the EMC filter, such as with circuits able to cause reso-
nances, impermissible voltages at higher frequencies etc. can lead to bodily injury and
death as well as cause substantial material damages (e.g. destruction of the filter hous-
ing).
EMC filters must be protected in the application against impermissible exceeding of the
rated currents by overcurrent protective.
In case of leakage currents > 3.5 mA you shall mount the PE conductor stationary with
the required cross section before beginning of operation and save it against disconnect-
ing. For leakage currents IL 4) < 10 mA the PE conductor must have a KU value 3) of 4.5;
for leakage currents IL 10 mA the PE conductor must have a KU value of 6.
3) The KU value (symbol KU) is a classification parameter of safety−referred failure types designed to ensure protection against hazardous
body currents and excessive heating.
A value of KU = 4.5 with respect to interruptions is attained:
− with a permanently connected protective earth circuit 1.5 mm2
− with a protective earth circuit 2.5 mm2 connected via shroud connectors (IEC 60309−2).
KU = 6 with respect to interruptions is achieved for fixed−connection lines 10 mm2 where the type of connection and line layout corre-
spond to the requirements for PEN conductors as specified in relevant standards.
4) IL = leakage current let−go
Please read Important notes and Cautions and
warnings at the end of this document.
Page 13 of 14
B84143−*−R410−02−7659
Important notes
Page 3 of 3
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As a
rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or failure
before the end of their usual service life cannot be completely ruled out in the current state
of the art, even if they are operated as specified. In customer applications requiring a very high
level of operational safety and especially in customer applications in which the malfunction or
failure of an electronic component could endanger human life or health (e.g. in accident
prevention or life-saving systems), it must therefore be ensured by means of suitable design of the
customer application or other action taken by the customer (e.g. installation of protective circuitry
or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or
failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our Material
Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed
questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products. Consequently,
we cannot guarantee that all products named in this publication will always be available.
The aforementioned does not apply in the case of individual agreements deviating from the
foregoing for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of
the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CSMP, CSSP, CTVS, DSSP, MiniBlue,
MiniCell, MKK, MLSC, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap, SIFERRIT,
SIFI, SIKOREL, SilverCap, SIMDAD, SIMID, SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse,
WindCap are trademarks registered or pending in Europe and in other countries. Further
information will be found on the Internet at www.epcos.com/trademarks.