Specification For Approval
Customer :
Description : Heat Exchanger 50W/K
Customer Part No. : Rev. :
Delta Model No. : HEX050QA Rev : 04
Sample Issue No. :
Sample Issue Date : Apr 20 2016
Delta Electronics, Inc.
252, Shang Ying Road, Kuei San District TEL : 886-(0)3-3591968
Taoyuan Hsien 333, Taiwan, R. O. C. FAX : 886-(0)3-3591991
Please send one copy of this specification back after you
signed approval for production pre-arrangement
Approved by :
Date :
ME EE CE
00 ISSUE SPEC 汪則鑫 7/17'13 汪則鑫 7/17'13 涂雅森 7/17'13 ------ 陳英琦 7/17'13 7/17'13
01 Add NTC fail definition (p.9)
Modify fan speed curve (p.11) 涂雅森 7/30'13 汪則鑫 7/30'13 涂雅森 7/30'13 陳英琦 7/30'13 7/30'13
02 Update safety certificate (p.10) 汪則鑫 2/7'14 汪則鑫 2/7'14 涂雅森 2/7'14 ------ 陳英琦 2/7'14 2/7'14
03 Modify 1-2 alarm description (p.2) 則鑫
8/8'14
汪則鑫
8/8'14
涂雅森
8/8'14
------ 陳英琦
8/8'14
8/8'14
04 Correct spec. section 1-2 (p.2) & add
section 7 warranty (p.11) 汪則 4/20'16 汪則鑫 4/20'16 涂雅森 4/20'16 ------ 陳英琦 4/20'16 4/20'16
ISSUE
DATE
*** SAMPLE HISTORY***
DRAWN APPROVEDDESCRIPTIONREV.
CUSTOMER :
CUSTOMER P/N :
DELTA MODEL : HEX050QA
CHECKED
Table of content
1. Description .............................................................................................................. 2
1-1. General description : ..................................................................................... 2
1-2. Main feature & Model number (Operation 48VDC).................................. 2
1-3. Dimension ....................................................................................................... 3
1-3-1 Drawing ................................................................................................ 3
1-3-2 Mounting panel cutout ........................................................................ 4
1-4. Configuration & Maintenance ...................................................................... 5
1-5. Thermal path and Airflow baffle ................................................................... 6
2. Electrical specification .......................................................................................... 7
2-1. Indicator & Connector (HEX panel side) .................................................... 7
2-2. Standalone control mode ............................................................................. 8
3. Environmental condition ..................................................................................... 10
3-1. Operating temperature ............................................................................... 10
3-2. Storage temperature ................................................................................... 10
3-3. Humidity ........................................................................................................ 10
3-4. Ingress Protection rating ............................................................................ 10
3-5. MTBF ............................................................................................................. 10
4. Reliability table ..................................................................................................... 10
5. Safety Certification .............................................................................................. 10
5-1. UL , cUL, TUV, CE ....................................................................................... 10
6. Accessory ..............................................................................................................11
6-1. Power cable ...................................................................................................11
6-2. Function cable...............................................................................................11
7. Warranty ................................................................................................................11
Page 1
Specification For Approval
Customer :
Description : Heat Exchanger 50W/K
Customer P/N : rev. :
Delta model no. : HEX050QA rev. : 03
Sample revision. : Issue no. :
Sample issue date : Quantity : sets
Page 2
Part no. :
Delta model no. : HEX050QA
1. Description
1-1. General description :
The Heat Exchanger (HEX) is designed for direct air to air heat exchange to remove the
heat from the cabinet . It is easy to be installed in the cabinet with the nuts. (Recommended
on the roof of the cabinet)
The internal and the external air circulation loops of the HEX are separated to prevent
the introduction of dust, humidity and dirt. The fan on the external air loop conforms to IP55
protection rating.
1-2. Main feature & Model number (Operation 48VDC)
Main feature Unit
Model Number
HEX050QA
Outline Dimension mm
550 L x 434 D x 155 H
Weight Kg
9.0 ± 0.5
Cooling Capacity (*Note 1) W/K
50
Rated Voltage VDC
48
Rated Current (*Note 2) A 4,0
Operating Voltage Range VDC
40 ~ 60
Operating Current A 1.4 (TYP.) / 1.7 (MAX.)
Operating Power W
68 (TYP.) / 80 (MAX.)
Maximum Operating Temperature °C
65
Internal Airflow Rate CFM
180 (TYP.)
External Airflow Rate 270 (TYP.)
Mounting Location N/A
Roof Mount
Fan Speed Control N/A
PWM 5 ~ 100% duty cycle
Controller N/A
Built-in
