SITOP PSU8200 1ph
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
SITOP power supply
SITOP PSU8200 1ph
Manual
SITOP PSU8200 24 V/5 A
6EP3333
-8SB00-0AY0
SITOP PSU8200 24
V/10 A
6EP3334
-8SB00-0AY0
SITOP PSU8200 24 V/20 A
6EP1336
-3BA10
SITOP PSU8200 24 V/40 A
6EP3337-8SB00-0AY0
08.2016
C98130
-A7633-A1-5-7629
Overview
Safety instructions
1
Description, device design,
dimension drawing
2
Mounting/removal
3
Mounting position, mounting
clearances
4
Installation
5
Technical data
6
Safety, approvals, EMC
7
Ambient conditions
8
Applications
9
Environment
10
Service & Support
11
C98130-A7633-A1-5-7629
09/2016 Subject to change
Copyright © Siemens AG 2016.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 3
Overview
1-phase SITOP PSU8200 power supplies from the SITOP modular product line are high-
performance, regulated technology power supplies for automated systems and machines.
In addition to the basic functions required, these low-profile power supply units have an
outstanding overload behavior.
The key benefits of the product include:
Suitable for connecting to almost any 1-phase line supply around the world
AC and DC input voltages possible (only for 6EP1336-3BA10)
Output voltage can be adjusted in the range 24 - 28 (28.8) V
Power-Boost in operation with 3x rated current for 25 ms
Extra-Power with 1.5x rated current for 5 seconds for switching on loads with a high
inrush current
Especially low width without requiring any lateral mounting clearances
Ambient temperature -25 ... 70 °C (derating from 60 °C)
Selectable short-circuit response (constant current or latching shutdown)
A soft characteristic can be selected for a parallel connection (for uniform load distribution
of power supply units of the same type)
3 LEDs are used to display the operating state
Signaling contact "24 V O.K."
Overview
SITOP PSU8200 1ph
4 Manual, 08.2016, C98130-A7633-A1-5-7629
Remote "ON/OFF" contact for switching the power supply output into a no current
condition (only for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0)
To increase the system availability, these reliable power supplies can be expanded using
SITOP supplementary modules (redundancy module, selectivity module, buffer module),
as well as SITOP DC-USV modules
Ordering data
The following device versions are available:
Regulated power supply unit SITOP PSU·8200 1ph
Type
Order number
1-phase 120/230 V AC input,
24 V / 5 A output
6EP3333-8SB00-0AY0
1-phase 120/230 V AC input,
24 V / 10 A output
6EP3334-8SB00-0AY0
1 and 2-phase AC or DC input,
24 V DC / 20 A output
6EP1336-3BA10
1 and 2-phase 120/230 V AC input,
24 V /40 A output
6EP3337-8SB00-0AY0
Accessories
Type
Order number
Device identification labels 20 mm × 7 mm, Ti grey
3RT2900-1SB20
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 5
Table of contents
Overview................................................................................................................................................. 3
1 Safety instructions ................................................................................................................................... 7
2 Description, device design, dimension drawing........................................................................................ 9
2.1 Device description ..................................................................................................................... 9
2.2 Connections and terminal designation.................................................................................... 12
2.3 Potentiometer .......................................................................................................................... 14
2.4 Status displays and signaling ................................................................................................. 15
2.5 Change-over switch ................................................................................................................ 18
2.6 Remote contact ....................................................................................................................... 20
2.7 Block diagram ......................................................................................................................... 21
2.8 Dimensions and weight ........................................................................................................... 24
3 Mounting/removal ................................................................................................................................. 27
4 Mounting position, mounting clearances ................................................................................................ 29
4.1 Standard mounting position .................................................................................................... 29
4.2 Other mounting positions ........................................................................................................ 31
4.2.1 6EP3333-8SB00-0AY0 ........................................................................................................... 31
4.2.2 6EP3334-8SB00-0AY0 ........................................................................................................... 33
4.2.3 6EP1336-3BA10 ..................................................................................................................... 35
4.2.4 6EP3337-8SB00-0AY0 ........................................................................................................... 37
5 Installation ............................................................................................................................................ 39
5.1 Line-side connection ............................................................................................................... 39
5.2 Output-side connection ........................................................................................................... 41
6 Technical data ...................................................................................................................................... 43
6.1 Input ........................................................................................................................................ 43
6.2 Output ..................................................................................................................................... 45
6.3 Efficiency ................................................................................................................................. 53
6.4 Closed-loop control ................................................................................................................. 55
6.5 Protection and monitoring ....................................................................................................... 56
6.6 MTBF ...................................................................................................................................... 56
6.7 Mechanical system ................................................................................................................. 57
6.8 Accessories ............................................................................................................................. 58
6.9 Dimension drawing ................................................................................................................. 58
Table of contents
SITOP PSU8200 1ph
6 Manual, 08.2016, C98130-A7633-A1-5-7629
7 Safety, approvals, EMC ........................................................................................................................ 59
7.1 Safety ..................................................................................................................................... 59
7.2 Test voltage ............................................................................................................................ 60
7.3 Approvals ............................................................................................................................... 61
7.4 EMC ....................................................................................................................................... 62
8 Ambient conditions ................................................................................................................................ 63
9 Applications .......................................................................................................................................... 65
9.1 Parallel connection to increase power rating ......................................................................... 65
9.2 Parallel connection for redundancy ....................................................................................... 67
9.3 Series connection for increased voltage ................................................................................ 68
9.4 Overload protection in the 24 V output circuit ........................................................................ 69
9.5 Protection against short-time voltage dips ............................................................................. 70
9.6 Protecting against longer power failures ................................................................................ 71
10 Environment ......................................................................................................................................... 73
11 Service & Support ................................................................................................................................. 75
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 7
Safety instructions
1
WARNING
Correct handling of the devices
When operating electrical devices, it is inevitable that certain components will carry
dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury
as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.
Safety instructions
SITOP PSU8200 1ph
8 Manual, 08.2016, C98130-A7633-A1-5-7629
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 9
Description, device design, dimension drawing
2
2.1
Device description
SITOP PSU8200 5 A 1ph and SITOP PSU8200 10 A 1ph are primary-clocked power
supplies for connection to 1-phase AC line supplies. An electronically regulated DC voltage
that can be set via a potentiometer is available at the output of the device. The output of the
device is isolated, no-load proof and short-circuit proof. The LEDs indicate the operating
state. The operating state of the device can be processed via the signaling contact. The
device can be switched ON/OFF remotely using a remote contact.
AC input
DC output
24 - 28.8 V potentiometer
Signaling contact (13, 14), remote contact (15, 16)
Indicator lights (24 V O.K., OVERLOAD, SHUT DOWN)
A/B selector switch
DIN rail slider
Convection
Clearance above/below
Figure 2-1 Design (example: 6EP3334-8SB00-0AY0)
Description, device design, dimension drawing
2.1 Device description
SITOP PSU8200 1ph
10 Manual, 08.2016, C98130-A7633-A1-5-7629
SITOP PSU8200 20 A 1ph is a primary-clocked power supply for connection to a 1-phase or
2-phase AC line supply or a DC supply. An electronically regulated DC voltage that can be
set via a potentiometer is available at the output of the device. The output of the device is
isolated, no-load proof and short-circuit proof. The LEDs indicate the operating state. The
operating state of the device can be processed via the signaling contact.
AC/DC input
DC output
24 - 28.8 V potentiometer
Signaling contact (13, 14)
Indicator lights (24 V O.K., OVERLOAD, SHUT DOWN)
A/B selector switch
DIN rail slider
Convection
Clearance above/below
Figure 2-2 Design 6EP1336-3BA10
Description, device design, dimension drawing
2.1 Device description
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 11
SITOP PSU8200 40 A 1ph is a primary-clocked power supply for connection to a 1-phase or
2-phase AC line supply. An electronically regulated DC voltage that can be set via a
potentiometer is available at the output of the device. The output of the device is isolated,
no-load proof and short-circuit proof. The LEDs indicate the operating state. The operating
state of the device can be processed via the signaling contact.
