General purpose relays 6 - 10A
Plug-in mount
10A General purpose relay
Type 60.12
- 2 pole, 10 A
Type 60.13
- 3 pole, 10 A
2 & 3 pole changeover contacts
Cadmium Free contacts (preferred version)
AC coils & DC coils
UL Listing (certain relay/socket combinations)
Contact material options
Lockable test button with mechanical flag
indicator (preferred version)
90 series sockets
Coil EMC suppression
Timer accessories 86 series
European Patent
For UL ratings see:
“General technical information” page V
60.12 60.13
2 pole, 10A
8 pin plug-in
3 pole, 10A
11 pin plug-in
For outline drawing see page 8
Contact specification
Contact configuration 2 CO (DPDT) 3 CO (3PDT)
Rated current/Maximum peak current A 10/20 10/20
Rated voltage/
Maximum switching voltage VAC 250/400 250/400
Rated load AC1 VA 2500 2500
Rated load AC15 (230VAC) VA 500 500
Single phase motor rating (230VAC) kW 0.37 0.37
Breaking capacity DC1: 30/110/220V A 10/0.4/0.15 10/0.4/0.15
Minimum switching load mW (V/mA) 500 (10/5) 500 (10/5)
Standard contact material AgNi AgNi
Coil specification
Nominal voltage (UN) VAC (50/60Hz) 6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 - 400
VDC 6 - 12 - 24 - 48 - 60 - 110 -125 - 220
Rated power AC/DC VA (50Hz)/W 2.2/1.3 2.2/1.3
Operating range AC (0.8…1.1)UN(0.8…1.1)UN
DC (0.8…1.1)UN(0.8…1.1)UN
Holding voltage AC/DC 0.8UN/0.5UN0.8UN/0.5UN
Must drop-out voltage AC/DC 0.2UN/0.1UN0.2UN/0.1UN
Technical data
Mechanical life AC/DC cycles 20·106/50·10620·106/50·106
Electrical life at rated load AC1 cycles 200·103200·103
Operate/release time ms 11/4 11/4
Insulation between coil
and contacts (1.2/50μs) kV 4 3.6
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type)
I-2018www.findernet.com
4
A
60 SERIES
General purpose relays 6 - 10A
60
SERIES
Plug-in mount - 6A
Bifurcated contacts for low level switching
Type 60.12 - 52xx
- 2 pole, 6 A
Type 60.13 - 52xx
- 3 pole, 6 A
2 & 3 pole changeover contacts
Cadmium Free contacts
(Gold plated Silver Nickel)
AC coils & DC coils
Lockable test button with mechanical flag
indicator (preferred version)
90 series sockets
Coil EMC suppression
Timer accessories 86 series
European Patent
For UL ratings see:
“General technical information” page V
60.12 - 52xx 60.13 - 52xx
2 pole, 6A
Bifurcated contacts with AgNi + Au
8 pin plug-in
3 pole, 6A
Bifurcated contacts with AgNi + Au
11 pin plug-in
For outline drawing see page 8
Contact specification
Contact configuration 2 CO (DPDT) 3 CO (3PDT)
Rated current/Maximum peak current A 6/10 6/10
Rated voltage/
Maximum switching voltage VAC 250/400 250/400
Rated load AC1 VA 1500 1500
Rated load AC15 (230VAC) VA 250 250
Single phase motor rating (230VAC) kW 0.185 0.185
Breaking capacity DC1: 30/110/220V A 6/0.3/0.12 6/0.3/0.12
Minimum switching load mW (V/mA) 50 (5/5) 50 (5/5)
Standard contact material AgNi + Au AgNi + Au
Coil specification
Nominal voltage (UN) VAC (50/60Hz) 6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 - 400
VDC 6 - 12 - 24 - 48 - 60 - 110 -125 - 220
Rated power AC/DC VA (50Hz)/W 2.2/1.3 2.2/1.3
Operating range AC (0.8…1.1)UN(0.8…1.1)UN
