EAM series
Small, Low leakage current type (1-Stage filter)
EAM -10 -000 -O
Ordering information
*
The dimensions change when the option is set.
Refer to External view.
1 2 3 4
Features of EAM series
Circuit Diagram Derating Curve
LINE
Case
: Mounting Plate
1
24
3
CY : Line to ground capacitor
LOAD
Small, Low leakage current type(1-Stage filter)
- Single Phase 250 VAC -Small-size
-Quick and easy push-down terminal
Just connect the wires,push-down and tighten
the screws with a screwdriver
Ambient Temperature [C]
Load Factor [%]
9050 60 70 80
20
0
-4040-30-20
100
80
60
40
55
Specifications
No. Items EAM-03-000 EAM-06-000 EAM-10-000 EAM-16-000 EAM-20-000 EAM-30-000
1Rated Voltage[V] AC 1f 250 / DC250
2 Rated Current[A] 3 6 10 16 20 30
3 Test Voltage (Terminal-Mounting Plate) 2,500 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
4 Isolation Resistance (Terminal-Mounting Plate) 500 VDC 500MW min at room temperature and humidity
5 Leakage current 125/250V 60Hz 5A/10 A max
6 DC resistance 180mW max 110mW max 40mW max 20mW max 10mW max 6mW max
7 Safety agency approval temperatures -25 to +85C (Refer to Derating Curve)
8 Operating temperature -40 to +85C (Refer to Derating Curve)
9 Operating humidity 20 to 95%RH (Non condensing)
10 Storage temperature/humidity -40 to +85C/20 to 95%RH (Non condensing)
11 Vibration 10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1hour each X, Y and Z axis
12 Impact 196.1m/s2 (20G), 11ms Once each X, Y and Z axis
13 Safety agency approvals UL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil3-1, ENEC (At only AC input)
14 Case size (without projection) /Weight
39X30X85 mm [1.54X1.18X3.35 inches] (WXHXD) /170g max (Option : -D refer to external view)
DIN rail installation type is optionThe terminal cover is retracted inside the unit
1 Model Name
2 Rated Current
3 Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code Leakage Current
(Input 125/250V 60Hz)
Line to ground
capacitor
(nominal value)
000 5 A/ 10 A max Not Provided
101 12.5 A/ 25 A max 100pF
221 25 A/ 50 A max 220pF
331 37.5 A/ 75 A max 330pF
471
50 A/
100 A max 470pF
* When the line to ground capacitor code is
different, the attenuation characteristic is
different.
4 Options
D
:DIN rail installation type
R
EA/ES-2