AC input
DC output
24 - 28 V potentiometer
Signaling contacts (13, 14)
Indicator lights (24 V O.K., OVERLOAD, SHUT DOWN)
Selector switch
Mounting rail slider
Convection
Clearance above/below
Figure 2-3 Design of the 6EP3337-8SB00-0AY0
Description, device design, dimension drawing
2.2 Connections and terminal designation
SITOP PSU8200 1ph
12 Manual, 08.2016, C98130-A7633-A1-5-7629
2.2
Connections and terminal designation
The line input terminals can be used to establish the connection to the supply voltage.
The output terminals are used to connect to the loads to be supplied (see also Section
Installation (Page 39)).
Connections and terminal designations for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0
Line input L1, N, PE One screw terminal each
output "+" 2 screw terminals
output "–" 2 screw terminals
signaling contact 13, 14 One screw terminal each
remote contact 15, 16 One screw terminal each
*1)
Do not subject the end stop to higher loads
Figure 2-4 Terminal data for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0
Description, device design, dimension drawing
2.2 Connections and terminal designation
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 13
Connections and terminal designations for the 6EP1336-3BA10
Line input L1, N(L2),PE One screw terminal each
output "+" 2 screw terminals
output "–" 2 screw terminals
signaling contact 13, 14 One screw terminal each
*1)
Do not subject the end stop to higher loads
Figure 2-5 Terminal data for 6EP1336-3BA10
Connections and terminal designations for 6EP3337-8SB00-0AY0
Line input L1, N(L2),PE One screw terminal each
output "+" 2 screw terminals
output "–" 2 screw terminals
signaling contact 13, 14 One screw terminal each
*1)
Do not subject the end stop to higher loads
Figure 2-6 Terminal data for 6EP3337-8SB00-0AY0
Description, device design, dimension drawing
2.3 Potentiometer
SITOP PSU8200 1ph
14 Manual, 08.2016, C98130-A7633-A1-5-7629
2.3
Potentiometer
The potentiometer on the front of the device is used to adjust the output voltage. The
output voltage is set to 24 V in the factory, and can be adjusted in the range 24 - 28.8 V (for
6EP3337-8SB00-0AY0, 24 - 28 V); for example, to compensate voltage drops across long
supply lines to the connected load.
Figure 2-7 Potentiometer (example: 6EP3334-8SB00-0AY0)
NOTICE
Thermal overload possible
When adjusting the output voltage to > 24 V, the output current must be derated by 4 %/V,
or the permissible ambient temperature must be taken into account with 3 °C/V.
Note
It is only permissible to use an insulated screwdriver whe
n actuating the potentiometer.
For information on actuating the potentiometer (screwdriver, torque), see Figure 2-5
Terminal data for 6EP1336-3BA10 (Page 13), Figure 2-6 Terminal data for 6EP3337-8SB00-
0AY0 (Page 13), Figure 2-4 Terminal data for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-
0AY0 (Page 12)
Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 15
2.4
Status displays and signaling
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
Operating display
Green LED for "24 V O.K."
Yellow LED for overload in "constant current" mode
Red LED for latching shutdown in "shut down" mode
Signaling contact (13, 14) Relay contact (NO contact, contact rating 30 V AC / 0.5 A, 60 V DC / 0.3 A,
30 V DC / 1 A) for "24 V O.K."
Figure 2-8 Operating display and signaling contact for 6EP3333-8SB00-0AY0 and 6EP3334-
8SB00-0AY0
Signaling
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
Green LED lit
Signaling contact,
contact 13 - 14 closed
Normal operation, output voltage > 20 V ± 0.5 V
LED off
Signaling contact,
contact 13 - 14 opened (quiescent position)
No supply voltage
Yellow LED lit
Signaling contact,
contact 13 - 14 opened (quiescent position)
Overload, output voltage < 20 V ± 0.5 V
(only in the "constant current" mode)
Red LED lit
Signaling contact,
contact 13 - 14 opened (quiescent position)
Latching shut down or remote OFF
Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP PSU8200 1ph
16 Manual, 08.2016, C98130-A7633-A1-5-7629
6EP1336-3BA10 (24 V/20 A)
Operating display
Green LED lit for "24 V O.K."
Yellow LED lit for overload condition (U
out
< 20 V ± 0.5 V)
Red LED lit for latching shutdown as a result of overload
(only for selector switch B in the "ON" position)
Signaling contact Relay contact (NO contact, contact rating 30 V AC / 0.5 A; 60 V DC / 0.3 A;
30 V DC / 1 A) for "24 V O.K."
Figure 2-9 Operating display and signaling contact
for 6EP1336-3BA10
Signaling
6EP1336-3BA10 (24 V/20 A)
LED green (5.1) off
Signaling contact, contact 13 - 14 opened (quiescent posi-
tion)
No supply voltage
Green LED (5.1) lit
Signaling contact, contact 13 - 14 closed
Normal operation,
output voltage > 20 V ± 0.5 V
Yellow LED (5.2) lit
Signaling contact, contact 13 - 14 opened (quiescent posi-
tion)
Overload (Uout < 20 V ± 0.5 V)
Red LED (5.3) lit
Signaling contact, contact 13 - 14 opened (quiescent posi-
tion)
Latching shutdown due to overload
Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 17
6EP3337-8SB00-0AY0 (24 V/40 A)
Operating display
Green LED lit for "24 V O.K."
Yellow LED lit for overload condition (U
out
< 20 V ± 0.5 V)
Red LED lit for latching shutdown as a result of overload
(only for selector switch B in the "ON" position)
Signaling contact Relay contact (NO contact, contact rating 30 V AC / 0.5 A; 60 V DC / 0.3 A;
30 V DC / 1 A) for "24 V O.K."
Figure 2-10 Operating display and signaling contact for 6EP3337-8SB00-0AY0
Signaling
6EP3337-8SB00-0AY0 (24 V/40 A)
Green LED off
Signaling contact, contact 13 - 14 opened (quiescent posi-
tion)
Supply voltage missing
Green LED lit
Signaling contact, contact 13 - 14 closed
Normal operation,
output voltage > 20 V ± 0.5 V
Yellow LED lit
Signaling contact, contact 13 - 14 opened (quiescent posi-
tion)
Overload (Uout < 20 V ± 0.5 V)
Red LED lit
Signaling contact, contact 13 - 14 opened (quiescent posi-
tion)
Latching shutdown due to overload
Description, device design, dimension drawing
2.5 Change-over switch
SITOP PSU8200 1ph
18 Manual, 08.2016, C98130-A7633-A1-5-7629
2.5
Change-over switch
Figure 2-11 Selector switch
The two switches A and B are used to influence the output characteristic:
Description, device design, dimension drawing
2.5 Change-over switch
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 19
Switch
ON
OFF
A
influences the output
characteristic in the
load range
Parallel operation:
"Soft" characteristic curve (see, e.g. Figure 6-8 Output
characteristic curve 6EP3333-8SB00-0AY0 parallel
operation (Page 50)) for operating two or more devic-
es in parallel: The output voltage falls with increasing
output current (namely, also for the overcurrent
pulse!).
This means that for full output current the highest
output voltage can normally no longer be attained.
Single operation:
Delivery state
"Hard" characteristic curve (see, e.g.
Figure 6-4 Output characteristic curve
6EP3333-8SB00-0AY0 stand-alone op-
eration (Page 48)) for normal operation
(single operation): The output voltage is
independent of the output current.
B
influences the output
characteristic in the
overload range
Latching shutdown:
If the output current rises above the rated value and
above the current limit, the device reduces the output
voltage (see, e.g. Figure 6-12 Output characteristic
curve 6EP3333-8SB00-0AY0 latching shutdown
(Page 51)). If the output voltage falls below 20 V, the
device shuts down latching, the red LED lights up.
This limit voltage of 20 V is independent of the set
output voltage. The "Short-term overload current"
feature is not available in this operating mode.
6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0
are reset using power supply OFF for a minimum of
60 s or remote OFF and ON at the remote contact.
6EP1336-3BA10 is reset by switching off the power
supply for longer than 5 s.
For 6EP3337-8SB00-0AY0, for an overload condition,
the device is shutdown. A reset is initiated by switch-
ing off the line supply and then switching it on again
after the red LED goes the dark.