DC (0.8…1.1)UN(0.8…1.1)UN
Holding voltage AC/DC 0.8UN/0.5UN0.8UN/0.5UN
Must drop-out voltage AC/DC 0.2UN/0.1UN0.2UN/0.1UN
Technical data
Mechanical life AC/DC cycles 20·106/50·10620·106/50·106
Electrical life at rated load AC1 cycles 250·103250·103
Operate/release time ms 11/4 11/4
Insulation between coil
and contacts (1.2/50μs) kV 4 3.6
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type)
I-2018www.findernet.com
5
A
60
SERIES
60 SERIES
General purpose relays 6 - 10A
Flange mount - General purpose relay 10A
Type 60.62
- 2 pole, 10 A
Type 60.63
- 3 pole, 10 A
Faston 187, (4.8x0.8mm)
2 & 3 pole changeover contacts
AC coils & DC coils
Cadmium Free contacts
Contacts material options
For UL ratings see:
“General technical information” page V
60.62 60.63
2 pole, 10A power contacts
Flange mount
Faston 187
3 pole, 10A power contacts
Flange mount
Faston 187
For outline drawing see page 8
Contact specification
Contact configuration 2 CO (DPDT) 3 CO (3PDT)
Rated current/Maximum peak current A 10/20 10/20
Rated voltage/
Maximum switching voltage VAC 250/400 250/400
Rated load AC1 VA 2500 2500
Rated load AC15 (230VAC) VA 500 500
Single phase motor rating (230VAC) kW 0.37 0.37
Breaking capacity DC1: 30/110/220V A 10/0.4/0.15 10/0.4/0.15
Minimum switching load mW (V/mA) 500 (10/5) 500 (10/5)
Standard contact material AgNi AgNi
Coil specification
Nominal voltage (UN) VAC (50/60Hz) 6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 - 400
VDC 6 - 12 - 24 - 48 - 60 - 110 -125 - 220
Rated power AC/DC VA (50Hz)/W 2.2/1.3 2.2/1.3
Operating range AC (0.8…1.1)UN(0.8…1.1)UN
DC (0.8…1.1)UN(0.8…1.1)UN
Holding voltage AC/DC 0.8UN/0.5UN0.8UN/0.5UN
Must drop-out voltage AC/DC 0.2UN/0.1UN0.2UN/0.1UN
Technical data
Mechanical life AC/DC cycles 20·106/50·10620·106/50·106
Electrical life at rated load AC1 cycles 200·103200·103
Operate/release time ms 11/4 11/4
Insulation between coil
and contacts (1.2/50μs) kV 4 3.6
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type) Z
I-2018www.findernet.com
6
A
60 SERIES
General purpose relays 6 - 10A
60
SERIES
Ordering information
Example: 60 series plug-in relay, 3 CO (3PDT), 12VDC coil, test button and mechanical indicator.
A B C D
6 0 . 1 3 . 9 . 0 1 2 . 0 0 4 0
Series
Type
1 = 8/11 pin plug-in
6 = Faston 187 (4.8x0.8mm)
with flange mount
No. of poles
2 = 2 pole
3 = 3 pole
Coil version
4 = Current sensing (60.12/13 only)
8 = AC (50/60Hz)
9 = DC
Coil voltage
See coil specifications
A: Contact material
0 = Standard
5 = AgNi + Au
B: Contact circuit
0 = CO (nPDT)
2 = Bifurcated contacts
60.12/13 - 6A only
D: Special versions
0 = Standard
C: Options
0 = None
2 = Mechanical indicator
3 = LED (AC)
4 = Lockable test button +
mechanical indicator
5* = Lockable test button + LED (AC)
54* = Lockable test button + LED (AC) +
mechanical indicator
6* = LED + diode (DC, polarity positive
to pin 2)
7* = Lockable test button + LED + diode
(DC, polarity positive to pin 2)
74* = Lockable test button + LED +
diode (DC, polarity positive to pin
2) + mechanical indicator
* Options not available for 220VDC and
400VAC versions.
