January 2001 • Supersedes June 1997 • 2001 Hi-Tech Fuses, Inc. 4
Table 2b - Electrical Characteristics of Trans-Guard FX Fuses (Parallel Fuses)
NOMINAL
VOLTAGE
RATING
CURRENT
RATING
(A)
FUSE
MODEL NUMBER
(Order Two fuses)
RATED
MAXIMUM
VOLTAGE
MAXIMUM CONTINUOUS
CURRENT (IN AIR)
(6)
PEAK ARC
VOLTAGE
(kV)
MINIMUM
MELT I2t MAXIMUM
TOTAL I2t
(3) (4)
(kV) (2) (kV) 25O C 40O C 55O C (5) (AMP2 SEC) (AMP2 SEC)
8.3 60 HTFX230030 10.0 80.0 77.0 75.0 26 21,000
120,000
8.3 80 HTFX230040 10.0 98.0 95.0 92.0 26 34,000
180,000
8.3 100 HTFX230050 8.3
105.0 24 51,200
250,000
8.3 130 HTFX330065 8.3 158.0 154.0 151.0 24 100,800
400,000
8.3 160 HTFX330080 8.3 186.0 180.0 175.0 24 189,000
740,000
8.3 200 HTFX330100 8.3 235.0 229.0 221.0 24 313,000
1,300,000
8.3 250 HTFX330125 8.3 265.0 256.0 249.0 24 460,500
1,800,000
15.5 60 HTFX240030 17.2 80.0 77.0 75.0 45 21,000
110,000
15.5 80 HTFX240040 17.2 98.0 95.0 92.0 45 34,800
170,000
15.5 100 HTFX240050 17.2 104.0 101.0 98.0 45 51,200
310,000
15.5 130 HTFX340065 15.5 152.0 147.0 143.0 39 100,800
440,000
15.5 160 HTFX340080 15.5 172.0 167.0 160.0 39 157,500
740,000
15.5 200 HTFX340100 15.5 222.0 214.0 208.0 39 320,000
1,520,000
Notes to Table 2a and 2b:
1. Designs have a 50,000 Amps rms. Symmetrical Rating (except 3A 17.2 kV which was tested at 44 kA maximum).
2. Current ratings shown in Table 2b are achieved by using a parallel combination of two fuses (order two fuses).
To facilitate equal sharing of the interrupting duty, the two fuses should be resistance matched (± 2%) and be
mounted such that the current paths to and from each fuse are symmetrical.
3. Tabulated Maximum Total I2t values are for currents of 50,000 amperes at the nominal voltage of the fuse.
Fuses that have a Rated Maximum Voltage higher than their Nominal Voltage Rating will have a higher I2t let-
through when applied at voltages up to these higher values. For example, Maximum Total I2t values are
increased by approximately 30% when 8.3 kV fuses are applied at 10 kV and approximately 25% when 15.5 kV
fuses are used at 17.2 kV.
4. Maximum total I2t values are reduced for currents below 50,000 A. For example, at 10,000 A, maximum total I2t
values are approximately 15% less than the published values.
5. Peak arc voltages quoted are for 50,000 A currents at the rated maximum voltage listed. Reduced currents and
voltages will reduce the peak arc voltage. Consult the factory for further information.
6. Maximum continuous currents at higher ambient temperatures, and in confining enclosures:
• These may be determined by derating the fuses by 0.2% per degree C over 25O C (for example at 85O C the
derating would be 60 x .2 = 12%, making the maximum continuous current of a 30 A fuse 41 x .88 = 36.1 A).
• When fuses are applied in a confining enclosure, such as a dry-well canister, additional derating of a fuse’s
maximum continuous current is necessary. Specifically, the maximum continuous current for fuses used in a
dry-well canister, with the canister completely submerged in oil, will be reduced by an additional 2%. When
calculating the derating for temperature, as described above, the temperature of the oil surrounding the
canister should be used. For other types of enclosures, please consult the factory.
7. Reduction in the long time melting current of the fuses (approximately one hour and longer) due to higher
ambient temperatures and use in enclosures is the same as described above for "maximum continuous currents".
See time-current characteristics for melting characteristics in this time region.
Trans-Guard FX Full-Range Current-Limiting Fuses