In order to also be able to charge large capacitances
in this operating mode at the output, non-latching
shutdown is performed during the first 10 seconds
after switching on the power or after a remote on.
During these first 10 s, the device responds for over-
load as if the switch is OFF.
Constant current:
Delivery state
If the output current rises above the rated
value and above the current limit, the
device reduces the output voltage. The
yellow LED lights up if the output voltage
falls below 20 V.
Delivery condition: A-OFF; B-OFF
Note
Selector switches may only be activated when the device is switched off.
Description, device design, dimension drawing
2.6 Remote contact
SITOP PSU8200 1ph
20 Manual, 08.2016, C98130-A7633-A1-5-7629
2.6
Remote contact
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
Remote contact (15, 16) Non-isolated input for remote ON/OFF switching of the power supply.
Function: The device is remotely switched off when contacts 15 - 16 are short-circuited
(R < 8 kΩ). If the power supply is shut down and latched in the "latching shutdown" mode
as a result of an overload, then it can be restarted using remote OFF followed by remote
ON.
Figure 2-12 Remote contact for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0
Description, device design, dimension drawing
2.7 Block diagram
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 21
2.7
Block diagram
Figure 2-13 Block diagram for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0
Description, device design, dimension drawing
2.7 Block diagram
SITOP PSU8200 1ph
22 Manual, 08.2016, C98130-A7633-A1-5-7629
Figure 2-14 Block diagram for 6EP1336-3BA10
Description, device design, dimension drawing
2.7 Block diagram
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 23
Figure 2-15 Block diagram for 6EP3337-8SB00-0AY0
Description, device design, dimension drawing
2.8 Dimensions and weight
SITOP PSU8200 1ph
24 Manual, 08.2016, C98130-A7633-A1-5-7629
2.8
Dimensions and weight
Figure 2-16 Dimension drawing 6EP3333-8SB00-0AY0
Figure 2-17 Dimension drawing 6EP3334-8SB00-0AY0
Description, device design, dimension drawing
2.8 Dimensions and weight
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 25
Figure 2-18 Dimension drawing for 6EP1336-3BA10
Figure 2-19 Dimension drawing for 6EP3337-8SB00-0AY0
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
Dimensions (W × H × D) in mm
45 × 125 × 125
55 × 125 × 125
Weight
approx. 0.8 kg
approx. 1.0 kg
Description, device design, dimension drawing
2.8 Dimensions and weight
SITOP PSU8200 1ph
26 Manual, 08.2016, C98130-A7633-A1-5-7629
6EP1336-3BA10
(24 V/20 A)
6EP3337-8SB00-0AY0
(24 V/40 A)
Dimensions (W × H × D) in mm
90 × 125 × 120
145 × 145 × 150
Weight
approx. 1.2 kg
approx. 3 kg
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 27
Mounting/removal
3
WARNING
Installing the device in a housing or a control cabinet
The SITOP PSU8200 1ph power supply is a built-in device. It must be installed in a housing
or control cabinet, to which only qualified personnel have access.
The device can be mounted in a control cabinet on standard mounting rails.
Mounting
To mount the device, position it with the mounting rail guide at the upper edge of the
standard mounting rail and press down to lock it into place. If it is too difficult to snap them
into place, press the slider at the same time, as described under "Removal".
Removal
To remove, pull up the slider using a screwdriver and disengage the device at the bottom
edge of the standard mounting rail. Then you can remove the device from the upper edge of
the standard mounting rail.
Figure 3-1 Mounting/removal (example): 6EP3334-8SB00-0AY0)
Mounting/removal
SITOP PSU8200 1ph
28 Manual, 08.2016, C98130-A7633-A1-5-7629
WARNING
Use in hazardous zones
If the devices are to be used in hazardous zones (II 3G Ex nA nC IIC T3 Gc or II 3G Ex nA
nC IIC T4 Gc), they must be installed in a distribution box with degree of protection IP54 or
higher. This distribution box must comply with the requirements of EN 60079-15.
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 29
Mounting position, mounting clearances
4
4.1
Standard mounting position
The device is mounted on standard mounting rails according to EN 60715. The device must
be mounted vertically in such a way that the input terminals and the output terminals are at
the bottom to ensure correct cooling.
A clearance of at least 50 mm should be maintained above and below the device (maximum
depth of the cable duct, 50 mm).
No space is required at the side.
Output current as a function of the ambient temperature and mounting height
Figure 4-1 6EP3333-8SB00-0AY0 standard mounting position
Figure 4-2 6EP3334-8SB00-0AY0 standard mounting position
Mounting position, mounting clearances
4.1 Standard mounting position
SITOP PSU8200 1ph
30 Manual, 08.2016, C98130-A7633-A1-5-7629
Figure 4-3 6EP1336-3BA10 standard mounting position
Figure 4-4 6EP3337-8SB00-0AY0 standard mounting position
Figure 4-5 Mounting height derating
For details, see Ambient conditions (Page 63)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 31
4.2
Other mounting positions
For mounting positions that deviate from the standard mounting position, derating factors
(reduction of the output power or the permissible ambient temperature) must be observed in
accordance with the following diagrams.
Note
In the case of mounting positions that deviate from the standard mounting position, reduc
ed
mechanical resistance of the devices against vibration and shock must be expected.
Particularly when installing on a vertically fastened standard mounting rail, additional
measures may be required, e.g. to prevent the device from slipping on the standar
d
mounting rail.
4.2.1
6EP3333-8SB00-0AY0
Figure 4-6 6EP3333-8SB00-0AY0 mounting position (1)
Figure 4-7 6EP3333-8SB00-0AY0 mounting position (2)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU8200 1ph
32 Manual, 08.2016, C98130-A7633-A1-5-7629
Figure 4-8 6EP3333-8SB00-0AY0 mounting position (3)
Figure 4-9 6EP3333-8SB00-0AY0 mounting position (4)
Figure 4-10 6EP3333-8SB00-0AY0 mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 33
4.2.2
6EP3334-8SB00-0AY0
Figure 4-11 6EP3334-8SB00-0AY0 mounting position (1)
Figure 4-12 6EP3334-8SB00-0AY0 mounting position (2)
Figure 4-13 6EP3334-8SB00-0AY0 mounting position (3)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU8200 1ph
34 Manual, 08.2016, C98130-A7633-A1-5-7629
Figure 4-14 6EP3334-8SB00-0AY0 mounting position (4)
Figure 4-15 6EP3334-8SB00-0AY0 mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 35
4.2.3
6EP1336-3BA10
Figure 4-16 6EP1336-3BA10 mounting position (1)
Figure 4-17 6EP1336-3BA10 mounting position (2)
Figure 4-18 6EP1336-3BA10 mounting position (3)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU8200 1ph
36 Manual, 08.2016, C98130-A7633-A1-5-7629
Figure 4-19 6EP1336-3BA10 mounting position (4)
Figure 4-20 6EP1336-3BA10 mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 37
4.2.4
6EP3337-8SB00-0AY0
Figure 4-21 6EP3337-8SB00-0AY0 mounting position (1)
Figure 4-22 6EP3337-8SB00-0AY0 mounting position (2)
Figure 4-23 6EP3337-8SB00-0AY0 mounting position (3)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU8200 1ph
38 Manual, 08.2016, C98130-A7633-A1-5-7629
Figure 4-24 6EP3337-8SB00-0AY0 mounting position (4)
Figure 4-25 6EP3337-8SB00-0AY0 mounting position (5)
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 39
Installation
5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1
Line-side connection
The SITOP PSU8200 1ph (6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0) power
supply is designed for connection to a 1-phase AC line supply with a rated voltage of
120/230 V AC, 50 - 60 Hz.
Figure 5-1 Line connection for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0
The SITOP PSU8200 1ph (6EP1336-3BA10) power supplies are designed to be connected
to a 1-phase AC line voltage or to 2 line conductors of three-phase line supplies (TN, TT or
IT system according to VDE 0100 T 300/IEC 364-3) with a rated voltage of 120 - 230 V,
50 - 60 Hz or a DC voltage.