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type Coil version A B C D
60.12/13 AC 000 - 2 - 3 - 4 - 5 0
AC 0 0 54 /
AC 5 0 - 2 0 - 2 - 3 - 4 - 5 0
AC 5 0 - 2 54 /
DC 000 - 2 - 4 - 6 - 7 0
DC 0 0 74 /
DC 5 0 - 2 0 - 2 - 4 - 6 - 7 0
DC 5 0 - 2 74 /
current sensing 0 0 4 0
60.62/63 AC-DC 0 - 5 000
Descriptions: Options and Special versions
C: Option 3, 5, 54
LED (AC)
C: Option 6, 7, 74
LED + diode (DC, polarity
positive to pin 2)
1
2
3
Lockable test button and mechanical flag indicator (0040, 0050, 0054, 0070, 0074)
The dual-purpose Finder test button can be used in two ways:
Case 1) The plastic pip (located directly above the test button) remains intact. In this case, when the
test button is pushed, the contacts operate. When the test button is released the contacts return to
their former state.
Case 2) The plastic pip is broken-off (using an appropriate cutting tool). In this case, (in addition to
the above function), when the test button is pushed and rotated, the contacts are latched in the
operating state, and remain so until the test button is rotated back to its former position.
In both cases ensure that the test button actuation is swift and decisive.
E
U
R
O
P
E
A
N
E
U
R
O
P
E
A
N
PATENT
I-2018www.findernet.com
7
A
60
SERIES
60 SERIES
General purpose relays 6 - 10A
Technical data
Insulation according to EN61810-1 2 pole 3 pole
Nominal voltage of supply system VAC 230/400 230/400
Rated insulation voltage VAC 250 400 250 400
Pollution degree 3 2 3 2
Insulation between coil and contact set
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50μs) 4 3.6
Dielectric strength VAC 2000 2000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50μs) 4 3.6
Dielectric strength VAC 2000 2000
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength VAC/kV (1.2/50μs) 1000/1.5 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50µs) 4
Other data
Bounce time: NO/NC ms 1/4
Vibration resistance (5…55)Hz: NO/NC g 22/22
Shock resistance g 20
Power lost to the environment without contact current W 1.3 1.3
with rated current W 2.7 (60.12, 60.62) 3.4 (60.13, 60.63)
Contact specification
F 60 - Electrical life (AC) v contact current H 60 - Maximum DC1 breaking capacity
Resistive load - cosφ = 1
Inductive load - cosφ = 0.4
Cycles
contacts in series
DC breaking current (A)
DC voltage (V)
When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥100·103 can be expected.
In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Coil specifications AC coil data
Nominal
voltage
Coil code Operating range Resistance Rated coil
absorption
UNUmin Umax RI at UN (50Hz)
V V V ΩmA
68.006 4.8 6.6 4.6 367
12 8.012 9.6 13.2 19 183
24 8.024 19.2 26.4 74 90
48 8.048 38.4 52.8 290 47
60 8.060 48 66 450 37
110 8.110 88 121 1600 20
120 8.120 96 132 1940 18.6
230 8.230 184 253 7250 10.5
240 8.240 192 264 8500 9.2
400 8.400 320 440 19800 6
DC coil data
Nominal
voltage
Coil code Operating range Resistance Rated coil
absorption
UNUmin Umax RI at UN
V V V ΩmA
69.006 4.8 6.6 28 214
12 9.012 9.6 13.2 110 109
24 9.024 19.2 26.4 445 53.9
48 9.048 38.4 52.8 1770 27.1
60 9.060 48 66 2760 21.7
110 9.110 88 121 9420 11.7
125 9.125 100 138 12000 10.4
220 9.220 176 242 37300 5.8
I-2018www.findernet.com
8
A
60 SERIES
General purpose relays 6 - 10A
60
SERIES
Coil specifications
R 60 - DC coil operating range v ambient temperature R 60 - AC coil operating range v ambient temperature
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
Current sensing version
Current sensing DC coil data
Coil code Imin (A) IN (A) Imax (A) R (Ω)
4202 1.7 2.0 2.4 0.15
4182 1.5 1.8 2.2 0.19
4162 1.4 1.6 1.9 0.24
4142 1.2 1.4 1.7 0.31
4122 1.0 1.2 1.4 0.42
4102 0.85 1.0 1.2 0.61
4092 0.8 0.9 1.1 0.75
4062 0.5 0.6 0.7 1.70
4032 0.25 0.3 0.4 6.70
4012 0.085 0.1 0.15 61
Typical application with current sensing relays.
