https://www.phoenixcontact.com/us/products/2903148
03/22/2021Page1/9
Power supply unit-TRIO-PS-2G/1AC/24DC/5-2903148
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: 1-phase,
output: 24VDC/5A
Product Description
TRIO POWER power supplies with standard functionality
The TRIOPOWER power supply range with push-in connection has been perfected for use in machine building. All functions and the space-saving
design of the single and three-phase modules are optimally tailored to the stringent requirements. Under challenging ambient conditions, the power
supply units, which feature an extremely robust electrical and mechanical design, ensure the reliable supply of all loads.
Your advantages
Save time and costs, thanks to the Push-in connection and narrow design
Increase system availability, thanks to dynamic boost with 150% of the nominal current for five seconds
Maximum flexibility due to the wide temperature range from -25°C to +70°C and device startup at -40°C
Rugged design
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4046356960847
Weight per Piece (excluding packing) 560.000 g
Custom tariff number 85044030
Country of origin China
Technical data
Dimensions
Width 35 mm
https://www.phoenixcontact.com/us/products/2903148
03/22/2021Page2/9
Power supply unit-TRIO-PS-2G/1AC/24DC/5-2903148
Technical data
Dimensions
Height 130 mm
Depth 115 mm
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm
Ambient conditions
Degree of protection IP20
Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height ≤ 5000 m (>2000m, Derating: 10%/1000m)
Input data
Nominal input voltage range 100 VAC ... 240 VAC
110 VDC ... 250 VDC
Input voltage range 100 VAC ... 240 VAC -15% ... +10%
99 VDC ... 275 VDC
Dielectric strength maximum ≤ 300 VAC 15 s
AC frequency range 50 Hz ... 60 Hz ±10%
Discharge current to PE < 0.25 mA
Current consumption 2.2 A (100VAC)
1.9 A (120VAC)
1.1 A (230 V AC)
1.1 A (240VAC)
Nominal power consumption 272 VA
Inrush current ≤ 16 A (typical)
Mains buffering time typ. 20 ms (120VAC)
typ. 100 ms (230 V AC)
Input fuse 6.3 A (internal (device protection))
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.5
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
https://www.phoenixcontact.com/us/products/2903148
03/22/2021Page3/9
Power supply unit-TRIO-PS-2G/1AC/24DC/5-2903148
Technical data
Output data
Nominal output voltage 24 VDC ±1%
Setting range of the output voltage (USet)24 VDC ... 28 VDC (> 24 VDC, constant capacity restricted)
Nominal output current (IN)5 A
Dynamic Boost (IDyn.Boost)7.5 A (5 s)
Derating > 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback voltage resistance ≤ 35 VDC
Protection against overvoltage at the output (OVP) ≤ 30 VDC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Output power 120 W
Typical response time < 1 s
Maximum power dissipation in no-load condition < 1 W
Power loss nominal load max. < 16 W
General
Net weight 0.45 kg
Efficiency > 90 % (for 230 V AC and nominal values)
MTBF (IEC 61709, SN 29500) > 3380000 h (25°C)
> 1970000 h (40°C)
> 900000 h (60°C)
Insulation voltage input/output 3 kV AC (type test)
1.5 kV AC (routine test)
Degree of protection IP20
Protection class II (in closed control cabinet)
Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Connection data, input
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
https://www.phoenixcontact.com/us/products/2903148
03/22/2021Page4/9
Power supply unit-TRIO-PS-2G/1AC/24DC/5-2903148
Technical data
Connection data, input
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 10 mm
Connection data, output
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 8 mm
Connection data for signaling
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Standards
EMC requirements for noise immunity EN61000-6-1
EN61000-6-2
EMC requirements for noise emission EN61000-6-3
EN61000-6-4
Standard - Safety of transformers EN61558-2-16 (air clearances and creepage distances only)
Standard - Electrical safety IEC60950-1/VDE0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations EN50178/VDE0160 (PELV)
Standard – Safety extra-low voltage IEC60950-1 (SELV) and EN60204-1 (PELV)
Standard - Safe isolation DINVDE0100-410
Standard – Limitation of mains harmonic currents EN61000-3-2
Rail applications EN50121-4
Conformance/approvals
UL approvals UL Listed UL508
https://www.phoenixcontact.com/us/products/2903148
03/22/2021Page5/9
Power supply unit-TRIO-PS-2G/1AC/24DC/5-2903148
Technical data
Conformance/approvals
UL/C-UL Recognized UL 60950-1
EMC data
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electrostatic discharge EN 61000-4-2
Contact discharge 6 kV (Test Level 4)
Discharge in air 8 kV (Test Level 4)
Electromagnetic HF field EN61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst) EN61000-4-4
Input 4 kV (Test Level 4 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion A
Surge voltage load (surge) EN61000-4-5
Input 3 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion B
Conducted interference EN61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Comments Criterion A
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the
device itself.
