Du line
®
Fieldbus Installationbus
Specifications are subject to change without notice (05.04.2006) 1
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Supply type Ordering no.
20-30 VDC GH34850000724
Generates 28 V Hi-Line signal
Supplies and controls up to 64 valve I/O modules over
two wires
Up to 7 km transmission distance
Built-in Gas-arrestor for lightning protection
• H4 housing
LED-indications for Dupline carrier, Hi-Line carrier and
supply
DC power supplied
Product Description
Type Selection
Dupline®Hi-Line Booster Module for Valve Control
Type GH34850000
GH34850000724 is a con-
verter module for the
Dupline®irrigation control
concept. It converts a stan-
dard Dupline®signal to a
28V "Hi-Line" signal, which
can be used to supply and
control up to 64 Valve I/O
modules. GH34850000724
can be used with any type of
Dupline®channel generator,
including Modbus interfaces
and dedicated interfaces for
most PLC brands.
The two-wire Hi-Line cable
can be up to 7 km long.
Supply Specifications
Supply Supply must be galvanically
isolated from mains and PE,
and only connected to the
Dupline®channel generator
and the Dupline®booster
module.
Rated operational voltage through term. 21(+) & 22(-)
20 to 30 VDC (ripple included)
Ripple 3 V
Reverse polarity protection Yes
Rated operational current 300 mA
Transient protection voltage 800 V
Dielectric voltage
Supply – Dupline®None
Supply - Hi-Line None
Input/Output Specifications
Inputs
Terminals 24(+) & 25(-) Dupline®Bus
Current consumption 2 mA
Max. distance between
channel generator and
GH34850000 50 m
Outputs
Terminals 27(+) & 28(-) Hi-Line Bus
Short-circuit protection Yes
Overload protection Yes
Max. bus load
64 Valve modules
(GH64404412 or GH34404412)
General Specifications
Power ON delay max. 120 sec. (with 64
modules connected)
Indication for
Dupline®carrier in LED, yellow
Hi-Line carrier out LED, yellow
Supply LED, green
Environment
Degree of protection IP20 B
Pollution degree 3 (IEC 60664)
Operating temperature
to +50°C (+32° to +122°F)
Storage temperature
-20° to +85°C (-4° to +185°F)
Humidity (non-condensing) 20 to 80%
Dimensions H4- housing
Material Noryl SE1, Grey
Mechanical resistance
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Weight 200 g
GH34850000724
Type: Dupline®
H4-Housing
DC supply
Ordering Key
Du line
®
Fieldbus Installationbus
2Specifications are subject to change without notice (05.04.2006)
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
GH34850000
Mode of Operation
The purpose of the Dupline
Irrigation Bus System is to
reduce the cost of the wiring
in irrigation systems. By con-
necting the Irrigation Con-
troller with all the valves in the
field via a 2-wire bus, a much
simpler and more flexible
solution is achieved com-
pared to the traditional multi-
core cable with a hot-wire for
each valve. The bus system
enables the Irrigation Con-
troller to control each individ-
ual valve (open/closed) and it
also carries the power
required to operate the
valves, which must be 3-wire
12 VDC latching types. It is
also possible to send infor-
mation from the field to the
Irrigation Controller, e.g. puls-
es from a flow meter. Each
valve must be connected to a
bus I/O-module with 2 digital
outputs (open, close) and 2
digital inputs. The interface
between the Irrigation Con-
troller and the Dupline Master
Module is achieved via serial
communication (RS232 or
RS485) between the two
devices.
The GH34850000724 booster
module increases the voltage
level of the standard Dupline
signal to 28 VDC in order to
achieve sufficient voltage lev-
el to operate the valves. The
diagram below shows the
topology of the system.
Irrigation
Controller
Dupline
Master
Module
Dupline
Booster
Valve +
Flow meter
Valve +
Flow meter
I/O-module I/O-module
I/O-module I/O-module
Valve +
Flow meter
Valve +
Flow meter
Valve +
Flow meter
I/O-module
I/O-module I/O-module
Valve +
Flow meter
Valve +
Flow meter
RS232/
RS485 Dupline Hi-line
Du line
®
Fieldbus Installationbus
Specifications are subject to change without notice (05.04.2006) 3
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
System Characteristics
Cable requirements
Min. cable cross-section
1.5 mm2
Shield not required
Twist not required
Free topology
Distance and number
of valves
Max. 64 valves on one line
(128 outputs, 128 inputs)
Up to 7 km communication
distance
There must be min. 10 s
between two valve operations
on the line.
The table below shows the
max. number of valves on
one line as a function of dis-
tance and cross-section of
the cable. The "shaded" cells
are always valid. The un-
shaded cells are based on a
uniform distribution of the
valves and are hence valid
when the average distance
between the valves and the
Hi-Line Booster is below 0.75
of the distance between the
Hi-line Booster and the far-
thest valve.
1 km 2 km 3 km 4 km 5 km 6 km 7 km
1.5 sq.mm 64 64 64 64 64 54 44
2.5 sq.mm 64 64 64 64 64 64 64
12 VDC latching valve
Loss of bus signal
If the valve I/O-module looses the bus signal, it will automatically close the valve.
Wiring Diagram
18765432
21 28272625242322
20 - 30 V
Supply
Input
DUP COM
Dupline
Input
BUS+BUS -
Hi-Line
Output
+ - + - + -
GH34850000
Dimensions (mm)
H4-housing