Installation
5.1 Line-side connection
SITOP PSU8200 1ph
40 Manual, 08.2016, C98130-A7633-A1-5-7629
Figure 5-2 Line connection for 6EP1336-3BA10
The SITOP PSU8200 1ph (6EP3337-8SB00-0AY0) power supplies are designed to be
connected to a 1-phase AC line voltage or to 2 line conductors of three-phase line supplies
(TN, TT or IT system according to VDE 0100 T 300/IEC 364-3) with a rated voltage of
120/230 V, 50 - 60 Hz.
The line supply is connected using terminals L1, N and PE (see Figure 5-1 Line connection
for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 (Page 39)) or L1, N(L2) and PE
(Figure 5-2 Line connection for 6EP1336-3BA10 (Page 40)) and must be implemented
according to IEC 60364 and EN 50178 .
A protective device (miniature circuit-breaker or circuit-breaker) and a disconnection unit to
switch off the power supply must be provided. A ground-fault circuit interrupter is not
permissible against indirect contact as the only protective measure. This applies for the
complete line supply protected by the ground-fault circuit interrupter.
Protection
SITOP PSU8200 1ph
Line-side protection
6EP3333-8SB00-0AY0
(24 V/5 A)
Recommended:
Miniature circuit breaker (IEC 898), characteristic C, 6 A
6EP3334-8SB00-0AY0
(24 V/10 A)
Recommended:
Miniature circuit breaker (IEC 898), characteristic C, 10 A
6EP1336-3BA10
(24 V/20 A)
Recommended:
Miniature circuit breaker for single-phase operation: 10 A, characteristic C;
required for two-phase operation:
Miniature circuit breaker two-pole coupled or circuit
breaker for the US according to UL489, DIVQ: 3RV2711-1HD10 (120 V) or 3RV2711-
1ED10 (230 V)
6EP3337-8SB00-0AY0
(24 V/40 A)
Recommended:
Miniature circuit breaker for single-phase operation: 16 A, characteristic C;
required for two-phase operation:
Miniature circuit breaker two-pole coupled or circuit
breaker for the US according to UL489, DIVQ: 3RV2421-4BA10 (120 V) or 3RV2411-
1JA10 (230 V)
The protective conductor of the line supply must be connected at the PE terminal.
Other country-specific regulations may have to be observed when installing the device.
Installation
5.2 Output-side connection
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 41
5.2
Output-side connection
At its output, the SITOP PSU8200 1ph power supply provides an isolated (= non-grounded)
SELV output voltage (Safety Extra Low Voltage). The output of the power supply is no-load,
overload, and short-circuit proof. If an overload occurs, the electronic current limiting function
limits the output current to a maximum value (see Section Technical data (Page 43)).
Figure 5-3 Output connection (example: 6EP3334-8SB00-0AY0)
The output voltage is connected via the + and - terminals at the output of the power supply
(see Figure 5-3 Output connection (example: 6EP3334-8SB00-0AY0) (Page 41)). Ensure
that the output cables are dimensioned correctly for the maximum output current rms value
and fused accordingly.
Note
If the safety concept of the plant or system specifies that the DC output circuit should be
grounded (PELV, Protected Extra Low Voltage), then it is permissible that the output voltage
of the SITOP power supply is grounded.
In this case, ideally, the grounding at the output
should be directly connected from terminal "
-" of the power supply to a suitable connection
point of the protective conductor system (PE) of the plant or system.
Installation
5.2 Output-side connection
SITOP PSU8200 1ph
42 Manual, 08.2016, C98130-A7633-A1-5-7629
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 43
Technical data
6
Note
Technical data apply for a rated input voltage, rated load and 25
°C ambient temperature if
nothing else is specified.
6.1
Input
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
Input
1-phase, AC
1-phase, AC
Rated voltage U
in rated
120/230 V
120/230 V
Rated voltage U
in rated
for DC
-
-
Voltage range for AC
Remark
85 - 132/170 - 264 V
Automatic voltage switchover
85 - 132/170 - 264 V
Automatic voltage switchover
Voltage range for DC
Remark
-
-
Wide-range input
No
No
Overvoltage strength
-
-
Line failure buffering at Iout rated, min at
230 V
35 ms 35 ms
Rated line frequency
50 - 60 Hz
50 - 60 Hz
Line frequency range
47 - 63 Hz
47 - 63 Hz
Input current / at rated value of input
voltage 120 V
2.1 A 4 A
Input current / at rated value of input
voltage 230 V
1.2 A 1.9 A
Inrush current limiting (25 °C), max.
10 A
10 A
I
2
t, max
0.2 A
2
s
0.3 A
2
s
Integrated input fuse
Fuse T 3.15 A
Fuse T 6.3 A
Protection in the line feeder cable
(IEC 898)
Recommended: Circuit breaker, char-
acteristic C, 6 A
Recommended: Miniature circuit
breaker characteristic C, 10 A
Technical data
6.1 Input
SITOP PSU8200 1ph
44 Manual, 08.2016, C98130-A7633-A1-5-7629
6EP1336-3BA10
(24 V/20 A)
6EP3337-8SB00-0AY0
(24 V/40 A)
Input
1 and 2-phase AC or DC
1 and 2-phase AC
Rated voltage U
in rated
120 - 230 V
120/230 V
Rated voltage U
in rated
for DC
110 - 220 V
-
Voltage range for AC
Remark
85 - 275 V
Temperature derating for Uin < 100 V for
50 °C necessary
85 - 132/170 - 264 V
Voltage range for DC
Remark
88 - 350 V
Temperature derating for Uin < 100 V for
50 °C necessary
-
Wide-range input
Yes
No
Overvoltage strength
2.3 × U
in rated
, 1.3 ms
-
Line failure buffering at Iout rated, min at
230 V
20 ms 15 ms
Rated line frequency
50 - 60 Hz
50 - 60 Hz
Line frequency range
45 - 65 Hz
45 - 65 Hz
Input current / at rated value of input
voltage 120 V
4.6 A 15 A
Input current / at rated value of input
voltage 230 V
2.5 A 9 A
Inrush current limiting (25 °C), max.
20 A
50 A
I
2
t, max
5 A
2
s
30 A
2
s
Integrated input fuse
Fuse T 10 A
Fuse T 16 A
Protection in the line feeder cable
(IEC 898)
Recommended miniature circuit breaker
for single-phase operation: 10 A, charac-
teristic C;
required for two-phase operation: Minia-
ture circuit breaker two-pole coupled or
circuit breaker for the US according to
UL489, DIVQ: 3RV2711-1HD10 (120 V) or
3RV2711-1ED10 (230 V)
Recommended miniature circuit
breaker for single-phase opera-
tion: 16 A, characteristic C;
required for two-phase operation:
Miniature circuit breaker two-pole
coupled or circuit breaker for the
US according to UL489, DIVQ:
3RV2421-4BA10 (120 V) or
3RV2411-1JA10 (230 V)
Power consumption (active power) at full
load
515 W 1055 W
Technical data
6.2 Output
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 45
Figure 6-1 Power failure buffering
6.2
Output
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
Output Regulated and isolated
DC voltage
Regulated and isolated
DC voltage
Rated voltage Uout rated DC
24 V
24 V
Total tolerance, static ±
3 %
3 %
Static line regulation, approx.
0.03 %
0.05 %
Static load regulation, approx.
0.2 %
0.3 %
Residual ripple in the load range
Peak-peak, max.
50 mV
50 mV
Spikes peak-peak, max. (bandwidth,
approx. 20 MHz)
200 mV 200 mV
Adjustment range
24 - 28.8 V
24 - 28.8 V
Product function / output voltage can
be adjusted
Yes Yes
Output voltage setting
Remark
Via potentiometer
Max. 120 W
Via potentiometer
Max. 240 W
Operating display
Green LED for "24 V O.K."
Green LED for "24 V O.K."
Signaling Relay contact (NO contact, contact
rating 30 V AC / 0.5 A; 60 V DC / 0.3 A;
30 V DC / 1 A) for "24 V O.K."
Relay contact (NO contact, contact
rating 30 V AC / 0.5 A; 60 V DC / 0.3 A;
30 V DC / 1 A) for "24 V O.K."
Response when switching on/off
U
out
overshoots by approximately 3 %
U
out
overshoots by approximately 3 %
Starting delay, max.