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
https://www.phoenixcontact.com/us/products/2903148
03/22/2021Page6/9
Power supply unit-TRIO-PS-2G/1AC/24DC/5-2903148
Technical data
Environmental Product Compliance
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Block diagram
13
14
L/+
N/-
+
+
-
-
-
Classifications
eCl@ss
eCl@ss 10.0.1 27040701
eCl@ss 11.0 27040701
eCl@ss 4.0 27040700
eCl@ss 4.1 27040700
eCl@ss 5.0 27049000
eCl@ss 5.1 27049000
eCl@ss 6.0 27049000
eCl@ss 7.0 27049002
eCl@ss 9.0 27040701
ETIM
ETIM 4.0 EC002540
ETIM 6.0 EC002540
ETIM 7.0 EC002540
UNSPSC
UNSPSC 13.2 39121004
UNSPSC 18.0 39121004
UNSPSC 19.0 39121004
UNSPSC 20.0 39121004
UNSPSC 21.0 39121004
https://www.phoenixcontact.com/us/products/2903148
03/22/2021Page7/9
Power supply unit-TRIO-PS-2G/1AC/24DC/5-2903148
Approvals
Approvals
Approvals
DNV GL / UL Listed / UL Recognized / cUL Recognized / IECEE CB Scheme / cUL Listed / EAC / cULus Recognized / cULus Listed
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
DNV GL https://approvalfinder.dnvgl.com/ TAA00000BM
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
IECEE CB Scheme http://www.iecee.org/ DK-44782-A1-M1-UL
cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
EAC RU*DE*08.B.01873/19
https://www.phoenixcontact.com/us/products/2903148
03/22/2021Page8/9
Power supply unit-TRIO-PS-2G/1AC/24DC/5-2903148
Approvals
cULus Recognized
cULus Listed
Accessories
Accessories
Device circuit breakers
Electronic circuit breaker-CBM E4 24DC/0.5-10A NO-R-2905743
Multi-channel, electronic circuit breaker with active current limitation for protecting four loads at 24 V DC in the event
of overload and short circuit. With nominal current assistant and electronic locking of the set nominal currents. For
installation on DIN rails.
Electronic circuit breaker-CBM E8 24DC/0.5-10A NO-R-2905744
Multi-channel, electronic circuit breaker with active current limitation for protecting eight loads at 24 V DC in the event
of overload and short circuit. With nominal current assistant and electronic locking of the set nominal currents. For
installation on DIN rails.
Device protection
Type 3 surge protection device-PLT-SEC-T3-230-FM-PT-2907928
Type2/3 surge protection, consisting of protective plug and base element with Push-in connection. For single-phase
power supply network with integrated status indicator and remote signaling. Nominal voltage: 230VAC/DC
https://www.phoenixcontact.com/us/products/2903148
03/22/2021Page9/9
Power supply unit-TRIO-PS-2G/1AC/24DC/5-2903148
Accessories
Type 3 surge protection device-PLT-SEC-T3-24-FM-PT-2907925
Type3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote
signaling for single-phase power supply networks. Nominal voltage: 24VAC/DC
Potential distributor
Potential distributors-VIP-2/SC/PDM-2/24-2315269
VARIOFACE module, with two equipotential busbars (P1, P2) for potential distribution, for mounting on NS 35 rails.
Module width: 70.4 mm
Potential distributors-VIP-3/PT/PDM-2/24-2903798
VARIOFACE module with push-in connection and two equipotential busbars (P1, P2) for potential distribution, for
mounting on NS 35 rails. Module width: 57.1 mm
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com