An open circuit filiment of lamp L1 is detected by the current sensing
relay coil (K1) which causes the back-up safety lamp L2 to be energised,
and indication of failure at the control panel via lamp S1.
Example: navigation light.
L1 = Light
L2 = Safety light
S1= Control light
K1 = Relay
Current sensing AC coil data
Coil code Imin (A) IN (A) Imax (A) R (Ω)
4251 2.1 2.5 3.0 0.05
4181 1.5 1.8 2.2 0.10
4161 1.4 1.6 1.9 0.12
4121 1.0 1.2 1.4 0.22
4101 0.85 1.0 1.2 0.32
4051 0.42 0.5 0.6 1.28
4041 0.34 0.4 0.5 2.00
4031 0.25 0.3 0.4 3.57
4021 0.17 0.2 0.25 8.0
4011 0.085 0.1 0.15 32.1
Other types of current sensing relays are available on request.
Outline drawings
Type 60.12/60.12 - 52xx Type 60.13/60.13 - 52xx Type 60.62 Type 60.63
I-2018www.findernet.com
9
A
60
SERIES
90 SERIES
Socket overview for 60 series relays
Accessories
90.03
See page 10
Module Socket Relay Description Mounting Accessories
99.02 90.02 60.12 Screw terminal (Box clamp) socket Panel or 35mm rail
(EN60715) mount
- Coil indication and EMC
suppression modules
- Jumper link
- Timer modules
- Metal retaining clip
90.03 60.13 Double A1 terminal
90.21
See page 11
Module Socket Relay Description Mounting Accessories
99.01 90.20 60.12 Screw terminal (Box clamp) socket Panel or 35mm rail
(EN60715) mount
- Coil indication and EMC
suppression modules
- Metal retaining clip
90.21 60.13
90.83.3
See page 12
Module Socket Relay Description Mounting Accessories
90.82.3 60.12 Screw terminal (Box clamp) socket Panel or 35mm rail
(EN60715) mount
- Metal retaining clip
90.83.3 60.13
90.23
See page 12
Module Socket Relay Description Mounting Accessories
90.22 60.12 Screw terminal (Box clamp) socket Panel or 35mm rail
(EN60715) mount
- Metal retaining clip
90.23 60.13
90.26
See page 13
Module Socket Relay Description Mounting Accessories
90.26 60.12 Screw terminal (Plate clamp) socket Panel or 35 mm rail
(EN60715) mount
- Metal retaining clip
90.27 60.13
90.12
See page 13
Module Socket Relay Description Mounting Accessories
90.12 60.12 Flange mount solder socket M3 screw fixing
90.13 60.13
90.15
See page 14
Module Socket Relay Description Mounting Accessories
90.14 60.12 PCB socket PCB
90.14.1 60.12
90.15 60.13
90.15.1 60.13
060.48
Sheet of marker tags (CEMBRE Thermal transfer printers) for relay types 60.12 and 60.13,
plastic, 48 tags, 6x12mm 060.48
I-2018www.findernet.com
10
A
90 SERIES
Sockets and accessories for 60 series relays
60
SERIES
90.03
Approvals
(according to type):
Certain relay/socket
combinations
Screw terminal (Box clamp) socket
panel or 35mm rail (EN60715) mount
90.02
Blue
90.02.0
Black
90.03
Blue
90.03.0
Black
For relay type 60.12 60.13
Accessories
Metal retaining clip 090.33
6-way jumper link 090.06
Identification tag 090.00.2
Modules (see table below) 99.02
Timer modules (see table below) 86.00, 86.30
Technical data
Rated values 10A - 250V
Dielectric strength 2kVAC
Protection category IP 20
Ambient temperature °C –40…+70
Screw torque Nm 0.6
Wire strip length mm 10
Max. wire size for 90.02 and 90.03 sockets solid wire stranded wire
mm21x6 / 2x2.5 1x4 / 2x2.5
AWG 1x10 / 2x14 1x12 / 2x14
86.00
86.30
99.02
090.06
E
U
R
O
P
E
A
N
E
U
R
O
P
E
A
N
PATENT
Approvals
(according to type):
DC Modules with non-
standard polarity (+A2) on
request.
