EMD-FL-C-10 Order No.: 2866022
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866022
PHOENIX CONTACT Deutschland GmbH Page 2 / 5
http://www.phoenixcontact.de Feb 2, 2011
The operating states are indicated using colored LEDs, errors that may occur can be sent to a control system via a
floating contact or can shut down a part of the system. Some device versions are equipped with startup and response
delays in order to briefly tolerate measured values outside the set monitoring range.
Technical data
Input data
Input current range 0 mA ... 100 mA AC/DC (Connection terminals: I1 and GND)
0 A ... 1 A AC/DC (Connection terminals: I2 and GND)
0 A ... 10 A AC/DC (Connection terminals: I3 and GND)
Overload capacity 800 mA (at IN = 100 mA)
3 A (at IN = 1 A)
12 A (at IN = 10 A)
Maximum temperature coefficient < 0.1 %/K
Function Overcurrent, undercurrent, window, error memory
Min. setting range 5 % ... 95 % (From IN)
Max. setting range 10 % ... 100 % (From IN)
Setting range for response delay 0.1 s ... 10 s
Setting range for starting delay 0 s ... 10 s
Basic accuracy ± 5 % (of scale end value)
Setting accuracy ≤ 5 % (of scale end value)
Repeat accuracy ≤ 2 %
Recovery time 500 ms
Contact side
Contact type 2 floating PDT contacts
Maximum switching voltage 250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max. 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse 5 A (fast-blow)
Power supply
Supply voltage range 24 V AC ... 240 V AC -15% ... +10%
24 V DC ... 240 V DC -20% ... +25%
General data
Width 22.5 mm
Height 90 mm
Depth 113 mm