Note: If the power
system has a marked
conductor, it must
connect through the FI
and not be grounded at
any point downstream.
RP2
Maximum
Rated Fault
Line Trip
Current Current Cat. No.
16A 10mA RP2101
25A 30mA RP2203
25A 300mA RP2230
25A
40A 30mA RP2303
40A 300mA RP2330
40A
63A 30mA RP2403
63A 300mA RP2430
63A 500mA RP2450
80A
80A
80A
100A
100A
100A
125A
125A
125A
Fault
Trip
Current Cat. No.
30mA RP4203
300mA RP4230
500mA RP4250
30mA RP4303
300mA RP4330
500mA RP4350
30mA RP4403
300mA RP4430
500mA RP4450
30mA RP4503
300mA RP4530
500mA RP4550
30mA RP4603
300mA RP4630
500mA RP4650
30mA RP4703
300mA RP4730
500mA RP4750
RP4
aFor 2-Phase applications, terminal 5
and 6 (next to Neutral terminals) must
be connected to one phase for the test
circuit to be operable.
bFor voltage systems without a neutral
conductor. Please use jumper from “1”
or “3” to top “N” terminal. This will
assure proper functioning of the “test”
circuit.
Type Designation
__ __ __
(a) (b) (c)
(a) = 2-2 pole; 4-4 pole
(b) = 1-16A; 2-25A; 3-40A; 4-63A;
5-80A; 6-100A; 7-125A
(c) = 01 - 10mA
= 03 - 30mA
= 30 - 300mA
= 50 - 500mA
Voltage Rating (maximum)
Short Circuit Withstand Rating
Fault Trip Current Calibration
Typical Life
Standard Pack and Weight
Terminal Size Acceptability
Terminal Torque
230V AC, 50Hz 400Y/230V AC, 50Hz
No back-up fuse: Rated current (RC) 16/25/40A: 500A; RC 63/80A: 800A; RC 100A: 1000A; RC 125A-
1250A. With back-up fuse: 10kA; Size of fuse: (2 pole version): RC 25/40/63: 100A; (4 pole version): RC
25/40/63A: 100A; RC 80/100/125A: 125A
FI trips are calibrated at less than fault trip current for ensured safety (Typical trip range between
66.6-83.3% fault trip current, e.g., typical trip at 20-25mA for fault RC of 30mA)
Fully functional after 5,000 operations to DIN/VDE 0664T10, IEC 61008-1 and 2000 additional fault current trips.
1/230g (0.6 lb.) 1/420-460g (0.9 lb.-1.0 lb.)
1.5-50mm2(16-1 AWG) 1.5-50mm2(16-1 AWG)
3Nm (26.5 lb.in.) 3Nm (26.5 lb.in.)
a, b
RH11 - Auxiliary Contact and Signal Switch (switchable) (C.O./N.C.)
Circuit Diagram
Contact Wire
Rating Size Torque Cat. No. Circuit Diagram
6A / 230V AC 1-1.5mm2(16 AWG) max. 0.8Nm (7lb.in.) RH11
1A / 110V DC
Std. Pk.: 1
Unit Weight: 45 grams (0.12 lb.)
Width: 9mm (.354in.)
RP
Stock items are shown in BOLD.
RP - Series
RCCB Earth Leakage
Circuit Breakers
RCCB Series compact Earth
Leakage Circuit Break ers de tect
and in ter rupt earth (ground) faults.
They are VDE approved for the Eu -
ro pe an system of pro tect ing peo -
ple, animals, equipment and prop -
er ty from danger ous line-to-ground
and shock haz ard cur rents.
US applications include ground-
fault pro tec tion of equip ment
(GFPE) using the 10mA and 30mA
fault current rat ings, es pe cial ly
when high distributed ca pac i tance
or other leakag es cause ex ces sive
nui sance trips at lower fault cur -
rents. Applications for the 300mA
and 500mA ratings are equip ment
protection and fire preven tion, lim -
it ing the energy of a fault to less
than the minimum ignition en er gy
for many materials.