1 s
1 s
Voltage rise, typ.
30 ms
70 ms
Voltage rise time of the output voltage,
maximum
500 ms 500 ms
Technical data
6.2 Output
SITOP PSU8200 1ph
46 Manual, 08.2016, C98130-A7633-A1-5-7629
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
Rated current I
out rated
5 A
10 A
Current range
Remark
0 - 5 A
for Uin < 100 V/< 200 V: 80 % Iout rated
0 - 10 A
60 … 70 °C derating approx. 2 %
Iout rated/K;
for U
in
< 100 V/< 200 V: 80 % I
out rated
Output active power / typical
120 W
240 W
Constant overload current for a short
circuit when powering up, typical
6 A 12 A
Short-time overload current for a short
circuit during operation, typical
15 A 30 A
Duration of the overload capability,
overcurrent / for a short circuit while
powering up
150 ms 150 ms
Duration of the overload capability,
overcurrent / for a short circuit while in
operation
Remark
25 ms
per 1 min
25 ms
per 1 min
Can be connected in parallel to in-
crease the power rating
Remark
Yes
Switchable characteristic
Yes
Switchable characteristic
Number of devices that can be con-
nected in parallel to increase the power
rating, units
2 2
Output characteristic See Figure 6-4 Output characteristic
curve 6EP3333-8SB00-0AY0 stand-
alone operation (Page 48)
See Figure 6-5 Output characteristic
curve 6EP3334-8SB00-0AY0 stand-
alone operation (Page 49)
6EP1336-3BA10
(24 V/20 A)
6EP3337-8SB00-0AY0
(24 V/40 A)
Output Regulated and isolated DC voltage Regulated and isolated DC voltage
Rated voltage Uout rated DC 24 V 24 V
Total tolerance, static ±
3 %
3 %
Static line regulation, approx.
0.1 %
0.1 %
Static load regulation, approx.
0.3 %
0.3 %
Residual ripple in the load range
Peak-peak, max.
100 mV 100 mV
Spikes peak-peak, max. (bandwidth,
approx. 20 MHz)
200 mV 240 mV
Adjustment range
24 - 28.8 V
24 - 28 V
Product function / output voltage can
be adjusted
Yes Yes
Technical data
6.2 Output
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 47
6EP1336-3BA10
(24 V/20 A)
6EP3337-8SB00-0AY0
(24 V/40 A)
Output voltage setting
Remark
Via potentiometer
Max. 480 W
Via potentiometer
Max. 960 W
Operating display
Green LED for "24 V O.K."
Green LED for "24 V O.K."
Signaling Relay contact (NO contact, contact
rating 30 V AC / 0.5 A; 60 V DC / 0.3 A;
30 V DC / 1 A) for "24 V O.K."
Relay contact (NO contact, contact
rating 30 V AC / 0.5 A; 60 V DC / 0.3 A;
30 V DC / 1 A) for "24 V O.K."
Response when switching on/off
No overshoot of U
out
(Soft-Start)
No overshoot of U
out
(Soft-Start)
Starting delay, max.
0.25 s
0.5 s
Voltage rise, typ.
50 ms
50 ms
Voltage rise time / of the output volt-
age / maximum
150 ms 150 ms
Rated current I
out rated
20 A
40 A
Current range
Remark
0 - 20 A
60 ... 70 °C derating:3 % Iout rated/K
0 - 40 A
60 … 70 °C derating 1 % Iout rated/K;
derating for Uin < 120 V: see Figure 6-3
Output derating for 6EP3337-8SB00-
0AY0 (Page 48)
Output active power / typical
480 W
960 W
Constant overload current/for a short
circuit when powering up/typical
30 A -
Short-
time overload current / for a short
circuit in operation / typical
60 A -
Duration of the overload capability,
overcurrent / for a short circuit while
powering up
150 ms -
Duration of the overload capability,
overcurrent / for a short circuit while in
operation
Remark
25 ms
per 1 min
-
Can be connected in parallel to in-
crease the power rating
Remark
Yes
Switchable characteristic
Yes
Switchable characteristic
Number of devices that can be con-
nected in parallel to increase the power
rating, units
2 2
Power Boost in operation:
Extra Power in operation
60 A for 25 ms
30 A for 5 s (pro min)
120 A for 25 ms
60 A for 5 s (pro min)
Output characteristic See Figure 6-6 6EP1336-3BA10 single
operation output characteristic
(Page 49)
See Figure 6-7 6EP3337-8SB00-0AY0
single operation output characteristic
(Page 49)
Technical data
6.2 Output
SITOP PSU8200 1ph
48 Manual, 08.2016, C98130-A7633-A1-5-7629
Figure 6-2 Starting delay/voltage rise
Figure 6-3 Output derating for 6EP3337-8SB00-0AY0
Figure 6-4 Output characteristic curve 6EP3333-8SB00-0AY0 stand-alone operation
Technical data
6.2 Output
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 49
Figure 6-5 Output characteristic curve 6EP3334-8SB00-0AY0 stand-alone operation
Figure 6-6 6EP1336-3BA10 single operation output characteristic
Figure 6-7 6EP3337-8SB00-0AY0 single operation output characteristic
The device supplies a constant output voltage until the current limit is reached. In the event
of an overload, the output current and the output voltage are reduced.
Technical data
6.2 Output
SITOP PSU8200 1ph
50 Manual, 08.2016, C98130-A7633-A1-5-7629
Selector switch A on (parallel operation):
The output voltage falls with increasing output current.
Figure 6-8 Output characteristic curve 6EP3333-8SB00-0AY0 parallel operation
Figure 6-9 Output characteristic curve 6EP3334-8SB00-0AY0 parallel operation
Figure 6-10 6EP1336-3BA10 parallel operation output characteristic
Technical data
6.2 Output
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 51
Figure 6-11 6EP3337-8SB00-0AY0 parallel operation output characteristic
Selector switch B on (latching shutdown):
The device is shutdown if the overload lasts longer than 100 ms. 6EP3333-8SB00-0AY0 and
6EP3334-8SB00-0AY0 are reset using power supply OFF for a minimum of 60 s or remote
OFF and ON at the remote contact. 6EP1336-3BA10 is reset using power supply OFF for a
minimum of 5 s or remote OFF and ON at the remote contact. 6EP3337-8SB00-0AY0 is
reset using power supply OFF and ON again after the red LED has gone dark.
Figure 6-12 Output characteristic curve 6EP3333-8SB00-0AY0 latching shutdown
Figure 6-13 Output characteristic curve 6EP3334-8SB00-0AY0 latching shutdown
Technical data
6.2 Output
SITOP PSU8200 1ph
52 Manual, 08.2016, C98130-A7633-A1-5-7629
Figure 6-14 6EP1336-3BA10 latching shutdown output characteristic
Figure 6-15 6EP3337-8SB00-0AY0 latching shutdown output characteristic
Technical data
6.3 Efficiency
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 53
6.3
Efficiency
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
Efficiency at U
out rated
, I
out rated
, approx.
93 %
94 %
Power loss at U
out rated
, I
out rated
, approx.
9 W
18 W
No-load operation power loss, approx.
1.5 W
1.5 W
Power loss in the "latching shutdown"
state
1.2 W 1.2 W
6EP1336-3BA10
(24 V/20 A)
6EP3337-8SB00-0AY0
(24 V/40 A)
Efficiency at U
out rated
, I
out rated
, approx.
93 %
92 %
Power loss at U
out rated
, I
out rated
, approx.
42 W
83 W
No-load operation power loss, approx.
10 W
7 W
Power loss in the "latching shutdown"
state
6.5 W 3 W
Figure 6-16 Power efficiency 6EP3333-8SB00-0AY0
Technical data
6.3 Efficiency
SITOP PSU8200 1ph
54 Manual, 08.2016, C98130-A7633-A1-5-7629
Figure 6-17 Power efficiency 6EP3334-8SB00-0AY0
Figure 6-18 Efficiency 6EP1336-3BA10
Technical data
6.4 Closed-loop control
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 55
Figure 6-19 Efficiency 6EP3337-8SB00-0AY0
6.4
Closed-loop control
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
6EP1336-3BA10
(24 V/20 A)
6EP3337-8SB00-0AY0
(24 V/40 A)
Dyn. line regulation
(U
in rated
± 15 %), max.