Operating Status N/A
LED Indicator
Fan alarm / NTC alarm N/A
Dry Contact Output
Acoustic Noise at 1.5M (SPL) dB-A
64.0 dB-A (TYP.)
*Note 1 : The cooling capacity (W/K or W/°C) is defined as Q/ (TI-TA)
Q : Heat dissipation (W) from inside
TI : Return temperature of internal air circuit (K OR °C)
TA : Ambient temperature of external air circuit (K OR °C)
*Note 2 : Rated current is announcement of safety
Page 3
Part no. :
Delta model no. : HEX050QA
1-3. Dimension
1-3-1 Drawing
(1) Material : Aluminum sheet t=1.5mm
(2) Finish : Powder paint 75~120um, Color RAL 7032.
(3) Dimensional tolerance :
X.X [X.XX] ± 1mm [0.04”]
X.XX [X.XXX] ± 0.3mm [0.012”]
Page 4
Part no. :
Delta model no. : HEX050QA
1-3-2 Mounting panel cutout
Page 5
Part no. :
Delta model no. : HEX050QA
1-4. Configuration & Maintenance
The HEX is composed of the key components as the following :
Chassis , Heat Exchange Core , Controller and Fan Tray . The user can slide out the
fan tray easily for replacement of the controller and fans .
Item Q'ty Description
1 1 Chassis assy
2 1 Controller assy
3 1 Internal fan tray
4 1 External fan tray
Page 6
Part no. :
Delta model no. : HEX050QA
1-5. Thermal path and Airflow baffle
With the forced convection using the axial fan , the warm air generated by the
equipment will be blowing into internal return opening and pass though the HEX core,
then flow out from internal supply opening , the air supply of the cold air will be used to
cool down the system ; While on the opposite side , cooler air from the out environment
will be drawn from external air inlet side and bring the heat of the HEX core out from the
external air exhaust side . The thermal exchange path is shown in the figure below.
Page 7
Part no. :
Delta model no. : HEX050QA
2. Electrical specification
2-1. Indicator & Connector (HEX panel side)
Connector " -48V VDC "
Connector "COMM"
Alarm logic depends (Pin1 to Pin2 ----- MAX. ± 75VDC ,50mA)
Fan and NTC normal
Pin1 and Pin2 dry contact output open
Fan failed
Pin1 and Pin2 dry contact output close
NTC failed
Pin1 and Pin2 dry contact output close
NTC FAILED
The NTC failed alarm will be active when NTC resistor work in abnormal range such as
1.NTC cable does not connect to control board
2.NTC damage (short or open)
Fan will run at high speed when NTC failed alarm is active.
Switch "TEST"
When pressing the “TEST/CLEAN” button, both outer fans and inner fans will run from
low speed to high speed for test. The testing process is around 2 minutes, and the LED of
INNER FAN and OUTER FAN will be blinking in GREEN color.
When the fan failed, the LED will be blinking red. It can be turned off by press the
“TEST/CLEAN” button again.
Page 8
Part no. :
Delta model no. : HEX050QA
LED of "INNER FAN & OUTER FAN"
(GREEN) : Fan normal
(RED) : Fan failed
(Blinking GREEN) :Fan is normal during test
(Blinking RED) : Fan failed during test
LED of "STATUS"
(GREEN) : NTC normal
(RED) : NTC open or short
2-2. Standalone control mode
HEX detects ambient temperature to control cooling capacity.
Cooling capacity (W/K) V.S Temperature
Page 9
Part no. :
Delta model no. : HEX050QA
Inner fan speed V.S. Temperature
Full speed: 3200 RPM ± 10%
Half speed: 1450RPM ± 200RPM (45% of full speed)
Outer fan speed V.S. Temperature
Full speed: 3200 RPM ± 10%
Half speed: 1450RPM ± 200RPM (45% of full speed)
Page 10
Part no. :
Delta model no. : HEX050QA
3. Environmental condition
3-1. Operating temperature
-10°C ~ +65°C (14°F ~ 149°F)
3-2. Storage temperature
-40°C ~ +70°C (-40°F ~ 158°F)
3-3. Humidity
External air loop : 0 ~ 100% RH
Internal air loop: 0 ~ 90% RH, non-condensing
3-4. Ingress Protection rating
IEC60529 IP55 (NEMA 3)
GR-487
3-5. MTBF
The L10 Fan life is expected to be at least 80,000 hours continuous operation at 40°C
with 15 ~ 65%RH .@ label rated voltage
4. Reliability table
Test item Condition
Thermal shock GR-487 3.30
Temp. Cycling/ High Humidity GR487 3.38.2
Water , Dust Intrusion and
Water Resistance (EXTERNAL SIDE)
GR-487 3.38.1
(follow IEC60529 IP55)
Salt fog test (EXTERNAL SIDE) GR487 3.38.1
Transportation Shock GR-487 3.39.1
Transportation Vibration
Packaged Environment
GR-487 3.39.3
(follow ETSI 300 019-2-2 T2.3 random vibration)
Environmentally Induced
Vibration
GR-487 3.39.5
(follow ETSI 300 019-2-4 table 3 class 4M5
random vibration)
5. Safety Certification
5-1. UL , cUL, TUV, CE
Page 11
Part no. :
Delta model no. : HEX050QA
6. Accessory
6-1. Power cable
6-2. Function cable
7. Warranty
Delta Electronics, Inc warrants one year (twelve months) from the
date of shipment , this warranty covers customer below application :
Customer follows Delta specification to install and operate the
product.
The product and any parts do not be modified (including both
mechanical and electrical modification) by customer themselves .
This warranty cover only repair, replacement or refund for defective
Delta products does not include any loss of data or any costs associated with
determining the source of system problems, costs for transportation, removal
or reinstallation of equipment or labor for repairs or replacement made in the
field.
 
  

 

 

  


 


 

 



 

 


  


 

 

 
 

 
