1
Thermal-magnetic (TM and AS-line) AS168XAC1
www.schurter.com /PG20
Circuit Breakers
Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 1 pole
Description
- Thermal-magnetic circuit breaker
- High short circuit performance
- Availability of AC and DC in the same frame size
- DIN-Rail Mounting
Standards
- Approval Reference Type: AS168X
- IEC 60934
- UL508, UL1077
- CSA C22.2
Applications
- Industrial appliances
Weblinks
pdf datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
General data
Rated Voltage AC IEC : 240 V; 50/60 Hz
␣ UL/CSA : 277 V; 50/60 Hz
Rated Voltage DC 65 V
Rated current 0.5 - 52 A , see approbations
Conditional short circuit capa-
city IEC 60934
Icn: AC 240 V / DC 65 V: 5 kA (no fuse)
Conditional short circuit capa-
city UL 1077
Inc: AC 277 V: 10 kA (with fuse class
H/J, 4x rated current (min. 15 A))
Icn: AC 125 V: 10 kA (no fuse)
Icn: AC 277 V: 5 kA (no fuse)
Icn: DC 65 V: 2 kA (no fuse)
Conditional short circuit capa-
city UL 508
Icn: AC 277 V: 5 kA (no fuse)
Degree of Protection from front side IP 40 acc. to IEC 60529
Lifetime 1 x Ir : 6000 switching cycles
Dielectric Strength 50 Hz: > 2 kV
Impulse 1.2/50 μs
Vibration Resistance ± 0.75 mm @ 5 - 57 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 57 - 500 Hz
acc. to IEC 60068-2-6, test Fc
Insulation Resistance 250/440 VAC > 5 MΩ
Shock Resistance 25 G / 10 ms
acc. to IEC 60068-2-27, test Ea
Ambient temperature -20 °C to 60 °C
Weight 100 - 130 g
Tripping Type
Positively trip free
Actuation Type Manual ON/OFF
Permissible wire cross section 1.5 - 25 mm² / 16 - 4 AWG
Switched neutral
Rated Voltage AC 277 V
Rated current AC/DC 65 A
Function The switched neutral closes with ma-
nual closure of the poles and opens
automatically with thermal magnetic
tripping of the poles.
Add-on modules
Add-on modules Technical data for the additional module
see separate data sheet
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in General Product
Information