0.1 % 0.1 % 1 % 1 %
Dyn. load regulation
(Iout: 50/100/50 %),
U
out
± typ.
2 % 4 % 1 % 1 %
Load step regulation
time
50 to 100%, typ.
250 µs 250 µs 1 ms 1 ms
Load step regulation
time
100 to 50%, typ.
500 μs 500 μs 1 ms 1 ms
Regulation
time / maximum
1 ms 1 ms 5 ms 5 ms
Dyn. load regulation
(Iout: 10/90/10 %), Uout
± typ.
- - 2 % 2 %
Load step regulation
time
10 to 90 %, typ.
- - 1 ms 1 ms
Load step regulation
time
90 to 10 %, typ.
- - 1 ms 1 ms
Technical data
6.5 Protection and monitoring
SITOP PSU8200 1ph
56 Manual, 08.2016, C98130-A7633-A1-5-7629
6.5
Protection and monitoring
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
Output overvoltage protection
< 33 V
< 33 V
Current limitation, typ.
6 A
12 A
Property of the output /
short-circuit proof
Yes Yes
Short-circuit protection Optional constant current characteristic
curve or latching shutdown
Optional constant current characteristic
curve or latching shutdown
Continuous short-circuit current /
rms value / typical
Remark
3.5 A
Overload capability 150 % Iout rated up to
5 s/min
7 A
Overload capability 150 % Iout rated up to
5 s/min
Overload/short-circuit indicator
Yellow LED for "overload", red LED for "latching shutdown"
6EP1336-3BA10
(24 V/20 A)
6EP3337-8SB00-0AY0
(24 V/40 A)
Output overvoltage protection
< 33 V
< 32 V
Current limitation, typ.
21.5 A
41 A
Property of the output /
short-circuit proof
Yes Yes
Short-circuit protection Optional constant current characteristic
approx. 23 A or latching shutdown
Optional constant current characteristic
approx. 41 A or latching shutdown
Continuous short-circuit current /
rms value / typical
Remark
23 A
Overload capability 150 % Iout rated up to
5 s/min
41 A
Overload capability 150 % Iout rated up to
5 s/min
Overload / short-circuit indicator Yellow LED for "overload", red LED for
"latching shutdown"
Yellow LED for "overload", red LED for
"latching shutdown"
6.6
MTBF
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
6EP1336-3BA10
(24 V/20 A)
6EP3333-8SB00-0AY0
(24 V/40 A)
Mean Time Between Failures SN29500: > 1200000 hours
at 40 °C, rated load, 24-hour
operation
SN29500: > 620000 hours at
40 °C, rated load, 24-hour
operation
SN29500: > 800000 hours at
40 °C, rated load, 24-hour
operation
Technical data
6.7 Mechanical system
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 57
6.7
Mechanical system
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
Connection system
Screw-type terminal
Screw-type terminal
Connections/line input L1, N, PE: 1 screw terminal each for
0.2 - 2.5 mm² solid (finely stranded)
L1, N, PE: 1 screw terminal each for
0.2 - 2.5 mm² solid (finely stranded)
Connections/output +, -: 2 screw terminals each for
0.2 - 2.5 mm² solid (finely stranded)
+, -: 2 screw terminals each for
0.2 - 2.5 mm² solid (finely stranded)
Width /of the housing
45 mm
55 mm
Height/of the housing
125 mm
125 mm
Depth/of the housing
125 mm
125 mm
Mounting width
45 mm
55 mm
Mounting height
225 mm
225 mm
Weight, approx.
0.8 kg
1.0 kg
Product properties/of the housing/
housing that can be lined up next to
other housings
Yes Yes
Type of mounting / panel mounting
No
No
Type of mounting / rail mounting
Yes
Yes
Type of mounting / S7-300 rail mount-
ing
No No
Mounting Can be snapped onto standard
TH35 × 7,5/15 (EN 60715) mounting
rails
Can be snapped onto standard
TH35 × 7,5/15 (EN 60715) mounting
rails
6EP1336-3BA10
(24 V/20 A)
6EP33337-8SB00-0AY0
(24 V/40 A)
Connection system Screw-type terminal Screw-type terminal
Connections/line input L, N(L2), PE: 1 screw terminal each for
0.2 - 6 (4) mm² solid (finely stranded)
L, N(L2), PE: 1 screw terminal each for
0.2 - 6 (4) mm² solid (finely stranded)
Connections/output +, -: 2 screw terminals each for
0.2 - 6 (4) mm² solid (finely stranded)
+, -: 2 screw terminals each for
0.5 - 16 mm² solid (finely stranded)
Width /of the housing
90 mm
145 mm
Height/of the housing
125 mm
145 mm
Depth/of the housing
125 mm
150 mm
Mounting width
90 mm
145 mm
Mounting height
225 mm
245 mm
Weight, approx.
1.2 kg
3 kg
Product properties/of the housing/
housing that can be lined up next to
other housings
Yes Yes
Type of mounting / panel mounting
No
No
Type of mounting / rail mounting
Yes
Yes
Technical data
6.8 Accessories
SITOP PSU8200 1ph
58 Manual, 08.2016, C98130-A7633-A1-5-7629
6EP1336-3BA10
(24 V/20 A)
6EP33337-8SB00-0AY0
(24 V/40 A)
Type of mounting / S7-300 rail mount-
ing
No No
Mounting Can be snapped onto standard
TH35 × 7,5/15 (EN 60715) mounting
rails
Can be snapped onto standard
TH35 × 15 (EN 60715) mounting rails
6.8
Accessories
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
6EP1336-3BA10 (24 V/20 A)
6EP3337-8SB00-0AY0 (24 V/40 A)
Electrical accessories
Buffer module, redundancy module
Mechanical accessories Device identification labels 20 mm × 7 mm, Ti grey
3RT2900-1SB20
6.9
Dimension drawing
See Section Dimensions and weight (Page 24)
CAD data that can be downloaded from the Internet:
6EP3333-8SB00-0AY0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00963)
6EP3334-8SB00-0AY0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00966)
6EP1336-3BA10
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00385)
6EP3337-8SB00-0AY0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01213)
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 59
Safety, approvals, EMC
7
7.1
Safety
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
6EP1336-3BA10 (24 V/20 A)
6EP3337-8SB00-0AY0 (24 V/40 A)
Primary/secondary galvanic isola-
tion
Yes
Electrical isolation SELV output voltage Uout acc. to EN 60950-1 and EN 50178
Protection class
Class I
Degree of protection (EN 60529)
IP20
Leakage current, typ. 1 mA
Leakage current, max.