6-way jumper link for 90.02 and 90.03 sockets 090.06 (blue) 090.06.0 (black)
Rated values 10 A - 250 V
Approvals
(according to type):
86 series timer modules
Multi-voltage: (12…240)VAC/DC;
Multi-functions: AI, DI, SW, BE, CE, DE, EE, FE; (0.05s…100h) 86.00.0.240.0000
(12…24)VAC/DC; Bi-function: AI, DI; (0.05s…100h) 86.30.0.024.0000
(110…125)VAC; Bi-function: AI, DI; (0.05s…100h) 86.30.8.120.0000
(230…240)VAC; Bi-function: AI, DI; (0.05s…100h) 86.30.8.240.0000
Approvals (according to type):
99.02 coil indication and EMC suppression modules for 90.02 and 90.03 sockets
Diode (+A1, standard polarity) (6…220)VDC 99.02.3.000.00
LED (6…24)VDC/AC 99.02.0.024.59
LED (28…60)VDC/AC 99.02.0.060.59
LED (110…240)VDC/AC 99.02.0.230.59
LED + Diode (+A1, standard polarity) (6…24)VDC 99.02.9.024.99
LED + Diode (+A1, standard polarity) (28…60)VDC 99.02.9.060.99
LED + Diode (+A1, standard polarity) (110…220)VDC 99.02.9.220.99
LED + Varistor (6…24)VDC/AC 99.02.0.024.98
LED + Varistor (28…60)VDC/AC 99.02.0.060.98
LED + Varistor (110…240)VDC/AC 99.02.0.230.98
RC circuit (6…24)VDC/AC 99.02.0.024.09
RC circuit (28…60)VDC/AC 99.02.0.060.09
RC circuit (110…240)VDC/AC 99.02.0.230.09
Residual current by-pass (110…240)VAC 99.02.8.230.07
I-2018www.findernet.com
11
A
60
SERIES
90 SERIES
Sockets and accessories for 60 series relays
90.21
Approvals
(according to type):
Screw terminal (Box clamp) socket
panel or 35mm rail (EN60715) mount
90.20
Blue
90.20.0
Black
90.21
Blue
90.21.0
Black
For relay type 60.12 60.13
Accessories
Metal retaining clip
(supplied with socket - packaging code SMA) 090.33
Modules (see table below) 99.01
Technical data
Rated values 10A - 250V
Dielectric strength 2kVAC
Protection category IP 20
Ambient temperature °C –40…+70
Screw torque Nm 0.5
Wire strip length mm 10
Max. wire size for 90.20 and 90.21 sockets solid wire stranded wire
mm21x6 / 2x2.5 1x6 / 2x2.5
AWG 1x10 / 2x14 1x10 / 2x14
90.20 90.21
99.01
Approvals
(according to type):
* Modules in Black
housing are available on
request.
Green LED is standard.
Red LED available on
request.
