https://www.phoenixcontact.com/us/products/2800787
09/10/2014Page2/5
Surge protection device-PT-IQ-2X1-24DC-UT-2800787
Technical data
Dimensions
Depth 77.5 mm
Horizontal pitch 1 Div.
Ambient conditions
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
General
Housing material PA 6.6
Inflammability class according to UL 94 V0
Color black
Mounting type DIN rail mounting
Type DIN rail module, two-section, divisible
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN24 V
Maximum continuous operating voltage UC30 V DC
21 V AC
Nominal current IN1000 mA (Up to 45°C)
Operating effective current IC at UC≤ 1 mA (per path)
Residual current IPE ≤ 1 mA (per path)
Nominal discharge current In (8/20) µs (Core-Earth) 10 kA
Total surge current (8/20) µs 20 kA
Impulse discharge current (10/350)˽µs, peak value limp 2.5 kA
Voltage protection level UP (Core-Earth) ≤ 75 V (C1 - 1 kV/500 A)
≤ 135 V (C2 - 10 kV / 5 kA)
≤ 55 V (C3 - 25 A)
≤ 60 V (C3 - 50 A)
Response time tA (Core-Earth) ≤ 1 ns
≤ 1 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 300 kHz)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 1.1 MHz