3.5 mA
Test voltage See Table 7-1 Test voltage for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0
(Page 60)
See Table 7-2 Test voltage for 6EP1336-3BA10 and 6EP3337-8SB00-0AY0
(Page 61)
Safety, approvals, EMC
7.2 Test voltage
SITOP PSU8200 1ph
60 Manual, 08.2016, C98130-A7633-A1-5-7629
7.2
Test voltage
Figure 7-1 Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
Connect the input terminals with one another
Connect the output terminals, signaling contact and PE with one another
Test (C)
Connect the output terminals and signaling contact with one another and measure with
respect to PE
Table 7- 1 Test voltage for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test 60 s 4200 V DC 2200 V DC 700 V DC
60 s
3000 V AC
1500 V AC
500 V AC
Production test 1 s 4200 V DC 4200 V DC 500 V DC
1 s
3000 V AC
3000 V AC
350 V AC
Field test
1 s
2200 V DC
2200 V DC
500 V DC
1 s
1500 V AC
1500 V AC
350 V AC
Note:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
Safety, approvals, EMC
7.3 Approvals
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 61
Table 7- 2 Test voltage for 6EP1336-3BA10 and 6EP3337-8SB00-0AY0
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 V DC
2200 V DC
700 V DC
60 s 3000 V AC 1500 V AC 500 V AC
Production test
1 s
2200 V DC
2200 V DC
500 V DC
1 s 1500 V AC 1500 V AC 350 V AC
Field test
1 s
2200 V DC
2200 V DC
500 V DC
1 s
1500 V AC
1500 V AC
350 V AC
Remark:
Tripping current for DC measurement: 0
mA
Tripping current for AC measurement: < 100 mA
7.3
Approvals
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
6EP1336-3BA10
(24 V/20 A)
6EP3337-8SB00-0AY0
(24 V/40 A)
CE marking Yes, (2014/35/EG and
2014/30/EG)
Yes, (2014/35/EG and
2014/30/EG)
Yes, (2014/35/EG and
2014/30/EG)
UL/cUL (CSA) approval cULus-Listed (UL 508,
CSA C22.2 No. 107.1), File
E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1), File
E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1), File
E197259
Explosion protection EPS 12 ATEX 1 640 X
IECEx EPS 14.0057X
II 3G Ex nA nC IIC T4 Gc
cCSAus HazLoc Class I,
Div 2, Group A,B,C,D T4
EPS 12 ATEX 1 442 X
IECEx EPS 14.0062X
II 3G Ex nA nC IIC T3 Gc
cCSAus HazLoc Class I,
Div 2, Group A,B,C,D T3
EPS 11 ATEX 1 309 X
IECEx EPS 14.0071X
II 3G Ex nA nC IIC T3 Gc
cULus HazLoc Class I, Div 2,
Group A,B,C,D T3
CB approval
Yes, (IEC 60950-1)
No
Yes, (IEC 60950-1)
SEMI F47 compliance
Fulfilled
-
-
Marine approvals
GL, ABS
GL, ABS
Available soon
Safety, approvals, EMC
7.4 EMC
SITOP PSU8200 1ph
62 Manual, 08.2016, C98130-A7633-A1-5-7629
7.4
EMC
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
Electrostatic discharge
EN 61000-4-2
8 kV contact, 8 kV air
Electromagnetic fields EN 61000-4-3 80 - 1000 MHz 25 V/m
1000 - 2700 MHz 10 V/m
High-speed transient disturbance vari-
ables (burst)
EN 61000-4-4 4 kV at line supply connections
2 kV at the DC output
Surge voltages EN 61000-4-5 3 kV symmetrical at the line supply connections
6 kV symmetrical at the line supply connections
500 V symmetrical/asymmetrical on DC output cables
High-frequency fields
EN 61000-4-6
10 V; 0.15 - 80 MHz
Magnetic fields
EN 61000-4-8
30 A/m; 50 Hz
Voltage dips
EN 61000-4-11
-
Voltage interruptions
EN 61000-4-11
-
Emitted interference
EN 55022
Class B
Line harmonics limit
EN 61000-3-2
Class A
Generic standards
EN61000-6-2
Immunity for industrial environments
EN61000-6-3
Emission for residential areas
6EP1336-3BA10 (24 V/20 A)
6EP3337-8SB00-0AY0 (24 V/40 A)
Electrostatic discharge
EN 61000-4-2
8 kV contact, 8 kV air
Electromagnetic fields EN 61000-4-3 80 - 1000 MHz 25 V/m
1000 - 2700 MHz 10 V/m
High-speed transient disturbance vari-
ables (burst)
EN 61000-4-4 4 kV at line supply connections
2 kV at the DC output
Surge voltages EN 61000-4-5 3 kV symmetrical at the line supply connections
5 kV asymmetrical at the line supply connections
500 V symmetrical/asymmetrical on DC output cables
High-frequency fields EN 61000-4-6 10 V; 0.15 - 80 MHz
Magnetic fields EN 61000-4-8 30 A/m; 50 Hz
Voltage dips EN 61000-4-11 100 % for 20 ms
60 % for 200 ms
30 % for 500 ms
Voltage interruptions
EN 61000-4-11
100 % for 5000 ms
Emitted interference
EN 55022
Class B
Line harmonics limit
EN 61000-3-2
Class A
Generic standards
EN61000-6-2
Noise immunity for industrial environments
EN61000-6-3
Emission for residential areas
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 63
Ambient conditions
8
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
6EP1336-3BA10 (24 V/20 A)
6EP3337-8SB00-0AY0 (24 V/40 A)
Ambient temperature
-25 ... 70 °C for natural convection (self convection)
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat, constant
EN 60068-2-14 temperature change
Transport and storage
temperature
-40 ... 85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-30 humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721, without condensation
Degree of pollution
2
Mechanical stressing
during operation
Tested according to:
EN 60068-2-6 vibration, test Fc:
7 mm deflection in the range 5 - 8.4 Hz
2 g acceleration in the range 8.4 - 150 Hz
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s2 , test duration 11 ms
Ambient conditions
SITOP PSU8200 1ph
64 Manual, 08.2016, C98130-A7633-A1-5-7629
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
6EP1336-3BA10 (24 V/20 A)
6EP3337-8SB00-0AY0 (24 V/40 A)
Damaging gases Tested according to:
EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
1080 - 795 hPa (-1000 - 2000 m)
For operation at installation altitudes from 2000 m up to 6000 m: :
output power must be derated by -7.5 % / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m see Figure 4-5 Mounting height
derating (Page 30)
Overvoltage category:
III to 2000 m (EN 50178)
II from 2000 m to 6000 m (EN 50178)
II to 2000 m (EN 60950-1)
I from 2000 m to 6000 m (EN 60950-1)
Storage:
1080 - 660 hPa (-1000 - 3500 m)
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 65
Applications
9
9.1
Parallel connection to increase power rating
To increase the power rating, SITOP PSU8200 power supplies of the same type can be
directly connected in parallel.
The following must be observed:
The cables connected to each power supply at terminals "+" and "-" must have identical
lengths and the same cable cross-sections (or the same impedance) up to a common
external connection point (terminal strip) if possible.
The power supplies connected in parallel must be switched on simultaneously with a
common switch in the line feeder cable (e.g. with the main switch available in control
cabinets).
The output voltages measured in no-load operation for the power supplies that are not yet
connected in parallel should not deviate more than a maximum of 50 mV. This usually
corresponds to the factory setting. If the output voltage is changed, you should connect
the "-" terminals and then, in no-load operation, measure the voltage difference between
the "+" terminals that have not yet been connected. The voltage difference should not
exceed 50 mV.
Switch selector switch "A" (see ) to "Parallel operation".
Figure 9-1 Parallel connection
Applications
9.1 Parallel connection to increase power rating
SITOP PSU8200 1ph
66 Manual, 08.2016, C98130-A7633-A1-5-7629
NOTICE
Protective circuit for the parallel connection of more than two power supplies
When connecting more than two power supplies in parallel, additional measures must be
taken to prevent high backward feeding currents in the event of a secondary device
fault. For this purpose, a suitable protective circuit (e.g. decoupling diode
or DC-conform circuit breaker) must be installed between each "+" terminal of the power
supply and the common connection point.
Applications
9.2 Parallel connection for redundancy
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 67
9.2
Parallel connection for redundancy
Connecting several SITOP PSU8200 power supplies in parallel for redundancy purposes is
required if especially high demands are placed regarding the availability of a reliable 24 V
power supply.
Using the SITOP PSE202Uredundancy module, two 24 V power supplies of the same type
up to 20 A can be decoupled (Figure 9-2 Redundant configuration with two power supplies
and SITOP PSE202U redundancy module (Page 67)). When one of the devices fails, then
the other automatically takes over the power supply. If one of the power supplies fails, then
this is signaled using an LED on the redundancy module as well as an isolated relay contact.
When dimensioning the system, it must be ensured that n+1 redundant connected power
supplies can handle the total power requirement of the remaining n power supplies.
Note
For a high reliability of the supply, it is recommended that the redundant switched
power supplies are fused separately on the line
-side and, if possible, connected to different
power supply networks.
Figure 9-2 Redundant configuration with two power supplies and SITOP PSE202U redundancy
module
You can find additional information in the:
SITOP PSE202U manual (https://support.industry.siemens.com/cs/ww/en/view/42248598)
Applications
9.3 Series connection for increased voltage
SITOP PSU8200 1ph
68 Manual, 08.2016, C98130-A7633-A1-5-7629
9.3
Series connection for increased voltage
To achieve an output voltage of 48 V DC, two 24 V SITOP PSU8200 power supplies of the
same type can be connected in series. In this case, connect the "-" terminal of the first power
supply to the "+" terminal of the second power supply. The "+" terminal of the first power
supply and the "-" terminal of the second power supply are routed to the load.
