General Description:
22 AWG stranded (7x30) TC conductors, plenum, FEP insulation, twisted pairs, individually shielded
w/Beldfoil® (100% coverage), 22 AWG stranded TC drain wire, Flamarrest® jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material
222 7x30 TC - Tinned Copper
Total Number of Conductors: 4
Insulation
Insulation Material:
Insulation Material Wall Thickness (mm)
FEP - Fluorinated Ethylene Propylene 0.178
Inner Shield
Inner Shield Material:
Inner Shield Trade Name Type Inner Shield Material Coverage (%)
Beldfoil® (Z-Fold®) Tape Aluminum Foil-Polyester Tape 100
Inner Shield Drain Wire AWG:
AWG
24
Inner Shield Drain Wire Stranding: 7x32
Inner Shield Drain Wire Conductor Material: TC - Tinned Copper
Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded
Outer Jacket
Outer Jacket Material:
Outer Jacket Trade Name Outer Jacket Material Nom. Wall Thickness (mm)
Flamarrest® LS PVC - Low Smoke Polyvinyl Chloride 0.432
Overall Cable
Overall Nominal Diameter: 3.886 mm
Pair
Pair Color Code Chart:
Number Color
1Red & Black
2Green & White
Mechanical Characteristics (Overall)
Operating Temperature Range: -20°C To +90°C
Bulk Cable Weight: 28.276 Kg/Km
Page 1 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
82723 Multi-Conductor - Double-Pair Cable
Max. Recommended Pulling Tension: 204.617 N
Min. Bend Radius/Minor Axis: 44.450 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: CMP
NEC Articles: 800
CEC/C(UL) Specification: CMP
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Flame Test
UL Flame Test: NFPA 262
CSA Flame Test: FT6
Suitability
Suitability - Indoor: Yes
Plenum/Non-Plenum
Plenum (Y/N): Yes
Non-Plenum Number: 8723
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Impedance (Ohm)
36
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
141.083
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
246.075
Nominal Velocity of Propagation:
VP (%)
62
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
48.2307
Nom. Inner Shield DC Resistance:
DCR @ 20°C (Ohm/km)
49.215
Max. Operating Voltage - UL:
Voltage
300 V RMS
Page 2 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
82723 Multi-Conductor - Double-Pair Cable
Max. Recommended Current:
Description Current
10C temperature rise 2.3 Amps per conductor @25°C ambient
Put Ups and Colors:
Item # Putup Ship Weight Color Notes Item Desc
82723 877U1000 305 MT 9.072 KG NATURAL 2 PR #22 FEP FS FLRST
82723 877U2000 610 MT 18.144 KG NATURAL 2 PR #22 FEP FS FLRST
82723 877U500 152 MT 4.763 KG NATURAL 2 PR #22 FEP FS FLRST
82723 8771000 305 MT 9.072 KG NATURAL C 2 PR #22 FEP FS FLRST
82723 8775000 1,524 MT 45.359 KG NATURAL 2 PR #22 FEP FS FLRST
Notes:
C = CRATE REEL PUT-UP.
Revision Number: 3 Revision Date: 08-02-2013
© 2013 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
82723 Multi-Conductor - Double-Pair Cable