99.01 coil indication and EMC suppression modules for 90.20 and 90.21 sockets
Blue*
Diode (+A1, standard polarity) (6…220)VDC 99.01.3.000.00
Diode (+A2, non-standard polarity) (6…220)VDC 99.01.2.000.00
LED (6…24)VDC/AC 99.01.0.024.59
LED (28…60)VDC/AC 99.01.0.060.59
LED (110…240)VDC/AC 99.01.0.230.59
LED + Diode (+A1, standard polarity) (6…24)VDC 99.01.9.024.99
LED + Diode (+A1, standard polarity) (28…60)VDC 99.01.9.060.99
LED + Diode (+A1, standard polarity) (110…220)VDC 99.01.9.220.99
LED + Diode (+A2, non-standard polarity) (6…24)VDC 99.01.9.024.79
LED + Diode (+A2, non-standard polarity) (28…60)VDC 99.01.9.060.79
LED + Diode (+A2, non-standard polarity) (110…220)VDC 99.01.9.220.79
LED + Varistor (6…24)VDC/AC 99.01.0.024.98
LED + Varistor (28…60)VDC/AC 99.01.0.060.98
LED + Varistor (110…240)VDC/AC 99.01.0.230.98
RC circuit (6…24)VDC/AC 99.01.0.024.09
RC circuit (28…60)VDC/AC 99.01.0.060.09
RC circuit (110…240)VDC/AC 99.01.0.230.09
Residual current by-pass (110…240)VAC 99.01.8.230.07
I-2018www.findernet.com
12
A
90 SERIES
Sockets and accessories for 60 series relays
60
SERIES
90.83.3
Approvals
(according to type):
Screw terminal (Box clamp) socket
panel or 35mm rail (EN60715) mount
90.82.3
Blue
90.82.30
Black
90.83.3
Blue
90.83.30
Black
For relay type 60.12 60.13
Accessories
Metal retaining clip 090.33
Technical data
Rated values 10A - 250V
Dielectric strength 2kVAC
Protection category IP 20
Ambient temperature °C –40…+70
Screw torque Nm 0.8
Max. wire size for 90.82.3 and 90.83.3 sockets solid wire stranded wire
mm21x6 / 2x4 1x6 / 2x4
AWG 1x10 / 2x14 1x10 / 2x14
90.82.3 90.83.3
90.23
Approvals
(according to type):
Screw terminal (Box clamp) socket
panel or 35mm rail (EN60715) mount
90.22
Blue
90.23
Blue
For relay type 60.12 60.13
Accessories
Metal retaining clip
(supplied with socket - packaging code SMA) 090.33
Technical data
Rated values 10A - 250V
Dielectric strength 2kVAC
Protection category IP 20
Ambient temperature °C –40…+70
Screw torque Nm 0.5
Wire strip length mm 7
Max. wire size for 90.22 and 90.23 sockets solid wire stranded wire
mm21x6 / 2x2.5 1x6 / 2x2.5
AWG 1x10 / 2x14 1x10 / 2x14
90.2390.22
I-2018www.findernet.com
13
A
60
SERIES
90 SERIES
Sockets and accessories for 60 series relays
90.26
Approvals
(according to type):
Screw terminal (Box clamp) socket
panel or 35mm rail (EN60715) mount
90.26
Blue
90.26.0
Black
90.27
Blue
90.27.0
Black
For relay type 60.12 60.13
Accessories
Metal retaining clip
(supplied with socket - packaging code SMA) 090.33
Technical data
Rated values 10A - 250V
Dielectric strength 2kVAC
Protection category IP 20
Ambient temperature °C –40…+70
Screw torque Nm 0.8
Wire strip length mm 10
Max. wire size for 90.26 and 90.27 sockets solid wire stranded wire
mm21x4 / 2x2.5 1x4 / 2x2.5
AWG 1x12 / 2x14 1x12 / 2x14
90.26 90.27
90.12
Approvals
(according to type):
Flange mount solder socket mount with M3 screw 90.12 (black) 90.13 (black)
For relay type 60.12 60.13
Technical data
Rated values 10A - 250V
Dielectric strength 2kVAC
Ambient temperature °C –40…+70
90.12 90.13
I-2018www.findernet.com
14
A
90 SERIES
Sockets and accessories for 60 series relays
60
SERIES
90.15
Approvals
(according to type):
PCB socket Blue
Blue
90.14 (Ø20.5mm)
90.14.1 (Ø17.5mm)
90.15 (Ø22mm)
90.15.1 (Ø19mm)
For relay type 60.12 60.13
Technical data
Rated values 10A - 250V
Dielectric strength 2kVAC
Ambient temperature °C –40…+70
90.15
90.14 90.14.1 90.15.190.15 90.1590.14
90.14
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
9 0 . 2 1 S M A
A Standard packaging
SM Metal retaining clip
9 0 . 2 1 Without retaining clip
Please see general technical information