Depending on the grounding point of the secondary output voltages, voltages of +48 V,
±24 V or -48 V can be realized.
In the case of an asymmetric load distribution, it is not possible to guarantee correct
functionality.
WARNING
SELV is not guaranteed in the case of a fault
When connecting two power supplies in series, the continuous, permissible SELV voltage
of a maximum of 60 VDC according to EN 60950 cannot be guaranteed in the case of a
fault.
Figure 9-3 Series connection
Applications
9.4 Overload protection in the 24 V output circuit
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 69
9.4
Overload protection in the 24 V output circuit
If an overload occurs, the electronic current limiting function limits the SITOP PSU8200
output current to a maximum value (see Section Technical data (Page 43)). The output
cables are protected against a thermal overload if they are dimensioned corresponding to
the maximum rms output current, or protected using additional components (for example,
miniature circuit breaker, fuses).
However, a load circuit that fails as a result of overload, for instance, should frequently be
reliably and quickly identified and specifically switched off before the power supply goes into
current-limiting mode (in current-limiting mode, the supply voltage would also be reduced for
all of the remaining 24 V loads).
The SITOP PSE200U selectivity module with 4 outputs (versions with adjustable output
current range for each output from 0.5 - 3 A and 3 - 10 A) is available for this purpose; this
monitors the 24 V branches for overload and short circuit (Figure 9-4 Electronic protection of
24 V consumers with the SITOP PSE200U selectivity module (Page 69)). Brief current
peaks, e.g. as a result of a high inrush current, are permitted, and branches with a longer
overload are switched into a no-current condition. This is also ensured for cables in a high-
ohmic condition and for short-circuits that slowly develop over time.
When an output fails, the fault is signaled using a group signal contact or as a single channel
signal, and the branch of the module involved is displayed using an LED.
For versions with single-channel signaling, function blocks for evaluation purposes are
available at no charge for SIMATIC S7-1200/1500/300/400, for STEP 7 and TIA Portal as
well as for SIMOTION CPUs and SIMOTION SCOUT.
You can find additional information at:
Manual SITOP selectivity modules
(https://support.industry.siemens.com/cs/ww/en/view/108989004)
Figure 9-4 Electronic protection of 24 V consumers with the SITOP PSE200U selectivity module
Applications
9.5 Protection against short-time voltage dips
SITOP PSU8200 1ph
70 Manual, 08.2016, C98130-A7633-A1-5-7629
9.5
Protection against short-time voltage dips
In the case of a drop in the line-side supply voltage, the SITOP PSU8200 power supply can
still maintain the output voltage for a short time in the millisecond range (see section
Technical data (Page 43)).
For line supplies that manifest frequent brief voltage dips, in order to increase the power
supply reliability, it may make sense to increase the line buffering time in the device using an
additional SITOP PSE201U buffer module.
The SITOP PSE201U buffer module, based on electrolytic capacitors, is connected in
parallel to the 24 V power supply output (Figure 9-5 Buffering brief power failures using the
SITOP PSE201U buffer module (Page 70)). The buffer time is 200 ms at 40 A up to 1.6 s for
a load current of 5 A. This time can be increased a multiple number of times by connecting
buffer modules in parallel; the maximum buffer time is 10 s.
You can find additional information at:
SITOP PSE201U manual (https://support.industry.siemens.com/cs/ww/en/view/41129219)
Figure 9-5 Buffering brief power failures using the SITOP PSE201U buffer module
Applications
9.6 Protecting against longer power failures
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 71
9.6
Protecting against longer power failures
Sudden and longer failures of the line supply voltage can result in undefined states and
significant danger as a result of the associated failure of the plant or system control. The
SITOP power supply product portfolio includes various DC-UPS solutions to prevent the
failure of the 24 V power supply voltage.
Power supply failures up into the minutes range can be buffered using the maintenance-free
SITOP UPS500 DC-UPS modules based on capacitors (Figure 9-6 24 V buffering to allow
the saving of process data and controlled shutdown of PCs (Page 71)).
Figure 9-6 24 V buffering to allow the saving of process data and controlled shutdown of PCs
Using the free-of-charge SITOP DC-UPS software tool, DC-UPS systems can be simply
integrated into PC-based automation solutions. This supports further processing of the status
signals and safely running down the PC.
You can find additional information at:
Manual, DC UPS with capacitors
(https://support.industry.siemens.com/cs/ww/en/ps/18042/man)
Applications
9.6 Protecting against longer power failures
SITOP PSU8200 1ph
72 Manual, 08.2016, C98130-A7633-A1-5-7629
Using DC UPS SITOP UPS1600 and SITOP UPS1100 battery modules, buffer times in the
range of hours can be implemented. Intelligent battery management using Energy Storage
Link automatically detects the UPS1100 energy storage device, and ensures optimum
temperature-controlled charging and continuous monitoring. The UPS1600 can be flexibly
integrated into the widest range of automation applications with its digital inputs/outputs as
well as optional USB interface or Ethernet/PROFINET port.
Figure 9-7 24 V buffering with SITOP UPS1600 to maintain communication, signaling functions,
sensor measured values and position values
For open, PC-based automation systems, configuration and monitoring is realized using the
SITOP UPS Manager PC software, which is available at no charge. This allows PC
responses to the operating states of the DC UPS to be freely selected and offers
comprehensive diagnostic functions.
For TIA-based automation systems, the UPS1600 is engineered using the TIA Portal.
Special function blocks for SIMATIC S7-300/400/1200 and S7-1500 available at no charge
make it easy to integrate operating and diagnostics information into STEP 7 user
programs. Preconfigured UPS faceplates for WinCC visualization can be downloaded at no
charge.
You can find additional information at:
DC UPS SITOP UPS1600/UPS1100 Manual
(https://support.industry.siemens.com/cs/ww/en/view/84977415)
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 73
Environment
10
The devices are in conformance with RoHS.
As a rule, only non-silicon precipitating materials are used.
Disposal guidelines
Packaging and packaging aids can and should always be recycled. The product itself may
not be disposed of as domestic refuse.
Environment
SITOP PSU8200 1ph
74 Manual, 08.2016, C98130-A7633-A1-5-7629
SITOP PSU8200 1ph
Manual, 08.2016, C98130-A7633-A1-5-7629 75
Service & Support
11
Technical support
Technical support for all IA/DT products can be accessed through the following
communication channels:
Phone: + 49 (0) 911 895 7222
E-Mail (mailto:support.automation@siemens.com)
Internet:
Online support request form (http://www.siemens.de/automation/support-request)
Technical documentation on the Internet
Operating instructions and manuals for SITOP are available in the Internet:
Operating instructions/manuals (http://www.siemens.de/sitop/manuals)
SITOP power supply homepage
General news about our power supplies is available in the Internet at the SITOP homepage:
SITOP (http://www.siemens.de/sitop)
Information material
SITOP information can be downloaded from the Internet:
Information and download center (http://www.siemens.de/sitop-infomaterial)
CAx data
2D/3D data and circuit diagram macros can be downloaded from the Internet:
Siemens image database (http://www.siemens.de/sitop-cax)
Request all CAx data via the CAx download manager:
CAx shopping cart (http://www.siemens.de/cax)
SITOP Selection Tool
Simply and quickly select the optimum the power supply or DC-UPS:
SITOP Selection Tool (http://www.siemens.de/sitop-selection-tool)
Online catalog and ordering system
The online catalog and the online ordering system are available through the Industry Mall
homepage:
Industry Mall (http://www.siemens.com/industrymall/de)
Service & Support
SITOP PSU8200 1ph
76 Manual, 08.2016, C98130-A7633-A1-5-7629
Contact persons
If you have any questions regarding the use of our products, then contact the Siemens
contact person in your regional Siemens sales office.
You can find these addresses as follows:
On the Internet (http://www.siemens.de/automation/partner)
In Catalog CA 01